Omega Products DP63000A-E User Manual

M-43
Digital Panel Meters
For Temperature, Process,
Voltage and Current
The DP63000 Series provides the user the ultimate in flexibility, from its complete user programming to the optional setpoint control and communication capability. The DP63000-TC accepts a thermocouple input. The DP63000-RTD accepts an RTD input and both provide a temperature display in Celcius or Farenheit. The meter also features minimum and maximum display capture, display offset, °F or °C indicator, and programmable user input. The display can be toggled either manually or automatically between the selected displays. Other models include process, DC voltage or current input signal and provides a display in the desired unit of measure.
DP63000
Starts at
$
125
Thermocouple InputsRTD InputsProgrammable
Temperature Offset
Selectable °F or °C with
1 or 0.1 Degree Resolution
3 Selectable
Process Ranges
0 to 10 Vdc, 0 to 20 mA,
0 to 50 mA
4 Selectable DC
Voltage Ranges
0 to 200 mV, 2 V,
20 V, 200 V
4 Selectable DC
Current Ranges
200 mA, 2 mA,
20 mA, 200 mA
LCD, Reflective or
LCD with Green/Red LED Backlight
12.2 mm (0.48") H Digits Optional Alarm
Output Modules
Optional Serial
Communication Modules (RS232 or RS485)
Operates from 9 to 28 Vdc
Power Source (85 to 250 Vac Optional Supply)
Display Color
Change Capability at Setpoint Output
NEMA 4X/IP65 Sealed
Front Bezel
Minimum and Maximum
Display Capture
The DP63000 Series display has
12.2 mm (0.48") H digits. The LCD model is available in 2 versions, reflective and red/green backlight. The backlight version is user­selectable for the desired color and also has variable display intensity. The capability of the DP63000 can be easily expanded with the addition of option modules. Setpoint capability is field-installable with the addition of the setpoint output modules. Serial communications capability for RS232 or RS485 is added with a serial option module.
The DP63000 can be powered from an optional power supply that attaches directly to the back of a DP63000. The power supply is powered from 85 to 250 Vac and provides up to 400 mA to drive the unit and sensors.
DP63000B-E, $135, shown smaller than actual size.
DP63000A-E, $125, shown smaller than actual size.
DP6-COM1, DPS-RLYO2, $30, shown smaller than actual size.
M-44
M
Common Specifications
Display: 5-digit LCD, 12.2 mm (0.48") high digits
DP63000A: Reflective LCD with full viewing angle DP63000B: Transmissive LCD with selectable red or
green LED backlight, viewing angle optimized; display color change capability with output state when using an output module
Response Time: 500 ms Memory: Non-volatile E
2
PROM memory retains all programming parameters and max/min values when power is removed
Power: Input voltage range is 9 to 28 Vdc with short circuit and input polarity protection (for 85 to 250 Vac power operation, must use a model DP6-MLPS1 or a Class 2 or SELV-rated power supply)
Normal Mode Rejection: 60 dB 50/60 Hz
Input Current Input Current
@ 9 Vdc @ 9 Vdc Without With
Model No. Display Color DP6-RLY0 DP6-RLY0 DP63000A –– 10 mA 40 mA DP63000B Red
(max intensity) 85 mA 115 mA
DP63000B Green
(max intensity) 95 mA 125 mA
Environmental Conditions
Operating Temperature Range for DP63000A-I: -35 to 75°C (-31 to 167°F)
Operating temperature range depends on display color and intensity level as per below:
Storage Temperature:
-35 to 85°C (-31 to 185°F) Operating and Storage Humidity: 0 to 85% max relative
humidity (non-condensing)
Altitude: Up to 2000 meters Construction: This unit is rated for NEMA 4X/IP65
requirements for indoor use, Installation Category I, Pollution Degree 2; high-impact plastic case with clear viewing window; panel gasket and mounting clip included
Weight:100 g (3.2 oz)
Intensity
Level Temperature
1 and 2 -35 to 75°C (-31 to 167°F)
Display 3 -35 to 70°C (-31 to 158°F)
4 -35 to 60°C (-31 to 140°F) 5 -35 to 50°C (-31 to 122°F)
Green 1 and 2 -35 to 75°C (-31 to 167°F) Display 3 -35 to 65°C (-31 to 149°F)
4 -35 to 50°C (-31 to 122°F) 5 -35 to 35°C (-31 to 95°F)
Thermocouple Inputs
Readout: Thermocouple Input Resolution: 1 or 0.1° Scale: °F or °C Offset Range: -999 to 9999 display units Isolation: TC+ and TC- terminals are
not electrically isolated from the power supply or optional comms cards
Maximum Input Voltage: 30 Vdc, TC+ to TC Maximum Input Voltage TC-: 3 Vdc max with respect
to common
Input Accuracy Accuracy @
Type Range @ 23°C ±°C* -35 to 75°C ±°C*
-200 to 400°C 2.3 5.8
(-328 to 752°F)
-200 to 871°C 2.7 4.9
(-328 to 1600°F)
-200 to 760°C 1.9 4.3
(-328 to 1400°F)
-200 to 1372°C 2.3 5.8
(-328 to 2502°F)
-50 to 1768°C 4.5 15.0
(-58 to 3214°F)
-50 to 1768°C 4.5 15.0
(-58 to 3214°F)
100 to 300°C 9.1 <540°C 42.6 <540°C
(392 to 3308°F) 4.5 >540°C 15.0 >540°C
-200 to 1300°C 2.8 8.1
(-328 to 2372°F)
mV -10.00 to 65.00 0.02 mV 0.08 mV
Red Display
Green Display
Accuracy* Accuracy*
Input Type Range (18 to 28°C) (0 to 50°C) 100 Ω Pt
alpha = .00385 -200 to 850°C 0.4°C 1.6°C 100 Ω Pt
alpha = .00392 -200 to 850°C 0.4°C 1.6°C 120 Ω Nickel
alpha = .00672 -80 to 260°C 0.2°C 0.5°C 10 Ω Copper
alpha = .00427 -100 to 260°C 0.4°C 0.9°C
RTD Inputs
Readout: RTD input Resolution: 1 or 0.1° Scale: °F or °C Offset Range: -19999 to 19999 display units Isolation: Input and EXC terminals are not electrically isolated
from the power supply or optional communications cards
Maximum Input Voltage: 30 Vdc Type: 2-, 3- or 4-wire
Excitation Current:
100 Ω Range: 165 µA 10 Ω Range: 2.5 mA
Lead Resistance:
100 Ω Range: 10 Ω/lead max 10 Ω Range: 3 Ω/lead max
Balanced Lead Resistance: Automatically compensated
up to maximum per lead Unbalanced Lead Resistance: Uncompensated
* After 20 minute warm-up. Accuracy is specified in 2 ways: accuracy @ 23°C and 15 to 75% RH environment, and accuracy over a -35 to 75°C and 0 to 85% RH (non condensing) environment. Accuracy specified over the -35 to 75°C operating range includes meter tempco and cold junction tracking effects.
* After 20 minute warm-up. Accuracy is specified in 2 ways: accuracy at 23°C and 15 to 75% RH environment, and accuracy over a -35 to 75°C and 0 to 85% RH (non condensing) environment. Accuracy specified over the -35 to 75°C operating range includes meter tempco effects. The specification includes the A/D conversion errors and linearization conformity. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.