Omega Products DP6060-6H0 User Manual

1
8 DIN Dual Input Process
Panel Meter
With Optional USB Communications
DP6060 Series
U Modular USB,
RS232, RS485 Serial Communication Options and Relays
U Math Functions:
Addition, Difference, Average, Multiplication, Division, Min, Max, Weighted Average, Ratio, Concentration, and More
U 0 to 20 mA, 4 to 20 mA,
0 to 5V, 1 to 5V, and ±10V Inputs
U Large Dual-Line 6-Digit
Display, 15 and 12 mm (0.60 and 0.46")
U Sunlight Readable
Display Models
U NEMA 4X (IP65) Front U Universal 85 to 265 Vac,
or 12/24 Vdc Input Power Models
U Isolated 24 Vdc @
200 mA Transmitter Power Supply
U Free Software for
Operation, Monitoring, and Programming
The DP6060 Series process meter combines two independently programmed analog inputs with powerful math functions to make an advanced meter capable of handling complex math requirements common in the process industry. Various math functions may be applied to the inputs including addition, difference, average, multiplication, division, ratio, and more. A customizable dual-line display allows a wide variety of input variables, math calculations, or units and tags to be displayed
based on your application needs. Sunlight readable display models have an extraordinarily bright LED display. The DP6060 has two red LED displays, an upper display 15 mm (0.60") high, and a lower display 12 mm (0.46") high. Each display is a full 6 digits (-99999 to
999999). The displays can be set up to read input channels (A or B), math function channel C, toggle between A & B, B & C, A & C, A & B & C, toggle between channels A, B, or C & units, the max/min of any of the channels, including the math channel (C), set points, gross (without tare) or net (with tare) and gross values of channel A or B, or the MODBUS input. No jumpers to set for input selection. All setup and programming are done via the front panel. Three levels of password protection help maintain the reliability of the programming. The Copy feature is used to copy (or clone) all the settings from one DP6060 to other meters in about 20 seconds! The Copy function is a standard feature on all meters. It does not require a communications adaptor, only an optional cable assembly. The DP6060 minimizes the menu selections by auto-detecting the installed options to determine what menu navigation is required.
General Specifications
Display: Both displays are 6 digits
(-99999 to 999999), red LEDs with leading zero blanking Upper Display: 15 mm (0.60") high Lower Display: 12 mm (0.46") high
M-1
Display Intensity: 8 intensity levels Display Update Rate: 5/second
(200 ms)
Overrange: Display flashes 999999 Underrange: Display flashes -99999 Display Assignment: The upper
and lower displays may be assigned to process values for Channels A (Ch-A), B (Ch-B), or C (Ch-C), toggle between (Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch-A, Ch-B, & Ch-C), toggle between Channel and units, show channel gross value (no tare) or toggle net (tare) and gross values, show relay set points, max and min values, or MODBUS input; the second display may also be set to show engineering units or be off, with no display
Front Panel: NEMA 4X (IP65) Programming Methods: 4 front
panel buttons, digital inputs, PC and software, MODBUS registers, or cloning using copy function
Noise Filter: Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: Programmable from
0.1 to 99.9% of calibrated span Recalibration: Calibrated at the
factory. Recalibration is recommended at least every 12 months
Max/Min Display: Max (peak)/min (valley) readings reached by the process are stored until reset by the user or until power to the meter is cycled
Password: 3 programmable passwords restrict modification of programmed settings; Pass 1: Allows use of function keys and digital inputs; Pass 2: Allows use of function keys, digital inputs and editing set/ reset points; Pass 3: Restricts all programming, function keys, and digital inputs
M
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost
Power Options: 85 to 265 Vac 50/60 Hz, 90 to 265 Vdc, 20 W maximum, or jumper selectable 12/24 Vdc ±10%, 15 W maximum
Fuse (External, Required): UL recognized, 5 A maximum, slow blow; up to 6 meters may share one 5 A fuse
Isolated Transmitter Power Supply: 24 Vdc ±5% @ 200 mA maximum (standard), (12/24 Vdc powered models rated @ 100 mA maximum); 5 or 10 Vdc @ 50 mA maximum, selectable with internal jumper J4
Normal Mode Rejection: Greater than 60 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line; 500 V input-to-output or output-to-P+ supply
Overvoltage Category: Installation overvoltage category II; local level with smaller transient overvoltages than installation overvoltage category III
Operating Temperature Range:
-40 to 65°C Storage Temperature Range:
-40 to 85°C Relative Humidity: 0 to 90%
non-condensing Connections: Removable screw
terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters
Enclosure: UL 94V-0, color: black
Mounting: required: 92 x 45 mm (3.622 x 1.772"); two panel mounting bracket assemblies are provided
Tightening Torque: Screw terminal connectors: 5 lb-in (0.56 Nm)
Overall Dimensions: 119 W x 62 H x 143 mm D (4.68 x 2.45 x 5.64")
Weight: 269 g (9.5 oz)
1
8 DIN, high impact plastic,
1
8 DIN panel cutout
Dual Process Input
Inputs: 2 inputs, each separately, field
selectable: 0 to 20, 4 to 20 mA, 10V (0 to 5, 1 to 5, 0 to 10V), MODBUS PV (slave)
Channels: Channel A, Channel B, Channel C (math channel)
Accuracy: ±0.03% of calibrated span ±1 count, square root and programmable exponent accuracy range: 10 to 100% of calibrated span
Temperature Drift: 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C maximum from -40 to 0°C ambient
Signal Input Conditioning: Linear, square root, programmable exponent, or round horizontal tank volume calculation
Multi-Point Linearization: 2 to 32 points for PV or PV1; 2 to 8 points for PV2 (dual-scale level feature)
Programmable Exponent:
1.0001 to 2.9999 Low-Flow Cutoff: 0 to 999999
(0 disables cutoff function) Decimal Point: Up to 5 decimal
places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd
Calibration Range: 4 to 20 mA: Minimum span; input 1 and input 2: 0.15 mA ±10 V: Minimum span; input 1 and 2: 0.10V An Error message will appear if input 1 and input 2 signals are too close together
Input Impedance: Voltage Ranges: Greater than 500 kΩ Current Ranges: 50 to 100 Ω (depending on resettable fuse impedance)
Input Overload: Current input protected by resettable fuse, 30 Vdc max; fuse resets automatically after fault is removed
Relays
Rating: 2 or 4 SPDT (Form C) internal
and/or 4 SPST (Form A) external; rated 3 A @ 30 Vdc and 125/250 Vac resistive load; 1/14 HP ( 50 W) @ 125/250 Vac for inductive loads such as contactors, solenoids, etc.
Noise Suppression: Recommended for each relay contact switching inductive loads
Deadband: 0 to 100% of span, user programmable
High or Low Alarm: User may program any alarm for high or low trip point; unused alarm LEDs and relays may be disabled (turned off)
Relay Operation: Automatic (non­latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), off (disable unused relays and enable interlock feature, manual on/off control mode)
Time Delay: 0 to 999.9 seconds, on and off relay time delays; programmable and independent for each relay
Fail-Safe Operation: Programmable and independent for each relay
Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter
Serial Communications
Protocol: MODBUS RTU Meter Address/Slave ID: 1 - 247
M-2
Baud Rate: 300 to 19,200 bps Transmit Time Delay: Programmable
between 0 and 199 ms
Data: 8 bit (1 start bit, 1 or 2 stop bits) Parity: Even, odd, or none with 1 or
2 stop bits Byte-to-Byte Timeout:
0.01 to 2.54 seconds Turn Around Delay:
Less than 2 ms (fixed)
Isolated 4 to 20 mA Transmitter Output
Output Source: Process variable (PV),
max, min, set points 1 through 8, manual control setting, or MODBUS input
Scaling Range: 1.000 to 23.000 mA for any display range
Factory Calibration: 4.000 to
20.000 = 4 to 20 mA output Analog Output Programming:
23.000 mA maximum for all parameters: overrange, underrange, max, min, and break
Accuracy: ± 0.1% of span ± 0.004 mA Temperature Drift: 0.4 µA/°C
maximum from 0 to 65°C ambient,
0.8 µA/°C maximum from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply: Terminals I+ & R: 24 Vdc ± 5% @ 40 mA maximum, may be used to power the 4 to 20 mA output or other devices
External Loop Power Supply: 35 Vdc maximum
Output Loop Resistance: 24 Vdc Power Supply: 10Ω minimum, 700Ω maximum 35 Vdc (External) Power Supply: 100 Ω minimum, 1200 Ω maximum
Digital I/O Expansion Module
Channels: 4 digital inputs and
4 digital outputs per module System: Up to 2 modules for a total of
8 inputs and 8 outputs Digital Input Logic:
High: 3 to 5 Vdc Low: 0 to 1.25 Vdc
Digital Output Logic: High: 3.1 to 3.3 Vdc Low: 0 to 0.4 Vdc
Source Current: 10 mA maximum Sink Current: 1.5 mA minimum +5 V Terminal: To be used as pull-up
for digital inputs only
4-Relay Expansion Module
Relays: 4 Form A (SPST) rated 3 A @
30 Vdc and 125/250 Vac resistive load; 1/14 HP ( 50 W) @ 125/250 Vac for inductive loads