Omega Products FLD106 Installation Manual

INSTALLATION, OPERATION
& MAINTENANCE INSTRUCTIONS
AIR COOLED CONDENSERS
FLUID COOLERS
HEAT RECLAIM UNITS
CONTENT
SAFETY CONSIDERATIONS .........................2
INTRODUCTION..............................................2
HANDLING.......................................................3
INSTALLATION ...............................................3
STEPS #1 INSPECTION/LOCATION:..3
STEP #3 WIRING:.........................................3
STEPS #4 PIPING/LEAK TESTING ....3
OPERATION .....................................................4
FAN MOTORS/FAN CYCLING...................4
MAINTENANCE - CLEANING .......................4
TABLE 1: FLUID COOLERS: ..........................5
TABLE 2: CONDENSER & HEAT
RECLAIM ............................................6 to 16
Fig # 1: Standard legs .......................................17
Condenser/Fluid Cooler Dimensions........18& 19
Fig. #2 : Extended Legs....................................20
Fig #3 : 2 fans ...................................................21
Fig # 4: 1 fan ....................................................22
Table #3............................................................23
Table #4............................................................24
Table #5............................................................25
Table #6............................................................26
Table #7............................................................27
Replacement part list…………………... 28 & 29
WARRANTIES................................................30
SAFETY CONSIDERATIONS
Installing, starting up, and servicing equipment can be hazardous due to system pressures, electrical components and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
When working on the equipment, observe precautions in the literature and on the tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloths and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
WARNING
Before installation, always check to be sure main power to systems is OFF. Electrical shock can cause personal injury or death.
INTRODUCTION
Air Cooled condensers series CCR, CMR, CLR, CLW, CLX, CNR, CNW, CNX, CVR, CVW, CVX, CCD, CQD, CLD, CMD, CH8, CL8, CHD and CID are designed for refrigerant condensing of refrigeration and air conditioning systems. They can be manufactured for single or multiple circuits, for single or multiple compressors.
Fluid coolers series FCD, FLD, FID, FMD, FNV, FVD, FVV and FND are designed to cool glycol, oil or any other fluid that is not corrosive to copper and will not let the leaving air temperature exceed 140°F (60°C).
Heat recovery units HCD and HMD are designed to recover heat from refrigeration system in warehouse or shipping area.
2
HANDLING
CAUTION : Do not use forklift truck to handle units. Use only chains with hooks and spread bars to lift units.
When a unit is shipped on its side, two or three hangers are installed. Use them to unload the unit from truck.
A lift truck can be used with the wood base in that position only to lower the unit on the ground.
Two others hangers, four, six or eight legs (depending on the unit) and the required hardware are supplied attached to the cabinet.
Lifting method 1 :
Install all the legs on the same side as
hangers.
Gently lower the unit on those legs.
Install hangers on opposite side.
Raise the other side and install other legs.
Install chains and spread bars to raise the
unit to its final position.
Lifting method 2 :
Gently lower the unit on a flat surface.
Install hangers on opposite side.
Install chains and spread bars to raise the
unit.
Lift the unit and install all the legs.
Lift the unit to it’s final position.
See fig # 1 for more details. If the unit as been ordered with extended legs, see fig. #2 for field assembly. Also refer to table #1, #2 for unit weight.
INSTALLATION
STEP #1 INSPECTION:
If the unit is suspected of having been damaged in transit, immediately notify the carrier and file a claim with that carrier. The refrigeration coil section(s) of the unit should display a pressurised nitrogen gas holding charge. Unit should then be pressurised to 350 psi with dry nitrogen gas and leak-checked prior to rigging; this to insure no coil damage has occurred after the unit left the factory. Bolts & nuts may have become loose in transit, as well as electrical components. Please make sure that everything is tight prior to start­up.
STEP #2 LOCATION:
Condensers and fluid coolers are installed on the roof or ground level. If a unit is installed on the ground it must be fenced to prevent possible damage. Heat recovery units are installed inside at the ceiling level. Check loading capacity of the roof, the ceiling or the floor before installation.
The unit is intended to be installed in an atmosphere containing only neutral water vapour, natural precipitation and air. Use in any other atmosphere must be checked for compatibility with metals, materials and coating used in manufacturing of this equipment.
Unit positioning as well as firmness and perfect levelness of mounting base supports are important: Good installation practices are well known and are to be followed. Air flow paths on all sides as well as coil inlet and fan discharge areas are not to be restricted. Unit positioning that may result in air recirculation as well as prevailing wind impedance is to be avoided.
If a unit is to be placed close to a wall the minimum distance should be 24 inches for single row of fans and 48 inches for double row of fans. If units are to be placed side by side, the minimum distances should be 48 inches for single row of fans and 96 inches for a double row of fans. The chosen location must be convenient and allow safe accessibility for maintenance.
STEP #3 WIRING:
NOTE: A wiring diagram is provided with the unit, it is located on the inner face of the electrical box access door.
All wiring must be done in accordance with national and local codes. Check the nameplate with the current characteristics to be used for wiring unit. Internal wiring connections of the fan motors, optional controls and contactors have been completed at the factory. Once wired, make sure the unit has been grounded. Disconnect switch at the unit must be provided by others.
On air cooled condensers with flooding valve, one fan (single width unit) or one pair of fans (double width unit) must operate when compressor is operating to avoid internal damage to the condenser coil.
3
STEP #4 PIPING:
probably occur.
CAUTION: The unit has not been designed to carry the weight of any extended piping or valves. The piping must be well supported otherwise tube breaking at the coil will most
All refrigerant or fluid system components must be installed in accordance with applicable local and national codes and in accordance with good engineering practice required for proper operation.
Use top quality refrigeration tubing that is internally free of dirt, humidity or other contaminants. Unsealed tubing should not be used. Long radius elbows are recommended.
Dry nitrogen must be swept through the lines while joints are brazed to avoid oxidation and carbon deposits.
IMPORTANT: The use of a calibrated pressure gage and regulator must always be used with nitrogen gas cylinders.
To minimise hydraulic shock line breakage possibilities, valving and controls must be designed to eliminate any rapid introduction of hot gas into cold piping. Most especially if the piping contains liquid refrigerant or is at a much lower pressure than the hot discharge gas, which can be the case of double-wide condensers that feature one-half operation during winter. Plans should be for utilising either a slow-shifting three-way/four-way valve, or not completely lowering to suction pressure the condenser coil side that deactivates during winter. Most often, a combination of both of these options works well in geographic areas that encounter lower than freezing seasonal outdoor temperatures.
Air-cooled condensers must be provided with inverted “P” trap with a purge connection. A separate sub cooling circuit may be necessary if liquid line must rise to level higher than the unit.
Vibration in the discharge or liquid line must be corrected immediately to avoid piping and/or header breakage and refrigerant loss.
Generally, horizontal-piping runs should grade slightly downwards in the direction of the flow. Liquid line piping must be arranged so that it is free draining from the condenser to the receiver. It is best to pipe liquid lines so that there is an immediate drop, at least 2 or 3 feet, at the
condenser outlet, before headering or running horizontally.
STEP #5 LEAK TESTING:
Leak testing and evacuation must be done in accordance with local and national codes.
Once all refrigerant connections are made, leak test all joints before charging the system with refrigerant. After leak testing, all moisture and non-condensable gas must be evacuated from the system. Attach high vacuum line pump and gage on both high and low pressure sides of the system. A minimum vacuum level of 100 microns is required to effectively remove moisture.
Be sure all valves such as compressor, hot gas, receiver, and liquid solenoid valves are open. Break the vacuum in the system with the refrigerant to be used. Always charge the refrigerant into the system through a new 16 cu. in drier (field supplied) in the charging manifold line.
OPERATION
The notice below depicts the label that is affixed to the control box cover.
WARNING
ONE FAN (SINGLE WIDTH UNIT) OR ONE
PAIR OF FANS (DOUBLE WIDTH UNIT)
OPERATE SIMULTANEOUSLY TO AVOID
Not complying to this condition can cause uneven rapid expansion and contraction of the condenser core tubing contributing to condenser tubes failures. Violation of this condition will void the warranty of the misused unit.
For a refrigeration system to function properly, the condensing pressure and temperature must be maintained within certain limits.
To prevent excessively low head pressure during winter operation, two basic control methods are used, refrigerant side control and air side control.
Warranty Condition
AND THE COMPRESSOR MUST
DAMAGE TO THE CONDENSER COIL.
4
1) A) Refrigerant-side control is accomplished
by modulating the amount of active condensing surface available for condensing by flooding the coil with liquid refrigerant. This method requires a receiver and a larger charge of refrigerant. See fig. #3.
B) Refrigerant-side control by doing the one-half condenser operation. The condenser is initially resigned with two equal sections, each accommodating 50% of the load during normal operation.
During winter an ambient controlled flow divider valve blocks off one section of the condenser and pumps down the inactive section in the suction. This saves the flooding overcharge and sometimes allows the shutdown of the fans on the inactive condenser side. Fig. #4
2) Airside control is accomplished by cycling
fans in response to condensing pressure or outdoors-ambient temperature. To reduce stress on the condenser coil, one fan or one pair of fans must operate when a condenser is operating. Speed control on the constant operating fan may be used to reduce motor cycling and stabilise the operating pressure. See table 3 to 6 for more information.
For low ambient operation this method must be combined with refrigerant side control.
FAN MOTORS:
Check the fan blade clearances within the venturies, as well as check for proper rotation. Fan motors operating at higher elevations will draw lower than rated amp as well as draw less effective air volume across the coil surface. This is due to the reduced density of the higher altitude air, which results in higher compressor, and higher discharge pressure along with reduced unit capacity. Please consult factory if you suspect this situation.
The fan motors are permanently lubricated for service free operation. The motor may restart on automatic thermal protection. Motors are readily serviced by removing fan guards and fans. If a motor is inoperative or it cycles on thermal protection, check supply voltage at the motor leads. Fan motors may cycle on thermal protection if the coil is blocked.
Units equipped with axial fans, CVR, CVW, CVX: The entire fan assembly, motor, blade and ventury need to be replaced if there is a failure of any kind. With the two speed version, 3 contactors are used per motor. Do not attempt to manually close one of these contactors; this may result in motor winding damage.
FAN CYCLING:
Optional temperature or pressure controls are located in the control box. Air temperature sensors are located in the air flow and pressure controls are directly connected to the circuit in a return bend.
Optional line duty controls are connected directly to the fan motors. Controls are double pole single throw, one line remain live on the motors. Units must be completely disconnected before servicing.
Optional pilot duty controls are connected to 3 pole motor contactors. If controls or contactors are defective, they must be replaced.
MAINTENANCE
CLEANING:
After one day of operation, check for any vibration that might have developed in the unit. It is recommended that the unit be inspected occasionally for dirt accumulation. Grease and dust should be removed from the fans and fan guards.
Periodical cleaning of finned surfaces can be done by washing down dust with warm water spray and a mild detergent. Do not use alkaline or acidic solution as it will attack the coil material.
The inner face of the coil may be cleaned by the access panel on the side of the units or by removing the fan guards.
Always pressure -clean in reverse of the air flow.
5
TABLE 1: FLUID COOLERS
Fluid
CoolerID
FCD02 1 1 190 FLD015 1 1 654 FCD03 1 1 201 FLD018 1 2 985 FCD04 1 1 210 FLD021 1 2 1005 FID010 1 1 515 FLD023 1 2 1063 FID011 1 1 525 FLD026 1 2 1091 FID013 1 1 592 FLD028 1 2 1117 FID014 1 1 602 FLD030 1 2 1159 FID016 1 1 641 FLD035 1 3 1460 FID017 1 1 654 FLD040 1 3 1490 FID020 1 2 985 FLD042 2 2 1625 FID023 1 2 1005 FLD043 1 3 1570 FID025 1 2 1063 FLD045 1 3 1609 FID029 1 2 1091 FLD049 2 2 1792 FID031 1 2 1117 FLD050 1 4 1875 FID034 1 2 1159 FLD053 2 2 1781 FID039 1 3 1460 FLD054 1 4 1915 FID044 1 3 1490 FLD056 2 2 1882 FID046 2 2 1625 FLD057 1 4 2019 FID049 1 3 1570 FLD060 2 2 1934 FID051 1 3 1609 FLD061 1 4 2071 FID054 2 2 1792 FLD063 2 3 2323 FID055 1 4 1875 FLD066 1 5 2403 FID058 2 2 1781 FLD070 1 5 2475 FID059 1 4 1915 FLD075 1 5 2540 FID064 2 2 1882 FLD080 2 3 2508 FID065 1 4 2019 FLD085 2 3 2664 FID068 2 2 1934 FLD090 2 3 2742 FID069 1 4 2071 FLD099 2 4 3029 FID070 2 3 2323 FLD106 2 4 3129 FID073 1 5 2403 FLD113 2 4 3338 FID079 1 5 2475 FLD120 2 4 3442 FID085 1 5 2540 FLD124 2 5 4198 FID088 2 3 2508 FLD132 2 5 4298 FID095 2 3 2664 FLD142 2 5 4560 FID101 2 3 2742 FLD150 2 5 4690 FID112 2 4 3029 FLD159 2 6 5292 FID119 2 4 3129 FLD170 2 6 5642 FID129 2 4 3338 FLD180 2 6 5798 FID137 2 4 3442 FLD190 2 6 6535 FID141 2 5 4198 FMD05 1 1 308 FID149 2 5 4298 FMD07 1 1 335 FID162 2 5 4560 FMD08 1 1 350 FID171 2 5 4690 FMD09 1 2 489 FID178 2 6 5292 FMD11 1 2 518 FID194 2 6 5642 FMD12 1 2 532 FID205 2 6 5798 FMD13 1 2 544
FID214 2 6 6535 FMD14 1 2 566 FLD009 1 1 515 FMD18 1 3 727 FLD010 1 1 525 FMD20 1 3 741 FLD012 1 1 592 FMD21 1 3 767 FLD013 1 1 602 FMD23 1 3 789 FLD014 1 1 641
Width
(fan)
Length
(fan)
Shipping
Weight
(lb)
Fluid
Cooler ID
Width
(fan)
Length
(fan)
Shipping
Weight
(lb)
6
TABLE 2: CONDENSER AND HEAT RECLAIM
Condenser
ID
CCD02 1 1 1.8 5.8 190 CL8053 2 2 47 153 1882
CCD03 1 1 2.7 8.7 201 CL8054 1 4 46 150 2019
CCD04 1 1 3.5 12 210 CL8055 2 3 34 112 2323
CH8010 1 1 5.8 19 515 CL8059 1 5 43 140 2403
CH8013 1 1 8.8 29 592 CL8068 1 5 57 187 2475
CH8015 1 1 12 38 641 CL8071 2 3 52 169 2508
CH8020 1 2 12 38 985 CL8081 2 3 69 225 2664
CH8026 1 2 17 57 1063 CL8094 2 4 68 224 3029
CH8029 1 2 23 76 1117 CL8108 2 4 91 299 3338
CH8038 1 3 26 85 1460 CL8118 2 5 85 280 4198
CH8040 2 2 23 75 1625 CL8135 2 5 114 373 4560
CH8044 1 3 34 112 1570 CL8141 2 6 164 553 5292
CH8051 2 2 35 115 1792 CL8162 2 6 218 717 5642
CH8052 1 4 34 112 1875 CLD009 1 1 5.8 19 515
CH8058 2 2 47 153 1882 CLD010 1 1 5.8 19 525
CH8059 1 4 46 150 2019 CLD012 1 1 8.8 29 592
CH8060 2 3 34 112 2323 CLD013 1 1 8.8 29 602
CH8065 1 5 43 140 2403 CLD014 1 1 12 38 641
CH8074 1 5 57 187 2475 CLD015 1 1 12 38 654
CH8078 2 3 52 169 2508 CLD018 1 2 12 38 985
CH8088 2 3 69 225 2664 CLD021 1 2 12 38 1005
CH8104 2 4 68 224 3029 CLD023 1 2 17 57 1063
CH8118 2 4 91 299 3338 CLD026 1 2 17 57 1091
CH8130 2 5 85 280 4198 CLD028 1 2 23 76 1117
CH8147 2 5 114 373 4560 CLD030 1 2 23 76 1159
CH8156 2 6 197 664 5292 CLD035 1 3 26 85 1460
CH8177 2 6 262 860 5642 CLD040 1 3 26 85 1490
CHD010 1 1 5.8 19 515 CLD042 2 2 23 75 1625
CHD012 1 1 5.8 19 525 CLD043 1 3 34 112 1570
CHD013 1 1 8.8 29 592 CLD045 1 3 34 112 1609
CHD014 1 1 8.8 29 602 CLD049 2 2 35 115 1792
CHD015 1 1 12 38 641 CLD050 1 4 34 112 1875
CHD016 1 1 12 38 654 CLD053 2 2 35 115 1781
CHD020 1 2 12 38 985 CLD054 1 4 34 112 1915
CHD024 1 2 12 38 1005 CLD056 2 2 47 153 1882
CHD026 1 2 17 57 1063 CLD057 1 4 46 150 2019
CHD029 1 2 17 57 1091 CLD060 2 2 47 153 1934
CHD030 1 2 23 76 1117 CLD061 1 4 46 150 2071
CHD032 1 2 23 76 1159 CLD063 2 3 34 112 2323
CHD040 1 3 26 85 1460 CLD066 1 5 43 140 2403
CHD044 1 3 26 85 1490 CLD070 1 5 57 187 2475
CHD045 1 3 23 75 1625 CLD075 1 5 57 187 2540
CHD048 1 3 34 112 1570 CLD080 2 3 52 169 2508
CHD049 2 2 34 112 1609 CLD085 2 3 69 225 2664
CHD055 2 2 35 115 1792 CLD090 2 3 69 225 2742
Width
Length
(fan)
(fan)
Refrigerant
Charge
Summer (lb)
Refrigerant
Charge
Winter (lb)
Shipping
Weight (lb)
Condenser
ID
Width
(fan)
Length
(fan)
Refrigerant
Charge
Summer (lb)
Refrigerant
Charge
Winter (lb)
Shipping
Weight (lb)
7
Condenser
ID
CHD056 1 4 34 112 1875 CLD099 2 4 68 224 3029
CHD059 2 2 35 115 1781 CLD106 2 4 68 224 3129
CHD060 1 4 34 112 1915 CLD113 2 4 91 299 3338
CHD061 2 2 47 153 1882 CLD120 2 4 91 229 3442
CHD062 1 4 46 150 2019 CLD124 2 5 85 280 4198
CHD063 2 2 47 153 1934 CLD132 2 5 85 280 4298
CHD064 1 4 46 150 2071 CLD142 2 5 114 373 4560
CHD073 2 3 34 112 2323 CLD150 2 5 114 373 4690
CHD074 1 5 43 140 2403 CLD159 2 6 164 553 5292
CHD077 1 5 57 187 2475 CLD170 2 6 218 717 5642
CHD079 1 5 57 187 2540 CLD180 2 6 218 717 5798
CHD089 2 3 52 169 2508 CMD05 1 1 3.3 11 308
CHD092 2 3 69 225 2664 CMD07 1 1 4.9 16 335
CHD096 2 3 69 225 2742 CMD08 1 1 6.5 22 350
CHD110 2 4 68 224 3029 CMD09 1 2 6.3 21 489
CHD118 2 4 68 224 3129 CMD11 1 2 9.5 31 518
CHD123 2 4 91 299 3338 CMD12 1 2 9.5 31 532
CHD127 2 4 91 229 3442 CMD13 1 2 13 42 544
CHD138 2 5 85 280 4198 CMD14 1 2 13 42 566
CHD148 2 5 85 280 4298 CMD18 1 3 14 47 727
CHD153 2 5 114 373 4560 CMD20 1 3 14 47 741
CHD159 2 5 114 373 4690 CMD21 1 3 19 62 767
CHD177 2 6 164 553 5292 CMD23 1 3 19 62 789
CHD184 2 6 218 717 5642 CQD008 1 1 5.8 19 525
CHD191 2 6 218 717 5798 CQD009 1 1 5.8 19 535
CID010 1 1 5.8 19 515 CQD010 1 1 8.8 29 602
CID011 1 1 5.8 19 525 CQD011 1 1 8.8 29 612
CID013 1 1 8.8 29 592 CQD012 1 1 12 38 651
CID014 1 1 8.8 29 602 CQD013 1 1 12 38 664
CID016 1 1 12 38 641 CQD016 1 2 12 38 1085
CID017 1 1 12 38 654 CQD019 1 2 12 38 1025
CID020 1 2 12 38 985 CQD021 1 2 17 57 1083
CID023 1 2 12 38 1005 CQD022 1 2 17 57 1111
CID025 1 2 17 57 1063 CQD023 1 2 23 76 1137
CID029 1 2 17 57 1091 CQD024 1 2 23 76 1179
CID031 1 2 23 76 1117 CQD031 1 3 26 85 1490
CID034 1 2 23 76 1159 CQD034 1 3 26 85 1520
CID039 1 3 26 85 1460 CQD035 1 3 34 112 1600
CID044 1 3 26 85 1490 CQD036 1 3 34 112 1639
CID046 2 2 23 75 1625 CQD041 2 2 35 115 1832
CID049 1 3 34 112 1570 CQD042 1 4 34 112 1915
CID051 1 3 34 112 1609 CQD044 2 2 35 115 1821
CID054 2 2 35 115 1792 CQD045 1 4 34 112 1955
CID055 1 4 34 112 1875 CQD046 2 2 47 153 1922
CID058 2 2 35 115 1781 CQD047 1 4 46 150 2059
CID059 1 4 34 112 1915 CQD048 2 2 47 153 1974
CID064 2 2 47 153 1882 CQD049 1 4 46 150 2111
CID065 1 4 46 150 2019 CQD057 1 5 43 140 2453
CID068 2 2 47 153 1934 CQD058 1 5 57 187 2525
Width
(fan)
Length
(fan)
Refrigerant
Charge
Summer (lb)
Refrigerant
Charge
Winter (lb)
Shipping
Weight (lb)
Condenser
ID
Width
(fan)
Length
(fan)
Refrigerant
Charge
Summer (lb)
Refrigerant
Charge
Winter (lb)
Shipping
Weight (lb)
8
Condenser
ID
CID069 1 4 46 150 2071 CQD061 1 5 57 187 2590
CID070 2 3 34 112 2323 CQD069 2 3 52 169 2568
CID073 1 5 43 140 2403 CQD070 2 3 69 225 2724
CID079 1 5 57 187 2475 CQD072 2 3 69 225 2800
CID085 2 5 57 187 2540 CQD083 2 4 68 224 3109
CID088 2 3 52 169 2508 CQD091 2 4 68 224 3209
CID095 2 3 69 225 2664 CQD093 2 4 91 299 3418
CID101 2 3 69 225 2742 CQD096 2 4 91 299 3522
CID112 2 4 68 224 3029 CQD104 2 5 85 280 4298
CID119 2 4 68 224 3129 CQD114 2 5 85 280 4398
CID129 2 4 91 299 3338 CQD116 2 5 114 373 4660
CID137 2 4 91 229 3442 CQD121 2 5 114 373 4790
CID141 2 5 85 280 4198 CQD137 2 6 164 553 5412
CID149 2 5 85 280 4298 CQD140 2 6 218 717 5762
CID162 2 5 114 373 4560 CQD145 2 6 218 717 5918
CID171 2 5 114 373 4690 HCD02 1 1 0.6 0.6 190
CID178 2 6 164 553 5292 HCD03 1 1 0.9 0.9 201
CID194 2 6 218 717 5642 HCD04 1 1 1.2 1.2 210
CID205 2 6 218 717 5798 HMD05 1 1 1.1 1.1 308
CL8009 1 1 5.8 19 515 HMD07 1 1 1.6 1.6 335
CL8012 1 1 8.8 29 592 HMD08 1 1 2.1 2.1 350
CL8014 1 1 12 38 641 HMD09 1 2 2.1 2.1 489
CL8018 1 2 12 38 985 HMD11 1 2 3.1 3.1 518
CL8024 1 2 17 57 1063 HMD12 1 2 3.1 3.1 532
CL8027 1 2 23 76 1117 HMD13 1 2 4.3 4.3 544
CL8035 1 3 26 85 1460 HMD14 1 2 4.3 4.3 566
CL8036 2 2 23 75 1625 HMD18 1 3 4.6 4.6 727
CL8041 1 3 34 112 1570 HMD20 1 3 4.6 4.6 741
CL8047 2 2 35 115 1792 HMD21 1 3 6.3 6.3 767
CL8048 1 4 34 112 1875 HMD23 1 3 6.3 6.3 789
Width
(fan)
Length
(fan)
Refrigerant
Charge
Summer (lb)
Refrigerant
Charge
Winter (lb)
Shipping
Weight (lb)
Condenser
ID
Width
(fan)
Length
(fan)
Refrigerant
Charge
Summer (lb)
Refrigerant
Charge
Winter (lb)
Shipping
Weight (lb)
9
Loading...
+ 21 hidden pages