PROGRAMMABLE INTERFACE
DISPLAY FOR RATE, TOTAL AND
CONTROL COMMANDS
FMI-100
U Displays Instantaneous
and Total Flow
U Digital RS232 or RS485
Interface (Multi-Drop Up
to 64 Devices)
U Programmable, Optically-
Isolated Pulse and
Digital Outputs
U For Use with
FMA1700/1800 or
FMA5400/5500 Series
U 16 Point Programmable
Controls, With
Ramping Up/Down
U Free Configuration
and Monitoring
Utility Software
FMI-102D with FMA1702
Both models
shown smaller
than actual size.
FMI-102D
with FMA5404
D
The FMI-100 Series is for
flowmeters and controllers with
analog 0 to 5, 5 to 10, 0 to 10 Vdc
or 4 to 20 mA input output interface,
where flow indications/control,
totalizers or alarm functions are
required. Also when re-transmission
of the flow rate and/or totalizer
functions via optically-isolated pulse
output or serial communication is
desired. Local or programmable set
point control for flow controllers (no
host PC presence required).
The graphical LCD has large
13 mm (0.51") digits for flow rate
and 5.5 mm (0.21") for total and can
be set by user to simultaneously
show different combination of the
flow parameters: flow rate,
totalizers, flow alarms, and
diagnostic events. All configuration
parameter settings are easily
accessed via a simple user-interface
menu driven by a 6 button key-pad
which can be password-protected.
For flowmeters and/or flow
controllers, FMI-100 provides
jumpers selectable for 0 to 5 Vdc or
4 to 20 mA analog set point control
signals. The flow rate set point can
be adjusted locally via key-pad,
remotely via host PC using digital
communication interface, or
programmed in advance using
built-in 16 steps batch table with
ramping up/down support.
The programmable flow pulse
output operates independently
from the totalizers and based on
configuration settings can provide
pulse frequency proportional to
instantaneous fluid flow rate. The
FMI-100 provides two independent
programmable flow totalizers.
Both totalizers are updated every
100 ms and can be set to activate
different events. Main totalizer
accumulated total is backed-up
D-1
in EEPROM memory every
second. And it provides the user
with a flexible alarm/warning
system that monitors the fluid
flow for conditions that fall outside
configurable limits as well as visual
feedback for the user via the LCD
or via an optically-isolated output.
All process data and settings can
be read and modified manually via
local LCD key-pad or through the
digital RS232 or RS485
communication interface. Proprietary
ASCII software interface command
set and free Communication Utility
software are provided.
SPECIFICATIONS
ADC/DAC Resolution: 12-bit
Analog Inputs: 0 to 5 Vdc, 4 to 20 mA, 5 to 10 Vdc
(jumper-selectable), 0 to 10 Vdc (contact Flow Engineers at
Omega for details)
Analog Outputs: 0 to 5 Vdc, 4 to 20 mA (jumper-selectable)
LCD: 128 x 64 graphic LCD with instantaneous flow reading
and total volume indication, adjustable LCD contrast and
back light
Key-Pad: Local 6 tactical push buttons
Pulse Output: User-programmable, optically-isolated,
with preset active low time interval (10 to 6550 mS).
Digital Output: Two programmable, optically-isolated,
UCE @ 40 Vdc, ICE @ 150 mA (voltage isolation; 250 Vrms)
Digital Interface: RS232 or RS485 (multidrop capability up
to 64 devices)
Protocol: Proprietary ASCII software interface command set
Speed: 1200/2400/4800/9600/19200/38400/57600/115200
baud (user selectable)
Configuration:
Stop Bit: 1
Data Bits: 8
Parity: None
Flow Control: None
Addressing: Maximum 255 addresses
(for RS485 option only)
Type: RS232 or RS485 2-wire
Power Requirements: 12 to 26 Vdc (up to 60 mA maximum)
Interface Connectors: Process I/O signals and digital
RS232/RS485 interface, miniature 9-pin female D-SUB
connector; digital optically-isolated outputs; TERM BLOCK
HEADER 4POS 3.5 mm male pins, shrouded
Environment: Installation Level II, Pollution Degree II,
(per IEC 664)
Electromagnetic Compatibility: Compliant ref. 89/336/EEC
as amended; emission standard; EN 55011:1991, Group 1,
Class A immunity standard: EN 55082- 1:1992
Operating Temperature: -10 to 70°C (14 to 158°F)
Dimensions: 86.4 W x 76.2 H x 19.1 mm D
(3.4 x 3.0 x 0.75")
Weight: Approximately 125 g (0.3 lb)
To Order
Model No. Description
FMI-102 RS232 monitor/control interface, no display
FMI-105 RS485 monitor/control interface, no display
FMI-102-10V RS232 monitor/control interface, no display for 0 to 10V input/output
FMI-105-10V RS485 monitor/control interface, no display for 0 to 10V input/output
FMI-102D Rate/total, display, RS232 monitor/control interface
FMI-105D Rate/total, display, RS485 monitor/control interface
FMI-102D-10V Rate/total, display, 0 to 10V input/output monitor/control interface
FMI-105D-10V Rate/total, display, 0 to 10V input/output monitor/control interface
Comes complete with operator’s manual.
Mounting Kits (Sold Separately)
Model No. Description
FMI-100-MKM-DD Meter mounting kit two 9-pin D connectors
FMI-100-MKM-RD Meter mounting kit RJ11 to 9-pin D
FMI-100-MKM-FD Meter mounting kit flat wire to 9-pin D
FMI-100-MKC-2C Controller mounting kit 12 Vdc North American with communication
FMI-100-MKC-2N Controller mounting kit 12 Vdc North American no communication
FMI-100-MKC-4C Controller mounting kit 24 Vdc North American with communication
FMI-100-MKC-4N Controller mounting kit 24 Vdc North American no communication
For units with 230 Vac European plug add “-EU” to the model number, for additional cost.
For units with 240 Vac Austrialian plug add “-AU” to the model number, for additional cost.
For units with 240 Vac UK plug add “-UK” to the model number, for additional cost.
Ordering Example: FMI-105, RS485 interface (no display) with FMI-100-MKM-RD meter mounting kit with cable.
Visit omega.com/fmi-100 for Pricing and Details