M-57
1
⁄8 DIN Digital Panel Meters
For DC Voltage and
Current Inputs
Specifications
Display: 5-digit, 14.2 mm (0.56") red
sunlight readable or standard green
LEDs, (-19999 to 99999)
Power:
AC Versions:
AC Power: 85 to 250 Vac,
50/60 Hz, 15 VA
Isolation: 2300 Vrms for 1 minute
to all inputs and outputs
DC Power: 11 to 36 Vdc, 11 W
(derate operating temperature to
40°C if operating <15 Vdc and
3 plug-in option cards are installed)
AC Power: 24 Vac, ± 10%,
50/60 Hz, 15 VA
Isolation: 500 Vrms for 1 minute to all
inputs and outputs (50V working)
Keypad: 3 programmable function keys,
5 keys total
A/D Converter: 16-bit resolution
Update Rates:
A/D Conversion Rate: 20 readings/s
Step Response: 200 ms max to
within 99% of final readout value
(digital filter and internal zero
correction disabled), 700 ms max
(digital filter disabled, internal zero
correction enabled)
Display Update Rate: 1 to 20 updates/s
The DP63600 Series panel meters
offer many features and
performance capabilities suitable for
a wide range of industrial
applications. These meters accept
universal DC voltage/current inputs.
The optional plug-in output cards
allow the opportunity to configure
the meter for present applications,
while providing easy upgrades for
future needs.
The meters employ a bright,
14.2 mm (0.56") LED display. The
unit is available with a red sunlight
readable or a standard green LED.
The intensity of display can be
adjusted from dark room to sunlight
readable, making it ideal for viewing
in variable light applications.
The meters provide a max and min
reading memory with programmable
capture time. The capture time is
used to prevent detection of false
max or min readings which may
occur during start-up or unusual
process events.
DP63600
Starts at
$
254
⻬ Universal DC Input
⻬ Green Display or
Red Sunlight-Readable
Display
⻬ 5-Digit, 14.2 mm
(0.56") LED
⻬ 4 V (300 Vdc Max) and
5 Current (2A dc Max)
Ranges
⻬ 3 Resistance Ranges—
10 KΩ Max
⻬ Field-Upgradeable
Option Cards
⻬ AC and DC Powered
Versions
⻬ NEMA 4X (IP65)
The meters have 4 setpoint outputs,
implemented on plug-in option
cards.The plug-in cards provide
dual form “C” relays (5A), quad
form “A” (3A), or either quad-sinking
or quad-sourcing open collector
logic outputs. The setpoint alarms
can be configured to suit a variety
of control and alarm requirements.
Communication and bus capabilities
are also available as option cards;
these include RS232, RS485, and
MODBUS®.
Setpoint Output On/Off Delay Time:
0 to 3275 seconds
Analog Output Update Rate:
0 to 10s
Max/Min Capture Delay Time:
0 to 3275 s
Memory: Non-volatile EEPROM
retains all programmable parameters
and display values
Environmental Conditions:
Operating Temperature Range:
0 to 50°C (32 to 122°F) [0 to 45°C
(32 to 113°F) with all 3 plug-in cards
installed]
Storage Temperature Range:
-40 to 60°C (-40 to 140°F)
Operating and Storage Humidity:
0 to 85% max RH non-condensing
Altitude: Up to 2000 m (6562')
Connections: High-compression,
cage-clamp terminal block
Construction: This unit is rated for
NEMA 4X (IP65) outdoor use, IP20
touch-safe, Installation Category II,
Pollution Degree 2, 1-piece bezel/case,
flame-resistant, synthetic rubber
keypad—panel gasket and mounting
clip included
Weight: 295 g (10.4 oz)
Excitation Power
Transmitter Power: 24 Vdc, ±5%,
regulated, 50 mA max
Reference Voltage: 2 Vdc, ±2%
Compliance: 1 kΩ load min (2 mA max)
Temperature Coefficient:
40 ppm/°C max
Reference Current: 1.75 mAdc, ±2%
Compliance: 10 kΩ load max
Temperature Coefficient:
40 ppm/°C max
Output Modules: For complete
specifications, see LDP63100 Series,
page M-100
DP63600-DC, $254,
shown smaller
than actual size.
Panel Punches
Available, Visit
omega.com/panelpunches