Omega Products DP7000 User Manual

DP7000 Series Temperature Digital Controller
Specification and Operating Instructions
Wiring Diagram
Probe input
1 2
+–
7 8
POWER SUPPLY
9 10 11
NC COM NO
OUTPUT
Description
The DP7000 Series controllers are designed for many heating and cool­ing, high temperature applications. The probe temperature is displayed on the bright 3-digit display. The user is able to program 18 different parameters including set point, hysteresis, cycle time and ambient probe adjustment using the silicone front keypad. The unit features error or alarm warning, internal buzzer and password protection. Select between thermocouple J, K or S type, temperature display in °C or °F and 115 VAC, 230 VAC or 12 VDC power supplies.
The model reference is given by: DP700X
Where each suffix can take the following values:
Thermocouple Type J Display Color Red X 1 = 115 VAC - °F; 2 = 115 VAC - °C
3 = 230 VAC - °F; 4 = 230 VAC - °C 5 = 12 VAC/DC - °F; 6 = 12 VAC/DC - °C
Installation
NOTE: Unit must be mounted away from vibration, impacts, water and corrosive gases.
• Cut hole in panel 71 x 29 mm (2.80 x 1.14˝).
• Apply silicone (or rubber gasket) around the perimeter of the hole to prevent leakage.
• Insert unit into hole of panel.
• Slide removable fitting clips onto unit from the back until secure to panel.
• Remove back cover to wire unit.
• Wiring diagram is displayed on the top of the unit.
NOTE: DO NOT INSTALL PROBE CABLE NEAR POWER CABLES.
• Replace cover once wiring is completed.
Technical Data
Supply voltages
115 VAC 10%, 230 VAC 10%, 12 VAC/DC 10%
Supply powers
4 VAC (230 V)
Storage temperature
-20 to 80°C (-4 to 176°F)
Operating temperature
0 to 70°C (32 to 158°F)
Probe range
0 to 700°C (32 to 999°F) for thermocouple J 0 to 999°C (32 to 999°F) for thermocouple K, S
Accuracy
Better than 1% full scale
Resolution
1° (3 digits)
Response Time
16 seconds
Display
Red LED, 3-digit and sign
Input
Thermocouple (types J, K or S)
Output
SPDT relay 250 V / 15(5) A 30LRA
Dimensions
76 x 34 x 60 mm (3 x 1.34 x 2.36 in)
Front Protection
IP64
OMEGA ENGINEERING, INC.
1 - 888 - TC - OMEGA USA & Canada 1 - 203 - 359 - 1660 INTERNATIONAL
List of parameters
Description
SP
Set Point
r0
Differential or Hysteresis
r1
Lower Value Set Point
r2
Higher Value Set Point
d0
Cooling or heating control
c0
Minimum stopping time
c2
Output status with probe error
P1
Ambient Probe Adjustment
P5
Ambient Probe Type
H5
Access code to parameters
A0
Alarm 1 Hysteresis
A1
Alarm 1 Threshold
A2
Alarm 1 Exclusion Time
A3
Alarm 1 Type
A4
Alarm 2 Hysteresis
A5
Alarm 2 Threshold
A6
Alarm 2 Exclusion Time
A7
Alarm 2 Type
Parameter descriptions
SP= Set Point. Temperature we wish to regulate the machine (variable
from r1 to r2)
r0= Differential or Hysteresis r1= Lower value for SP r2= Higher value for SP d0= Cooling or heating control
if d0 = Ht and TS is the temperature of ambient probe:
if TS >= SP the load is disconnected if TS <= SP-r0 the load is connected
if d0 = Co then:
if TS <= SP the load is disconnected if TS >= SP+r0 the load is connected
c0= Minimum stopping time of the load c2= Output status with probe error P1= Ambient probe adjustment P5= Ambient probe type
P2= tcJ (J type), P2=tch (K type), P2=tcS (S type)
H5= Access code to parameters (it is set to 00 from factory) A0, A1, A2, A3 = Alarm 1 parameters
If A3=OFF alarm 1 disabled If A3=HI then a high temperature alarm is set:
if TS >=SP+A1 the alarm 1 is activated if TS <=SP+A1-A0 the alarm 1 is de-activated
If A3=LO then a low temperature alarm is set:
if TS <=SP-A1 the alarm 1 is activated
if TS >=SP-A1+A0 the alarm 1 is de-activated The alarm 1 in not activated until the time since instrument is turn on is higher than A2
A4, A5, A6, A7 = Alarm 2 parameters (similar to alarm 1)
Units
Degrees Degrees Degrees Degrees Option Seconds Range Degrees Range Numeric Degrees Degrees Seconds Range Degrees Degrees Seconds Range
Range
r1 to r2 1 to 99 0 to r2 r1 to 999 Co/Ht 0 to 999 On/Off
-30 to 30 tcJ, tch, tcS 0 to 255 1 to 999 0 to 999 0 to 999 OFF,HI,LO 1 to 999 0 to 999 0 to 999 OFF,HI,LO
Parameter Programming
Set Point (SP) is the only parameter the user can access without code protection.
• Press SET. SP text will appear on the display.
• Press SET again. The real value is shown on the display.
• The value can be modified with the UP and DOWN arrows.
• Press SET to enter any new values.
• Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit programming mode.
Access to all code protected parameters.
• Press SET for 8 seconds. The access code value 00 is shown on the display. (Unit comes with code set at 00 from factory).
• With the UP and DOWN arrows, code can be set to user needs.
• Press SET to enter the code. If code is correct, the first parameter label is shown on the display (SP).
• Move to the desired parameter with the UP and DOWN keys.
• Press SET to view the value on the display.
• The value can be modified with the UP and DOWN arrows.
• Press SET to enter the value and exit.
• Repeat until all necessary parameters are modified.
• Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit programming mode.
*The keyboard code can be reset to ZERO by turning off the controller and turning it on again while keeping the SET key depressed.
Led indication, buzzer and display messages
The led OUT indicates if the load is connected or not.
In normal operation, the probe temperature will be shown on the display. In case of alarm or error, the following messages can be shown:
• Er = Memory Error
• oo = Open Probe Error
• -- = Ambient temperature out of range
In case of alarm or error the internal buzzer is activated. The buzzer can be silenced pressing the SET and DOWN arrows at the same time (when a new alarm or error occurs the buzzer sounds again).
Maintenance, cleaning and repair
After final installation of the unit, no routine maintenance is required.
Clean the surface of the display controller with a soft and damp cloth. Never use abrasive detergents, petrol, alcohol or solvents.
All repairs must be made by authorized personnel.
OMEGA ENGINEERING, INC.
1 - 888 - TC - OMEGA USA & Canada 1 - 203 - 359 - 1660 INTERNATIONAL
M-4438/0207
Loading...