United Kingdom:One Omega Drive, River Bend Technology Centre
ISO 9002 Certified
Northbank, Irlam, Manchester
M44 5BD United Kingdom
TEL: +44 (0)161 777 6611FAX: +44 (0)161 777 6622
Toll Free in United Kingdom: 0800-488-488
e-mail: sales@omega.co.uk
OMEGAnet®Online Service Internet e-mail
omega.comi n f o @ o m e g a . c o m
It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and EMC/EMI
regulations that apply. OMEGA is constantly pursuing certification of its products to the European New
Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any
errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, human applications.
Page 3
GENERAL INFORMATION
The FP6500 Series are adjustable depth insertion paddlewheels that come in brass or 316 stainless models to fit
3” to 48” pipe. Installation fittings are standard 1-1/2"
NPT. Fittings such as saddles and weldolets may be
purchased locally or from Omega.
Ruby bearings and a non-drag Hall-effect sensor give these
meters the widest flow range of any of the paddlewheel
types. A sensor detects the passage of miniature magnets in the six rotor blades. The resulting square-wave
signal can be sent for hundreds of feet over unshielded
cable without a transmitter and connected directly to
many PLC’s and other controls without any additional
electronics.
#22 AWG 3-con, 18’ (6m);
Maximum cable run 2,000’ (650m)
FEATURES
Housing screw (connect ground to one)
Cable-seal strain relief
Rugged cast aluminum housing
Compression nut
Adapter fitting with 1-1/2" NPT threads
Rotor housing
Removable jewel bearings
Rotor
Page 4
10
X Dia.
5
X Dia.
FLOW
INSTALLATION
"D"
These ow sensors are not recommended
for installation downstream of the boiler
feedwater pump where installation fault
may expose the meter to boiler pressure
and temperature. Maximum recommended
temperature is 200ºF.
Piping. For best results, the FP6500 should be installed
with at least ten diameters of straight pipe upstream and five
downstream. Certain extreme situations such as partiallyopened valves are particularly difficult and may require fifteen
diameters upstream (See Straight Pipe Recommendations).
Immersion. The FP6500-Series standard sensors are not
designed for continuous underwater operation.
Fitting Installation. FP6500 sensors come with a 1-1/2”
male NPT pipe thread adapter fitting. Any fitting that provides
the matching NPT female thread may be used. Installation
procedure compensates for fitting height differences. Cut a
minimum 1-3/4” hole in the pipe. If possible, measure the
wall thickness and write it down for use in depth setting.
Then install the threaded fitting (saddle, weldolet, etc.) on
the pipe.
Meter Installation. Loosen the compression nut so that
the adapter slides freely. Pull the meter fully upward and
finger-tighten the compression nut. Using a thread sealant,
install the adapter in the pipe fitting. Do not overtighten.
Now loosen the compression nut, lower the meter to the
appropriate depth setting (see diagram and instructions
below). Be sure flow is in the direction of the arrow on the
housing. Tighten compression nut fully.
Depth Setting. It is important for accuracy that the sensor
be inserted to the correct depth into the pipe.
Horizontal is the preferred installation orientation, since it
improves low-flow performance slightly and avoids problems
with trapped air. Bottom, top, and vertical pipe installations
are all acceptable if required by the piping layout. See Full
Pipe Recommendations.
POSITIONING THE METER
Fair (unacceptable if
air is present)
Best
compression nut
threaded adapter fitting
1. In Table 1, find Dimension C for your sensor model
and pipe size.
2. Subtract wall thickness of your pipe (Table 2) to
find Dimension D.
3. Measuring from the outside of the pipe to the joint in
the housing, as shown in the diagram, adjust the sensor
to Dimension D and hand tighten compression nut.
4. Align the conduit housing with the centerline of the pipe,
as shown below. Be sure the arrow on the housing
points in the direction of flow.
Post-valve cavitation can create air pocketKeeps pipe full at sensor
RECOMMENDEDNOT RECOMMENDED
Air can be trapped
Allows air to bleed off
Caution: These flow sensors are not recommended for installation downstream of the boiler feedwater pump where installation fault may expose
the flow sensor to boiler pressure and temperature. Maximum recommended temperature is 200°F.
Page 9
CONNECTION, OPERATION & REPAIR
RED (+) 6-24 Vdc
WHITE (signal)
BLACK (-) Power
18' cable standard
CONNECTION
Sensors are supplied with 18 ft. of cable. See diagram for
color coding of connections.
Calibration (“K-Factor”). In order to properly process pulses
from the flow sensor, a number must be entered into the control to which the sensor is connected. This number, called the
K-factor, is the number of pulses the sensor puts out per unit
of fluid passing through the pipe. It is provided in pulses per
gallon, and is given on the chart “K-factors for Various Pipe
Sizes.” These numbers are based on extensive testing, which
has shown close agreement between different FP6500-Series
sensors in the same installation. Typically, most K-factor error can be attributed to installation variables, such as depth
setting and fitting configuration.
Flow Range. These sensors are designed to operate at
flow velocities of 0.3 to 30 feet per second. (See char t
for conversion to gallons per minute.) If erratic readings
are encountered at low flows, check the chart to see if
flow is below minimum for the pipe size. The standard
shaft and bearings should have a long life at continuous
high flow.
REPAIR
CAUTION! Never attempt to remove
a ow sensor when there is pressure
in the pipe. Loosen the compression
nut slowly to release any trapped
pressure. If uid sprays out when
removing the sensor, stop turning and depressurize
the pipe. Failure to do so could result in the sensor
being thrown from the pipe, resulting in damage or
serious injury.
Rotor Replacement. Rotors are easily field-replaced.
Shaft and rotor are a single unit, and are not replaced
separately. If replacement is due only to normal shaft
wear, bearing replacement is probably not necessary.
If the rotor has been damaged by impact, the bearings
should also be replaced. Rotor and bearings can be ordered as a kit, FP15827. Follow these steps:
It is occasionally possible to field calibrate a sensor by catching the fluid in a measured container and comparing with the
number of pulses recorded. (To record individual pulses, set
the K-factor on the control to 1.00.) This is especially desirable if the installation has less than the recommended length
of straight pipe upstream of the sensor.
OPERATION
Theory. In principle, an inser tion flow sensor measures the
velocity of flow at one point in the pipe, and flow rate and total
can be inferred from this one point. Accuracy is decreased
by any factor which makes the flow at the measured point
unrepresentative of the entire flow stream. This includes
distorted flow patterns caused by upstream fittings too close
to the sensor. The worst offenders are fittings that increase
the flow on one side of the pipe, such as partially-opened gate
or butterfly valves. Fluid moving in a pipe does not all flow at
the same velocity. Toward the center of the pipe, fluid moves
faster than at the wall, and the relationship between the two
changes as overall flow rate increases. This change in the
“velocity profile” can result in non-linearity, which means that
the K-factor that is correct for one flow rate may be incorrect
for another. The recommended depth settings have been
carefully chosen to minimize this source of error, and should
be followed carefully, especially in the smaller pipe sizes.
1. Unscrew the threaded bearing housings to expose
the shaft ends. If bearings are being replaced, back
them completely out.
2. Remove the rotor. Put the new rotor in its place.
3. Thread in one bearing housing part way, then the
other. Take care to star t the end of the shaft into
the bearing hole before tightening further.
4. Screw in bearing housings until they bottom.
Note: Do not use excessive force.
5. Check for free spin. Blowing lightly on the rotor
should result in it spinning rapidly and coasting to
a smooth stop.
Page 10
2
1
9
14
8
15
16
12
5
6
4
3
7
13
11
10
15
8
PARTS EXPLOSION
Troubleshooting. The flow sensor has only one moving part,
the rotor. If this is turning properly and there is no signal,
the Hall-effect sensor is not operating properly. To check
the signal, apply 12 Vdc power to the red (+) and black (-)
leads. Set a multimeter to voltage reading. Put the positive
multimeter lead on the red wire and the negative lead on the
white wire. Slowly turn the rotor. Voltage reading should swing
between +12 Volts and 0 Volts as the rotor turns. If it does
not, the Hall effect sensor is not working properly. Checking
for continuity is not a useful test of these sensors.
This flow sensor can be returned to the factor y for repair.
FP6500-Series Parts Listing
IP Parts Listing
1Upper housing
2Gasket
3Lower housing
4Housing screw
5Plug, steel
6Plug, plastic
7Strain relief
8Sensor with cable
9Tube
10Compression nut
11Ferrule
12Adapter fitting
13Rotor housing O-ring
14Rotor housing
15Jewel bearings
16Rotor with shaft
Rotor repair kit
17
(includes of #15 & #16)
Page 11
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 13 months f rom date of purchase. OMEGA’s WARRANTY adds an additional one (1) month
grace period to the normal one (1) year product warranty to cover handling and shipping time. This
ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be re t u rned to the factory for evaluation. O M E G A’s Customer Serv i c e
D e p a rtment will issue an Authorized Return (AR) number immediately upon phone or written re q u e s t .
Upon examination by OMEGA, if the unit is found to be defective, it will be re p a i red or replaced at no
c h a rge. O M E G A’s WARRANTY does not apply to defects resulting from any action of the purc h a s e r,
including but not limited to mishandling, improper interfacing, operation outside of design limits,
i m p roper re p a i r, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a result of excessive corro s i o n ;
or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s c o n t rol. Components in which wear is not warranted, include but are not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. Howev er,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any
damages that result from the use of its products in accordance with information provided by
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
R E P R E S E N TATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTA B I L I T Y
AND FITNESS FOR A PA RTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF
L I A B I L I T Y: The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this ord e r, whether based on contract, warr a n t y, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liab ility is bas ed. In no event shal l O MEGA be liabl e for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or
a c t i v i t y, medical application, used on humans, or misused in any way, OMEGA assumes no re s p o n s i b i l i t y
as set forth in our basic WA R R A N TY/ DISCLAIMER language, and, additionally, purchaser will indemnify
OMEGA and hold OMEGA h a rmless from any liability or damage whatsoever arising out of the use of the
P roduct(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN
(AR ) N U MBER F R OM OMEG A’S CUSTO M ER SERVICE DE PA RT M E NT (IN O R D ER TO AV O I D
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return
package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR WARRANTY RETURNS, please have the
following information available BEFORE
contacting OMEGA:
1 . P u rchase Order number under which the pro d u c t
was PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relative to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA
for current repair charges. Have the following
information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST
of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords
our customers the latest in technology and engineering.
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the
prior written consent of OMEGA ENGINEERING, INC.