DP6060 Dual-Input Process Meter Instruction Manual
2
Page 3
DP6060 Dual-Input Process Meter Instruction Manual
W
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 37 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace
period to the normal three (3) year product warranty to cover handling and shipping time. This ensures
that OMEGA’s customers receive maximum coverage on each product. If the unit malfunctions, it must be
returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized
Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is
found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to
defects resulting from any action of the purchaser, including but not limited to mishandling, improper
interfacing, operation outside of design limits, improper repair, or unauthorized modification. This
WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having
been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper
specification; misapplication; misuse or other operating conditions outside of OMEGA’s control.
Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any
damages that result from the use of its products in accordance with information provided by
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company
will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY:
The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with
respect to this order, whether based on contract, warranty, negligence, indemnification, strict
liability or otherwise, shall not exceed the purchase price of the component upon which liability is
based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as
set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUEST/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN
(AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return
package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance
and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the
following information available BEFORE
contacting OMEGA:
1. Purchase Order number under which the
product was PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible.
This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
FOR NON-WARRANTY REPAIRS, consult
OMEGA for current repair charges. Have the
following information available BEFORE contacting
OMEGA:
1. Purchase Order number to cover the COST of
the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems
relative to the product.
3
Page 4
DP6060 Dual-Input Process Meter Instruction Manual
Warning!
!
CAUTION: Read complete
instructions prior to
installation and operation
of the meter.
This product is not recommended for life support
applications or applications where malfunctioning
could result in personal injury or property loss.
Anyone using this product for such applications
does so at his/her own risk. OMEGA shall not be
held liable for damages resulting from such
improper use.
WARNING: Risk of
electric shock or
personal injury.
4
Page 5
DP6060 Dual-Input Process Meter Instruction Manual
Table of Contents
INTRODUCTION ------------------------------------------------------------ 8
ORDERING INFORMATION --------------------------------------------- 9
SPECIFICATIONS --------------------------------------------------------- 10
General ----------------------------------------------------------------------------- 10
Dual Process Input ------------------------------------------------------------- 12
Relays ------------------------------------------------------------------------------ 13
Isolated 4-20 mA Transmitter Output ------------------------------------ 14
Modbus® RTU Serial Communications --------------------------------- 15
DPA1044 Digital Input & Output Expansion Module ---------------- 15
COMPLIANCE INFORMATION ---------------------------------------- 16
Configuration for 12 or 24 VDC Power Option ------------------------ 20
Transmitter Supply Voltage Selection (P+, P-) ----------------------- 21
Connections ---------------------------------------------------------------------- 21
Connectors Labeling --------------------------------------------------------- 22
Power Connections ---------------------------------------------------------- 22
Signal Connections ---------------------------------------------------------- 23
Modbus RTU Serial Communications ----------------------------------- 24
Relay Connections ----------------------------------------------------------- 24
Switching Inductive Loads -------------------------------------------------- 25
F4 Digital Input Connections ----------------------------------------------- 26
4-20 mA Output Connections ---------------------------------------------- 26
Analog Output Transmitter Power Supply ------------------------------ 26
External Relays & Digital I/O Connections ----------------------------- 27
Interlock Relay Feature ----------------------------------------------------- 28
SETUP AND PROGRAMMING ---------------------------------------- 29
Front Panel Buttons and Status LED Indicators --------------------- 30
Display Functions & Messages -------------------------------------------- 31
Main Menu ------------------------------------------------------------------------ 35
Setting Numeric Values ------------------------------------------------------ 36
Setting Up the Meter (setup) ------------------------------------------------ 37
5
Page 6
DP6060 Dual-Input Process Meter Instruction Manual
Setting the Input Signal (Input) ------------------------------------------ 38
Setting the Decimal Point (dEc pt) -------------------------------------- 38
Programming the Meter (prog) ------------------------------------------- 39
Multi-Point Linearization (Linear) ------------------------------------ 40
Multi-Point Calibration & Scaling -------------------------------------- 40
DP6000-SOFT Software ------------------------------------------------ 40
Scaling the Meter without a Signal Source ------------------------- 40
Scaling the Meter for Channel A (SCal A) ------------------------- 41
Scaling the Meter for Channel B (SCal B) ------------------------- 41
Error Message (Error) -------------------------------------------------- 42
Calibrating the Meter with External Source ------------------------- 42
Calibrating the Meter for Channel A (CAL-A) ----------------------- 43
Calibrating the Meter for Channel B (CAL-B) ----------------------- 43
Setting the Display Parameter & Intensity (dsplay) ----------------- 44
Display Setup Menu --------------------------------------------------------- 45
Setting the Input Units or Custom Tags (units) ---------------------- 46
Setting the Relay Operation (relay) ------------------------------------- 47
Setting the Relay Assignment (asSign) -------------------------------- 48
Setting the Relay Action ---------------------------------------------------- 49
Programming Set and Reset Points ------------------------------------- 50
Setting Fail-Safe Operation ------------------------------------------------ 50
Programming Time Delay -------------------------------------------------- 50
Relay Action for Loss of 4-20 mA Input (Loop Break) --------------- 50
Relay and Alarm Operation Diagrams ----------------------------------- 51
High Alarm Operation (Set > Reset) ------------------------------------- 51
Low Alarm Operation (Set < Reset) -------------------------------------- 52
High Alarm with Fail-Safe Operation (Set > Reset) ------------------ 53
Low Alarm with Fail-Safe Operation (Set < Reset) ------------------- 54
Pump Alternation Control Operation ------------------------------------- 55
Relay Sampling Operation ------------------------------------------------- 56
Signal Loss or Loop Break Relay Operation --------------------------- 57
Time Delay Operation ------------------------------------------------------- 58
DP6060 Dual-Input Process Meter Instruction Manual
Acknowledging Relays ------------------------------------------------------ 62
Pump Alternation Control Applications (Altern) --------------------- 63
Setting Up the Interlock Relay (Force On) Feature ------------------ 64
Scaling the 4-20 mA Analog Output (Aout) ---------------------------- 65
Reset Menu (reset) ------------------------------------------------------------ 66
Control Menu (Contrl) -------------------------------------------------------- 66
Setting Up the Password (pass) ------------------------------------------- 67
Protecting or Locking the Meter ------------------------------------------- 67
Making Changes to a Password Protected Meter -------------------- 68
Disabling Password Protection -------------------------------------------- 68
Advanced Features Menu ---------------------------------------------------- 69
Advanced Features Menu & Display Messages ---------------------- 70
Noise Filter (filter) -------------------------------------------------------- 73
Noise Filter Bypass (bypass) ---------------------------------------------- 73
Rounding Feature (round) ------------------------------------------------- 74
Modbus RTU Serial Communications (serial) ---------------------- 74
Select Menu (SElect) ------------------------------------------------------- 75
Signal Input Conditioning (Functn) -------------------------------------- 76
Multi-Point Linearization (Linear) ---------------------------------------- 77
Math Function (math) ----------------------------------------------------- 78
Math Constants (Const) ---------------------------------------------------- 79
Low-Flow Cutoff (CutofF) -------------------------------------------------- 79
Analog Output Programming (AoutPr) ---------------------------------- 79
Programmable Function Keys User Menu (user) -------------------- 81
Tare (tare A, tare B) ------------------------------------------------------ 83
Internal Calibration (ICAL) -------------------------------------------------- 83
Meter Copy Function (Copy) ----------------------------------------------- 85
METER OPERATION ----------------------------------------------------- 87
Front Panel Buttons Operation -------------------------------------------- 87
Function Keys Operation ---------------------------------------------------- 87
F4 Operation --------------------------------------------------------------------- 88
Maximum/Minimum Readings ---------------------------------------------- 88
Figure 21. Acknowledge Relays w/Function Key or Digital Input .. 62
INTRODUCTION
The DP6060 is a multipurpose, easy to use digital dual-input process meter ideal for
level, flow rate, temperature transmitter, or pressure transmitter applications. It accepts
current and voltage signals (e.g. 4-20 mA, 0-10 V). Various math functions may be
applied to the inputs including addition, difference, absolute difference, average,
weighted average, multiplication, division, minimum, maximum, draw, ratio, and
concentration. This is in addition to the signal input conditioning functions (linear,
square root, programmable exponent, or round horizontal tank calculations).
The displays, relays, and the analog output may be assigned to input channels A or B,
or math result channel C.
Three of the front panel buttons can be custom-programmed for a specific operation.
The basic model includes an isolated 24 VDC transmitter power supply that can be
used to power the input transmitters or other devices. An additional isolated 24 VDC
power supply is included with the 4-20 mA output option. A digital input is standard.
A fully loaded DP6060 meter has the following: four SPDT relays, 4-20 mA output, and
two 24 VDC power supplies. The DP6060 capabilities may be enhanced by adding the
following external expansion modules: four SPST relays –creating an eight-relay dualinput process meter, two digital I/O modules with four inputs and four outputs each,
serial communication adapters for use with DP6000-SOFT or Modbus RTU, and a dual
4-20 mA expansion module.
8
Page 9
DP6060 Dual-Input Process Meter Instruction Manual
ORDERING INFORMATION
Standard Display Models
85-265 VAC
Model
DP6060-6R0 DP6060-7R0 No options
DP6060-6R2 DP6060-7R2 2 relays
DP6060-6R3 DP6060-7R3 4-20 mA output
DP6060-6R4 4 relays
DP6060-6R5 2 relays & 4-20 mA output
DP6060-6R7 4 relays & 4-20 mA output
Sunlight Readable Display Models
85-265 VAC
Model
DP6060-6H0 DP6060-7H0 No options
DP6060-6H2 DP6060-7H2 2 relays
DP6060-6H3 DP6060-7H3 4-20 mA output
Accessories
Model Description
DPA1002 DIN rail mounting kit for two expansion modules
DPA1004 4 SPST (Form A) relays
DPA1044 4 digital inputs & 4 digital outputs (2 may be connected)
DPA1200 Meter copy cable
DPA1232 RS-232 serial adapter
DPA1485 RS-485 serial adapter
DPA7485-I RS-232 to RS-422/485 isolated converter
DPA7485-N RS-232 to RS-422/485 non-isolated converter
DPA8008 USB serial adapter
DPA8232-N USB to RS-232 non-isolated converter
DPA8485-I USB to RS-422/485 isolated converter
DPA8485-N USB to RS-422/485 non-isolated converter
12/24 VDC
Model
12/24 VDC
Model
Options Installed
Options Installed
9
Page 10
DP6060 Dual-Input Process Meter Instruction Manual
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY Upper display: 0.60" (15 mm) high, red LEDs
DISPLAY
INTENSITY
DISPLAY
UPDATE RATE
OVERRANGE
UNDERRANGE
DISPLAY
ASSIGNMENT
PROGRAMMING
METHODS
NOISE FILTER Programmable from 2 to 199 (0 will disable filter)
FILTER BYPASS Programmable from 0.1 to 99.9% of calibrated span
RECALIBRATION All ranges are calibrated at the factory. Recalibration is
MAX/MIN
DISPLAY
PASSWORD
NON-VOLATILE
MEMORY
POWER
OPTIONS
Lower display: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead zero blanking
Eight user selectable intensity levels
5/second (200 ms)
Display flashes
Display flashes
Upper and Lower displays may be assigned to
The
process values for Channels A (Ch-A), B (Ch-B), or C (ChC), toggle between (Ch-A & Ch-B, Ch-A & Ch-C, Ch-B &
Ch-C, and Ch-A, Ch-B, & Ch-C), toggle between Channel &
units, show channel gross value (no tare) or toggle net
(tare) and gross values, show relay set points, max & min
values, or Modbus input. The lower display may also be set
to show engineering units or be off, with no display.
Four front panel buttons, digital inputs, PC and DP6000-SOFT
software, Modbus registers, or cloning using Copy function.
recommended at least every 12 months.
Max/min readings reached by the process are stored until
reset by the user or until power to the meter is cycled.
Three programmable passwords restrict modification of
programmed settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
All programmed settings are stored in non-volatile memory
for a minimum of ten years if power is lost.
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC 10%, 15 W max
999999
-99999
10
Page 11
DP6060 Dual-Input Process Meter Instruction Manual
FUSE Required external fuse: UL Recognized, 5 A max, slow
ISOLATED
TRANSMITTER
POWER SUPPLY
NORMAL MODE
REJECTION
ISOLATION 4 kV input/output-to-power line
OVERVOLTAGE
CATEGORY
ENVIRONMENTAL Operating temperature range: -40 to 65°C
CONNECTIONS Removable screw terminal blocks accept 12 to 22 AWG
ENCLOSURE 1/8 DIN, high impact plastic, UL 94V-0, color: black
MOUNTING 1/8 DIN panel cutout required:
TIGHTENING
TORQUE
OVERALL
DIMENSIONS
WEIGHT 9.5 oz (269 g)
WARRANTY 3 years parts & labor
blow; up to 6 meters may share one 5 A fuse
Terminals P+ & P-: 24 VDC 10%. 12/24 VDC powered models
selectable for 24, 10, or 5 VDC supply (internal jumper J4).
85-265 VAC models rated @ 200 mA max, 12/24 VDC powered
models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC
supply.
Greater than 60 dB at 50/60 Hz
500 V input-to-output or output-to-P+ supply
Installation Overvoltage Category II:
Local level with smaller transient overvoltages than
Installation Overvoltage Category III.
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
wire, RJ45 for external relays, digital I/O, and serial
communication adapters.
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies are provided.
Screw terminal connectors: 5 lb-in (0.56 Nm)
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm)
(W x H x D)
11
Page 12
DP6060 Dual-Input Process Meter Instruction Manual
Dual Process Input
TWO INPUTS Two inputs, each separately field selectable:
CHANNELS Channel A, Channel B, Channel C (Math channel)
PROGRAMMA-
Constant P (Adder): -99999 to 999999, default: 0.000
Constant F (Factor): 0.00001 to 999999, default: 1.000
Name Function Setting
Addition (A+B+P)*F Sunm
Difference (A-B+P)*F diF
Absolute diff. ((Abs(A-B))+P)*F diFAbS
Average (((A+B)/2)+P)*F AvG
Multiplication ((A*B)+P)*F nmulti
Divide ((A/B)+P)*F divide
Max of A or B ((AB-Hi)+P)*F Hi-Ab
Min of A or B ((AB-Lo)+P)*F Lo-Ab
Draw ((A/B)-1)*F drAuw
Weighted avg. ((B-A)*F)+A uw avg
Ratio (A/B)*F ratio
Concentration (A/(A+B))*F Concen
Note: The F constant can be any value from 0.00001 to
999999. If the value is less than 1, it will have the same effect
as a divider. For example, the average could also be derived
by using (A+B)*F, where F = 0.500.
1. Select Input for A and B
2. Set up the engineering units for A, B, and C
3. Set up decimal point for A, B, and C
4. Program A & B
5. Set up the displays for A, B, or C
6. Select the transfer function for A & B (e.g. Linear)
7. Select Math function for Channel C
8. Program constants for Factor (F) and Adder (P).
0.005% of calibrated span/C max from 0 to 65C ambient,
0.01% of calibrated span/C max from -40 to 0C ambient
Linear, square root, programmable exponent, or
round horizontal tank volume calculation
2 to 32 points for channel A and B
12
Page 13
DP6060 Dual-Input Process Meter Instruction Manual
BLE EXPONENT
LOW-FLOW
CUTOFF
DECIMAL POINT Up to five decimal places or none:
0-999999 (0 disables cutoff function)
d.ddddd, d.dddd, d.ddd, d.dd, d.d, ordddddd
CALIBRATION
RANGE
INPUT
IMPEDANCE
INPUT
OVERLOAD
F4 DIGITAL INPUT
CONTACTS
F4 DIGITAL INPUT
LOGIC LEVELS
Input
Range
4-20 mA 0.15 mA
10 V
An error message will appear if the input 1 and input 2
signals are too close together.
Voltage ranges: greater than 500 k
Current ranges: 50 - 100
Current input protected by resettable fuse, 30 VDC max.
Fuse resets automatically after fault is removed.
3.3 VDC on contact. Connect normally open contacts
across F4 to COM.
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Minimum Span
Input 1 & Input 2
0.10 V
(depending on resettable fuse impedance)
Relays
RATING 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A)
NOISE
SUPPRESSION
DEADBAND 0-100% of span, user programmable
HIGH OR LOW
ALARM
RELAY
OPERATION
external; rated 3 A @ 30 VDC and 125/250 VAC resistive
load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads
Noise suppression is recommended for each relay contact
switching inductive loads; see page 25 for details.
User may program any alarm for high or low trip point.
Unused alarm LEDs and relays may be disabled (turn off).
Automatic (non-latching)
Latching (requires manual acknowledge)
Sampling (based on time)
Pump alternation control (2 to 8 relays)
Off (disable unused relays and enable Interlock feature)
Manual on/off control mode
13
Page 14
DP6060 Dual-Input Process Meter Instruction Manual
RELAY RESET User selectable via front panel buttons or digital inputs
TIME DELAY 0 to 999.9 seconds, on & off relay time delays
FAIL-SAFE
OPERATION
AUTO
INITIALIZATION
1. Automatic reset only (non-latching), when the input
passes the reset point.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared (L)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
Programmable and independent for each relay
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
When power is applied to the meter, relays will reflect the
state of the input to the meter.
Isolated 4-20 mA Transmitter Output
OUTPUT
SOURCE
SCALING RANGE 1.000 to 23.000 mA for any display range
CALIBRATION Factory calibrated: 4.000 to 20.000 = 4-20 mA output
ANALOG OUT
PROGRAMMING
ACCURACY ± 0.1% of span ± 0.004 mA
TEMPERATURE
DRIFT
ISOLATED
TRANSMITTER
POWER SUPPLY
EXTERNAL LOOP
POWER SUPPLY
OUTPUT LOOP
RESISTANCE
35 VDC (external)
Process channel A, B, or C, max or min for channel A, B, or
highest or lowest max or min of A and B, set points 1-8,
Modbus input, or manual control mode
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
0.4 µA/C max from 0 to 65C ambient,
0.8 µA/C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
Terminals I+ & R: 24 VDC 10%. May be used to power the
4-20 mA output or other devices.Refer to Figure 7 on page
22 and Figure 16 on page 26.
All models rated @ 40 mA max.
35 VDC maximum
Power supply Minimum Maximum
24 VDC
10 700
100 1200
14
Page 15
DP6060 Dual-Input Process Meter Instruction Manual
TIME DELAY
DATA 8 bit (1 start bit, 1 or 2 stop bits)
PARITY Even, Odd, or None with 1 or 2 stop bits
BYTE-TO-BYTE
TIMEOUT
TURN AROUND
DELAY
Note: Refer to the Modbus Register Tables located at www.omega.com for
details.
Programmable between 0 and 199 ms
0.01 – 2.54 second
Less than 2 ms (fixed)
DPA1044 Digital Input & Output Expansion Module
CHANNELS 4 digital inputs & 4 digital outputs per module
SYSTEM Up to 2 modules for a total of 8 inputs & 8 outputs
DIGITAL INPUT
LOGIC HIGH
DIGITAL INPUT
LOGIC LOW
DIGITAL OUTPUT
LOGIC HIGH
DIGITAL OUTPUT
LOGIC LOW
SOURCE
CURRENT
SINK
CURRENT
+5 V
TERMINAL
3 to 5 VDC
0 to 1.25 VDC
3.1 to 3.3 VDC
0 to 0.4 VDC
10 mA maximum output current
1.5 mA minimum input current
To be used as pull-up for digital inputs only.
Connect normally open contacts across +5 V & DI 1-4.
15
Page 16
DP6060 Dual-Input Process Meter Instruction Manual
COMPLIANCE INFORMATION
Safety
UL & c-UL LISTED USA & Canada
UL FILE NUMBER E356479
FRONT PANEL UL Type 4X, NEMA 4X, IP65; panel gasket provided
LOW VOLTAGE
DIRECTIVE
Electromagnetic Compatibility
EMISSIONS
Radiated
Emissions
AC Mains
Conducted
Emissions
IMMUNITY
RFI - Amplitude
Modulated
Electrical Fast
Transients
Electrostatic
Discharge
RFI - Conducted
AC Surge
Surge
Power-Frequency
Magnetic Field
Voltage Dips
Voltage
Interruptions
UL 508 Industrial Control Equipment
EN 61010-1:2001
Safety requirements for measurement, control, and
laboratory use
EN 55022:2006/A1:2007
Class A ITE emissions requirements
Class A
Class A
EN 61326-1:2006
Measurement, control, and laboratory equipment
EN 61000-6-2:2005
EMC heavy industrial generic immunity standard
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
±2kV AC mains, ±1kV other
±4kV contact, ±8kV air
10V, 0.15-80 MHz, 1kHz 80% AM
±2kV Common, ±1kV Differential
1KV (CM)
3 A/m 70%V for 0.5 period
40%V for 5 & 50 periods
70%V for 25 periods
<5%V for 250 periods
16
Page 17
DP6060 Dual-Input Process Meter Instruction Manual
Note:
Testing was conducted on DP6060 meters installed through the
covers of grounded metal enclosures with cable shields grounded at
the point of entry representing installations designed to optimize
EMC performance.
Declaration of Conformity available at www.omega.com
SAFETY INFORMATION
!
CAUTION: Read complete
instructions prior to
installation and operation
of the meter.
WARNING!
Hazardous voltages exist within enclosure. Installation and service
should be performed only by trained service personnel.
WARNING: Risk of
electric shock or
personal injury.
INSTALLATION
There is no need to remove the meter from its case to complete the
installation, wiring, and setup of the meter for most applications.
Instructions are provided for setting up a 12/24 VDC powered meter to
operate from 12 VDC and for changing the transmitter power supply to
output 5 or 10 VDC instead of 24 VDC, see page 20.
Unpacking
Remove the meter from box. Inspect the packaging and contents for
damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your
supplier or the factory for assistance.
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x
45 mm). Refer to Figure 1 below, for more details.
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
17
Page 18
DP6060 Dual-Input Process Meter Instruction Manual
A
A
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X
rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two
screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To
achieve a proper seal, tighten the mounting bracket screws evenly until
meter is snug to the panel along its short side. DO NOT OVER TIGHTEN,
as the rear of the panel may be damaged.
3.622" (92 mm)
Square Corners to 0.060"
B
1.772"
(45mm)
(1.5mm) Max Radius
Panel Cutout
to DIN 43700
Tolerances:
: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Figure 1. 1/8 DIN Panel Cutout Dimensions
Gasket
Panel
Removable
Connectors
Mounting
Bracket
Mounting
Screw
Figure 2. Panel Mounting Details
18
Page 19
DP6060 Dual-Input Process Meter Instruction Manual
MOUNTING DIMENSIONS
Figure 3. Meter Dimensions - Side View
O
C
R
-
+
O
C
N
C
N
C
N
N
O
N
N
C
C
N
O
N
C
C
Figure 4. Meter Dimensions - Top View
19
Page 20
DP6060 Dual-Input Process Meter Instruction Manual
Configuration for 12 or 24 VDC Power Option
Do not exceed voltage rating of the selected
configuration.
Warning!
Meters equipped with the 12/24 VDC power option are shipped
from the factory ready to operate from 24 VDC.
To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J9 jumper, located behind the power
connector, for 12 V as shown below.
J9 CONFIGURATION
+
_
MAIN BOARD
J9
12 V
24 V
Factory
Default
M-LINK
24 VDC
12 VDC
POWER
Figure 5. Jumper Configuration for 12/24 VDC Power
20
Page 21
DP6060 Dual-Input Process Meter Instruction Manual
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12/24 VDC power
option, are shipped from the factory configured to provide 24 VDC
power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal
jumper J4 must be configured accordingly.
To access the voltage selection jumper:
1. Remove all the wiring connectors.
2. Unscrew the back cover.
3. Slide out the back cover by about 1 inch.
4. Configure the J4 jumper, located behind the input signal
connector, for the desired excitation voltage as shown.
Figure 6. Transmitter Supply Voltage Selection
Connections
All connections are made to removable screw terminal connectors
located at the rear of the meter.
!
Caution!
Use copper wire with 60°C or 60/75°C insulation for all line
voltage connections. Observe all safety regulations.
Electrical wiring should be performed in accordance with
all applicable national, state, and local codes to prevent
damage to the meter and ensure personnel safety.
21
Page 22
DP6060 Dual-Input Process Meter Instruction Manual
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all
connectors available with requested configuration.
Do not connect any equipment other than Omega’s
Warning!
expansion modules, cables, or meters to the RJ45
M-LINK connector. Otherwise damage will occur to the
equipment and the meter.
Figure 7. Connector Labeling for Fully Loaded DP6060
Power Connections
Power connections are made to a two-terminal connector labeled
POWER on Figure 7. The meter will operate regardless of DC polarity
connection. The + and - symbols are only a suggested wiring convention.
POWER
-
+
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
Figure 8. Power Connections
22
Page 23
DP6060 Dual-Input Process Meter Instruction Manual
Signal Connections
Signal connections are made to a nine-terminal connector labeled
SIGNAL on Figure 7. The COM (common) terminals are the return for
the 4-20 mA and the 10 V input signals. The two COM terminals
connect to the same common return, and are not isolated.
Current and Voltage Connections
The following figures show examples of current and voltage connections.
There are no switches or jumpers to set up for current and voltage inputs.
Setup and programming is performed through the front panel buttons.
Figure 9. Transmitters Powered by Internal Supply
Figure 10. Transmitter Powered by Ext. Supply or Self-Powered
The current input is protected against current overload by a resettable
fuse. The display may or may not show a fault condition depending on
the nature of the overload.
The fuse limits the current to a safe level when it detects a fault
condition, and automatically resets itself when the fault condition is
removed.
23
Page 24
DP6060 Dual-Input Process Meter Instruction Manual
Figure 11. Voltage Input Connections
The meter is capable of accepting any voltage from -10 VDC to +10 VDC.
Modbus RTU Serial Communications
Serial communications connection is made to an RJ45 connector
labeled M-LINK on Figure 7. For interfacing to the DP6060, use the
DPA1232 for RS-232, the DPA1485 for RS-485, or the DPA8008 for
USB. The same port is used for interfacing with all expansion modules
(e.g. external relays, digital I/O).
Use the DPA1200 meter copy cable for meter-to-meter interfacing for
cloning purposes (i.e. copying settings from one meter to other meters).
Relay Connections
Relay connections are made to two six-terminal connectors labeled
RELAY1 – RELAY4 on Figure 7. Each relay’s C terminal is common
only to the normally open (NO) and normally closed (NC) contacts of the
corresponding relay. The relays’ C terminals should not be confused
with the COM (common) terminal of the INPUT SIGNAL connector.
RELAY4RELAY3
436521
CNONO NCNCC
Figure 12. Relay Connections
RELAY2RELAY1
436521
CNONO NCNCC
24
Page 25
DP6060 Dual-Input Process Meter Instruction Manual
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching
inductive loads to prevent disrupting the microprocessor’s operation. The
suppressors also prolong the life of the relay contacts. Suppression can be
obtained with resistor-capacitor (RC) networks assembled by the user or
purchased as complete assemblies. Refer to the following circuits for RC network
assembly and installation:
C
C
R
R
Figure 13. AC and DC Loads Protection
Choose R and C as follows:
R: 0.5 to 1 Ω for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to
confirm proper operation.
3. Install the RC network at the meter's relay screw terminals. An RC network
may also be installed across the load. Experiment for best results.
Use a diode with a reverse
breakdown voltage two to
three times the circuit
voltage and forward current
at least as large as the load
current.
Figure 14. Low Voltage DC Loads Protection
Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
Note:
25
Page 26
DP6060 Dual-Input Process Meter Instruction Manual
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input connected
with a normally open closure across F4 and COM, or with an active low
signal applied to F4.
Figure 15. F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the
connector terminals labeled MA OUT. The 4-20 mA output may be
powered internally or from an external power supply.
24 V
MA OUT
-
+
12-35 VDC
Power
Supply
RI- I+
132
RELAY1
321
MA OUT
+
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
24 V
RI- I+
132
-
RELAY1
321
-
+
4-20 mA
Input Meter
Figure 16. 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be
used to power other devices, if the analog output is not used. The I+
terminal is the +24 V and the R terminal is the return.
26
Page 27
DP6060 Dual-Input Process Meter Instruction Manual
External Relays & Digital I/O Connections
The relay and the digital I/O expansion modules DPA1004 & DPA1044
are connected to the meter using a CAT5 cable provided with each
module. The two RJ45 connectors on the expansion modules are
identical and interchangeable; they are used to connect additional
modules to the system.
Note: The jumper located between the RJ45 connectors of the
DPA1044 must be removed on the second digital I/O module in
order for the system to recognize it as module #2.
Do not connect or disconnect the expansion modules
with the power on!
Warning!
More detailed instructions are provided with each
optional expansion module.
Figure 17. Expansion Modules & DIN Rail Mounting Kit
RLY5RLY6RLY7RLY8
12
NO C NO C NO C NO C
345678
Figure 18. External Relays Module Connections
27
Page 28
DP6060 Dual-Input Process Meter Instruction Manual
123456
+5I1I2I3I4 O1
5 VDCGND
DI 1-4DO 1-4
78
O2 O3
910
O4G
Figure 19. Digital I/O Module Connections
Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one, or more,
alarm/control relays for use as interlock relay(s). Interlock contact(s) are
wired to digital input(s) and trigger the interlock relay. This feature is
enabled by configuring the relay, and relative digital input(s) (see page
64). In one example, dry interlock contacts are connected in series to
one digital input which will be used to force on (energize) the assigned
interlock power relay when all interlock contacts are closed (safe). The
interlock relay front panel LED flashes when locked out. The interlock
relay would be wired in-series with the load (N/O contact). See below.
Figure 20. Interlock Connections
28
Page 29
DP6060 Dual-Input Process Meter Instruction Manual
SETUP AND PROGRAMMING
The meter is factory calibrated prior to shipment to read in milliamps
and volts, depending on the input selection. The calibration equipment
is certified to NIST standards.
Overview
There are no jumpers to set for the meter input selection.
Setup and programming is done through the front panel buttons.
After power and input signal connections have been completed and
verified, apply power to the meter.
29
Page 30
DP6060 Dual-Input Process Meter Instruction Manual
Front Panel Buttons and Status LED Indicators
Button
Symbol
Description LED Status
Menu
1-8 Alarm 1-8 indicator
Right arrow/F1
Up arrow/F2
Enter/F3
1-8
M
A
B
C
1-4
Notes:
F4 is a digital input. Alarms 5-8
are enabled when relay
expansion module installed.
Press the Menu button to enter or exit the Programming Mode at
any time.
Press the Right arrow button to move to the next digit during digit or
decimal point programming.
Press or hold the Up arrow button to scroll through the menus,
decimal point, or to increment the value of a digit.
Press the Enter button to access a menu or to accept a setting.
Press and hold the Menu button for three seconds to access the
advanced features of the meter.
Note:
LEDs for relays in manual mode
flash with the “M” LED every 10
seconds.
30
Flashing: Relay in
manual control mode
Channel displayed
Flashing: Tare
Flashing: Relay
interlock switch open
Page 31
DP6060 Dual-Input Process Meter Instruction Manual
Display Functions & Messages
The following table shows the main menu functions and messages in
the order they appear in the menu.
Display Parameter Action/Setting Description
setup
Input
Ch-A*
mA
volt
units
Ch-A*
Dec pt
Ch-A*
prog
InCAL
Ch-A*
SCAL A
SCAl B
Cal A
Cal B
Inp 1
Dis 1
Inp 2
Dis 2
Error
dsplay
big
Setup
Input
Input
4-20 mA
0-10 VDC
Unit
Unit
Decimal point
Decimal point
Program
Input
Calibration
Input A
Scale A
Scale B
Calibrate A
Calibrate B
Input 1
Display 1
Input 2
Display 2
Error
Display
Upper display
Enter Setup menu
Enter Input selection menu
Set input type for channel A (*or B)
Set meter for 4-20 mA input
Set meter for 10 VDC input
Select the display units/tags
Set unit or tag for channel A (*or B or C)
Set decimal point
Set decimal point for channel A (*or B or C)
Enter the Program menu
Enter the Input Calibration menu
Set input type for channel A (*or B)
Enter the Scale menu for channel A
Enter the Scale menu for channel B
Enter the Calibration menu for channel A
Enter the Calibration menu for channel B
Calibrate input 1 signal or program input 1
value
Program display 1 value
Calibrate input 2 signal or program input 2
value (up to 32 points)
Program display 2 value (up to 32 points)
Error, calibration not successful, check
signal or programmed value
Enter the Display menu
Assign the upper display parameter
31
Page 32
DP6060 Dual-Input Process Meter Instruction Manual
Display Parameter Action/Setting Description
Little
D Ch-A
D Ch-B
D Ch-C
D Ab
D AC
D BC
D AbC
D set1*
D Hi-A
D Lo-A
D HL-A
D Hi-B
D Lo-B
D HL-B
D Hi-C
D Lo-C
D HL-C
D a-u
D B-u
D C-u
A Gros
A nt-G
B Gros
Lower display
Display Ch-A
Display Ch-B
Display Ch-C
Display AB
Display AC
Display BC
Display ABC
Display Set 1*
Display Hi A
Display Lo A
Display
Hi/Low A
Display Hi B
Display Lo B
Display
Hi/Low B
Display Hi C
Display Lo C
Display
Hi/Low C
Display A and
units/tags
Display B and
units/tags
Display B and
units/tags
Display A gross
Display A net
and gross
Display B gross
Assign the lower display parameter
Assign display to channel A
Assign display to channel B
Assign display to channel C (math)
Alternate display of channel A & B
Alternate display of channel A & C
Alternate display of channel B & C
Alternate display of channel A, B, & C
Displays relay 1(*through 8) set point.
Display high value of channel A
Display low value of channel A
Alternate between high/low value of
channel A
Display high value of channel B
Display low value of channel B
Alternate between high/low value of
channel B
Display high value of channel C
Display low value of channel C
Alternate between high/low value of
channel C
Alternate display of channel A and the
unit/tag
Alternate display of channel B and the
unit/tag
Alternate display of channel C and the
unit/tag
Display input channel A gross (no tare)
Alternate display of channel A net (tare)
and gross (no tare)
Display input channel B gross (no tare)
32
Page 33
DP6060 Dual-Input Process Meter Instruction Manual
cleared
Alternate
Sample
Off
Fail-safe
Fail-safe 1
On
Off
Fail-safe 2
Delay
Delay 1
On 1
Off 1
Delay 2
Alternate display of channel B net (tare)
and gross (no tare)
Display Modbus input register
Set display intensity level from 1 to 8
Enter the Relay menu
Assign relays to channels or Modbus
Relay 1 assignment
Assign relay to channel A (*or B or C)
Assign relay to Modbus register
Relay 1 setup
Set relay 1 action
Set relay for automatic reset
Set relay for auto or manual reset any time
Set relay for latching operation
Set relay for latching operation with manual
reset only after alarm condition has cleared
Set relay for pump alternation control
Set relay for sample time trigger control
Turn relay off
Enter Fail-safe menu
Set relay 1-8 fail-safe operation
Enable fail-safe operation
Disable fail-safe operation
Set relays 2-8 fail-safe operation
Enter relay Time Delay menu
Enter relay 1 time delay setup
Set relay 1 On time delay
Set relay 1 Off time delay
Enter relays 2-8 time delay setup
33
Page 34
DP6060 Dual-Input Process Meter Instruction Manual
Display Parameter Action/Setting Description
break
ignore
On
Off
Aout
AOut 1*
Dis 1
Out 1
Dis 2
Out 2
reset
Rst Hi
Rst Lo
Rst HL
Rst tr
Contrl
Auto
mAn
pass
Pass 1*
unloc
locd
999999
-99999
Loop break
Ignore
On
Off
Analog output
Aout Channel
Display 1
Output 1
Display 2
Output 2
Reset
Reset high
Reset low
Reset
high & low
Reset tare
Control
Automatic
Manual
Password
Password 1*
Unlocked
Locked
Flashing
Set relay condition if loop break detected
Ignore loop break condition
(Processed as a low signal condition)
Relay goes to alarm condition when loop
break detected
Relay goes to non-alarm condition when
loop break detected
Enter the Analog output scaling menu
Analog Output source channel (*1-3)
Program display 1 value
Program output 1 value (e.g. 4.000 mA)
Program display 2 value
Program output 2 value (e.g. 20.000 mA)
Press Enter to access the Reset menu
Press Enter to reset max display
Press Enter to reset min display
Press Enter to reset max & min displays
Press Enter to reset (cancel) tare
Enter Control menu
Press Enter to set meter for automatic
operation
Press Enter to manually control relays or
analog output operation
Enter the Password menu
Set or enter Password 1 (*through 3)
Program password to lock meter
Enter password to unlock meter
Over/under range condition
34
Page 35
DP6060 Dual-Input Process Meter Instruction Manual
Main Menu
The main menu consists of the most commonly used functions: Reset,
Control, Setup
Press Menu button to enter Programming Mode then press the Up
arrow button to scroll main menu.
, and Password.
Press Menu, at any time, to exit and return to Run Mode. Changes
made to settings prior to pressing Enter are not saved.
Changes to the settings are saved to memory only after pressing
Enter.
The display moves to the next menu every time a setting is
accepted by pressing Enter.
35
Page 36
DP6060 Dual-Input Process Meter Instruction Manual
.
.
Setting Numeric Values
The numeric values are set using the Right and Up arrow buttons. Press
Right arrow to select next digit and Up arrow to increment digit value.
The digit being changed is displayed brighter than the rest.
Press and hold up arrow to auto-increment the display value.
Press the Enter button, at any time, to accept a setting or Menu button
to exit without saving changes.
000
Select
Next
Digit
004
Increment
Digital
Value
004.000
dis 1dis 1dis 1
00 5
000
Accept
Setting
Next
Setting
36
Page 37
DP6060 Dual-Input Process Meter Instruction Manual
Setting Up the Meter (setup)
The Setup menu is used to select:
1. Input signal the meter will accept for channel A and channel B
2. Units for A, B, and C
3. Decimal point position for A, B, and C
4. Program the meter using the Scale or Calibrate functions
5. Display parameter and intensity
6. Relay assignment and operation
7. 4-20 mA analog output scaling
Press the Menu button to exit at any time.
37
Page 38
DP6060 Dual-Input Process Meter Instruction Manual
Setting the Input Signal (Input)
Enter the Input menu to set up the meter to display current (mA) or
voltage (
volt) inputs for channel A and channel B.
The current input is capable of accepting any signal from 0 to 20 mA.
Select current input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC.
Select voltage input to accept 0-5, 1-5, 0-10, or
10 VDC signals.
Channel C is the Math Function calculation, which is set up in the
Advanced Features menu.
Setting the Decimal Point (dEc pt)
The decimal point may be set with up to five decimal places or with no
decimal point at all.
Pressing the Right arrow moves the decimal point one place to the right
until no decimal point is displayed, and then it moves to the leftmost
position.
There are three decimal points to set up for three channels: Ch-A, Ch-B,
and Ch-C.
After the decimal points are set up, the meter moves to the
menu.
Program
38
Page 39
DP6060 Dual-Input Process Meter Instruction Manual
Programming the Meter (prog)
It is very important to read the following information, before proceeding
to program the meter:
The meter is factory calibrated prior to shipment to read in
milliamps and volts depending on the input selection. The
calibration equipment is certified to NIST standards.
Use the Scale menu to scale the process input (e.g. 4-20 mA). A
calibrated signal source is not needed to scale the meter.
Use the Calibrate menu to apply a signal from a calibrator or a
flowmeter.
The
Program menu contains the Scale and the Calibrate menus for
channels A & B.
The process inputs may be calibrated or scaled to any display value
within the range of the meter.
Note: The Scale and Calibrate functions are exclusive of each other.
The meter uses the last function programmed. Only one of these
methods can be employed at a time. The Scale and Calibrate functions
can use up to 32 points (default is 2). The number of points should be
set in the Advanced Menu under the menu selection prior to scaling and
calibration of the meter, see page 77 for details.
39
Page 40
DP6060 Dual-Input Process Meter Instruction Manual
Multi-Point Linearization (Linear)
The process inputs may be calibrated or scaled to any display value
within the range of the meter.
Additional parameters, not needed for most applications, are
programmed in the
Linearization
Advanced Features menu; see Multi-Point
, page 77.
Multi-Point Calibration & Scaling
The meter is set up at the factory for 2-point linear calibration. The
number of points for multi-point calibration/scaling is set up in the
Advanced Features menu. Up to 32 linearization points may be
selected. See page 77 for details.
DP6000-SOFT Software
The meter can also be programmed using the PC-based DP6000-SOFT
software available for free download at www.omega.com.
Data logging for one meter at the time is available with DP6000-SOFT
software. More advanced data acquisition may be accomplished by
using any Modbus RTU compliant software.
In order to program the meter using a computer, the meter must be
connected using a USB, RS-232, or RS-485 serial adapter, see
ORDERING INFORMATION on page 9 for details.
Scaling the Meter without a Signal Source
The process inputs (4-20 mA, 10 VDC) can be scaled to display the
process variables in engineering units.
A signal source is not needed to scale the meter; simply program the
inputs and corresponding display values.
40
Page 41
DP6060 Dual-Input Process Meter Instruction Manual
Scaling the Meter for Channel A (SCal A)
Scaling the Meter for Channel B (SCal B)
For instructions on how to program
numeric values see
Values
Setting Numeric
, page 36.
41
Page 42
DP6060 Dual-Input Process Meter Instruction Manual
Error Message (Error)
An error message indicates that the calibration or scaling process was
not successful.
After the error message is displayed, the meter reverts to input 2 during
calibration or scaling and to input 1 during internal calibration, allowing
the appropriate input signal to be applied or programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals or it is
connected backwards.
2. Wrong signal selection in
Setup menu.
3. Minimum input span requirements not maintained.
4. Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and
input 2 signals required to complete the calibration or scaling of the meter.
Input RangeInput 1 & Input 2 Span
4-20 mA 0.15 mA
10 VDC
0.10 VDC
Calibrating the Meter with External Source
To scale the meter without a signal source
refer to
Source
Scaling the Meter without a Signal
, page 40.
Warm up the meter for at least 15 minutes
before performing calibration to ensure
specified accuracy.
The meter can be calibrated to display the process variable in
engineering units by applying the appropriate input signal and following
the calibration procedure.
The use of a calibrated signal source is strongly recommended to
calibrate the meter.
42
Page 43
DP6060 Dual-Input Process Meter Instruction Manual
Calibrating the Meter for Channel A (CAL-A)
Calibrating the Meter for Channel B (CAL-B)
43
Page 44
DP6060 Dual-Input Process Meter Instruction Manual
Setting the Display Parameter & Intensity (dsplay)
The Upper display (Big) can be programmed to display:
8. Channel gross value (no tare) or toggle net (tare) and gross
values
9. Modbus input
10. Off (no display)
11. Engineering units or custom legends
Display Intensity: The meter has eight display intensity levels to give
the best performance under various lighting conditions. Select intensity
8 for outdoor applications. The default intensity setting is 8.
Little) can be programmed to display:
44
Page 45
DP6060 Dual-Input Process Meter Instruction Manual
Display Setup Menu
After setting up the input and display, press the Menu button to exit
programming and skip the rest of the setup menu.
The displays can be set up to read channels A, B, or C, toggle between
A & B, B & C, A & C, A & B & C, toggle between channels A, B, or C &
units, the max/min of any of the channels, including the math channel
(C), set points, gross (without tare) or net (with tare) & gross values of
channel A or B, or the Modbus input. In addition to the parameters
available on the Upper display, the Lower display can display
Engineering units or it could be turned off.
45
Page 46
DP6060 Dual-Input Process Meter Instruction Manual
Setting the Input Units or Custom Tags (units)
Enter the input unit or custom tag that will be displayed if alternating
rate, total, or grand total and units is selected in the
is selected as the lower display parameter. See the flow chart on
unit
page 45 to access the display menu to show the unit or tag on the lower
display. The engineering units or custom legends can be set using the
following 7-segment character set:
Display Character
0
1
2
3
4
5
6
7
8
9
A
b
C
c
d
e
f
g
9
H
h
I
I
j
Notes: Degree symbol represented by (<) if programming with DP6000SOFT. The letters “m” and “w” use two 7-segment LEDs each; when
selected the characters to the right are shif ted one position.
Press and hold up arrow to auto-scroll the characters in the display.
0
1
2
3
4
5
6
7
8
9
A
b
C
c
d
E
F
G
g
H
h
I
i
J
Display Character
k
l
m
n
O
o
p
q
r
s
t
u
v
uw
x
y
z
/
[
]
=
!
units menu, or d
K
L
m
n
O
o
P
q
r
S
t
u
V
w
X
Y
Z
-
/
]
[
=
Degree(<)
Space
46
Page 47
DP6060 Dual-Input Process Meter Instruction Manual
Setting the Relay Operation (relay)
This menu is used to set up the assignment and operation of the relays.
During setup, the relays do not follow the input and
!
Caution!
1. Relay assignment
2. Relay action
3. Set point
4. Reset point
5. Fail-safe operation
6. Time delay
7. Relay action for loss (break) of 4-20 mA input (ignore, on, off)
a. Channel A
b. Channel B
c. Channel C (Math channel)
d. Modbus
a. Automatic reset only (non-latching)
b. Automatic + manual reset at any time (non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm
e. Pump alternation control (automatic reset only)
f. Sampling (the relay is activated for a user-specified time)
g. Off (relay state controlled by Interlock feature)
a. On (enabled)
b. Off (disabled)
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
they will remain in the state found prior to entering
the Relay menu.
condition has cleared)
47
Page 48
DP6060 Dual-Input Process Meter Instruction Manual
Setting the Relay Assignment (asSign)
48
Page 49
DP6060 Dual-Input Process Meter Instruction Manual
Setting the Relay Action
Operation of the relays is programmed in the Action menu. The relays
may be set up for any of the following modes of operation:
1. Automatic reset (non-latching)
2. Automatic + manual reset at any time (non-latching)
3. Latching (manual reset only, at any time)
4. Latching with Clear (manual reset only after alarm condition
has cleared)
5. Pump alternation control (automatic reset only)
6. Sampling (the relay is activated for a user-specified time)
7. Off (relay state controlled by Interlock feature)
The following graphic shows relay 1 action setup; relay 2-8 are set up in
a similar fashion.
49
Page 50
DP6060 Dual-Input Process Meter Instruction Manual
Programming Set and Reset Points
High alarm indication: program set point above reset point.
Low alarm indication: program set point below reset point.
The deadband is determined by the difference between set and reset
points. Minimum deadband is one display count. If the set and reset
points are programmed with the same value, the relay will reset one
count below the set point.
Note: Changes are not saved until the reset point has been accepted.
Setting Fail-Safe Operation
In fail-safe mode of operation, the relay coil is energized when the
process variable is within safe limits and the relay coil is de-energized
when the alarm condition exists. The fail-safe operation is set
independently for each relay. Select
disable fail-safe operation.
on to enable or select off to
Programming Time Delay
The On and Off time delays may be programmed for each relay
between 0 and 999.9 seconds. The relays will transfer only after the
condition has been maintained for the corresponding time delay.
On time delay is associated with the set point.
The
Off time delay is associated with the reset point.
The
Relay Action for Loss of 4-20 mA Input (Loop Break)
The loop break feature is associated with the 4-20 mA input. Each relay
may be programmed to go to one of the following conditions when the
meter detects the loss of the input signal (i.e. < 0.005 mA):
1. Turn
2. Turn
3. Ignore (Processed as a low signal condition)
Note: This is not a true loop break condition; if the signal drops below
0.005 mA, it is interpreted as a “loop break” condition.
On (Go to alarm condition)
Off (Go to non-alarm condition)
50
Page 51
DP6060 Dual-Input Process Meter Instruction Manual
Relay and Alarm Operation Diagrams
The following graphs illustrate the operation of the relays, status LEDs,
and ACK button.
High Alarm Operation (Set > Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay.
To detect a new alarm condition, the signal must go below the set point,
and then go above it.
51
Page 52
DP6060 Dual-Input Process Meter Instruction Manual
Low Alarm Operation (Set < Reset)
Input
Reset
Set
Relay
LED
energized
on
de-energized
off
Automatic (non-latching)
Relay
LED
ACK
pressed
Automatic or Manual (non-latching)
Relay
LED
ACK
pressed
Manual (latching)
Relay
LED
ACK
pressed
Manual only after passing above Reset (latching with clear)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay.
For relay to turn back "on", signal must go above set point, and then go
below it.
52
Page 53
DP6060 Dual-Input Process Meter Instruction Manual
High Alarm with Fail-Safe Operation (Set > Reset)
Input
Set
Reset
Relay
LED
energized
off
de-energized
on
Automatic (non-latching)
Relay
LED
ACK
pressed
Automatic or Manual (non-latching)
Relay
LED
ACK
pressed
Manual (latching)
Relay
LED
ACK
pressed
Manual only after passing below Reset (latching with clear)
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
53
Page 54
DP6060 Dual-Input Process Meter Instruction Manual
Low Alarm with Fail-Safe Operation (Set < Reset)
Input
Reset
Set
Relay
LED
de-energized
on
energized
off
Automatic (non-latching)
Relay
LED
ACK
pressed
Automatic or Manual (non-latching)
Relay
LED
ACK
pressed
Manual (latching)
Relay
LED
ACK
pressed
Manual only after passing above Reset (latching with clear)
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
54
Page 55
DP6060 Dual-Input Process Meter Instruction Manual
LEDs indicate the relay status
Pump Alternation Control Operation
Input
Input
de-energized energized
Pump 1
Relay1 &
Relay1 Set
Relay2 Set
Relay2 Reset
Pump 2
Relay1 Set
Relay2 Set
de-energized energized
Relay2 Reset
Relay1 Reset
Pump 1
55
Input
de-energized energized
Pump 1
Pump 2
Relay1 Set
Relay2 Set
Relay1 Reset
Relay2 Reset
Pump 2
Page 56
DP6060 Dual-Input Process Meter Instruction Manual
Relay Sampling Operation
Input
Set
Reset
Relay
LED
Sample
Tim e
Sample
Tim e
Sample
Tim e
When the signal crosses the set point, the relay trips and the sample
time starts. After the sample time has elapsed, the relay resets. The
cycle repeats every time the set point is crossed, going up for high
alarms and going down for low alarms.
The sample time can be programmed between 0.1 and 5999.9 seconds.
56
Page 57
DP6060 Dual-Input Process Meter Instruction Manual
Signal Loss or Loop Break Relay Operation
The following graph shows the loop break relay operation for a high
alarm relay.
Input
Set
Reset
de-energizedenergized
Relay
LED
Relay
LED
offon
Loop Break = Ignore
Loop Break = Off
Relay
LED
Loop Break = On
When the meter detects a break in the 4-20 mA loop, the relay will go to
one of the following selected actions:
1. Turn
2. Turn
On (Go to alarm condition)
Off (Go to non-alarm condition)
3. Ignore (Processed as a low signal condition)
57
Page 58
DP6060 Dual-Input Process Meter Instruction Manual
Time Delay Operation
The following graphs show the operation of the time delay function.
Input
Set
Reset
<Tdelay<Tdelay>=Tdelay
Relay
LED
*
On Time Delay
Input
Set
Reset
<Tdelay<Tdelay>=Tdelay
Relay
LED
*
Off Time Delay
When the signal crosses the set point, the
On time delay timer starts
and the relay trips when the time delay has elapsed. If the signal drops
below the set point (high alarm) before the time delay has elapsed, the
On time delay timer resets and the relay does not change state. The
same principle applies to the
Off time delay.
Note: If “Automatic or Manual (A-mAn)” reset mode is selected, the
LED follows the reset point and not the relay state when the
relay is acknowledged.
58
Page 59
DP6060 Dual-Input Process Meter Instruction Manual
Relay Operation Details
Overview
The relay capabilities of the meter expand its usefulness beyond simple
indication to provide users with alarm and control functions. These
capabilities include front panel alarm status LEDs as well as either 2 or
4 optional internal relays and/or 4 external relays expansion module.
Typical applications include high or low temperature, level, pressure or
flow alarms, control applications such as simple on/off pump control,
and pump alternation control for up to 8 pumps. There are four basic
ways the relays can be used:
1. High or Low Alarms with Latching or Non-Latching Relays
2. Simple On/Off Control with 100% Adjustable Deadband
3. Sampling (Based on Time)
4. Pump Alternation Control for up to 8 Pumps
Relays Auto Initialization
When power is applied to the meter, the front panel LEDs and alarm
relays will reflect the state of the input to the meter. The following table
indicates how the alarm LEDs and relays will react on power-up based
on the set and reset points:
Alarm # HI or LO
Alarm
1 HI 1000 500 499 Off
2 LO 700 900 499 On
3 LO 250 400 499 Off
4 HI 450 200 499 On
Set
Point
Reset
Point
Power-Up
Reading
Fail-Safe Operation
The following table indicates how the relays behave based on the failsafe selection for each relay:
Fail-Safe
Selection
Off Open Closed Closed Open Relays go to
On Closed Open Open Closed Relays go to
Note: NO = Normally Open, NC = Normally Closed. This refers to the
Non-Alarm State Alarm State Power Failure
NO NC NO NC
condition of the relay contacts when the power to the meter is off.
Relay &
LED
non-alarm state
alarm state
59
Page 60
DP6060 Dual-Input Process Meter Instruction Manual
Front Panel LEDs
The LEDs on the front panel provide status indication for the following:
The meter is supplied with four alarm points that include front panel
LEDs to indicate alarm conditions. This standard feature is particularly
useful for alarm applications that require visual-only indication. The
LEDs are controlled by the set and reset points programmed by the
user. When the display reaches a set point for a high or low alarm, the
corresponding alarm LED will turn on. When the display returns to the
reset point the LED will go off. The front panel LEDs responds
differently for latching and non-latching relays.
For non-latching relays, the LED is always off during normal condition
and always on during alarm condition, regardless of the state of the
relay (e.g. Relay acknowledged after alarm condition).
For latching relays, the alarm LEDs reflects the status of the relays,
regardless of the alarm condition. The following tables illustrate how the
alarm LEDs function in relation to the relays and the acknowledge
button (Default: F3 key assigned to ACK):
Latching and Non-Latching Relay Operation
The relays can be set up for latching (manual reset) or non-latching
(automatic reset) operation.
Relay terminology for following tables
TerminologyRelay Condition
On Alarm (Tripped)
Off Normal (Reset)
Ack Acknowledged
The On and Off terminology does not refer to the status of the relay’s
coil, which depends on the fail-safe mode selected.
Warning!
In latching relay mode, latched
relays will reset (unlatch) when
power is cycled.
60
Page 61
DP6060 Dual-Input Process Meter Instruction Manual
Non-Latching Relay (Auto)
Automatic reset only
ConditionLEDRelay
Normal Off Off
Alarm On On
Ack (No effect) On On
Normal Off Off
In this application, the meter is set up for automatic reset (non-latching
relay). Acknowledging the alarm while it is still present has no effect on
either the LED or the relay. When the alarm finally goes away, the relay
automatically resets and the LED also goes off.
Non-Latching Relay (A-man)
Automatic + manual reset at any time
ConditionLEDRelay
Normal Off Off
Alarm On On
Normal Off Off
Next Alarm On On
Ack On Off
Normal Off Off
In this application, the meter is set up for automatic and manual reset at
any time (non-latching relay). The LED and the relay automatically reset
when the meter returns to the normal condition.
The next time an alarm occurs, the operator acknowledges the alarm
manually while the alarm condition still exists. This causes the relay to
reset, but the LED stays on until the meter returns to the normal
condition.
Latching Relay (LatcH)
Manual reset any time
ConditionLEDRelay
Normal Off Off
Alarm On On
Ack Off Off
In this application, the meter is set up for manual reset at any time.
Acknowledging the alarm even if the alarm condition is still present
resets the relay and turns off the LED.
61
Page 62
DP6060 Dual-Input Process Meter Instruction Manual
A
Latching Relay (Lt-Clr)
Manual reset only after alarm condition has cleared
ConditionLEDRelay
Normal Off Off
Alarm On On
Ack (No effect) On On
Normal On On
Ack Off Off
In this application, the meter is set up for manual reset only after the
signal passes the reset point (alarm condition has cleared).
Acknowledging the alarm while it is still present has no effect on either
the LED or the relay. When the alarm is acknowledged after it returns to
the normal state, the LED and the relay go off. Notice that the LED
remains on, even after the meter returns to the normal condition. This is
because, for latching relays, the alarm LED reflects the status of the
relay, regardless of the alarm condition.
Acknowledging Relays
There are two ways to acknowledge relays programmed for manual
reset:
1. Via the programmable front panel function keys F1-F3 (Default:
F3 assigned to ACK).
2. Remotely via a normally open pushbutton wired across one of
the digital inputs and the +5 V terminals on the digital I/O
modules, or using the F4 digital input, which is triggered with a
contact closure to COM, or with an active low signal (see page
26).
When the ACK button or the assigned digital input is closed, all relays
programmed for manual reset are acknowledged.
DPA1044 Digital I/O Module
12345678910
I1I2I3 I4
+5
DI 1-4
Figure 21. Acknowledge Relays w/Function Key or Digital Input
62
O1O2 O3 O4 G
DO 1-4
CK
GND
Page 63
DP6060 Dual-Input Process Meter Instruction Manual
Pump Alternation Control Applications (Altern)
For pump control applications where two or more similar pumps are
used to control the level of a tank or a well, it is desirable to have all the
pumps operate alternately. This prevents excessive wear and
overheating of one pump over the lack of use of the other pumps.
Up to 8 relays can be set up to alternate every time an on/off pump
cycle is completed. The set points and reset points can be programmed,
so that the first pump on is the first pump off.
Application #1: Pump Alternation Using Relays 1 & 2
1. Relays 1 and 2 are set up for pump alternation.
2. Relays 3 and 4 are set up for low and high alarm indication.
Set and Reset Point Programming with Pump Alternation
1. Pump #1 turns on when level reaches 30.000, when level drops
below 10.000 pump #1 turns off.
2. The next time level reaches 30.000, pump #2 turns on, when level
drops below 10.000, pump #2 turns off.
3. If the level doesn’t reach 35.000 pump #1 and pump #2 will be
operating alternately.
4. If pump #1 cannot keep the level below 35.000 pump #2 will turn on
at 35.000, then as the level drops to 10.000 pump #1 turns off,
pump #2 is still running and shuts off below 5.000.
5. Notice that with the set and reset points of pump #2 outside the
range of pump #1, the first pump on is the first pump to go off. This
is true for up to 8 alternating pumps, if setup accordingly.
6. Relay #3 will go into alarm if the level drops below 4.000 and relay
#4 will go into alarm if the level exceeds 40.000.
7. Adding the 4 external relays expansion module allows using the 4
SPDT internal relays for pump alternation and the 4 SPST external
relays for high, high-high, low, and low-low alarm indication.
63
Page 64
DP6060 Dual-Input Process Meter Instruction Manual
Setting Up the Interlock Relay (Force On) Feature
Relays 1-4 can be set up as interlock relays. To set up the relays for the
interlock feature:
1. Access the
2. In the Advanced features –
inputs to
3. Connect a switch or dry contact between the +5V terminal and the
corresponding digital input (dI-1 to dI-4) terminal.
Setup – Relay – Action menu and set the action to off.
User menu program any of the digital
Force On any of the internal relays (1-4).
SW2
SW1
123456
+5I1I2I3I4O1
5 VDCGND
DI 1-4DO 1-4
64
78
O2 O3
910
O4G
Page 65
DP6060 Dual-Input Process Meter Instruction Manual
Interlock Relay Operation Example
Relays 1 & 2 are configured to energize (their front panel LEDs are off)
when SW1 & SW2 switches (above) are closed. If the contacts to these
digital inputs are opened, the corresponding front panel LEDs flash,
indicating this condition. The processes being controlled by the interlock
relay will stop, and will re-start only after the interlock relay is reactivated by the digital inputs (switches).
Note: If multiple digital inputs are assigned to the same relay, then the
corresponding logic is (AND) – i.e. both switches must be closed to trip
the relay.
Scaling the 4-20 mA Analog Output (Aout)
The 4-20 mA analog output can be scaled to provide a 4-20 mA signal
for any display range selected. To select the channel the analog output
is assigned to, see
No equipment is needed to scale the analog output; simply program the
display values to the corresponding mA output signal.
The
Analog Output menu is used to program the 4-20 mA output based
on display values.
Analog Output Source on page 80.
**
* IfInstalled
For instructions on how to program
numeric values see
Values
Setting Numeric
, page 36.
65
Page 66
DP6060 Dual-Input Process Meter Instruction Manual
Reset Menu (reset)
The Reset menu is used to reset the maximum or minimum reading
(peak or valley) reached by the process; both may be reset at the same
time by selecting “reset high & low” (
zero the display may be reset by selecting “reset tare” (
rst HL). The tare value used to
rst tr).
Control Menu (Contrl)
The Control menu is used to control the 4-20 mA analog output and the
relays manually, ignoring the input. Each relay and analog output can
be programmed independently for manual control. Selecting automatic
control sets all relays and analog output for automatic operation.
66
Page 67
DP6060 Dual-Input Process Meter Instruction Manual
Setting Up the Password (pass)
The Password menu is used for programming three levels of security to
prevent unauthorized changes to the programmed parameter settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs
Protecting or Locking the Meter
Enter the Password menu and program a six-digit password.
For instructions on how to program numeric values see
Values
, page 36.
Record the password for future reference. If appropriate, it may be
recorded in the space provided.
DP6060 Dual-Input Process Meter Instruction Manual
Making Changes to a Password Protected Meter
If the meter is password protected, the meter will display the message
Locd (Locked) when the Menu button is pressed. Press the Enter button
while the message is being displayed and enter the correct password to
gain access to the menu. After exiting the programming mode, the
meter returns to its password protected condition.
Disabling Password Protection
To disable the password protection, access the Password menu and
enter the correct password twice, as shown below. The meter is now
unprotected until a new password is entered.
If the correct six-digit password is entered, the meter displays the
message
password is programmed.
If the password entered is incorrect, the meter displays the message
Locd (Locked) for about two seconds, and then it returns to Run Mode.
To try again, press Enter while the
unLoc (Unlocked) and the protection is disabled until a new
Locked message is displayed.
Did you forget the password?
The password may be disabled by entering a master
password once. If you are authorized to make changes,
enter the master password 508655 to unlock the meter.
68
Page 69
DP6060 Dual-Input Process Meter Instruction Manual
Advanced Features Menu
To simplify the setup process, functions not needed for most
applications are located in the
Press and hold the Menu button for three seconds to access the
advanced features of the meter.
Advanced Features menu.
69
Page 70
DP6060 Dual-Input Process Meter Instruction Manual
Advanced Features Menu & Display Messages
The following table shows the functions and messages of the Advanced
Features
Display Parameter Action/Setting
filtEr
Ch-A
Ch-b
bypASs
Ch-A
Ch-b
Round
seriAl
SelEct
Functn
Ch-A
Ch-b
nmath
Sunm
Dif
difabs
Avg
nmulti
menu in the order they appear in the menu.
Set noise filter value
Set filter value for channel A
Set filter value for channel B
Set filter bypass value
Set filter bypass value for channel A
Set filter bypass value for channel B
Set the rounding value for display
variables
Set serial communication parameters
Set slave ID or meter address
Select baud rate
Set transmit delay for serial
communication
Select parity
Even, Odd, or None with 1 or 2 stop bits
Set byte-to-byte timeout
Enter the Select menu (function, cutoff,
out)
Select linear, square root, programmable
exponent, or round horizontal tank function
Select menu for channel A
Select menu for channel B
Set meter for linear function and select
number of linearization points
Set the number of linearization points
(default: 2)
Set meter for square root extraction
Set meter for programmable exponent and
enter exponent value
Set meter for round horizontal tank volume
calculation
Enter the tank’s length in inches
Enter the tank’s diameter in inches
Enter the setup menu for channel C math
functions
Channel C = (A+B+P)*F
Channel C = (A-B+P)*F
Channel C = ((Absolute value of (AB))+P)*F
Channel C = (((A+B)/2)+P)*F
Channel C = ((A*B)+P)*F
70
SlaveId
Baud
Tr dLY
Parity
t-byt
Linear
No pts
Square
Prog E
Rht
Length
dianmr
Filter
Channel A
Channel B
Bypass
Channel A
Channel B
Round
Serial
Slave ID
Baud rate
Transmit delay
Parity
Time byte
Select
Signal input
conditioning
Channel A
Channel B
Linear
Number of
points
Square root
Programmable
exponent
Round
horizontal tank
Length
Diameter
Math
Sum
Difference
Absolute
difference
Average
Multiplication
Page 71
DP6060 Dual-Input Process Meter Instruction Manual
Display Parameter Action/Setting
Divide
Hi-ab
Lo-ab
Drauw
uwAvg
ratio
Concen
Const
adder
factor
CutofF
Ch-A
Ch-b
AoutPr
AOut 1*
Source
break
O-rang
u-rang
nmAx
nmin
Calib
4 nmA
20 nmA
User
F1*
F4
dI I
dO 1
ICal
Ch-A
Ch-b
Divide
Max of A or B
Min of A or B
Draw
Weighted avg.
Ratio
Concentration
Constant
Adder
Factor
Cutoff
Channel A
Channel B
Analog output
programming
Analog output 1
Source
Loop break
Overrange
Underrange
Maximum
Minimum
Calibrate
4 mA output
20 mA output
User I/O
F1* function key
F4 function
Digital input 1
Digital output 1
Internal
calibration
Channel A
Channel B
Channel C = ((A/B)+P)*F
C = ((High value of channel A or B)+P)*F
C = ((Low value of channel A or B)+P)*F
Channel C = ((A/B)-1)*F
Channel C = ((B-A)*F)+A
Channel C = (A/B)*F
Channel C = (A/(A+B))*F
Constant used in channel C math
Addition constant used in channel C math
calculations (P)
Multiplication constant used in channel C
math calculations (F)
Set low-flow cutoff
Set low-flow cutoff for Channel A
Set low-flow cutoff for Channel B
Program analog output parameters
Program analog output 1 (*1-3)
parameters
Select source for the 4-20 mA output
Set relay condition if loop break detected
Program mA output for display overrange
Program mA output for display underrange
Program maximum mA output allowed
Program minimum mA output allowed
Calibrate 4-20 mA output (internal
reference source used for scaling the
output)
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
Assign function keys and digital I/O
Assign F1 function key (*F1/F2/F3)
Assign F4 function (digital input)
Assign digital input 1 – 8, if expansion
modules are connected
Assign digital output 1 – 8, if expansion
modules are connected
Enter internal calibration (used for
recalibrating the meter with a calibrated
signal source)
Perform calibration on channel A
Perform calibration on channel B
71
Page 72
DP6060 Dual-Input Process Meter Instruction Manual
Display Parameter Action/Setting
C CAL
C lo
C Hi
v CAL
v Lo
v Hi
Copy
Send
Done
Diag
LED t
Info
Current
calibration
Current low
Current high
Voltage
calibration
Voltage low
Voltage high
Copy
Send
Done
Diagnostics
LED test
Information
Calibrate 4-20 mA current input (internal
reference source used for scaling the
input)
Calibrate low current input (e.g. 4 mA)
Calibrate high current input (e.g. 20 mA)
Calibrate voltage input
Calibrate low voltage input (e.g. 0 V)
Calibrate high voltage input (e.g. 10 V)
Enter copy function
Send meter settings to another meter
Copy function completed
Display parameter settings
Test all LEDs
Display software and S/N information
72
Page 73
DP6060 Dual-Input Process Meter Instruction Manual
Noise Filter (filter)
The noise filter is available for unusually noisy signals that cause an
unstable process variable display. The noise filter averages the input
signal over a certain period. The filter level determines the length of time
over which the signal is averaged. The filter level can be set between 2
and 199. The higher the filter level, the longer the averaging time and so
the longer it takes the display to settle to its final value. Setting the filter
level to zero disables the filter function.
Noise Filter Bypass (bypass)
The noise filter bypass changes the behavior of the meter so that small
variations in the signal are filtered out but large abrupt changes in the
input signal are displayed immediately. The bypass value determines
the minimum amount of signal change to be displayed immediately. All
signal changes smaller than the bypass value are filtered or averaged
by the meter. The noise filter bypass may be set between 0.1 and
99.9% of full scale.
73
Page 74
DP6060 Dual-Input Process Meter Instruction Manual
Rounding Feature (round)
The rounding feature is used to give the user a steadier display with
fluctuating signals. Rounding is used in addition to the filter function.
Rounding causes the display to round to the nearest value according to
the rounding selected. This setting affects the last two digits, regardless
of decimal point position.
Modbus RTU Serial Communications (serial)
The meter is equipped with serial communications capability as a
standard feature using Modbus RTU Serial Communication Protocol.
To communicate with a computer or other data terminal equipment, an
RS-232, RS-485, or USB adapter option is required; see
Information
on page 9 for details.
Do not connect any equipment other than Omega’s
expansion modules, cables, or meters to the RJ45
Warning!
M-LINK connector. Otherwise damage will occur to the
equipment and the meter.
Note: More detailed instructions are provided with each optional serial
communications adapter. Note: Refer to the Modbus Register
Tables located at www.omega.com for details.
Ordering
When using more than one meter in a multi-drop mode, each meter
must be provided with its own unique address. The meter address
(Slave ID) may be programmed between 1 and 247. The transmit delay
may be set between 0 and 199 ms. The parity can be set to even, odd,
or none with 1 or 2 stop bits.
74
Page 75
DP6060 Dual-Input Process Meter Instruction Manual
Select Menu (SElect)
The Select menu is used to select the signal input conditioning function
applied to the inputs (linear, square root, programmable exponent, or
round horizontal tank), math function for A & B, constants, low-flow
cutoff, and analog output programming. The multi-point linearization is
part of the linear function selection.
75
Page 76
DP6060 Dual-Input Process Meter Instruction Manual
Signal Input Conditioning (Functn)
The Function menu is used to select the input-to-output transfer function
applied to the input signal: linear, square root, programmable exponent,
or round horizontal tank volume calculation. The multi-point linearization
is part of the linear function selection.
Meters are set up at the factory for linear function with 2-point
linearization. The linear function provides a display that is linear with
respect to the input signal.
Square Root Linearization (Square)
The square root function is used to calculate flow measured with a
differential pressure transmitter. The flow rate is proportional to the
square root of the differential pressure. Scale the meter so that the low
input signal (e.g. 4 mA) is equal to zero flow and the high input signal
(e.g. 20 mA) is equal to the maximum flow.
Programmable Exponent Linearization (Prog E)
The programmable exponent function is used to calculate open-channel
flow measured with a level transmitter in weirs and flumes. The flow rate
is proportional to the head height. Scale the meter so that the low input
signal (e.g. 4 mA) is equal to zero flow and the high input signal (e.g. 20
mA) is equal to the maximum flow. This method works well for all weirs
and flumes that have a simple exponent in the flow calculation formula.
For weirs and flumes with complex exponents it is necessary to use a
strapping table and the 32-point linearization of the meter.
76
Page 77
DP6060 Dual-Input Process Meter Instruction Manual
Multi-Point Linearization (Linear)
Meters are set up at the factory for linear function with 2-point
linearization. Up to 32 linearization points can be selected for each
channel under the linear function. The multi-point linearization can
linearize the display for non-linear signals such as those from level
transmitters used to measure volume in odd-shaped tanks or to convert
level to flow using weirs and flumes with complex exponent.
Round Horizontal Tank Linearization (rHt)
This function is used to calculate volume in a round horizontal tank with
flat ends. The volume is calculated based on the diameter and length of
the tank. The tank’s dimensions can be entered in inches or
centimeters; the meter automatically calculates the volume in gallons or
liters. After entering the dimensions, complete the scaling process with
the display values calculated by the meter. The meter can be re-scaled
to display the volume in any engineering unit without the need to reenter the dimensions again.
Note: After Scale is displayed continue pressing the Enter button until
the meter completes the scaling of the input and display values.
77
Page 78
DP6060 Dual-Input Process Meter Instruction Manual
Changing the Volume from Gallons to Liters
In the above graphic, entering the 48" for the diameter and 120" for the
length of the round horizontal tank, the meter automatically calculates
that the volume of the tank is 940.02 gallons.
1. Convert gallons to liters
1 US gallon = 3.7854 L
940.02 gal = 3558.4 L
2. Go to the
3. Go to the
Setup menu and change the decimal point to 1 decimal.
Program – Scale menu and press Enter until dis 2 is
shown on the Upper display.
4. Press Enter and change the display 2 value to 3558.4.
5. The meter is now displaying the volume in liters.
Note: The display can be scaled to display the volume in any
engineering units.
Math Function (math)
The Math menu is used to select the math function that will determine
the channel C value. These math functions are a combination of input
channels A and B, and will display when channel C is selected in the
Display menu.
The following math functions are available.
Function Display Description
Sunm
Dif
difabs
Avg
nmulti
Divide
Hi-ab
Lo-ab
Drauw
uwAvg
ratio
Concen
Sum
Difference
Absolute
difference
Average
Multiplication
Divide
Max of A or B
Min of A or B
Draw
Weighted avg.
Ratio
Concentration
Channel C = (A+B+P)*F
Channel C = (A-B+P)*F
Channel C = ((Absolute value of (AB))+P)*F
Channel C = (((A+B)/2)+P)*F
Channel C = ((A*B)+P)*F
Channel C = ((A/B)+P)*F
C = ((High value of channel A or B)+P)*F
C = ((Low value of channel A or B)+P)*F
Channel C = ((A/B)-1)*F
Channel C = ((B-A)*F)+A
Channel C = (A/B)*F
Channel C = (A/(A+B))*F
78
Page 79
DP6060 Dual-Input Process Meter Instruction Manual
Math Constants (Const)
The Math Constants menu is used to set the constants used in channel
C math. The math functions include input channel A and B, as well as
the adder constant P, and factor constant F.
The
Adder constant (P) may be set from -99.999 to 999.999.
The
Factor constant (F) may be set from 0.001 to 999.999.
The chart on page 78 details the math functions that may be selected in
Math Function menu.
the
Low-Flow Cutoff (CutofF)
The low-flow cutoff feature allows the meter to be programmed so that
the often-unsteady output from a differential pressure transmitter, at low
flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 999999. The meter will
display zero below the cutoff value. Programming the cutoff value to
zero disables the cutoff feature.
Analog Output Programming (AoutPr)
The Analog Output Programming menu is used to program the behavior
of the 4-20 mA output. The following parameters and functions are
programmed in this menu:
1. Source: Source for generating the 4-20 mA output
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Break: Analog output value when loop break is detected
5. Max: Maximum analog output value allowed regardless of input
6. Min: Minimum analog output value allowed regardless of input
7. Calibrate: Calibrate the internal 4-20 mA source reference used to
scale the 4-20 mA output
79
Page 80
DP6060 Dual-Input Process Meter Instruction Manual
Analog Output Source
The analog output source can be based on either of the input channels
(Ch-A, Ch-B), the math channel (Ch-C), maximum stored value of either
input channel (Hi-A, Hi-B), minimum stored value of either input channel
(Lo-A, Lo-B), relay set points, or the Modbus input.
Analog Output Calibration
To perform the analog output calibration it is recommended to use a
milliamp meter with a resolution of at least 0.1 µA to measure the output
current. The values saved internally during this procedure are used for
scaling the 4-20 mA output in the
Setup menu.
80
Page 81
DP6060 Dual-Input Process Meter Instruction Manual
Programmable Function Keys User Menu (user)
The User menu allows the user to assign the front panel function keys
F1, F2, F3, F4 (digital input) and up to eight digital inputs to access
most of the menus or to activate functions immediately (e.g. Reset max
& min). F4 is a digital input on the signal input connector. Up to eight
digital outputs can be assigned to a number of actions and functions
executed by the meter (e.g. Alarms, relay acknowledgement, etc.).
Please refer to the table below, which continues on the following page.
*If installed
Function Keys & Digital I/O Available Settings
Display Description Display Description
Rst HL
relay
Set 1
Rly d
Rly E
O Hold
D Hold
D AbC
Reset max & min
(A, B, C)
Relay menu
Set point 1 - 8
Disable relay
Enable relay
Relay output hold
Display hold while
active
Scrolls values for A, B
& C when activated.
Keeps the last value
for 10 seconds and
then it returns to its
assignment. Values
are displayed on the
upper display and the
corresponding
channel and units on
the Lower display.
Big Hi
Big Lo
Big HL
Lit Hi
Lit Lo
Lit HL
Lit HC
Lit LC
81
Max on upper display
(Channel A)
Min on upper display
(Channel A)
Max/min upper
display (Channel A)
Max on lower display
(Channel B)
Min on lower display
(Channel B)
Max/min lower display
(Channel B)
Max on lower display
(Channel C)
Min on lower display
(Channel C)
Page 82
DP6060 Dual-Input Process Meter Instruction Manual
Display Description Display Description
LitHLC
disabl
Contrl
Tare a
Tare b
Rst tr
AcH
reset
Rst Hi
Rst Lo
Max/min lower display
(Channel C)
Disable function key
Control Menu
Set channel A display
value to zero (A LED
flashes – same rate
as M)*
Set channel B display
value to zero (B LED
flashes – same rate
as M)*
Reset tare for A & B
(Channel LED off)
Acknowledge relays
Reset Menu
Reset max
Reset min
menu
Right
up
Enter
Alrm 1
F on 1
F on 2
F on 3
F on 4
Menu button
Right arrow button
Up arrow button
Enter button
Alarm 1 – 8 (Digital
Output)
Force on relay 1
Force on relay 2
Force on relay 3
Force on relay 4
* If math functions are displayed, the math function indicator LED “C”
will flash when either A or B channel is using a tare value (net value).
82
Page 83
DP6060 Dual-Input Process Meter Instruction Manual
Tare (tare A, tare B)
The tare function zero’s out the display. In the case of scale weight, tare
is used to eliminate container weight and provide net weight readings.
There are two tare functions; Capture Tare for channel A and B, and
Reset Tare. Display channel indicator letter flashes when a tare is used.
It will flash until the tare is reset.
0.2
lbs
Before tare
Gross (without tare) and net (with tare) values can be viewed
simultaneously. See page 44.
0.0
lbs
After capture tare
0.2
lbs
After reset tare
Internal Calibration (ICAL)
The meter is factory calibrated prior to shipment
to read in milliamps and volts depending on the
input selection. The calibration equipment is
The use of calibrated signal sources is necessary to perform the internal
calibration of the meter.
Check calibration of the meter at least every 12 months. Each input and
input type must be recalibrated separately.
Notes:
1. If meter is in operation and it is intended to accept only one input
type (e.g. 4-20 mA), recalibration of other input is not necessary.
2. Allow the meter to warm up for at least 15 minutes before
performing the internal calibration procedure.
The
Internal calibration menu is part of the Advanced Features menu.
1. Press and hold the Menu button for three seconds to access the
advanced features of the meter.
2. Press the Up
ICAL) and press Enter.
(
3. Select channel A (
certified to NIST standards.
arrow button to scroll to the Internal calibration menu
Ch-A) or channel B (Ch-b) and press enter.
83
Page 84
DP6060 Dual-Input Process Meter Instruction Manual
4. The meter displays either current calibration (
calibration (
v CAL), according to the input setup. Press Enterto
C CAL) or voltage
start the calibration process.
Example of Internal Calibration for current input:
5. The meter displays low input current message (C lo). Apply the
low input signal and press Enter. The display flashes for a moment
while the meter is accepting the low input signal.
6. After the display stops flashing, a number is displayed with the
leftmost digit brighter than the rest. The bright digit is the active digit
that can be changed by pressing the Up
arrow button to move to the next digit.
Right
arrow button. Press the
7. Set the display value to correspond to the input signal being
calibrated, typically 4.000 mA.
8. The display moves to the
high input calibration (C Hi). Apply the
high input signal and press Enter.
9. Set the display for the high input calibration, in the same way as it
was set for the low input calibration, typically 20.000 mA.
The graphic above shows the calibration of the current input. The
voltage input is calibrated in a similar way.
Tips:
Low and high input signals can be any valid values within the
range of the meter.
Observe minimum input span requirements between input 1
and input 2.
Low input should be less than high input signal.
84
Page 85
DP6060 Dual-Input Process Meter Instruction Manual
Error Message (Error)
An error message indicates that the calibration or scaling process was
not successful.
After the error message is displayed, the meter reverts to input 2 during
calibration or scaling and to input 1 during internal calibration, allowing
the appropriate input signal to be applied or programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals, or it is
connected backwards.
2. Wrong signal selection in
3. Minimum input span requirements not maintained.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and
input 2 signals required to complete the calibration or scaling of the meter.
Input Range Input 1 & Input 2 Span
4-20 mA 0.15 mA
10 VDC
Setup menu.
0.10 VDC
Meter Copy Function (Copy)
The Copy function is used to copy (or clone) all the settings from one
meter to other meters requiring exactly the same setup and
programming (
etc.).
i.e. type of input, scaling, decimal point, filter, bypass,
Only the DPA1200 meter copy cable must be used for
Warning!
To successfully copy settings from one meter to another, both meters
must have the same software version and the same baud rate setting.
See Determining Software Version, page 89 for instructions.
meter-to-meter interfacing.
Using standard CAT5 or other cable will cause
damage to both meters.
Copy Function Requirements
85
Page 86
DP6060 Dual-Input Process Meter Instruction Manual
Meter Copy or Cloning Instructions
Do not connect the two meters to
!
Caution!
1. Connect two meters using a DPA1200 meter copy cable.
Using standard CAT5 or other cable will cause
Warning!
2. Do not connect the two meters to the same signal source.
3. Power up both meters. Leave Clone meter in Run Mode.
4. Enter the
Advanced Features Menu on page 69.
5. Scroll to the
Enter.
6. The meter displays the message
flashes while sending data. The message
copying is completed.
damage to both meters. Use DPA1200 meter copy
cable only.
Advanced Features menu of the Master meter; see
Copy function using the Uparrow button then press
the same signal source while
cloning. Internal calibration may
be affected.
Send. Press Enter, the display
done is displayed when
7. The Clone meter displays the message CPY Rc while being
programmed then the message
The meter initializes and returns to Run Mode using the same
settings as the Master.
8. If meter to be cloned does not respond to the data being sent, refer
to
Copy Function Requirements above.
done when copying is completed.
86
Page 87
DP6060 Dual-Input Process Meter Instruction Manual
METER OPERATION
The meter is capable of accepting two input channels (A and B) of either
current (0-20 mA, 4-20 mA) or voltage signals (0-5 V, 1-5 V, 0-10 V,
10 V) and displaying these signals in engineering units from -99999 to
999999 (
50.000).
A math function channel (C) is available to perform operations on
channel A and B, with adder and factor constants, and display the
results. Engineering units or tags may be displayed with these three
channels.
The dual-line display can be customized by the user. Typically the upper
display is used to display the math channel C, while the lower display is
used to alternate between displaying input channels A and B.
Additionally the meter can be set up to display any input or math
channel on the upper display and a unit or tag on the lower display. The
relays and analog output can be programmed to operate based on any
input or math channel.
e.g. a 4-20 mA signal could be displayed as -50.000 to
Front Panel Buttons Operation
Button
Symbol
Description
Press to enter or exit Programming Mode,
view settings, or exit max/min readings
Press to reset max/min readings or other
parameter/function assigned through the
menu
Press to display max/min readings for channel
A or other parameter/function assigned
through the
Press to acknowledge relays or other
parameters/function assigned through the
User menu
User menu
User
Function Keys Operation
During operation, the programmable function keys operate according to
the way they have been programmed in the
menu.
The table above shows the factory default settings for F1, F2, and F3.
87
Advanced Features – User
Page 88
DP6060 Dual-Input Process Meter Instruction Manual
F4 Operation
A digital input, F4, is standard on the meter. This digital input is
programmed identically to function keys F1, F2, and F3. The input is
triggered with a contact closure to COM, or with an active low signal.
During operation, F4 operates according to the way is has been
programmed in the
Advanced Features – User menu.
Maximum/Minimum Readings
The max & min readings (peak & valley) reached by the process can be
displayed either continuously or momentary:
1. Display briefly by assigning to the F1-F3 function keys or to the
digital inputs in the
2. Display continuously by assigning either display to max/min
through the
Any of the F1-F3 function keys (buttons) and the digital inputs can be
programmed to reset the max & min readings. The meters are set at the
factory to display the max reading by pressing the Up arrow/F2 button
and to use the Right arrow/F1 button to access the
To display max and min channel A reading using function key with
factory defaults:
1. Press Up arrow/F2 button to display minimum reading of channel A
since the last reset/power-up. The display will then display the
maximum reading of channel A since the last reset/power-up.
2. Press the Up arrow/F2 button again to display the minimum reading
of channel A since the last reset/power up.
3. To reset max/min press Right arrow/F1 button to access the Reset
menu. The max & min displays are reset to actual values.
4. Press Menu to exit max/min display reading.
User menu.
Display menu.
Reset menu.
88
Page 89
DP6060 Dual-Input Process Meter Instruction Manual
TROUBLESHOOTING
The rugged design and the user-friendly interface of the meter should
make it unusual for the installer or operator to refer to this section of the
manual. However, due to the many features and functions of the meter,
it’s possible that the setup of the meter does not agree with what an
operator expects to see.
If the meter is not working as expected, refer to the
and recommendations below.
Diagnostics Menu (diag)
The Diagnostics menu is located in the AdvancedFeatures menu, to
Diagnostics menu see Advanced Features Menu, page 69.
access
It provides an easy way to view the programmed parameter settings for
troubleshooting purposes. Press the Enter
and the Menu button to exit at any time.
For a description of the diagnostic messages,
Menu &
Display Messages, page 70.
Determining Software Version
To determine the software version of a meter:
1. Go to the
2. Press Up arrow button and scroll to Information menu (
3. Press Enter to access the software number (
UER) information. Write down the information as it is displayed.
(
Continue pressing Enter until all the information is displayed.
4. The meter returns to Run Mode after displaying all the settings.
Diagnostics menu (diAG) and press Enter button.
button to view the settings
Diagnostics menu
see Advanced Features
Info).
SFT) and version
89
Page 90
DP6060 Dual-Input Process Meter Instruction Manual
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to
determine what’s happening, it might be better to start the setup
process from the factory defaults.
Instructions to load factory defaults:
1. Enter the Advanced Features menu. See Advanced Features
, page 69.
Menu
2. Press Up arrow to go to
3. Press and hold Right arrow for three seconds, press
Enter when display flashes
Note: If Enter is not pressed within three seconds, the display
returns to Run Mode.
4. The meter goes through an initialization sequence (similar as on
power-up), and loads the factory default settings.
Diagnostics menu
reset.
90
Page 91
DP6060 Dual-Input Process Meter Instruction Manual
Factory Defaults & User Settings
The following table shows the factory setting for most of the
programmable parameters on the meter. Next to the factory setting, the
user may record the new setting for the particular application.
Input type
Input type, channel A
Input type, channel B
Unit
Unit, channel A
Unit, channel B
Unit, channel C
Number of points
Number of points, ch A)
Number of points, ch B)
Scaling, (channel A)
Input 1, channel A
Display 1, channel A
Input 2, channel A
Display 2, channel A
Scaling (channel B)
Input 1, channel B
Display 1, channel B
Input 2, channel B
Display 2, channel B
Math, channel C
Adder (constant P)
Factor (constant F)
Filter
Filter, channel A
Filter, channel B
Bypass, channel A
Bypass, channel B
Round
Cutoff
Cutoff value, channel A
Cutoff value, channel B
Display assignment
Upper display
Lowerdisplay
Display intensity
Relay 1 assignment
Input
Ch-A
Ch-B
unit
Ch-A
Ch-B
Ch-C
No pts
Ch-A
Ch-B
Scal a
InP 1
Dis 1
InP 2
Dis 2
Scal b
InP 1
Dis 1
InP 2
Dis 2
Sum
Adder
Factor
Filter
Ch-A
Ch-B
bypass
bypass
Round
Cutoff
Ch-a
Ch-b
Dsplay
D Ch-A
d Ch-B
d-Inty
Ch-A
4-20 mA
4-20 mA
mA-A
mA-B
mA-C
2
2
4.000 mA
4.000
20.000 mA
20.000
4.000 mA
4.000
20.000 mA
20.000
Sum
0.000
1
70
70
0.2
0.2
1
0.000 (disabled)
0.000 (disabled)
Channel A
Channel B
8
Channel A
91
Page 92
DP6060 Dual-Input Process Meter Instruction Manual
Parameter DisplayDefault SettingUser Setting
Relay 1 action
Relay 1 set point
Relay 1 reset point
Relay 2 assignment
Relay 2 action
Relay 2 set point
Relay 2 reset point
Relay 3 assignment
Relay 3 action
Relay 3 set point
Relay 3 reset point
Relay 4 assignment
Relay 4 action
Relay 4 set point
Relay 4 reset point
Fail-safe relay 1
Fail-safe relay 2
Fail-safe relay 3
Fail-safe relay 4
On delay relay 1
Off delay relay 1
On delay relay 2
Off delay relay 2
On delay relay 3
Off delay relay 3
On delay relay 4
Off delay relay 4
Loop break relay 1
Loop break relay 2
Loop break relay 3
Loop break relay 4
Display 1 analog out
Output 1 value
Display 2 analog out
Output 2 value
Source analog output
Overrange output
Underrange output
Loop break output
Maximum output
Minimum output
Slave ID (Address)
Baud rate
Act 1
Set 1
RSt 1
Ch-A
Act 2
Set 2
RSt 2
Ch-A
Act 3
Set 3
RSt 3
Ch-A
Act 4
Set 4
RSt 4
Fls 1
Fls 2
Fls 3
Fls 4
On 1
Off 1
On 2
Off 2
On 3
Off 3
On 4
Off 4
ignore
ignore
ignore
ignore
Dis 1
Out 1
Dis 2
Out 2
Source
O-rang
u-rang
break
mAx
min
SlavId
baud
Automatic
1.000
0.500
Channel A
Automatic
2.000
1.500
Channel A
Automatic
3.000
2.500
Channel A
Automatic
4.000
3.500
Off
Off
Off
Off
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
Ignore
Ignore
Ignore
Ignore
4.000
4.000 mA
20.000
20.000 mA
Channel A
21.000 mA
3.000 mA
1.000 mA
23.000 mA
1.000 mA
247
9600
92
Page 93
DP6060 Dual-Input Process Meter Instruction Manual
Parameter DisplayDefault SettingUser Setting
Transmit delay
Parity
Byte-to-byte timeout
F1 function key
F2 function key
F3 function key
F4 function
(digital input)
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital output 1
Digital output 2
Digital output 3
Digital output 4
Password 1
Password 2
Password 3
Tr dly
Parity
t-byt
F1
F2
F3
F4
DI 1
DI 2
DI 3
DI 4
DO 1
DO 2
DO 3
DO 4
Pass 1
Pass 2
Pass 3
50 ms
Even
010 (0.1 sec)
Reset max & min
Upper Max & Min
Acknowledge relays
Acknowledge relays
Menu
Right arrow
Up arrow
Enter
Alarm 1
Alarm 2
Alarm 3
Alarm 4
000000 (unlocked)
000000 (unlocked)
000000 (unlocked)
Alphabetical List of Display Functions & Messages
Display Parameter Action/Setting Description
-99999
999999
20 ma
4 ma
A Gros
A nt-G
Ack
Act 1
Adder
Alm 1
Altern
A-man
Aout
AOut 1*
Aoutpr
Assign
Flashing
display
20 mA output
4 mA output
Display A gross
Display A net
and gross
Acknowledge
Action 1
Adder
Alarm 1
Alternate
Auto-manual
Analog output
Aout Channel
Analog output
programming
Assign
Underrange condition
Overrange condition
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
Display input channel A gross (no tare)
Alternate display of channel A net (tare) and
gross (no tare)
Acknowledge relays
Set relay 1 action
The channel C math function adder
constant P
Assign digital output to Alarm 1-8
Set relay for pump alternation control
Set relay for automatic & manual reset
Enter the Analog output scaling menu
Analog Output source channel (*1-3)
Enter analog output programming
Enter the relay channel assignment menu
93
Page 94
DP6060 Dual-Input Process Meter Instruction Manual
Display Parameter Action/Setting Description
Auto
Avg
B Gros
B nt-G
baud
Big
Big Hi
Big HL
Big Lo
break
bypASs
C CAL
C Hi
C lo
Cal A
Cal B
Calib
Ch-A*
Cm
Concen
Const
Contrl
Copy
CutofF
D Ab
D AbC
D AC
D a-u
D BC
D B-u
D Ch-A
D Ch-B
Automatic
Average
Display B gross
Display B net
and gross
Baud rate
Upper display
Max on Upper
display
Max/min Upper
display
Min on Upper
display
Loop break
Bypass
Current
calibration
Current high
Current low
Calibrate A
Calibrate B
Calibrate
Channel A*
Centimeter
Concentration
Constant
Control
Copy
Cutoff
Display A & B
Display A,
B,&C
Display A & C
Display A and
units/tags
Display B & C
Display B and
units/tags
Display Ch-A
Display Ch-B
Press Enter to set automatic operation
Channel C = (((A+B)/2)+P)*F
Display input channel B gross (no tare)
Alternate display of channel B net (tare) and
gross (no tare)
Select baud rate
Press Enter to assign the upper display
parameter (default: Ch-A)
Assign digital input to display max on the
upper display (channel A)
Assign digital input to toggle max/min on the
upper display (channel A)
Assign digital input to display min on the
upper display (channel A)
Set relay condition if loop break detected
Set filter bypass value
Calibrate 4-20 mA current input (internal
reference source used for scaling the input)
Calibrate high current input (e.g. 20 mA)
Calibrate low current input (e.g. 4 mA)
Enter the Calibration menu for channel A
Enter the Calibration menu for channel B
Calibrate 4-20 mA output (internal reference
source used for scaling the output)
Channel A (*B or C) selection
Select cm as the tank unit of measurement
Channel C = (A/(A+B))*F
Enter the math function constant menu
Enter Control menu to turn relays on/off, set
analog output manually, or return meter to
automatic operation
Enter copy function
Set low-flow cutoff (ch-A, ch-B)
Alternate display of channel A & B
Alternate display of channel A, B, & C
Alternate display of channel A & C
Alternate display of channel A and the
unit/tag
Alternate display of channel B & C
Alternate display of channel B and the
unit/tag
Assign display to channel A
Assign display to channel B
94
Page 95
DP6060 Dual-Input Process Meter Instruction Manual
Display Parameter Action/Setting Description
D Ch-C
D C-u
D Hi-A
D Hi-B
D Hi-C
D HL-A*
D Hold
D Lo-A
D Lo-B
D Lo-C
D off
D unit
Dec pt
DeLAY
Di 1
Diag
diamr
Dif
difabs
d-Inty
Dis 1
Dis 2
disabl
Divide
DLY 1
Do 1
done
Drauw
Dset 1
dsplay
Enter
Error
F On 1
F1*
Display Ch-C
Display C and
units/tags
Display Hi A
Display Hi B
Display Hi C
Display Hi/Low
A*
Display Hold
Display Lo A
Display Lo B
Display Lo C
Display off
Display unit
Decimal point
Delay
Digital input 1
Diagnostics
Diameter
Difference
Absolute
difference
Display
intensity
Display 1
Display 2
Disable
Divide
Delay 1
Digital output 1
Done
Draw
Display set 1
Display
Enter button
Error
Force On 1
F1 function key
Assign display to channel C (math)
Alternate display of channel C and the
unit/tag
Display high value of channel A
Display high value of channel B
Display high value of channel C
Alternate between high/low value of channel
A (*or B or C)
Set digital inputs and function keys for
display hold
Display low value of channel A
Display low value of channel B
Display low value of channel C
Display off (blank)
Display unit of channel A
Set decimal point
Enter relay Time Delay menu
Assign digital input 1-8, if expansion
modules are connected
Display parameter settings
Enter the tank’s diameter in inches or cm
Channel C = (A-B+P)*F
Channel C = ((Absolute value of (AB))+P)*F
Set display intensity level from 1 to 8
Program display 1 value
Program display 2 value (up to 32 points)
Disable function key
Channel C = ((A/B)+P)*F
Enter relay 1 time delay setup (1-8)
Assign digital output 1 – 8, if expansion
modules are connected
Copy function completed
Channel C = ((A/B)-1)*F
Select to display set point 1 (1-8)
Enter the Display menu
Assign digital input to Enter button/F3
Error, calibration not successful, check signal
or programmed value
Force relay 1 on using and digital input
Assign F1 (*or F2 or F3) function key
95
Page 96
DP6060 Dual-Input Process Meter Instruction Manual
Display Parameter Action/Setting Description
F4
Factor
FaiLSF
filter
FLS 1
Force
Functn
Hi-ab
ICal
ignore
InCAL
Inch
Info
Inp 1
Inp 2
Input
LatCH
LED t
Length
Linear
Lit HC
Lit Hi
Lit HL
LitHLC
Lit LC
Lit Lo
Little
Lo-ab
F4 function
Factor
Fail-safe
Filter
Fail-safe 1
Force
Signal input
conditioner
Max of A or B
Internal
calibration
Ignore
Input
Calibration
Inch
Information
Input 1
Input 2
Input
Latching
LED test
Length
Linear
Max on lower
display
Max on lower
display
Max/min lower
display
Max/Min lower
display
Min on lower
display
Min on lower
display
Lower display
Min of A or B
Assign F4 function (digital input)
The channel C math function multiplication
factor constant F
Enter Fail-safe menu
Set noise filter value
Set relay 1 fail-safe operation (1-8)
Force analog output value for loop break
Select linear, square root, programmable
exponent, or round horizontal tank function
C = ((High value of channel A or B)+P)*F
Enter internal calibration (used for
recalibrating the meter with a calibrated
signal source)
Ignore loop break condition
Enter the Input Calibration menu
Select inch as the tank unit of measurement
Display software and S/N information
Calibrate input 1 signal or program input 1
value
Calibrate input 2 signal or program input 2
value (up to 32 points)
Enter Input selection menu
Set relay for latching operation
Test all LEDs
Enter the tank’s length in inches or cm
Set meter for linear function and select
number of linearization points
Assign digital input to display max of
channel C on the Lower display
Assign digital input to display max of
channel A on the Lower display
Assign digital input to toggle max/min of
channel A on the Lower display
Assign digital input to toggle max/min of
channel C on the Lower display
Assign digital input to display min of
channel C on the Lower display
Assign digital input to display min of
channel A on the Lower display
Press Enter to assign the Lower display
parameter (default: Ch-B)
C = ((Low value of channel A or B)+P)*F
96
Page 97
DP6060 Dual-Input Process Meter Instruction Manual
Display Parameter Action/Setting Description
locd
Lt-CLr
mA
mAn
math
mAx
mbus
menu
min
nmulti
No PtS
O Hold
OFF
OFF 1
on
O-rang
Out 1
Out 2
pass
Pass 1
Pass 2
Pass 3
prog
Prog E
ratio
RELaY
reset
rht
Right
RLY 1
Rly d
Rly E
Locked
Latchingcleared
4-20 mA
Manual
Math
Maximum
Modbus Select to display Modbus input or to assign
Menu button Assign digital input to Menu button
Minimum
Multiplication
Num of points
Relays output
hold
Off
Off 1
On
Overrange
Output 1
Output 2
Password
Password 1
Password 2
Password 3
Program
Programmable
exponent
Ratio
Relay
Reset
Round
horizontal tank
Right arrow
Relay 1
Disable relay
Enable relay
Enter password to unlock meter
Set relay for latching operation with manual
reset only after alarm condition has cleared
Set meter for 4-20 mA input
Press Enter to manually control relays or
analog output operation
Select channel C math function
Program maximum mA output allowed
Modbus input as the analog output source
Program minimum mA output allowed
Channel C = ((A*B)+P)*F
Set meter for 2 to 32-point linearization
Assign digital input or function keys to hold
all relay states
Disable relay and front panel status LED,
turn relays off, program off time delay
Set relay 1 Off time delay (1-8)
Enable fail-safe operation, turn relays on,
program on time delay
Program mA output for display overrange
Program output 1 value (e.g. 4.000 mA)
Program output 2 value (e.g. 20.000 mA)
Enter the Password menu
Set or enter Password 1 (Allows use of the
F1–F3 function keys)
Set or enter Password 2 (Allows use of the
F1–F3 function keys and changing the
set/reset points)
Set or enter Password 3 (Restricts all
programming & F1–F3 keys)
Enter the Program menu
Set meter for programmable exponent and
enter exponent value
Channel C = (A/B)*F
Enter the Relay menu
Press Enter to access the Reset menu
Set meter for round horizontal tank volume
calculation
Assign digital input to Right arrow button/F1
Relay 1 setup (1-8)
Assign digital input and function keys to
disable all relays
Assign digital input to enable all relays
97
Page 98
DP6060 Dual-Input Process Meter Instruction Manual
Display Parameter Action/Setting Description
Round
RSt 1
Rst Hi
Rst HL
Rst Lo
Rst tr
Sampl
SCAL A
SCAL B
SelEct
send
seriAl
Set 1
setup
SlavId
Source
Square
Sunm
Tare A
Tare b
Tr dLY
units
unloc
up
u-rang
user
v CAL
v Hi
v Lo
Volt
uwAvg
Round
Reset 1
Reset high
Reset high &
low
Reset low
Reset tare
Sampling
Scale A
Scale B
Select
Send
Serial
Set 1
Setup
Slave ID
Source
Square root
Sum
Tare A
Tare B
Transmit delay
units
Unlocked
Up arrow
Underrange
User I/O
Voltage
calibration
Voltage high
Voltage low
Volt
Weighted avg.
Enter the round menu
Program reset point 1 (1-8)
Press Enter to reset max display
Press Enter to reset max & min displays
Press Enter to reset min display
Reset tare
Set relay for sampling operation
Enter the Scale menu for channel A
Enter the Scale menu for channel B
Enter Select menu (function, round, math,
constant, cutoff, output programming)
Send meter settings to another meter
Set serial communication parameters
Program set point 1 (1-8)
Enter Setup menu
Set Slave ID or meter address
Select source for the 4-20 mA output
Set meter for square root extraction
Channel C = (A+B+P)*F
Activate tare on channel A
Activate tare on channel B
Set transmit delay for serial communication
Enter in channel A, B, and C input
units/tags
Program password to lock meter
Assign digital input to Up arrow button/F2
Program mA output for display underrange
Assign function keys and digital I/O
Calibrate voltage input
Calibrate high voltage input (e.g. 10 V)
Calibrate low voltage input (e.g. 0 V)
Set meter for volt input
Channel C = ((B-A)*F)+A
Troubleshooting Tips
Symptom Check/Action
No display at all
Not able to change setup or
programming, Locd is displayed
Meter displays error message
during calibration (Error)
Check power at power connector
Meter is password-protected, enter
correct six-digit password to unlock
Check:
1. Signal connections
98
Page 99
DP6060 Dual-Input Process Meter Instruction Manual
2. Input selected in Setup menu
3. Minimum input span requirements
Meter displays
1. 999999
2. -99999
Display is unstable
Display response is too slow
Display reading is not accurate
Display does not respond to input
changes, reading a fixed number
Display alternates between
1. Hi and a number
2. Lo and a number
Relay operation is reversed
Relay and status LED do not
respond to signal
Flashing relay status LEDs
Meter not communicating with
application programs
If the display locks up or the meter
does not respond at all
Other symptoms not described
above
Check:
1. Input selected in Setup menu
2. Corresponding signal at Signal
connector
Check:
1. Input signal stability and value
2. Display scaling vs. input signal
3. Filter and bypass values (increase)
Check filter and bypass values
Check:
1. Signal input conditioner selected:
Linear, square root, etc.
2. Scaling or calibration
Check:
1. Display assignment, it might be
displaying max, min, or set point.
Press Menu to exit max/min display
readings.
Check:
1. Fail-safe in Setup menu
2. Wiring of relay contacts
Check:
1. Relay action in Setup menu
2. Set and reset points
Relays in manual control mode or relay
interlock switches opened.
Check:
1. Serial adapter and cable
2. Serial settings
3. Meter address and baud rate
Cycle the power to reboot the
microprocessor.
Call Technical Support for
assistance.
99
Page 100
M-5203
LIM6060OM_A
SFT065 Ver 3.100 & up
08/12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.