Omega Products FLR 1000 Installation Manual

Page 1
FLR 1000/1000BR/1000ST Series
Flow Sensors & Meters For Liquids
Page 2
Page 3
READ THIS MANUAL COMPLETELY BEFORE ATTEMPTING TO CONNECT OR OPERATE YOUR FLOW SENSOR. FAILURE TO DO SO MAY RESULT IN INJURY TO YOU OR DAMAGE TO THE FLOW SENSOR.
TABLE OF CONTENTS
A. Introduction ...........................................................................................4
1. Unpacking.........................................................................................4
2. Product Overview And Principle Of Operation ........................................5
B. Installation.............................................................................................6
1. General Considerations.......................................................................6
2. Mounting The Flow Sensor or Flow Meter ...........................................7
3. Tubing Connections ............................................................................8
4. Electrical Connections.........................................................................9
a) Overview .......................................................................................9
b) Connecting A Cable Assembly ........................................................10
c) Electrical Connections – Voltage Output Units...................................11
d) Electrical Connections – Units With Both Voltage & Pulse Outputs........12
e) Electrical Connections – Current Output Units (“I” Suffix) ....................13
f) Using a 0-5VDC Output Power Adapter Package ...............................14
C. Operation ...........................................................................................15
1. Start-Up ..........................................................................................15
2. Entrapped Air or Gas ........................................................................15
3. Flow Readings..................................................................................15
a) 0-5VDC Analog Outputs................................................................16
b) Pulse Outputs ...............................................................................16
c) 4-20mA Outputs...........................................................................16
d) Units with an Integral Display..........................................................17
4. Operating at Flow Rates Outside the Calibrated Flow Range ..................17
a) Flows Above the Maximum Rated Flow.............................................18
b) Flows Below the Maximum Rated Flow .............................................18
5. Zero Adjustments..............................................................................18
6. Recalibration....................................................................................18
7. Calibrating Units for different Liquids...................................................20
D. Maintenance And Product Care..............................................................21
1. General...........................................................................................21
2. Cleaning and Flushing ......................................................................21
3. Returning Units For Repair Or Recalibration..........................................21
E. Specifications.......................................................................................22
F. Dimensions..........................................................................................24
G. Connector Pin And Wire Color Cross Reference........................................29
H. Trouble Shooting Guide ........................................................................30
Page 4
A. Introduction
1. Unpacking
All units are suitably packaged to prevent damage during shipping. If external damage is noted upon receipt of the package, please contact
Omega Engineering immediately.
Open the package from the top, taking care not to cut too deeply into the package. Remove all the documentation and contents. Take care to remove all the items and check them against the packing slip. The products should also be checked for any concealed shipping damage. If any shortages or damage is noted, please contact the shipping company and/or Omega Engineering to resolve the problem.
Sensor, Calibration Certificate & Instruction Manual
(Model FLR 1000 shown, other models similar).
Typical Contents of Box:
FLR 3100/3100BR/3100ST
Series
drop
Caution: Take care not to
your sensor or subject it to
sudden impact. Read the installation section of this manual before providing power or tubing connections to the unit. Any damage caused by improper installation or careless handling will
not be repaired under warranty (see limited warranty on page 32 for more details).
pg. 4 of 33
Page 5
2. Product Overview and Principle of Operation
The FLR 1000 series of flow meters and sensors for liquids from Omega Engineering are capable of measuring flows as low as 13-100 ml/min or as high as 1.0-10.0 l/min. Highly repeatable results are achieved using a patented Pelton Turbine Wheel flow sensor design. This proven design minimizes zero drift while maintaining fast response and linear outputs with virtually no maintenance. Flow is measured using a miniature turbine wheel similar in size to a U.S. dime (16 mm diameter, 0.75 mm thick). The micro-turbine wheel is
supported on a very small sapphire shaft that is held in position by two sapphire bearings. The micro-turbine assembly is so light that it virtually floats in the liquid. This relieves force on the bearings and almost eliminates wear.
As flow passes through the sensor, a precision machined nozzle directs the fluid onto the very small teeth of the micro-turbine wheel. This causes the wheel to spin at a speed proportional to the flow rate.
The micro-turbine wheel has alternating white and black sections evenly spaced on one side of the wheel. An infrared light beam is directed onto the wheel. As the wheel rotates the infrared beam is reflected off each white section. The reflected beam is detected by a phototransistor that converts the reflections into electrical pulses. As the wheel spins faster the pulse rate increases. Processing circuitry provides analog and/or pulse output that are linearly proportional to the flow rate
When the wheel stops (under zero flow conditions), no pulses are generated. Consequently, zero drift is not possible and zero adjustments are never required.
Every unit is supplied with a calibration certificate detailing the results obtained during calibration. Units are calibrated using deionized water as the reference media. Flowing liquids with different specific gravities or viscosities may effect the calibration.
pg. 5 of 33
Page 6
B. Installation
1. General Considerations
It is recommended that a safety shut-off valve be installed upstream of (before) the sensor.
All wetted parts should be checked for compatibility with the liquid to be used. If there are any incompatibilities e.g. highly corrosive liquid, then the unit may be damaged or fail prematurely. Such damage will not be repaired under warranty.
Units should be installed in a clean, dry environment with an ambient temperature that is as stable as possible. Avoid areas with strong magnetic fields, strong air flows or excessive vibration.
If the liquid to be used may contain particles larger than 25 microns then a filter (25 microns or less) should be installed upstream of (before) the unit.
The required differential press (or pressure drop across the unit) decreases exponentially with decreases in flow rate.
CAUTI ON: Do not flow any gas throu g h a liquid flow sensor. This may damage t he micro-turbine assembly and void the warranty. Do not exceed the pressure, temperature or power operating ran g es detailed in the SPECIFICATIONS section of this manual. Omega Engineering sh all not b e l iable fo r a n y da mage or i njury
caused by incorrect operation of their products.
Pressure Drop vs. Percentage of the Full Scale
Rated Flow (may vary ±10% of indicated psid)
12
0.8
10
8
6
Delta P psid
4
2
0
10 20 30 40 50 60 70 80 90 100
% of rated flow
100-1000 ml/min Units All Other Ranges
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
Delta P Bar
pg. 6 of 33
Page 7
To calculate the pressure drop at a certain flow rate use the formula
PD = (YourFlow / MaxFlow)
2
x PD
max
PD = Pressure drop at YourFlow. YourFLow = flow rate (ml/min or l/min) MaxFlow = 100% rated flow for the sensor (in same units as YourFlow) PD
= Pressure drop at 100% rated flow (see chart above)
max
If the pressure available for the flow sensor is BELOW the pressure drop at the required flow then flow through the unit will not be possible.
For example: You have a sensor with a 50-500ml/min flow range and want to know the pressure drop (or minimum differential pressure required) at 300ml/min. According to the chart above, the pressure drop at 100% of flow is approx 10psi. Using the formula above:
PD = (300 / 500)
Therefore, at 300ml/min the minimum required differential pressure for this unit is 3.6 psid. This means that if the available pressure is below
3.6psid then flow through the unit may not be possible.
Pressure drop through a system is cumulative. If the total pressure drop across all the components in a system exceeds the minimum pressure available then flow will not be possible.
For example: A system has a pressure of 30-40psi. There are several components and the sum of their pressure drops at the required flow rate is 32psid. If the system is operating at 30psi flow would not be possible as the total of the pressure drops would be greater than the pressure available. The system will only operate if the system pressure is above 32psi.
If there is any possibility that there may be bubbles or entrapped gas in the system then the outlet tubing should be elevated above the inlet port. This will enable any gas that may become entrapped in the unit to escape (see section C2 for details of how to remove entrapped air or gas).
2. Mounting the Flow Sensor or Flow Meter.
The Omega Engineering FLR 1000 Series units have no particular installation requirements so may be mounted in any convenient position.
It is recommended that units be fixed to a suitable substrate with #4 screws using the two mounting holes provided.
2
x 10 = 3.6 psid
pg. 7 of 33
Page 8
Mounting The Sensor
(mounting hardware not included with sensor)
3. Tubing Connections
CAUTION: DO NOT FLOW ANY GAS THROUGH A LIQUID FLOW SENSOR OR FLOW METER. THIS WILL DAMAGE THE MICRO-TURBINE ASSEMBLY AND VOID THE WARRANTY.
All tubing must be clean and without crimps, burrs or scratches.
Only use the fittings factory installed on the unit. If the fittings are removed the calibration of the unit may be effected and leaking may occur. If different fittings are required please contact the Omega Engineering Service Department for assistance. When connecting the sensor to the tubing a wrench should be used to stop the fitting rotating in the sensor body. Take care not to over tighten the fittings or leaking may occur.
Connecting and tightening the Fittings
(FLR 1000-ST-D shown, other models similar)
Caution: DO NOT over tighten the fittings into the sensor body. Excessi ve force may damage the sensor body and will NOT be repaired under warranty.
pg. 8 of 33
Page 9
The flow direction for the sensor is clearly marked on the label. Do not reverse the flow direction or the unit will not function.
Close Up of Label Showing Flow Direction
(FLR 1000 shown, other models similar)
For the best results precautions should be taken to minimize the amount of turbulence in the flow stream. Avoid valves, fittings, curves in the tube, changes in the internal diameter or any other restrictions close to the inlet of the sensor. The tubing ID should be as large as possible and preferably not smaller than the ID of the fittings installed on the sensor.
For 0.2-2.0 L/min units a 10 cm straight length of tube before the sensor is recommended. For higher flow range units (0.5-5.0 L/min and 1.0-10.0 L/min), a 20 cm straight length of tubing before the sensor is recommended. If this is not possible it is recommended that straight lengths between all connections on the inlet side of the sensor are as long as possible and 90 degree fittings (with a large enough ID) are used instead of curves in the tubing.
4. Electrical Con ne ctions
Caution: Incorrect wiring may cause severe damage to the unit. Applying an AC voltage (115VAC or 230VAC) directly to the unit will cause damage. Read the following instructions carefully before making any connections.
a) Overview
The FLR 1000 series of flow sensors and flow meters provide a 0-5VDC, or 4-20mA, or 0-5VDC and pulse output proportional to the flow rate. This output may be connected to a display, data acquisition system or voltmeter / current meter.
pg. 9 of 33
Page 10
The FLR 1000-D, 1000-ST-D and 1000-BR-D series feature an integral display that provides a local flow reading. These units also have a 0-5VDC analog output available. If required, this may be connected to another display, data acquisition system or voltmeter.
A stable D.C. power supply is required to operate the unit. The voltage and current requirements depend on the configuration of the unit. Full details may be found in the Specification section of this manual.
Connecting wires should be as short as possible to avoid voltage drops. Twisted 2 pair conductor cable should be used if the length of the power wires is to be longer than 1 meter.
Units are supplied with an integral 4 pin connector. Connections to the unit are made using a mating cable assembly or power adapter package as detailed in the following sections (parts 5.b to 5.f of this manual). A connector pin and wire color cross reference may also be found in Appendix G (Page 29) of this manual.
b) Connecting the Cable Assembly
The connector on the end of the cable assembly should be pushed into the mating socket on the sensor taking care to ensure that it is the correct way up.
Connecting the Cable Assembly
(FLR 1000 shown, other models similar)
Electrical Connections are made to the cable assembly as detailed in the following sections.
pg. 10 of 33
Page 11
c) Electrical Connections – Voltage Output Units
The cable assembly should be connected to the sensor as detailed in section 5(b) above. Power should not be applied to the sensor until all the connections have been made and checked. Electrical connections should be made as follows:
Wiring Schematic For Voltage Output Units.
The RED wire should be connected to the Positive of the power source.
The BLACK wire should be connected to the Negative ( Ground ) of the
power source.
The WHITE wire provides the signal output and should be connected to
the positive terminal of the display, data acquisition system or voltmeter with an impedance of greater than 2500 (Ohms).
The GREEN wire (if present) is NOT used
Caution: Avoid high voltage static discharges to any of the connections. Do not short the input/output signal wires or allow them to contact the power wires at any time. DAMAGE WILL RESULT!
pg. 11 of 33
Page 12
d) Electrical Connections –Units with Both Voltage and Pulse
Outputs
The cable assembly should be connected to the sensor as detailed in section 5(b) above. Power should not be applied to the sensor until all the connections have been made and checked. Electrical connections should be made as follows:
Wiring Schematic For Voltage and Pulse Output.
The RED wire should be connected to the Positive of the power source.
The BLACK wire should be connected to the Negative ( Ground ) of the
power source.
The WHITE wire provides the signal output and should be connected to
the positive terminal of the display, data acquisition system or voltmeter with an impedance of greater than 2500 (Ohms).
The GREEN wire (“P” suffix only) is the pulse output and should be
connected to the Positive terminal of the data acquisition system with an impedance of greater than 10K (Ohms).
The PULSE and VOLTAGE output may be monitored simultaneously.
Caution: Avoid high voltage static discharges to any of the connections. Do not short the input/output signal wires or allow them to contact the power wires at any time. DAMAGE WILL RESULT!
pg. 12 of 33
Page 13
e) Electrical Connections – Current Output Units (“I” Suffix)
The FLR 1000–ST-I provides a 4-20mA active current output proportional to the flow rate.
The cable assembly should be connected to the sensor as detailed in section 5(b) above. Power should not be applied to the sensor until all the connections have been made and checked. Electrical connections should be made as follows:
Wiring Schematic For Current Ouput Units (“I” suffix only).
The RED wire should be connected to the Positive of the power source.
The BLACK wire should be connected to the Negative ( Ground ) of the
power source.
The WHITE wire provides the signal output (active current) and should be
connected to the positive terminal of the display, data acquisition system or current meter with an impedance of 0 - 500 (Ohms).
The GREEN wire is NOT used.
Caution: Avoid high voltage static discharges to any of the connections. Do not short the input/output signal wires or allow them to contact the power wires at any time. DAMAGE WILL RESULT!
pg. 13 of 33
Page 14
f) Using a 0-5VDC Output Power Adapter Package.
An optional 0-5VDC Output Power Adapter Package is available for use with the FLR 1000 series (not the FLR 1000-ST-I). This consists of a power source (115VAC or 230VAC) and cable assembly with pig-tail (soldered wire) ends for the signal output. This should be assembled as shown in the following diagram.
Connecting the Power Adapter to the Flow Sensor
(FLR 1000 shown, other models similar)
Electrical connections to the cable assembly should be made as follows:
YELLOW WIRE: This provides the 0-5VDC signal output and should be
connected to the positive terminal of the display, data acquisition system or voltmeter with an impedance of greater than 2500 (Ohms).
GREEN WIRE: For Pulse output units (“P” suffix only) the green wire
provides the pulse output and should be connected to the positive terminal of the data acquisition system with an impedance of greater than 10K (Ohms).
WHITE WIRE: This is the signal negative and should be connected to the
negative (ground) terminal of the voltmeter, display or data acquisition system.
Caution: Avoid high voltage static discharges to any of the connections. Do not short the output signal wires or allow them to contact the power wires at any time. DAMAGE WILL RESULT!
pg. 14 of 33
Page 15
C. Operation
CAUTION: USE WITH LIQUIDS ONLY. FLOWING GAS OR AIR THROUGH YOUR LIQUID F LOW SEN S OR WIL L DAMAGE THE MICRO-TURBINE ASSEMBLY. THIS TYPE OF DAMAGE WILL NOT BE REPAIRED UNDER WARRAN TY.
1. Start Up
Before applying power to the unit check all tubing and electrical connections. Once correct installation is verified switch on the power.
2. Entrapped Air or Gas
There may be a lot of air or gas trapped in your sensor after installation. This will usually escape the unit when flow (within the range of the unit) is first started.
Caution: The system should be primed with liquid and flow started gradually. This will prevent trapped air or gas from being forced through the sensor at a high velocity that may damage the sensor.
If gas remains entrapped in the unit it may be necessary to elevate the outlet tubing above the inlet of the unit. This should enable the trapped gas to escape the unit. The unit may be returned to it’s original position once all the gas has escaped.
If elevating the outlet tubing does not work, block or pinch the outlet tube whilst there is flow in the system. After approximately 5 seconds, release the restriction to allow normal flow. Doing this will build up pressure in the flow path that when released will help remove the entrapped gas. Repeat this until the entrapped gas is removed form the unit.
3. Flow Readin gs
The FLR 1000 Series provide a 0-5VDC, or 4-20mA (I suffix), or 0-5VDC and pulse output (P suffix) proportional to the flow rate. The type of output signal is detailed by the part number reference and on the calibration certificate.
The FLR 1000-D, FLR 1000-BR-D and FLR 1000-ST-D series features an integral display that provides a local flow reading and a 0-5VDC analog output.
Each unit is factory calibrated for a specific flow range. The flow range is shown on the unit’s label and calibration certificate. Units are calibrated using deionized water as the reference media.
pg. 15 of 33
Page 16
a) 0-5VDC Analog Outputs
By monitoring the voltage output signal it is possible to determine the flow rate of the liquid. Units are configured so that an output signal of 5.0VDC is provided when the maximum flow (i.e. Full Scale flow) is passing through the unit. The output signal is linear and scaleable enabling calculation of flow rates within the sensor’s range. For example:
For a flow range of 50-500ml/min:
At 500ml/min the output signal would be 5VDC
If the output signal were 3.5VDC then the flow rate would be:
(500 ÷ 5) × 3.5 = 350ml/min
If the maximum flow rate is exceeded non-linear and inaccurate readings will result.
b) Pulse Outputs
By monitoring the Pulse output frequency it is possible to determine the flow rate of the liquid. The pulse frequency for maximum flow through the unit (i.e. full scale flow) is detailed on the calibration certificate. This differs from unit to unit. This output is approximately linear and scaleable within the sensor’s range. For example:
For a flow range of 1.0-10.0l/min:
The calibration certificate gives the following:
At 10.0l/min the pulse output signal is 312Hz At 5.0l/min the pulse output signal is 150Hz At 2.0l/min the pulse output signal is 58Hz
If the output signal were 120Hz then the flow rate would be:
(5.0 ÷ 150) × 120 = 4.0 l/min (using the closest calibration point)
c) 4-20mA Outputs
By monitoring the current output signal it is possible to determine the flow rate of the liquid. Units are configured so that an output signal of 20mA is provided when the maximum flow (i.e. Full Scale flow) is passing through the unit. The output signal is 4mA when there is zero flow through the unit. The output signal is linear and scaleable enabling calculation of flow rates within the sensor’s range. For example:
pg. 16 of 33
Page 17
For a flow range of 20-200ml/min:
At 200ml/min the output signal would be 20mA
If the output signal were 9mA then the flow rate would be:
200 ÷ (20-4) × 9 = 112.5ml/min
d) Units With an Integral Display
The FLR 1000-D, FLR 1000-BR-D and FLR 1000-ST-D series features an integral 3 ½ digit LCD display. This is configured to read in ml/min for flow ranges up to 50-500 ml/min and in l/min for flow ranges of 0.1 – 1.0 L/min. The display will only operate if power is applied to the unit.
Flow readings may be taken directly from the display or by monitoring the 0-5VDC analog output provided by using a cable assembly or power adapter package (see above).
LCD Flow Display
(Model FLR1000-ST-D shown, other models with displays similar)
4. Operating at Flow Rates Outside the Calibrated Flow Range
CAUTION: If the flow through the unit exceeds 120% of the maximum rated (full scale ) flow the unit may be damaged. This type of damage will not be repaired under warranty.
Flow measurement is only accurate within the calibrated flow range for the unit. This is detailed on the calibration certificate. The unit will still operate, to some degree, outside this flow range.
Results obtained when operating outside the specified range of the unit are not accurate but may be considered repeatable.
pg. 17 of 33
Page 18
a) Flows Above the Maximum Rated Flow.
If the flow rate is above the maximum rated (or full scale) flow, the unit will still operate and provide an output signal proportional to the flow rate.
Flows must not exceed 120% of the maximum rated flow or the unit may be damaged.
b) Flows Below the Minimum Rate d Flow.
Signal outputs may be obtained at flow rates below the minimum specified for your unit. The amount of flow that may be measured below the minimum specified varies from unit to unit.
5. Zero Adjustments
It is impossible for there to be any zero drift so zero adjustments are never required.
6. Recalibration
The calibration of the unit may be easily verified using empirical methods.
It should be noted that the use of empirical methods outside a certified calibration laboratory is subject to inaccuracy and error. These methods should only be used to gain an indication of a sensor’s performance. Please contact the Omega Engineering Service Department if accurate, certified recalibration is required.
A typical empirical calibration check may be carried out as follows:
Carefully adjust the flow rate so that the maximum output signal is obtained. With the flow rate constant, liquid flowing through the unit should be gathered in a container over a timed interval. The total volume flowed over the timed period should then be measured using a measuring cylinder. The actual flow rate (in the same units as the flow sensor calibration certificate) may then be calculated. The actual maximum flow rate should then be compared to the specified maximum flow rate to determine the error in calibration. For example:
For a unit with a flow range of 20-200ml/min and a 0-5VDC output:
With a constant flow and constant 5VDC output the actual volume measured over 30 seconds was 102ml.
Therefore the actual flow rate is:
(102 / 30) x 60 = 204ml/min
The error is therefore 204 – 200 = 4ml/min or 2%
pg. 18 of 33
Page 19
A second empirical check should be made at a flow rate below the maximum for the unit eg at 50% of full scale. The calculated percentage error at this flow should then be compared to the error at maximum flow. If there is a big difference in the percentage errors then the flow signal is no longer linear and the unit may be damaged (consult the Omega Engineering Service Department).
Once it has been determined that the linearity is still acceptable and the error in flow reading at maximum flow has been calculated, there are 3 options:
i.) Minor adjustments to actual calibration of the unit may be made by turning the gain potentiometer on the side of the unit. For example:
For a unit with a flow range of 13-100ml/min and a 0-5VDC output:
With a constant flow and constant 5VDC output the actual volume measured over 60 seconds was 103ml.
The correct voltage output for a flow of 103 ml/min is:
(5/100) x 103 = 5.15 V
With the flow at a constant 103 ml/min the gain potentiometer should be carefully adjusted so that a voltage output reading of
5.15 V is obtained.
If the unit cannot be suitably adjusted please contact the Omega Engineering Service Department. Pulse outputs are not adjustable.
Adjusting the Gain Potentiometer Using a Flat Head Screwdriver
(FLR 1000 shown, other models similar)
pg. 19 of 33
Page 20
ii.) Adjust the scaling endpoints in the display or data acquisition system. For example:
For a unit with a flow range of 50-500ml/min and a 0-5VDC output:
With a constant flow and constant 5VDC output the actual volume measured over 60 seconds was 405ml.
Therefore the actual flow rate is:
(405 / 60) x 60 = 405ml/min
The display or data acquisition system may now to configured as follows:
0 VDC = Zero flow 5VDC = 405ml/min
iii.) Apply the error factor to each flow reading taken. For example:
For a unit with a flow range of 0.2-2.0l/min connected to a display:
With a constant flow rate of 2.0 l/min on the display, the actual volume measured over 20 seconds was 0.7l
Therefore the actual flow rate is:
(0.7 / 20) x 60 = 2.1 l/min
The error is therefore 2.1 – 2.0 = 0.1 l/min or 5%
If the display shows an uncorrected flow rate of 1.4 l/min then :
Corrected flow rate = Uncorrected flow rate + error = 1.4 + 5% =
1.47 l/min
7. Calibrating Units for Different Liquids
The FLR 1000 Series will operate with most translucent liquids subject to compatibility of the wetted parts. Best results are obtained with low viscosity (less than 10 centistokes) liquids. For information regarding higher viscosity liquids, contact the Omega Engineering Service
Department.
Units are calibrated with deionized water as the reference media. Using other liquids will effect the calibration. The amount of calibration error will depend on the characteristics of the liquid being flowed.
pg. 20 of 33
Page 21
The error in flow reading (or calibration) should be calculated and utilized as detailed in section 6 above.
D. Maintenance and Product Care
1. General
CAUTION: Do not disassemble your unit for any reason. If the unit appear s t o be mal f unct i oni n g please contact the Omega Engineering Se rvic e Depa rtment.
The FLR 1000 Series of flow meters and sensors require no periodic maintenance if used within the recommended specifications.
The next recommended recalibration date is stated on the calibration certificate supplied with the unit. Please contact the Omega Engineering Service Department for further information.
Inlet filters should be periodically checked and cleaned / replaced as necessary.
Regularly check all electrical and process connections for damage or deterioration.
If the sensor is to be stored, keep both the inlet and outlet ports sealed.
Do not store a unit with any chemical other than water (or air) inside it over an extended period of time. Prolonged exposure to chemicals other than water may lead to precipitation or corrosion.
2. Cleaning and Flushing
If there is a build up of deposits or residues from the measured chemicals it may be necessary to clean flowing clean, particle free water through the unit at a flow rate, pressure and temperature within the specifications of the unit. If necessary, flow may be reversed to assist flushing.
Under no circumstances should gas or air be flowed through the unit. This will cause severe damage.
3. Returning Units for Repair or Recalibration
To return a unit for repair or recalibration please contact the Omega Engineering Customer Service Department. An Authorized Return (AR) number will then be issued. The AR number should then be noted on the outside of the package and on any correspondence. Further details may be found on page 32 of this manual.
or flush
the unit. This should be done by
pg. 21 of 33
Page 22
E. Specifications For Liquid Units
FLR 1000 FLR 1000-BR FLR 1000-ST FLR 1000-ST-I
Analog Signal Accuracy (including linearity)
Repeatability ±0.2% Full Scale1
Pressure Rating 100 psig
Temperature Rating Operating Range: 5 to 55ºC
Temperature Sensitivity ±0.2% F.S. 1 or less per ºC
Wetted Materials Ryton®
316 Stainless
O-Ring Material Standard - Viton®
Fitting Material (Standard) Acetal Brass Stainless Steel
Fitting Material Optional Kynar PVDF
Stainless Steel
Recommended Filtration 25 microns or less
Compatible Liquids Low viscosity (ideally <10cS)
(6.8 bar)
Epoxy
Glass
Sapphire
Brass
2
Minimum amount of entrapped air or gas
±1.0% Full Scale1
Storage Range: 0 to 70ºC
Brass
®
Ryton
316 Stainless
Epoxy
Glass
Sapphire
EPDM Optional
Acetal
Kynar PVDF
Stainless Steel
Translucent or transparent
2
500 psig
(34.5 bar)
316 Stainless
Sapphire
Kynar PVDF
Ryton
Epoxy
Glass
Acetal
Brass
®
0-5VDC Output Signal Standard
Pulse Output Signal “P” Suffix Only
4-20mA Output Signal N/A N/A N/A Non Isolated
Typical Power Consumption
Response Time Typically <1 second for 63% of final value
Reliability 100,000 hours MTBF
Certifications CE Approved
Ratings IP10 (NEMA 1)
Warranty 1 year limited
Minimum 2.5 K load
7.5VDC peak buffered square wave
Typically 0-400Hz
±3.0% Full Scale accuracy
Standard: 12 VDC @ 35 mA
(11.5-15 VDC)
89/336/EEC (EN 55011 & EN
50082-1)
73/23/EEC Low Voltage Directive
N/A
N/A
Current loop
should be
<500
24VDC @ 65mA
None
1. Specifications from 10-100% of rated flow. Linearity is best fit straight line. All calibrations performed with deionized water unless otherwise stated on calibration certificate
pg. 22 of 33
Page 23
FLR 1000-D FLR 1000-BR-D FLR 1000-ST-D
Display 3.5 Digit Non Backlit LCD, 0.39” (10mm) high digits
Accuracy (including linearity)
Repeatability ±0.2% Full Scale1
Pressure Rating 100 psig
Temperature Rating Operating Range: 5 to 55ºC
Temperature Sensitivity ±0.2% F.S. 1 or less per ºC
Wetted Materials Ryton®
316 Stainless
O-Ring Material Standard - Viton®
Fitting Material (Standard) Acetal Brass Stainless Steel
Fitting Material Optional Acetal, Kynar PVDF, brass, or stainless steel
Recommended Filtration 25 microns or less
Compatible Liquids Low viscosity (ideally <10cS)
(6.8 bar)
Epoxy
Glass
Sapphire
2
Minimum amount of entrapped air or gas
±1.0% Full Scale1
Storage Range: 0 to 70ºC
Brass
Ryton®
316 Stainless
Epoxy
Glass
Sapphire
EPDM Optional
Translucent or transparent
2
500 psig
(34.5 bar)
316 Stainless*
Ryton
Epoxy
Glass
Sapphire)
®
0-5VDC Output Signal Standard
Typical Power Consumption
Response Time Typically <1 second for 97% of final value
Reliability 100,000 hours MTBF
Certifications CE Approved
Ratings IP10 (NEMA 1)
Warranty 1 year limited
Standard: 12 VDC @ 35 mA (11.5-15 VDC)
Minimum 2.5 K load
89/336/EEC (EN 55011 & EN 50082-1)
73/23/EEC Low Voltage Directive
1. Specifications from 10-100% of rated flow. Linearity is best fit straight line. All calibrations performed with deionized water unless otherwise stated on calibration certificate
.
pg. 23 of 33
Page 24
F.
Dimensions
ALL DIMENSIONS IN INCHES (MILLIMETERS IN BRACKETS)
FLR 1000 For Liquids 1/4” A cetal Fittings Shown
pg. 24 of 33
Page 25
FLR 1000-BR & FLR 1000-ST For Liquids 1/4” Compression Fittings Sho wn
pg. 25 of 33
Page 26
FLR 1000-ST-I For Liquids 1/4” Fittings Shown
pg. 26 of 33
Page 27
FLR 1000-D For Liquids 1/4” A cetal Fittings Shown
pg. 27 of 33
Page 28
FLR 1000-BR-D & FLR 1000-ST-D For Liquids 1/4” Compression Fittings Sho wn
pg. 28 of 33
Page 29
G. Connector Pin And Wire Color Cross Reference
End On View of Connector Socket and Connector
Standard Units:
Unit Outp ut Pin Cable Wire
Color
1 Black Signal & Power
2 White Voltage Output Voltage Output Current Output
3 Red Power Positive Power Positive Power Positive
4 Green Not Used Pulse Output Not Used
Voltage Voltage &
Pulse
Negative (Ground)
Signal & Power
Negative
(Ground)
Signal & Power
Current
Negative
(Ground)
pg. 29 of 33
Page 30
H. Troubleshooting Guide
Symptom Possible Cause Method of Correction
Unit Leaks Fittings not tight enough.
Sensor assembly cracked
No output signal or flow indication
Flow indication “bounces” or fluctuates
No power or low power
No flow passing through unit
Output shorted or overloaded
Improper connection
Moisture on internal electronics
Output circuitry damaged
Liquid not translucent enough.
Attempting to measure flows below the specified minimum for the unit Flow is actually fluctuating
Not using the fittings supplied by the manuafacturer
Entrapped air or gas
Turbulence in tubing or sensor
Fluctuating input power
Mechanical sensor assembly damaged
Tighten fittings (see section B4)
Unit must be returned for repair (see Section D3) Apply correct power
Display or output should read zero if there is no flow. Increase the flow rate until a reading is obtained. (Do not exceed the specified maximum flow!)
Check electrical connections (see section B5)
Check electrical connections (see section B5) and ensure connector is correctly plugged in.
Allow unit to dry out in a dry environment.
Unit must be returned for repair (see Section D3)
Contact the Omega Engineering Service Department for assistance.
Use higher flow rates.
Correct flow source to obtain steady flow
Use the supplied fittings
Remove entrapped air (see section C2)
Straighten the inlet tubing or lengthen it to at least 6” (150mm)
Correct the power source or change to a regulated supply
Unit must be returned for repair (see Section D3)
pg. 30 of 33
Page 31
Symptom Possible Cause Method of Correction
Flow indication is not linear and output too low at lower flows
Flow reading accuracy is outside the specification
Flow indication is fixed at one value
Attempting to measure flows below the specified minimum for the unit
Liquid is too viscous
Entrapped air or gas
Mechanical sensor assembly damaged
Liquid has a different viscosity and / or specific gravity than water at 20°C
Entrapped air or gas
Mechanical sensor assembly damaged
The maximum rated flow for the unit is being exceeded.
Output circuits may be damaged
Use higher flow rates
Best results are obtained with liquids that have a viscosity of 10cS or less. Contact the Omega Engineering Service Department for further information
Remove entrapped air (see section C2)
Unit must be returned for repair (see Section D3)
Calculate the flow reading error / offset as explained in section C6
Remove the entrapped air (see section C2)
Unit must be returned for repair (see Section D3)
Reduce the flow
Unit must be returned for repair (see Section D3)
pg. 31 of 33
Page 32
.
pg. 32 of 33
Page 33
M4574/0807 pg. 33 of 33
Loading...