Omega Products G3NE-205T-US-DC5 User Manual

COMPACT, LOW–COST SOLID STATE RELAYS (SSR)
G3NE Series
Starts at
$
G3NE-210T-US-DC24,
$25, shown actual size.
l Current Ratings to 20 Amps l Multi-Million Hour Life l Compatible with Temperature Controllers l Zero Voltage Switching l Built-In Varistor Effectively Absorbs
External Surges
l Wide Load Voltage Range: 75 to 264 Vac l DC Control Signal l Quick-Connect #110 Input Terminals and
#250 Output Connections
l Thermal Conductive Pad Included
The G3NE Series of low-cost solid state relays are used to control resistance heaters in conjunction with temperature controllers. Solid state relays are SPST, normally open switching devices with no moving parts, capable of millions of hours of operation. By applying a control signal, an SSR switches ON the AC load current, just as the moving contacts do on a mechanical relay. Three-phase loads can be controlled using 2 or 3 SSR’s. Use 3 SSR’s for Y or star 3-phase loads using a neutral line. Two SSR’s will control “delta” loads with no neutral line. Three solid state relays are also used when there is no neutral load to provide redundancy and extra assurance of control.
“Switching” takes place at the zero voltage crossover point of the alternating current cycle. Because of this, no appreciable electrical noise is generated, making SSR’s ideal for environments where there are apparatuses susceptible to RFI. Models are available with control voltages of 5, 12, or 24 Vdc.
SPECIFICATIONS
Operate Time:1⁄2 of load power source cycle + 1 mS max Release Time:1⁄2 of load power source cycle + 1 mS max Output ON Voltage Drop: 1.6V (RMS) max Leakage Current: 2 mA max (at 100 Vac), 5 mA max
(at 200 Vac)
Insulation Resistance: 100 M min (at 500 Vdc) Dielectric Strength: 2000 Vac, 50/60 Hz for 1 min
G3NE-210T-US-DC24,
$25, with Y92B-N50
heat sink, $13,
shown actual size.
Vibration Resistance: Malfunction: 10 to 55, 1.5 mm double amplitude
Shock Resistance: Malfunction: 1000 m/s Ambient Temperature:
Operating: -30 to 80°C (-22 to 176ºF) (with no icing
or condensation) Storage: -30 to 100°C (-22 to 212ºF) (with no icing
or condensation)
Ambient Humidity: Operating, 45 to 85% Weight: Approx 37 g (1.3 oz) Certified Standard: UL File No. E64562/CSA File No.
LR35535 TÜV R9051064 (VDE0435) (EN60950)
K-1
2
(approx 100G)
G3NE-205T (L)/210T(L)/220T(L)(-2)-US
Dimensions: mm (in)
Heat Sink
K-2
RATINGS INPUT (AT AN AMBIENT TEMPERATURE OF 25°C)
Without heat sink
G3NE-205T(L)(-2)-US
Ambient Temperature (ºC)
Load Current (A)
Load Current vs. Ambient Temperature
Without heat sink
W
With standard heat sink (Y92B-N50) or aluminum plate measuring 100 mm x 100 mm x t2 mm (W x H x D)
G3NE-210T(L)(-2)-US
Ambient Temperature (ºC)
Load Current (A)
Without heat sink
With standard heat sink (Y92B-N100) or aluminum plate measuring 300 mm x 300 mm x t3 mm (W x H x D)
G3NE-220T(L)(-2)-US
Load Current (A)
RATED OPERATING INPUT VOLTAGE LEVEL
VOLTAGE VOLTAGE IMPEDANCE MUST OPERATE VOLTAGE MUST RELEASE VOLTAGE
5 Vdc 4 to 6 Vdc 250 ±20% 4 Vdc max
12 Vdc 9.6 to 14.4 Vdc 600 ±20% 9.6 Vdc max
1 Vdc min
24 Vdc 19.2 to 28.8 Vdc 1.6 k ±20% 19.2 Vdc max
Note: Each model has 5, 12, and 24 Vdc input versions.
OUTPUT
APPLICABLE LOAD
LOAD CURRENT
RATED LOAD LOAD VOLTAGE
MODEL NO. VOLTAGE RANGE WITH HEAT SINK2WITHOUT HEAT SINK INRUSH CURRENT
G3NE-205T-US 0.1 to 5 A 0.1 to 5 A 60 A (60 Hz, 1 cycle) G3NE-210T-US 100 to 240 Vac 75 to 264 Vac 0.1 to 10 A 0.1 to 5 A 150 A (60 Hz, 1 cycle) G3NE-220T-US 0.1 to 20 A 0.1 to 5 A 220 A (60 Hz, 1 cycle)
Notes: 1 The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature chart above.
2
When a heat sink of the specified size is used.
1
To Order (Specify Model Number)
MODEL NO. PRICE DESCRIPTION
G3NE-205T-US-DC5 $24 240 Vac load, 5 A, 5 Vdc control voltage G3NE-205T-US-DC12 24 240 Vac load, 5 A, 12 Vdc control voltage G3NE-205T-US-DC24 24 240 Vac load, 5 A, 24 Vdc control voltage G3NE-210T-US-DC5 25 240 Vac load, 10 A, 5 Vdc control voltage G3NE-210T-US-DC12 25 240 Vac load, 10 A, 12 Vdc control voltage G3NE-210T-US-DC24 25 240 Vac load, 10 A, 24 Vdc control voltage G3NE-220T-US-DC5 26 240 Vac load, 20 A, 5 Vdc control voltage G3NE-220T-US-DC12 26 240 Vac load, 20 A, 12 Vdc control voltage G3NE-220T-US-DC24 26 240 Vac load, 20 A, 24 Vdc control voltage
HEAT SINKS, DIN RAIL OR PANEL MOUNTING OPTIONS
MODEL NO. PRICE DESCRIPTION
Y92B-N50 $13 Heat sink for 5 A and 10 A SSRs Y92B-N100 20 Heat sink for 20 A SSRs
Ordering Example: G3NE-205T-US-DC24, SSR for AC load, 5 A, 24 Vdc control voltage, and Y92B-N50, heat sink, $24 + 13 = $37.
MOST POPULAR MODELS HIGHLIGHTED!
K-3
One Omega Drive | Stamford, CT 06907 | 1-888-TC-OMEGA (1-888-826-6342) | info@omega.com
EPG05
www.omega.com
UNITED KINGDOM
www. omega.co.uk
Manchester, England
0800-488-488
UNITED STATES
www.omega.com
1-800-TC-OMEGA
Stamford, CT.
CANADA
www.omega.ca
Laval(Quebec)
1-800-TC-OMEGA
GERMANY
www.omega.de
Deckenpfronn, Germany
0800-8266342
Karviná, Czech Republic
FRANCE
www.omega.fr
Guyancourt, France
088-466-342
CZECH REPUBLIC
www.omegaeng.cz
596-311-899
BENELUX
www.omega.nl
Amstelveen, NL
0800-099-33-44
More than 100,000 Products Available!
Temperature
Calibrators, Connectors, General Test and Measurement Instruments, Glass Bulb Thermometers, Handheld Instruments for Temperature Measurement, Ice Point References, Indicating Labels, Crayons, Cements and Lacquers, Infrared Temperature Measurement Instruments, Recorders Relative Humidity Measurement Instruments, RTD Probes, Elements and Assemblies, Temperature & Process Meters, Timers and Counters, Temperature and Process Controllers and Power Switching Devices, Thermistor Elements, Probes and Assemblies,Thermocouples Thermowells and Head and Well Assemblies, Transmitters, Wire
Flow and Level
Air Velocity Indicators, Doppler Flowmeters, Level Measurement, Magnetic Flowmeters, Mass Flowmeters, Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area Flowmeters, Vortex Shedding Flowmeters
pH and Conductivity
Conductivity Instrumentation, Dissolved Oxygen Instrumentation, Environmental Instrumentation, pH Electrodes and Instruments, Water and Soil Analysis Instrumentation
Data Acquisition
Auto-Dialers and Alarm Monitoring Systems, Communication Products and Converters, Data Acquisition and Analysis Software, Data Loggers Plug-in Cards, Signal Conditioners, USB, RS232, RS485 and Parallel Port Data Acquisition Systems, Wireless Transmitters and Receivers
Pressure, Strain and Force
Displacement Transducers, Dynamic Measurement Force Sensors, Instrumentation for Pressure and Strain Measurements, Load Cells, Pressure Gauges, Pressure Reference Section, Pressure Switches, Pressure Transducers, Proximity Transducers, Regulators, Strain Gages, Torque Transducers, Valves
Heaters
Band Heaters, Cartridge Heaters, Circulation Heaters, Comfort Heaters, Controllers, Meters and Switching Devices, Flexible Heaters, General Test and Measurement Instruments, Heater Hook-up Wire, Heating Cable Systems, Immersion Heaters, Process Air and Duct, Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
click here to go to the omega.com home page
Loading...