Omega Products DP63500-T-GN-LV User Manual

1
8 DIN Digital Panel
Temperature Meters For
Thermocouple and RTD Inputs
DP63500-T Series
Starts at
$
243
Thermocouple and RTD
Panel Meter
5-Digit, 14.2 mm
(0.56") LED
Green or Red Sunlight
Readable Display
Conforms to ITS-90
Standards
°F or °C Unit Overlay
With Backlight
Field Upgradeable Option
Cards
NEMX 4X (IP65)
The DP63500-T Series panel meters offer many features and performance capabilities suitable for a wide range of industrial applications. These meters accept thermocouple or RTD inputs. The optional plug-in output cards allow the opportunity to configure the meter for present applications, while providing easy upgrades for future needs.
The meters have a bright, 14.2 mm (0.56") LED display. The unit is available with a red, sunlight­readable or a standard green LED. The intensity of display can be adjusted from dark room to sunlight readable, making it ideal for viewing in variable light applications.
The meters provide a maximum and minimum reading memory with programmable capture time. The capture time is used to prevent detection of false max or mi readings which may occur during start-up or unusual process events. The meters have 4 setpoint outputs, implemented on plug-in option cards.
Panel Punches
Available, Visit
omega.com/
panelpunches
DP63500-T, $243, shown actual size.
The plug-in cards provide dual form “C” relays (5 A), quad form “A” (3 A), or either quad-sinking or quad­sourcing open collector logic outputs. The setpoint alarms can be configured to suit a variety of control and alarm requirements. Communication and bus capabilities are also available as option cards; these include RS232, RS485, and MODBUS®.
Specifications
Display: 5-digit, 14.2 mm (0.56") red
Power:
AC Versions:
AC Power: 85 to 250 Vac,
50/60 Hz, 15 VA Isolation: 2300 Vrms for 1 minute
to all inputs and outputs
DC Power: 11 to 36 Vdc, 11 W (derate operating temperature to 40°C if operating <15 Vdc and 3 plug-in option cards are installed)
AC Power: 24 Vac, ± 10%, 50/60 Hz, 15 VA
Isolation: 500 Vrms for 1 minute to all inputs and outputs (50V working)
Keypad: 3 programmable function keys, 5 keys total
A/D Converter: 16-bit resolution Update Rates:
A/D Conversion Rate: 20 readings/s
M-52
Step Response: 200 ms max to
within 99% of final readout value (digital filter and internal zero correction disabled), 700 ms max (digital filter disabled, internal zero correction enabled)
Display Update Rate:
1 to 20 updates/s
Setpoint Output On/Off Delay Time:
0 to 3275 seconds
Analog Output Update Rate: 0 to 10 s Max/mi Capture Delay Time: 0 to 3275 s Ice Point Compensation: User value
(0.00 to 650.00 µV/°C) Memory: Non-volatile EEPROM retains
all programmable parameters and display values
Environmental Conditions:
Operating Temperature Range:
0 to 50°C (32 to 122°F) [0 to 45°C (32 to 113°F) with all 3 plug-in cards installed]
Storage Temperature Range:
-40 to 60°C (-40 to 140°F)
Operating and Storage Humidity:
0 to 85% max RH non-condensing
Altitude: Up to 2000 m (6563') Connections: High-compression,
cage-clamp terminal block Construction: This unit is rated for
NEMA 4X (IP65) outdoor use, IP20 touch-safe, Installation Category II, Pollution Degree 2, 1-piece bezel/case, flame-resistant, synthetic rubber keypad—panel gasket and mounting clip included
Weight: 295 g (10.4 oz)
M
Thermocouple Inputs
Resolution: Variable: 0.1, 0.2, 0.5, or 1, 2, or 5 degrees Scale: °F or °C Offset Range: -19,999 to 99,999 display units
Input Impedance: 20 M Lead Resistance Effect: 0.03 µV/ Maximum Continuous Overvoltage: 30 V
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 60°C)
-200 to 400°C (-328 to 752°F)
-270 to -200°C (-454 to -328°F) 1.2°C** 2.1°C
-200 to 871°C (-328 to 1600°F)
-270 to -200°C (-454 to -328°F) 1.0°C** 2.4°C
-200 to 760°C (-328 to 1400°F) 1.1°C 2.3°C
-200 to 1372°C (-328 to 2502°F)
-270 to -200°C (-454 to -328°F) 1.3°C** 3.4°C
-50 to 1768°C (-58 to 3214°F) 1.9°C 4.0°C
-50 to 1768°C (-58 to 3214°F) 1.9°C 4.0°C 100 to 300°C (100 to 572°F) 3.9°C 5.7°C
300 to 1820°C (572 to 3308°F) 2.8°C 4.4°C
-200 to 1300°C (-328 to 2372°F)
-270 to -200°C (-454 to -328°F) 1.3°C** 3.1°C 0 to 2315°C (32 to 4199°F) 1.9°C 6.1°C
After 20 minute warm-up. Accuracy is specified in 2 ways—accuracy over an 18 to 28°C (64 to 82°F) in a 15 to 75% RH environment and
*
accuracy over a 0 to 50°C (32 to 122°F) in a 0 to 85% RH (non-condensing) environment. Accuracy specified over the 0 to 50°C (32 to 122°F) operating range includes meter tempco and ice point tracking effects. The specification includes the A/D conversion errors, linearization conformity, and thermocouple ice point compensation. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
The accuracy over the interval -270 to -200°C (-454 to -328°F) is a function of temperature, ranging from 1°C at -200°C and degrading to
**
7°C at -270°C. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
RTD Inputs
Type: 3- or 4-wire, 2-wire can be compensated for
lead wire resistance
Excitation Current:
100 Range: 165 µA 10 Range: 2.6 mA
Lead Resistance:
100 Range: 10 /lead max 10 Range: 3 /lead max
RTD Inputs Table
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 50°C) 100 Pt alpha = 0.00385 -200 to 850°C 100 Pt alpha = 0.003919 -200 to 850°C 120 Nickel alpha = 0.00672 -80 to 260°C 10 Ω Copper alpha = 0.00427 -100 to 260°C
After 20 minute warm-up. Accuracy is specified in 2 ways—accuracy over an 18 to 28°C (64 to 82°F) in a 15 to 75% RH environment and
*
accuracy over a 0 to 50°C (32 to 122°F) in a 0 to 85% RH (non-condensing) environment. Accuracy specified over the 0 to 50°C (32 to 122°F) operating range includes meter tempco and ice point tracking effects. The specification includes the A/D conversion errors, linearization conformity, and thermocouple ice point compensation. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
(-328 to 1562°F) (-328 to 1562°F) (-112 to 500°F)
(-148 to 500°F)
0.4°C 1.6°C
0.4°C 1.6°C
0.2°C 0.5°C
0.4°C 0.9°C
Custom Range
Custom Range: Up to 16 data point pairs Input Range: -10 to 65 mV
0 to 400 : High range 0 to 25 : Low range
Display Range: -19999 to 99999
Custom Range Table
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 50°C) Custom mV Range -10 to 65 mV (1 µV res) 0.02% of rdg + 4 µV 0.12% of rdg + 5 µV Custom 100 Range 0 to 400 (10 M res) 0.02% of rdg + 0.04 0.12% of rdg + 0.05 Custom 10 Range 0 to 25 (1 M res) 0.04% of rdg + 0.005 0.20% of rdg + 0.007
After 20 minute warm-up. Accuracy is specified in 2 ways—accuracy over an 18 to 28°C (64 to 82°F) in a 15 to 75% RH environment and
*
accuracy over a 0 to 50°C (32 to 122°F) in a 0 to 85% RH (non-condensing) environment. Accuracy specified over the 0 to 50°C (32 to 122°F) operating range includes meter tempco and ice point tracking effects. The specification includes the A/D conversion errors, linearization conformity, and thermocouple ice point compensation. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
M-53