Omega Products FP7002 User Manual

PADDLEWHEEL FLOW AND TEMPERATURE SENSOR/TRANSMITTER SYSTEM
FP7002 Series
Built-in signal conditioner/ transmitter
U Measures Both Flow
and Temperature
U Wide Chemical
Compatibility
U 4 to 20 mA or 1 to 5 Vdc
Field-Selectable Output
U NEMA 4 (IP65) Housing U Compact Industrial
U Factory Calibrated—Easy
to Install
The FP7002 Series is a combination paddlewheel flow and temperature sensor with integral signal conditioner/ transmitter in a rugged NEMA-4 aluminum housing.
Omega’s FP7002 Series is ideal for applications that require a remote long-distance flow and temperature sensor. When ordered with an FP7000 Series installation fitting, the sensor/transmitter is factory calibrated to match the flow rate of the fitting selected. For example, if the user orders an FP7002 sensor/transmitter with an FP7010 PVC fitting, the analog output of the transmitter will be factory calibrated to give 20 mA output at the max flow rate of 50 GPM and 4 mA out at 0 GPM. The user can also convert an analog output to a 1 to 5 Vdc output without recalibrating the system.
The FP7002 also features an independent temperature sensor/ transmitter with an industry-standard 2-wire, 4 to 20 mA loop output scaled over a 0 to 100°C (32 to 212°F) temperature range.
Metal protection
head (cap removed
for detail)
FP7002, shown close to actual size.
Includes Built-In
Temperature Sensor
with Analog Output!
Built-in
temperature
sensor
Paddlewheel
sensor
An OMEGA
®
Exclusive
SYS/FP7002A/FP7010-GI system includes an FP7002A flow/temperature sensor with FP7010-GI fitting, calibrated for 3 to 50 GPM flow.
F-19
Provides Two Independent Analog Outputs For Flow and Temperature Measurement
CONNECT AN FP7002 TRANSMITTER TO OMEGA’S METERS WITH EMBEDDED INTERNET AND MONITOR A PROCESS FROM ANYWHERE VIA THE INTERNET!
Built-in
temperature
sensor
Paddlewheel
sensor
PADDLEWHEEL OUTPUT SPECIFICATIONS
Accuracy: ±2% FS Repeatability: ±1% FS Power: 12 to 18 Vdc @ 50 mA max Output: 3-wire, 4 to 20 mA (1 to 5 Vdc
with external 250 Ω resistor) Max Loop Resistance: Ω = (V supply–12V)/0.02 A
FP7002 Wetted Materials:
Sensor Body: Polypropylene O-Ring: FKM Paddle: PVDF Locking Nut: PVC
FP7002A Wetted Materials:
Sensor Body: Polypropylene O-Ring: FKM Paddle: PVDF Locking Nut: Brass Fluid Temperature/Pressure Range: Do not exceed maximum ratings of the piping. Depending on the material of the fitting, the operating temperature/pressure may be limited by the piping and not by the sensor. For all PVC tee fittings, do not exceed 150 psig @ 27°C (80°F), 100 psig @ 38°C (100°F), 60 psig @ 49°C (120°F) or 30 psig @ 60°C (140°F), owing to the insert in the tee. FP7000 sensor: 0 to 26°C (32 to 80°F) up to 150 psig; max pressure decreases 1.1 psig per each 0.56°C (1°F) above 27°C (80°F) for a max temperature of 93°C (200°F) at 18 psig max
Weight: FP7002: 0.3 kg (0.75 lb) FP7002A: 0.4 kg (1 lb) Max Viscosity: 5 cps
TEMPERATURE OUTPUT SPECIFICATIONS
Temperature Range:
0 to 100°C (32 to 212°F)
Accuracy: ±1.7°C (3.1°F) Power: 12 to 18 Vdc @ 30 mA Output: 2-wire, 4 to 20 mA
(1 to 5 Vdc with external 250 Ω resistor) Max Loop Resistance: Ω = (V supply – 12V)/0.02 A
SYS/FP7002/FP7007 system includes an FP7002 flow/temperature sensor with FP7007 fitting, calibrated for 2 to 30 GPM flow.
To Order Visit omega.com/fp7002 for Pricing and Details
Model No. Description FP7002 Paddlewheel flow and temperature sensor/transmitter for
FP7002A Paddlewheel flow and temperature sensor/transmitter for
Required Installation Fittings
PVC, Schedule 40* Galvanized Iron Tee Lay Length Pipe Size Range
Model No. meter (inch) Model No. (NPT) (GPM) FP7007 0.53 (21) FP7007-GI ³⁄₄ 2 to 30 FP7010 0.66 (26) FP7010-GI 1 3 to 50 FP7012 0.79 (31.3) FP7012-GI 1¹⁄₄ 5 to 90 FP7015 0.95 (37.5) FP7015-GI 1¹⁄₂ 7 to 125 FP7020 1.27 (50) FP7020-GI 2 11 to 205
FP7025 1.59 (62.5) FP7025-GI 2¹⁄₂ 15 to 285 FP7030 1.91 (75) FP7030-GI 3 25 to 460
All PVC fittings include 36" of PVC pipe on the flow inlet and 12" of PVC pipe on the flow outlet.
*
Accessories
Model No. Description PSS-12 12V single-output power supply TX4-100 4-conductor shielded cable, 30 meter (100')
Each transmitter/fitting system comes factory calibrated with operator’s manual.
Note: Your transmitter and fitting must be ordered as a system; see examples below. Ordering Examples: FP7002 sensor/transmitter with the FP7007 PVC fitting—use model
number SYS/FP7002/FP7007. SYS/FP7002A/FP7007-GI, sensor/transmitter with
PVC fittings (includes PVC locking nut)
galvanized iron fittings (includes brass locking nut)
F-20
MEASURES FLOW!
Program a DPi8-EI to accept the 4 to 20 mA signal from the FP7002 and to display the flow rate in the engineering units of your choice.
MEASURES TEMPERATURE!
Program a DPi8-EI to accept the 4 to 20 mA signal from the FP7002 and to display the temperature in the engineering units of your choice.
DPi8-EI indicator shown. Visit omega.com/dpi_series for complete details.
3
" galvanized fitting.
4
F