DP6060 Dual-Input Process Meter Instruction Manual
2
DP6060 Dual-Input Process Meter Instruction Manual
W
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 37 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace
period to the normal three (3) year product warranty to cover handling and shipping time. This ensures
that OMEGA’s customers receive maximum coverage on each product. If the unit malfunctions, it must be
returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized
Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is
found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to
defects resulting from any action of the purchaser, including but not limited to mishandling, improper
interfacing, operation outside of design limits, improper repair, or unauthorized modification. This
WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having
been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper
specification; misapplication; misuse or other operating conditions outside of OMEGA’s control.
Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any
damages that result from the use of its products in accordance with information provided by
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company
will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY:
The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with
respect to this order, whether based on contract, warranty, negligence, indemnification, strict
liability or otherwise, shall not exceed the purchase price of the component upon which liability is
based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as
set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUEST/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN
(AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return
package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance
and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the
following information available BEFORE
contacting OMEGA:
1. Purchase Order number under which the
product was PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible.
This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
FOR NON-WARRANTY REPAIRS, consult
OMEGA for current repair charges. Have the
following information available BEFORE contacting
OMEGA:
1. Purchase Order number to cover the COST of
the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems
relative to the product.
3
DP6060 Dual-Input Process Meter Instruction Manual
Warning!
!
CAUTION: Read complete
instructions prior to
installation and operation
of the meter.
This product is not recommended for life support
applications or applications where malfunctioning
could result in personal injury or property loss.
Anyone using this product for such applications
does so at his/her own risk. OMEGA shall not be
held liable for damages resulting from such
improper use.
WARNING: Risk of
electric shock or
personal injury.
4
DP6060 Dual-Input Process Meter Instruction Manual
Table of Contents
INTRODUCTION ------------------------------------------------------------ 8
ORDERING INFORMATION --------------------------------------------- 9
SPECIFICATIONS --------------------------------------------------------- 10
General ----------------------------------------------------------------------------- 10
Dual Process Input ------------------------------------------------------------- 12
Relays ------------------------------------------------------------------------------ 13
Isolated 4-20 mA Transmitter Output ------------------------------------ 14
Modbus® RTU Serial Communications --------------------------------- 15
DPA1044 Digital Input & Output Expansion Module ---------------- 15
COMPLIANCE INFORMATION ---------------------------------------- 16
Configuration for 12 or 24 VDC Power Option ------------------------ 20
Transmitter Supply Voltage Selection (P+, P-) ----------------------- 21
Connections ---------------------------------------------------------------------- 21
Connectors Labeling --------------------------------------------------------- 22
Power Connections ---------------------------------------------------------- 22
Signal Connections ---------------------------------------------------------- 23
Modbus RTU Serial Communications ----------------------------------- 24
Relay Connections ----------------------------------------------------------- 24
Switching Inductive Loads -------------------------------------------------- 25
F4 Digital Input Connections ----------------------------------------------- 26
4-20 mA Output Connections ---------------------------------------------- 26
Analog Output Transmitter Power Supply ------------------------------ 26
External Relays & Digital I/O Connections ----------------------------- 27
Interlock Relay Feature ----------------------------------------------------- 28
SETUP AND PROGRAMMING ---------------------------------------- 29
Front Panel Buttons and Status LED Indicators --------------------- 30
Display Functions & Messages -------------------------------------------- 31
Main Menu ------------------------------------------------------------------------ 35
Setting Numeric Values ------------------------------------------------------ 36
Setting Up the Meter (setup) ------------------------------------------------ 37
5
DP6060 Dual-Input Process Meter Instruction Manual
Setting the Input Signal (Input) ------------------------------------------ 38
Setting the Decimal Point (dEc pt) -------------------------------------- 38
Programming the Meter (prog) ------------------------------------------- 39
Multi-Point Linearization (Linear) ------------------------------------ 40
Multi-Point Calibration & Scaling -------------------------------------- 40
DP6000-SOFT Software ------------------------------------------------ 40
Scaling the Meter without a Signal Source ------------------------- 40
Scaling the Meter for Channel A (SCal A) ------------------------- 41
Scaling the Meter for Channel B (SCal B) ------------------------- 41
Error Message (Error) -------------------------------------------------- 42
Calibrating the Meter with External Source ------------------------- 42
Calibrating the Meter for Channel A (CAL-A) ----------------------- 43
Calibrating the Meter for Channel B (CAL-B) ----------------------- 43
Setting the Display Parameter & Intensity (dsplay) ----------------- 44
Display Setup Menu --------------------------------------------------------- 45
Setting the Input Units or Custom Tags (units) ---------------------- 46
Setting the Relay Operation (relay) ------------------------------------- 47
Setting the Relay Assignment (asSign) -------------------------------- 48
Setting the Relay Action ---------------------------------------------------- 49
Programming Set and Reset Points ------------------------------------- 50
Setting Fail-Safe Operation ------------------------------------------------ 50
Programming Time Delay -------------------------------------------------- 50
Relay Action for Loss of 4-20 mA Input (Loop Break) --------------- 50
Relay and Alarm Operation Diagrams ----------------------------------- 51
High Alarm Operation (Set > Reset) ------------------------------------- 51
Low Alarm Operation (Set < Reset) -------------------------------------- 52
High Alarm with Fail-Safe Operation (Set > Reset) ------------------ 53
Low Alarm with Fail-Safe Operation (Set < Reset) ------------------- 54
Pump Alternation Control Operation ------------------------------------- 55
Relay Sampling Operation ------------------------------------------------- 56
Signal Loss or Loop Break Relay Operation --------------------------- 57
Time Delay Operation ------------------------------------------------------- 58
DP6060 Dual-Input Process Meter Instruction Manual
Acknowledging Relays ------------------------------------------------------ 62
Pump Alternation Control Applications (Altern) --------------------- 63
Setting Up the Interlock Relay (Force On) Feature ------------------ 64
Scaling the 4-20 mA Analog Output (Aout) ---------------------------- 65
Reset Menu (reset) ------------------------------------------------------------ 66
Control Menu (Contrl) -------------------------------------------------------- 66
Setting Up the Password (pass) ------------------------------------------- 67
Protecting or Locking the Meter ------------------------------------------- 67
Making Changes to a Password Protected Meter -------------------- 68
Disabling Password Protection -------------------------------------------- 68
Advanced Features Menu ---------------------------------------------------- 69
Advanced Features Menu & Display Messages ---------------------- 70
Noise Filter (filter) -------------------------------------------------------- 73
Noise Filter Bypass (bypass) ---------------------------------------------- 73
Rounding Feature (round) ------------------------------------------------- 74
Modbus RTU Serial Communications (serial) ---------------------- 74
Select Menu (SElect) ------------------------------------------------------- 75
Signal Input Conditioning (Functn) -------------------------------------- 76
Multi-Point Linearization (Linear) ---------------------------------------- 77
Math Function (math) ----------------------------------------------------- 78
Math Constants (Const) ---------------------------------------------------- 79
Low-Flow Cutoff (CutofF) -------------------------------------------------- 79
Analog Output Programming (AoutPr) ---------------------------------- 79
Programmable Function Keys User Menu (user) -------------------- 81
Tare (tare A, tare B) ------------------------------------------------------ 83
Internal Calibration (ICAL) -------------------------------------------------- 83
Meter Copy Function (Copy) ----------------------------------------------- 85
METER OPERATION ----------------------------------------------------- 87
Front Panel Buttons Operation -------------------------------------------- 87
Function Keys Operation ---------------------------------------------------- 87
F4 Operation --------------------------------------------------------------------- 88
Maximum/Minimum Readings ---------------------------------------------- 88
Figure 21. Acknowledge Relays w/Function Key or Digital Input .. 62
INTRODUCTION
The DP6060 is a multipurpose, easy to use digital dual-input process meter ideal for
level, flow rate, temperature transmitter, or pressure transmitter applications. It accepts
current and voltage signals (e.g. 4-20 mA, 0-10 V). Various math functions may be
applied to the inputs including addition, difference, absolute difference, average,
weighted average, multiplication, division, minimum, maximum, draw, ratio, and
concentration. This is in addition to the signal input conditioning functions (linear,
square root, programmable exponent, or round horizontal tank calculations).
The displays, relays, and the analog output may be assigned to input channels A or B,
or math result channel C.
Three of the front panel buttons can be custom-programmed for a specific operation.
The basic model includes an isolated 24 VDC transmitter power supply that can be
used to power the input transmitters or other devices. An additional isolated 24 VDC
power supply is included with the 4-20 mA output option. A digital input is standard.
A fully loaded DP6060 meter has the following: four SPDT relays, 4-20 mA output, and
two 24 VDC power supplies. The DP6060 capabilities may be enhanced by adding the
following external expansion modules: four SPST relays –creating an eight-relay dualinput process meter, two digital I/O modules with four inputs and four outputs each,
serial communication adapters for use with DP6000-SOFT or Modbus RTU, and a dual
4-20 mA expansion module.
8
DP6060 Dual-Input Process Meter Instruction Manual
ORDERING INFORMATION
Standard Display Models
85-265 VAC
Model
DP6060-6R0 DP6060-7R0 No options
DP6060-6R2 DP6060-7R2 2 relays
DP6060-6R3 DP6060-7R3 4-20 mA output
DP6060-6R4 4 relays
DP6060-6R5 2 relays & 4-20 mA output
DP6060-6R7 4 relays & 4-20 mA output
Sunlight Readable Display Models
85-265 VAC
Model
DP6060-6H0 DP6060-7H0 No options
DP6060-6H2 DP6060-7H2 2 relays
DP6060-6H3 DP6060-7H3 4-20 mA output
Accessories
Model Description
DPA1002 DIN rail mounting kit for two expansion modules
DPA1004 4 SPST (Form A) relays
DPA1044 4 digital inputs & 4 digital outputs (2 may be connected)
DPA1200 Meter copy cable
DPA1232 RS-232 serial adapter
DPA1485 RS-485 serial adapter
DPA7485-I RS-232 to RS-422/485 isolated converter
DPA7485-N RS-232 to RS-422/485 non-isolated converter
DPA8008 USB serial adapter
DPA8232-N USB to RS-232 non-isolated converter
DPA8485-I USB to RS-422/485 isolated converter
DPA8485-N USB to RS-422/485 non-isolated converter
12/24 VDC
Model
12/24 VDC
Model
Options Installed
Options Installed
9
DP6060 Dual-Input Process Meter Instruction Manual
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY Upper display: 0.60" (15 mm) high, red LEDs
DISPLAY
INTENSITY
DISPLAY
UPDATE RATE
OVERRANGE
UNDERRANGE
DISPLAY
ASSIGNMENT
PROGRAMMING
METHODS
NOISE FILTER Programmable from 2 to 199 (0 will disable filter)
FILTER BYPASS Programmable from 0.1 to 99.9% of calibrated span
RECALIBRATION All ranges are calibrated at the factory. Recalibration is
MAX/MIN
DISPLAY
PASSWORD
NON-VOLATILE
MEMORY
POWER
OPTIONS
Lower display: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead zero blanking
Eight user selectable intensity levels
5/second (200 ms)
Display flashes
Display flashes
Upper and Lower displays may be assigned to
The
process values for Channels A (Ch-A), B (Ch-B), or C (ChC), toggle between (Ch-A & Ch-B, Ch-A & Ch-C, Ch-B &
Ch-C, and Ch-A, Ch-B, & Ch-C), toggle between Channel &
units, show channel gross value (no tare) or toggle net
(tare) and gross values, show relay set points, max & min
values, or Modbus input. The lower display may also be set
to show engineering units or be off, with no display.
Four front panel buttons, digital inputs, PC and DP6000-SOFT
software, Modbus registers, or cloning using Copy function.
recommended at least every 12 months.
Max/min readings reached by the process are stored until
reset by the user or until power to the meter is cycled.
Three programmable passwords restrict modification of
programmed settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
All programmed settings are stored in non-volatile memory
for a minimum of ten years if power is lost.
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC 10%, 15 W max
999999
-99999
10
DP6060 Dual-Input Process Meter Instruction Manual
FUSE Required external fuse: UL Recognized, 5 A max, slow
ISOLATED
TRANSMITTER
POWER SUPPLY
NORMAL MODE
REJECTION
ISOLATION 4 kV input/output-to-power line
OVERVOLTAGE
CATEGORY
ENVIRONMENTAL Operating temperature range: -40 to 65°C
CONNECTIONS Removable screw terminal blocks accept 12 to 22 AWG
ENCLOSURE 1/8 DIN, high impact plastic, UL 94V-0, color: black
MOUNTING 1/8 DIN panel cutout required:
TIGHTENING
TORQUE
OVERALL
DIMENSIONS
WEIGHT 9.5 oz (269 g)
WARRANTY 3 years parts & labor
blow; up to 6 meters may share one 5 A fuse
Terminals P+ & P-: 24 VDC 10%. 12/24 VDC powered models
selectable for 24, 10, or 5 VDC supply (internal jumper J4).
85-265 VAC models rated @ 200 mA max, 12/24 VDC powered
models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC
supply.
Greater than 60 dB at 50/60 Hz
500 V input-to-output or output-to-P+ supply
Installation Overvoltage Category II:
Local level with smaller transient overvoltages than
Installation Overvoltage Category III.
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
wire, RJ45 for external relays, digital I/O, and serial
communication adapters.
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies are provided.
Screw terminal connectors: 5 lb-in (0.56 Nm)
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm)
(W x H x D)
11
DP6060 Dual-Input Process Meter Instruction Manual
Dual Process Input
TWO INPUTS Two inputs, each separately field selectable:
CHANNELS Channel A, Channel B, Channel C (Math channel)
PROGRAMMA-
Constant P (Adder): -99999 to 999999, default: 0.000
Constant F (Factor): 0.00001 to 999999, default: 1.000
Name Function Setting
Addition (A+B+P)*F Sunm
Difference (A-B+P)*F diF
Absolute diff. ((Abs(A-B))+P)*F diFAbS
Average (((A+B)/2)+P)*F AvG
Multiplication ((A*B)+P)*F nmulti
Divide ((A/B)+P)*F divide
Max of A or B ((AB-Hi)+P)*F Hi-Ab
Min of A or B ((AB-Lo)+P)*F Lo-Ab
Draw ((A/B)-1)*F drAuw
Weighted avg. ((B-A)*F)+A uw avg
Ratio (A/B)*F ratio
Concentration (A/(A+B))*F Concen
Note: The F constant can be any value from 0.00001 to
999999. If the value is less than 1, it will have the same effect
as a divider. For example, the average could also be derived
by using (A+B)*F, where F = 0.500.
1. Select Input for A and B
2. Set up the engineering units for A, B, and C
3. Set up decimal point for A, B, and C
4. Program A & B
5. Set up the displays for A, B, or C
6. Select the transfer function for A & B (e.g. Linear)
7. Select Math function for Channel C
8. Program constants for Factor (F) and Adder (P).
0.005% of calibrated span/C max from 0 to 65C ambient,
0.01% of calibrated span/C max from -40 to 0C ambient
Linear, square root, programmable exponent, or
round horizontal tank volume calculation
2 to 32 points for channel A and B
12
DP6060 Dual-Input Process Meter Instruction Manual
BLE EXPONENT
LOW-FLOW
CUTOFF
DECIMAL POINT Up to five decimal places or none:
0-999999 (0 disables cutoff function)
d.ddddd, d.dddd, d.ddd, d.dd, d.d, ordddddd
CALIBRATION
RANGE
INPUT
IMPEDANCE
INPUT
OVERLOAD
F4 DIGITAL INPUT
CONTACTS
F4 DIGITAL INPUT
LOGIC LEVELS
Input
Range
4-20 mA 0.15 mA
10 V
An error message will appear if the input 1 and input 2
signals are too close together.
Voltage ranges: greater than 500 k
Current ranges: 50 - 100
Current input protected by resettable fuse, 30 VDC max.
Fuse resets automatically after fault is removed.
3.3 VDC on contact. Connect normally open contacts
across F4 to COM.
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Minimum Span
Input 1 & Input 2
0.10 V
(depending on resettable fuse impedance)
Relays
RATING 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A)
NOISE
SUPPRESSION
DEADBAND 0-100% of span, user programmable
HIGH OR LOW
ALARM
RELAY
OPERATION
external; rated 3 A @ 30 VDC and 125/250 VAC resistive
load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads
Noise suppression is recommended for each relay contact
switching inductive loads; see page 25 for details.
User may program any alarm for high or low trip point.
Unused alarm LEDs and relays may be disabled (turn off).
Automatic (non-latching)
Latching (requires manual acknowledge)
Sampling (based on time)
Pump alternation control (2 to 8 relays)
Off (disable unused relays and enable Interlock feature)
Manual on/off control mode
13
DP6060 Dual-Input Process Meter Instruction Manual
RELAY RESET User selectable via front panel buttons or digital inputs
TIME DELAY 0 to 999.9 seconds, on & off relay time delays
FAIL-SAFE
OPERATION
AUTO
INITIALIZATION
1. Automatic reset only (non-latching), when the input
passes the reset point.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared (L)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
Programmable and independent for each relay
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
When power is applied to the meter, relays will reflect the
state of the input to the meter.
Isolated 4-20 mA Transmitter Output
OUTPUT
SOURCE
SCALING RANGE 1.000 to 23.000 mA for any display range
CALIBRATION Factory calibrated: 4.000 to 20.000 = 4-20 mA output
ANALOG OUT
PROGRAMMING
ACCURACY ± 0.1% of span ± 0.004 mA
TEMPERATURE
DRIFT
ISOLATED
TRANSMITTER
POWER SUPPLY
EXTERNAL LOOP
POWER SUPPLY
OUTPUT LOOP
RESISTANCE
35 VDC (external)
Process channel A, B, or C, max or min for channel A, B, or
highest or lowest max or min of A and B, set points 1-8,
Modbus input, or manual control mode
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
0.4 µA/C max from 0 to 65C ambient,
0.8 µA/C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
Terminals I+ & R: 24 VDC 10%. May be used to power the
4-20 mA output or other devices.Refer to Figure 7 on page
22 and Figure 16 on page 26.
All models rated @ 40 mA max.
35 VDC maximum
Power supply Minimum Maximum
24 VDC
10 700
100 1200
14
DP6060 Dual-Input Process Meter Instruction Manual
TIME DELAY
DATA 8 bit (1 start bit, 1 or 2 stop bits)
PARITY Even, Odd, or None with 1 or 2 stop bits
BYTE-TO-BYTE
TIMEOUT
TURN AROUND
DELAY
Note: Refer to the Modbus Register Tables located at www.omega.com for
details.
Programmable between 0 and 199 ms
0.01 – 2.54 second
Less than 2 ms (fixed)
DPA1044 Digital Input & Output Expansion Module
CHANNELS 4 digital inputs & 4 digital outputs per module
SYSTEM Up to 2 modules for a total of 8 inputs & 8 outputs
DIGITAL INPUT
LOGIC HIGH
DIGITAL INPUT
LOGIC LOW
DIGITAL OUTPUT
LOGIC HIGH
DIGITAL OUTPUT
LOGIC LOW
SOURCE
CURRENT
SINK
CURRENT
+5 V
TERMINAL
3 to 5 VDC
0 to 1.25 VDC
3.1 to 3.3 VDC
0 to 0.4 VDC
10 mA maximum output current
1.5 mA minimum input current
To be used as pull-up for digital inputs only.
Connect normally open contacts across +5 V & DI 1-4.
15
DP6060 Dual-Input Process Meter Instruction Manual
COMPLIANCE INFORMATION
Safety
UL & c-UL LISTED USA & Canada
UL FILE NUMBER E356479
FRONT PANEL UL Type 4X, NEMA 4X, IP65; panel gasket provided
LOW VOLTAGE
DIRECTIVE
Electromagnetic Compatibility
EMISSIONS
Radiated
Emissions
AC Mains
Conducted
Emissions
IMMUNITY
RFI - Amplitude
Modulated
Electrical Fast
Transients
Electrostatic
Discharge
RFI - Conducted
AC Surge
Surge
Power-Frequency
Magnetic Field
Voltage Dips
Voltage
Interruptions
UL 508 Industrial Control Equipment
EN 61010-1:2001
Safety requirements for measurement, control, and
laboratory use
EN 55022:2006/A1:2007
Class A ITE emissions requirements
Class A
Class A
EN 61326-1:2006
Measurement, control, and laboratory equipment
EN 61000-6-2:2005
EMC heavy industrial generic immunity standard
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
±2kV AC mains, ±1kV other
±4kV contact, ±8kV air
10V, 0.15-80 MHz, 1kHz 80% AM
±2kV Common, ±1kV Differential
1KV (CM)
3 A/m 70%V for 0.5 period
40%V for 5 & 50 periods
70%V for 25 periods
<5%V for 250 periods
16
DP6060 Dual-Input Process Meter Instruction Manual
Note:
Testing was conducted on DP6060 meters installed through the
covers of grounded metal enclosures with cable shields grounded at
the point of entry representing installations designed to optimize
EMC performance.
Declaration of Conformity available at www.omega.com
SAFETY INFORMATION
!
CAUTION: Read complete
instructions prior to
installation and operation
of the meter.
WARNING!
Hazardous voltages exist within enclosure. Installation and service
should be performed only by trained service personnel.
WARNING: Risk of
electric shock or
personal injury.
INSTALLATION
There is no need to remove the meter from its case to complete the
installation, wiring, and setup of the meter for most applications.
Instructions are provided for setting up a 12/24 VDC powered meter to
operate from 12 VDC and for changing the transmitter power supply to
output 5 or 10 VDC instead of 24 VDC, see page 20.
Unpacking
Remove the meter from box. Inspect the packaging and contents for
damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your
supplier or the factory for assistance.
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x
45 mm). Refer to Figure 1 below, for more details.
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
17
DP6060 Dual-Input Process Meter Instruction Manual
A
A
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X
rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two
screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To
achieve a proper seal, tighten the mounting bracket screws evenly until
meter is snug to the panel along its short side. DO NOT OVER TIGHTEN,
as the rear of the panel may be damaged.
3.622" (92 mm)
Square Corners to 0.060"
B
1.772"
(45mm)
(1.5mm) Max Radius
Panel Cutout
to DIN 43700
Tolerances:
: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Figure 1. 1/8 DIN Panel Cutout Dimensions
Gasket
Panel
Removable
Connectors
Mounting
Bracket
Mounting
Screw
Figure 2. Panel Mounting Details
18
DP6060 Dual-Input Process Meter Instruction Manual
MOUNTING DIMENSIONS
Figure 3. Meter Dimensions - Side View
O
C
R
-
+
O
C
N
C
N
C
N
N
O
N
N
C
C
N
O
N
C
C
Figure 4. Meter Dimensions - Top View
19
DP6060 Dual-Input Process Meter Instruction Manual
Configuration for 12 or 24 VDC Power Option
Do not exceed voltage rating of the selected
configuration.
Warning!
Meters equipped with the 12/24 VDC power option are shipped
from the factory ready to operate from 24 VDC.
To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J9 jumper, located behind the power
connector, for 12 V as shown below.
J9 CONFIGURATION
+
_
MAIN BOARD
J9
12 V
24 V
Factory
Default
M-LINK
24 VDC
12 VDC
POWER
Figure 5. Jumper Configuration for 12/24 VDC Power
20
DP6060 Dual-Input Process Meter Instruction Manual
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12/24 VDC power
option, are shipped from the factory configured to provide 24 VDC
power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal
jumper J4 must be configured accordingly.
To access the voltage selection jumper:
1. Remove all the wiring connectors.
2. Unscrew the back cover.
3. Slide out the back cover by about 1 inch.
4. Configure the J4 jumper, located behind the input signal
connector, for the desired excitation voltage as shown.
Figure 6. Transmitter Supply Voltage Selection
Connections
All connections are made to removable screw terminal connectors
located at the rear of the meter.
!
Caution!
Use copper wire with 60°C or 60/75°C insulation for all line
voltage connections. Observe all safety regulations.
Electrical wiring should be performed in accordance with
all applicable national, state, and local codes to prevent
damage to the meter and ensure personnel safety.
21
DP6060 Dual-Input Process Meter Instruction Manual
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all
connectors available with requested configuration.
Do not connect any equipment other than Omega’s
Warning!
expansion modules, cables, or meters to the RJ45
M-LINK connector. Otherwise damage will occur to the
equipment and the meter.
Figure 7. Connector Labeling for Fully Loaded DP6060
Power Connections
Power connections are made to a two-terminal connector labeled
POWER on Figure 7. The meter will operate regardless of DC polarity
connection. The + and - symbols are only a suggested wiring convention.
POWER
-
+
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
Figure 8. Power Connections
22
DP6060 Dual-Input Process Meter Instruction Manual
Signal Connections
Signal connections are made to a nine-terminal connector labeled
SIGNAL on Figure 7. The COM (common) terminals are the return for
the 4-20 mA and the 10 V input signals. The two COM terminals
connect to the same common return, and are not isolated.
Current and Voltage Connections
The following figures show examples of current and voltage connections.
There are no switches or jumpers to set up for current and voltage inputs.
Setup and programming is performed through the front panel buttons.
Figure 9. Transmitters Powered by Internal Supply
Figure 10. Transmitter Powered by Ext. Supply or Self-Powered
The current input is protected against current overload by a resettable
fuse. The display may or may not show a fault condition depending on
the nature of the overload.
The fuse limits the current to a safe level when it detects a fault
condition, and automatically resets itself when the fault condition is
removed.
23
DP6060 Dual-Input Process Meter Instruction Manual
Figure 11. Voltage Input Connections
The meter is capable of accepting any voltage from -10 VDC to +10 VDC.
Modbus RTU Serial Communications
Serial communications connection is made to an RJ45 connector
labeled M-LINK on Figure 7. For interfacing to the DP6060, use the
DPA1232 for RS-232, the DPA1485 for RS-485, or the DPA8008 for
USB. The same port is used for interfacing with all expansion modules
(e.g. external relays, digital I/O).
Use the DPA1200 meter copy cable for meter-to-meter interfacing for
cloning purposes (i.e. copying settings from one meter to other meters).
Relay Connections
Relay connections are made to two six-terminal connectors labeled
RELAY1 – RELAY4 on Figure 7. Each relay’s C terminal is common
only to the normally open (NO) and normally closed (NC) contacts of the
corresponding relay. The relays’ C terminals should not be confused
with the COM (common) terminal of the INPUT SIGNAL connector.
RELAY4RELAY3
436521
CNONO NCNCC
Figure 12. Relay Connections
RELAY2RELAY1
436521
CNONO NCNCC
24
DP6060 Dual-Input Process Meter Instruction Manual
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching
inductive loads to prevent disrupting the microprocessor’s operation. The
suppressors also prolong the life of the relay contacts. Suppression can be
obtained with resistor-capacitor (RC) networks assembled by the user or
purchased as complete assemblies. Refer to the following circuits for RC network
assembly and installation:
C
C
R
R
Figure 13. AC and DC Loads Protection
Choose R and C as follows:
R: 0.5 to 1 Ω for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to
confirm proper operation.
3. Install the RC network at the meter's relay screw terminals. An RC network
may also be installed across the load. Experiment for best results.
Use a diode with a reverse
breakdown voltage two to
three times the circuit
voltage and forward current
at least as large as the load
current.
Figure 14. Low Voltage DC Loads Protection
Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
Note:
25
DP6060 Dual-Input Process Meter Instruction Manual
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input connected
with a normally open closure across F4 and COM, or with an active low
signal applied to F4.
Figure 15. F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the
connector terminals labeled MA OUT. The 4-20 mA output may be
powered internally or from an external power supply.
24 V
MA OUT
-
+
12-35 VDC
Power
Supply
RI- I+
132
RELAY1
321
MA OUT
+
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
24 V
RI- I+
132
-
RELAY1
321
-
+
4-20 mA
Input Meter
Figure 16. 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be
used to power other devices, if the analog output is not used. The I+
terminal is the +24 V and the R terminal is the return.
26
DP6060 Dual-Input Process Meter Instruction Manual
External Relays & Digital I/O Connections
The relay and the digital I/O expansion modules DPA1004 & DPA1044
are connected to the meter using a CAT5 cable provided with each
module. The two RJ45 connectors on the expansion modules are
identical and interchangeable; they are used to connect additional
modules to the system.
Note: The jumper located between the RJ45 connectors of the
DPA1044 must be removed on the second digital I/O module in
order for the system to recognize it as module #2.
Do not connect or disconnect the expansion modules
with the power on!
Warning!
More detailed instructions are provided with each
optional expansion module.
Figure 17. Expansion Modules & DIN Rail Mounting Kit
RLY5RLY6RLY7RLY8
12
NO C NO C NO C NO C
345678
Figure 18. External Relays Module Connections
27
DP6060 Dual-Input Process Meter Instruction Manual
123456
+5I1I2I3I4 O1
5 VDCGND
DI 1-4DO 1-4
78
O2 O3
910
O4G
Figure 19. Digital I/O Module Connections
Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one, or more,
alarm/control relays for use as interlock relay(s). Interlock contact(s) are
wired to digital input(s) and trigger the interlock relay. This feature is
enabled by configuring the relay, and relative digital input(s) (see page
64). In one example, dry interlock contacts are connected in series to
one digital input which will be used to force on (energize) the assigned
interlock power relay when all interlock contacts are closed (safe). The
interlock relay front panel LED flashes when locked out. The interlock
relay would be wired in-series with the load (N/O contact). See below.
Figure 20. Interlock Connections
28
DP6060 Dual-Input Process Meter Instruction Manual
SETUP AND PROGRAMMING
The meter is factory calibrated prior to shipment to read in milliamps
and volts, depending on the input selection. The calibration equipment
is certified to NIST standards.
Overview
There are no jumpers to set for the meter input selection.
Setup and programming is done through the front panel buttons.
After power and input signal connections have been completed and
verified, apply power to the meter.
29
DP6060 Dual-Input Process Meter Instruction Manual
Front Panel Buttons and Status LED Indicators
Button
Symbol
Description LED Status
Menu
1-8 Alarm 1-8 indicator
Right arrow/F1
Up arrow/F2
Enter/F3
1-8
M
A
B
C
1-4
Notes:
F4 is a digital input. Alarms 5-8
are enabled when relay
expansion module installed.
Press the Menu button to enter or exit the Programming Mode at
any time.
Press the Right arrow button to move to the next digit during digit or
decimal point programming.
Press or hold the Up arrow button to scroll through the menus,
decimal point, or to increment the value of a digit.
Press the Enter button to access a menu or to accept a setting.
Press and hold the Menu button for three seconds to access the
advanced features of the meter.
Note:
LEDs for relays in manual mode
flash with the “M” LED every 10
seconds.
30
Flashing: Relay in
manual control mode
Channel displayed
Flashing: Tare
Flashing: Relay
interlock switch open
Loading...
+ 70 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.