1
⁄8 DIN Temperature 
Panel Meter
With Optional USB  
Communications
DP6070 Series
U Modular USB, 
RS232, RS485 Serial 
Communication Options 
and Relays 
U J, K, T, E, R, S, B, N, C 
Thermocouples 
U 100 or 1000 Ω Platinum, 
10 Ω Copper, 120 Ω 
Nickel RTDs 
U 1 or 0.1° Resolution  
U Automatic Cold 
Junction Compensation 
U NEMA 4X (IP65) Front  
U Universal 85 to 265 Vac 
or 12/24 Vdc Input Power 
U Large Dual-Line 
6-Character Display,  
15 and 12 mm  
(0.60 and 0.46") 
U Sunlight Readable 
Display Models 
U 2 or 4 Relays Plus 
Isolated 4 to 20 mA 
Output Options 
U External 4-Relay and 
Digital I/O Expansion 
Modules 
U Free Software for 
Operation, Monitoring 
and Programming
The DP6070 temperature 
meter boasts specifications and 
functionality that clearly makes 
it one of the most advanced 
temperature meters available. 
It’s dual-line 6-character display, 
function keys, and optional 
expansion modules are only a few 
of the special features available.
The DP6070 accepts many  
thermocouple types and RTDs and 
can be configured to have either 
a 1° or 0.1° display resolution 
on any type of sensor input. The 
lower display makes configuration 
simpler. The display itself is quite 
configurable. There are many 
relay functions for up to 8 relays; 
including an Interlock Relay 
function. The 4 to 20 mA output 
can represent up to 12 different 
parameters/variables. This makes 
the DP6070 one of the most 
versatile meters on the market. 
Sunlight readable display models 
have an extraordinarily bright 
LED display. The upper display 
can be programmed to indicate 
current temperature, maximum or 
minimum temperature, alternating 
maximum/minimum temperatures, 
one of eight alarm set points, or 
MODBUS input. The lower display 
can also be configured to display 
engineering units, set points, 
user defined legends, or simply 
turned off. Input selection and 
configuration are conveniently 
set up via rear switches and 
front panel programming. Three 
levels of password protection 
help maintain the reliability of the 
programming.
General Specifications
Display: Both displays are 6 digits 
(-99999 to 999999), red LEDs with 
leading zero blanking 
 Upper Display: 15 mm (0.60") high  
 Lower Display: 12 mm (0.46") high
Display Intensity: 8 intensity levels  
Display Update Rate: 5/second 
(200 ms) 
Overrange: Display flashes 999999  
Underrange: Display flashes -99999 
DP6070 shown smaller 
than actual size.
M-1
Display Assignment: The upper 
and lower displays may be assigned  
to PV1, PV2, PCT (percent),  
max/min, alternate max and min,  
set points, units (lower display only), 
or MODBUS input 
Front Panel: NEMA 4X (IP65)  
Programming Methods: 4 front 
panel buttons, digital inputs, PC and  
software, MODBUS registers, or 
cloning using copy function 
Noise Filter: Programmable from  
2 to 199 (0 will disable filter) 
Filter Bypass: Programmable from 
0.1 to 99.9% of calibrated span 
Recalibration: Calibrated at the 
factory. Recalibration is recommended 
at least every 12 months
Max/Min Display: Max (peak)/min 
(valley) readings reached by the 
process are stored until reset by  
the user or until power to the meter  
is cycled 
Password: 3 programmable 
passwords restrict modification of 
programmed settings; Pass 1: Allows 
use of function keys and digital 
inputs; Pass 2: Allows use of function 
keys, digital inputs and editing set/ 
reset points; Pass 3: Restricts all 
programming, function keys, and 
digital inputs
Non-Volatile Memory: All 
programmed settings are stored in 
non-volatile memory for a minimum  
of ten years if power is lost 
Power Options: 85 to 265 Vac  
50/60 Hz, 90 to 265 Vdc, 20 W 
maximum, or jumper selectable  
12/24 Vdc ±10%, 15 W max 
Fuse (External, Required): UL 
recognized, 5 A max, slow blow; up  
to 6 meters may share one 5 A fuse 
M

Isolated Transmitter Power Supply: 
24 Vdc ±5% @ 200 mA maximum 
(standard), (12/24 Vdc powered 
models rated @ 100 mA maximum); 
5 or 10 Vdc @ 50 mA maximum, 
selectable with internal jumper J4 
Normal Mode Rejection: Greater 
than 60 dB at 50/60 Hz 
Isolation: 4 kV input/output-to-power 
line; 500V input-to-output or  
output-to-P+ supply
Overvoltage Category: Installation 
overvoltage category II, local level with 
smaller transient overvoltages than 
installation overvoltage category III
Operating Temperature Range: 
-40 to 65°C (-40 to 149°F) 
Storage Temperature Range: 
-40 to 85°C (-40 to 185°F) 
Relative Humidity: 0 to 90% 
non-condensing 
Connections: Removable screw 
terminal blocks accept 12 to  
22 AWG wire, RJ45 for external  
relays, digital I/O, and serial 
communication adaptors 
Enclosure: 
plastic, UL 94V-0, color: black 
Mounting: 
required: 92 x 45 mm (3.622 x 
1.772"); two panel mounting bracket 
assemblies are provided 
Tightening Torque: Screw terminal 
connectors: 5 lb-in (0.56 Nm) 
Overall Dimensions:  
119 W x 62 H x 143 mm D 
(4.68 x 2.45 x 5.64")
Weight: 269 g (9.5 oz) 
1
⁄8 DIN, high impact 
1
⁄8 DIN panel cutout 
Temperature Input 
Input: Thermocouple J, K, T, E, R, S, 
B, N, C; RTD 100 Ω platinum (0.00385 
and 0.00392 curves), 10 Ω copper, 
120 Ω nickel, 1000 Ω platinum 
Input Impedance: Greater than 100 kΩ  
Offset Adjust: User programmable 
offset adjust ±50.0 degrees 
Temperature Drift: ±2°C maximum 
from 0 to 65°C ambient temperature; 
±4°C maximum from -20 to 0°C 
ambient temperature 
Sensor Break: Display flashes 
“open”, relays can be programmed to 
go “on”, “off”, or to “ignore” (detected 
as an upscale condition)
Averaging: Up to 10 RTDs connected 
in parallel can be averaged 
Accuracy and Range: See table above
Relays 
Rating: 2 or 4 SPDT (Form C) internal 
and/or 4 SPST (Form A) external; 
rated 3 A @ 30 Vdc and 125/250 Vac 
resistive load; 1/14 HP (≈ 50 W) 
@ 125/250 Vac for inductive loads 
such as contactors, solenoids, etc. 
Noise Suppression: Recommended 
for each relay contact switching  
inductive loads
Deadband: 0 to 100% of span, user 
programmable 
High or Low Alarm: User may 
program any alarm for high or low trip 
point; unused alarm LEDs and relays 
may be disabled (turned off)
Relay Operation: Automatic (nonlatching), latching (requires manual 
acknowledge), sampling (based on 
time), pump alternation control  
(2 to 8 relays), off (disable unused 
relays and enable interlock feature, 
manual on/off control mode) 
Time Delay: 0 to 999.9 seconds, 
on and off relay time delays; 
programmable and independent for 
each relay 
Fail-Safe Operation: Programmable 
and independent for each relay 
Note: Relay coil is energized in non-alarm 
condition. In case of power failure, relay 
will go to alarm state.
Auto Initialization: When power is 
applied to the meter, relays will reflect 
the state of the input to the meter
Serial Communications 
Protocol: MODBUS RTU  
Meter Address/Slave ID: 1 - 247  
Baud Rate: 300 to 19,200 bps  
Transmit Time Delay: Programmable 
between 0 and 199 ms 
Data: 8 bit (1 start bit, 1 or 2 stop bits)  
Parity: Even, odd, or none with 1 or 2 
stop bits 
Byte-to-Byte Timeout: 
0.01 to 2.54 seconds 
Turn Around Delay: 
Less than 2 ms (fixed) 
Isolated 4 to 20 mA 
Transmitter Output 
Output Source: Process variable (PV), 
max, min, set points 1 through 8, manual 
control setting, or MODBUS input
Scaling Range: 1.000 to 23.000 mA 
for any display range 
Factory Calibration: 4.000 to 
20.000 = 4 to 20 mA output 
Analog Output Programming: 
23.000 mA maximum for all 
parameters: overrange, underrange, 
max, min, and break 
Accuracy: ± 0.1% of span ± 0.004 mA  
Temperature Drift: 0.4 µA/°C maximum 
from 0 to 65°C ambient, 0.8 µA/°C 
maximum from -40 to 0°C ambient 
Note: Analog output drift is separate from 
input drift. 
Isolated Transmitter Power Supply: 
Terminals I+ & R: 24 Vdc ± 5% @  
40 mA maximum, may be used to 
power the 4 to 20 mA output or  
other devices 
External Loop Power Supply:  
35 Vdc maximum 
Output Loop Resistance:  
 24 Vdc Power Supply:  
 10Ω minimum, 700Ω maximum  
 35 Vdc (External) Power Supply:  
 100 Ω minimum, 1200 Ω maximum
Digital I/O Expansion 
Module 
Channels: 4 digital inputs and 
4 digital outputs per module 
System: Up to 2 modules for a total 
of 8 inputs and 8 outputs 
Digital Input Logic: 
 High: 3 to 5 Vdc 
 Low: 0 to 1.25 Vdc 
Digital Output Logic:  
 High: 3.1 to 3.3 Vdc 
 Low: 0 to 0.4 Vdc 
Source Current: 10 mA maximum  
Sink Current: 1.5 mA minimum  
+5 V Terminal: To be used as pull-up 
for digital inputs only 
4-Relay Expansion Module 
Relays: 4 Form A (SPST) rated 3 A 
@ 30 Vdc and 125/250 Vac resistive 
load; 1/14 HP (≈ 50 W) @ 125/250 
Vac for inductive loads
Type Range °C (°F) Accuracy
-129 to 1093 (-200 to 2000) ±1°C
-129 to 1316 (-200 to 2400) ±1°C
-129 to 400 (-200 to 752) ±1°C
-129 to 982 (-200 to 1800) ±1°C
-46 to 1649 (-50 to 3000) ±2°C
400 to 1816 (752 to 3300) ±2°C
-73 to 1260 (-100 to 2300) ±2°C
0 to 2260 (32 to 4100) ±2°C
10Ω Copper -200 to 260 (-328 to 500) ±0.1°C
100Ω Pt -200 to 850 (-328 to 1562) ±0.4°C
120Ω Nickel -79 to 260 (-110 to 500) ±0.1°C
1000Ω Pt -200 to 482 (-328 to 900) ±0.4°C
M-2

Meter Copy 
The Copy feature is used to copy (or 
clone) all the settings from one DP6070  
to other DP6070 meters in about 
20 seconds! The Copy function is a 
standard feature on all meters. It does 
not require a communications adapter, 
only an optional cable assembly, model 
number DPA1200. See the ordering 
information for complete details
NEMA 4X Field Enclosures 
Thermoplastic NEMA 4X 
enclosures are constructed for 
either indoor or outdoor use.
DP6070 with DPA2812 NEMA 4X 
field enclosure, shown smaller 
than actual size.
Accessories
Model No.  Description
DPA1004
DPA1044
DPA1232
DPA1485
DPA8008
DPA7485-I
DPA7485-N
DPA8232-N
DPA8485-I
DPA8485-N
DPA1002
DPA1200
DPA2811
DPA2812
Comes complete with 2 side mounting brackets, software, and operator’s manual. 
Ordering Example: DP6070-6R2, temperature panel meter with 2 relays, and DPA8008, USB serial adaptor.  
OCW-2, OMEGACARESM extends standard 3-year warranty to a total of 5 years.
 4-relay expansion module - field installable
 4 digital inputs and 4 digital outputs module - field installable
 RS232 serial adaptor - field installable
 RS485 serial adaptor - field installable
 USB serial adaptor - field installable
 RS232 to RS422/485 isolated converter - field installable
 RS232 to RS422/485 non-isolated converter - field installable
 USB to RS232 non-isolated converter - field installable
 USB to RS422/485 isolated converter - field installable
 USB to RS422/485 isolated converter - field installable
 DIN rail mounting kit for 2 expansion modules
 Meter copy cable
 Plastic NEMA 4X enclosure for one DP6070 temperature meter
 Plastic NEMA 4X enclosure for two DP6070 temperature meters
Model No. Description
Standard 85 to 265 Vac Models
DP6070-6R0
DP6070-6R2
DP6070-6R3
DP6070-6R4
DP6070-6R5
DP6070-6R7
Standard 12/24 Vdc Low Voltage Models
DP6070-7R0
DP6070-7R2
DP6070-7R3
Sunlight Readable Models, 85 to 265 Vac
DP6070-6H0
DP6070-6H2
DP6070-6H3
Sunlight Readable Models, 12/24 Vdc Low Voltage
DP6070-7H0
DP6070-7H2
DP6070-7H3
Temperature panel meter
Temperature panel meter with 2 relays
Temperature panel meter with 4 to 20 mA output
Temperature panel meter with 4 relays
Temperature panel meter with 2 relays and 4 to 20 mA output
Temperature panel meter with 4 relays and 4 to 20 mA output
Temperature panel meter
Temperature panel meter with 2 relays
Temperature panel meter with 4 to 20 mA output
Temperature panel meter
Temperature panel meter with 2 relays
Temperature panel meter with 4 to 20 mA output
Temperature panel meter
Temperature panel meter with 2 relays
Temperature panel meter with 4 to 20 mA output
M-3
To Order Visit omega.com/dp6070 for Pricing and Details