Omega Products FP-5602 Installation Manual

http://www.omega.com
e-mail: info@omega.com
®
User’s Guide
FP-8500A/FP5600 Series
Flow Sensors
USA: One Omega Drive, Box 4047
ISO 9001 Certified Stamford, CT 06907-0047
Tel: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com
Canada: 976 Bergar
Laval (Quebec) H7L 5A1 Tel: (514) 856-6928 FAX: (514) 856-6886 e-mail: canada@omega.com
For immediate technical or application assistance:
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
SM
Customer Service: 1-800-622-2378 / 1-800-622-BEST
SM
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
SM
TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA
Mexico and Latin America: Tel: (95) 800-TC-OMEGA
SM
FAX: (95) 203-359-7807
En Espan˜ol: (203) 359-1660 ext: 2203 e-mail: espanol@omega.com
Servicing Europe:
Benelux: Postbus 8034, 1180 LA Amstelveen, The Netherlands
Tel: (31) 20 6418405 FAX: (31) 20 6434643 Toll Free in Benelux: 06 0993344 e-mail: nl@omega.com
Czech Republic: Ostravska 767, 733 01 Karvina
Tel: 420 (69) 6311899 FAX: 420 (69) 6311114 e-mail: czech@omega.com
France: 9, rue Denis Papin, 78190 Trappes
Tel: (33) 130-621-400 FAX: (33) 130-699-120 Toll Free in France: 0800-4-06342 e-mail: france@omega.com
Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
Tel: 49 (07056) 3017 FAX: 49 (07056) 8540 Toll Free in Germany: 0130 11 21 66 e-mail: germany@omega.com
United Kingdom: 25 Swannington Road, P.O. Box 7, Omega Drive,
ISO 9002 Certified Broughton Astley, Leicestershire, Irlam, Manchester,
LE9 6TU, England M44 5EX, England Tel: 44 (1455) 285520 Tel: 44 (161) 777-6611 FAX: 44 (1455) 283912 FAX: 44 (161) 777-6622
Toll Free in England: 0800-488-488
e-mail: uk@omega.com
omega.comomega.com
TM
OMEGA
®
OMEGAnetSMOn-Line Service Internet e-mail
http://www.omega.com info@omega.com
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WARNING: These products are not designed for use in, and should not be used for, patient connected applications.
OMEGA FP-8500A/FP-5600 Series
SAFETY INSTRUCTIONS
1. Do not remove from pressurized lines.
2. Do not exceed maximum temperature/pressure specifications.
3. Do not install/service without following installation instructions (see sensor manual).
4. Wear safety goggles and faceshield during installation/service.
5. Do not alter product construction.
6. Failure to follow safety instructions could result in severe personal injury!
1. Location of Fitting
Flange
Inlet
Outlet
Reducer
Recommended sensor upstream/ downstream mounting requirements.
10x I.D. 5x I.D.
15x I.D. 5x I.D.
2 x 90° Elbow 3 dimensions
Valve/Gate
50x I.D. 5x I.D.
40x I.D. 5x I.D.
2. Sensor Mounting Position
• Horizontal pipe runs: Mount sensor in the upright (0°) position for best overall performance. Mount at a maximum of 45° when air bubbles are present. Do not mount on the bottom of the pipe when sediments are present.
• Vertical pipe runs: Sensor must be mounted in lines with UPWARD flow only.
3. Sensor Wiring (Open-Collector Output)
OMEGA FPM-9010A or FP85A
FP-5600/FP-8501
Sensors
black (3.3 to 24 VDC)
Blk, Sensor Power
Red, Freq. input
Shld Gnd
red (signal out)
silver (DC return)
• Use 2-conductor shielded cable for cable extensions up to 300 m (1000 ft).
• Cable shield must be maintained through cable splice.
• OMEGA FPM-9010A, use 5 VDC power to sensor with pull-up resistor (open-collector configuration)
• Refer to your instrument manual for specific wiring details.
FP-5600 Sensor
black
silver red
• Pull-up resistor required (10 kΩ recommended).
• Use 2-conductor shielded cable for cable extensions up to 300 m (1000 ft).
• Cable shield must be maintained through cable splice.
90° Elbow
2 x 90° Elbow
-45°
10 kΩ
20x I.D. 5x I.D.
25x I.D. 5x I.D.
+45°
Process Pipe
Other instruments with
open-collector input
+
3.3 to 24
-
Gnd.
Input
VDC
Other
instrument
4. OMEGA Fittings
Type
Plastic Tee
PVC Glue-on Saddle (O-ring not required)
Iron Strap-on Saddle
Carbon Steel Weld-on Weldolet
Description
• 0.5 to 4 in. versions
• PVC or CPVC
• Mounts via glue-on fittings
• 2 to 4 in., cut 1-7/16 in. hole in pipe
• 6 to 8 in., cut 2-1/4 in. hole in pipe
• Align wedge arrows with saddle arrows during assembly.
• Pipes over 8 in., use iron saddle
• 2 to 4 in., cut 1-7/16 in. hole in pipe
• Over 4 in., cut 2-1/4 in. hole in pipe
• Special order over 12 in.
• 2 to 4 in., cut 1-7/16 in. hole in pipe
• Over 4 in., cut 2-1/4 in. hole in pipe
• Remove insert before welding
• Installed by certified welder only
• Special order over 12 in.
Type
Carbon Steel Threaded Tee
Metric Plastic Saddle
Metric Wafer Fitting
Metric Union Fitting
Description
• 0.5 to 2 in. versions
• Mounts on threaded pipe ends
• For pipes DN 65 to 200 mm
• Requires a 30 mm diam. hole in the pipe
• Wedge and saddle arrows must match
• For pipes DN 65 to 200 mm
• Follow installation guidelines
• For pipes from DN 15 to 50 mm
• PP or PVDF
• Follow installation guidelines