Tel: (95) 800-826-6342FAX: (95) 203-359-7807
En Espan˜ol: (95) 203-359-7803e-mail: espanol@omega.com
SM
SM
SM
Servicing Europe:
Postbus 8034, 1180 LA Amstelveen, The Netherlands
Tel: (31) 20 6418405FAX: (31) 20 6434643
Toll Free in Benelux: 0800 0993344
e-mail: nl@omega.com
Czech Republic:
France:
Germany/Austria:
United Kingdom:
ISO 9002 Certified
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives.
OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability
for any errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
One Omega Drive, River Bend Technology Centre
Northbank, Irlam, Manchester
M44 5EX, United Kingdom
Tel: 44 (161) 777-6611FAX: 44 (161) 777-6622
Toll Free in the United Kingdom: 0800-488-488
e-mail: info@omega.co.uk
Page 3
GETTING STARTED
This manual is divided into 5 sections which contain all the information needed to
install, configure, set up and operate the instrument. Each section is identified
clearly by a symbol as shown below.
•Level 3
–Hardware assignment and input type
–Alarm types and hysteresis
–Operator functions and totalizer setup
–Digital input and serial communications
•Level 4
–Ranges and passwords
Installation
•Siting
•Mounting
•Electrical connections
Symbol Identification and Section Contents
1
Page 4
CONTENTS
1DISPLAYS AND FUNCTION KEYS ................................................................ 3
5.4.4Control or Retransmission Analog Output ................................ 35
Page 5
1DISPLAYS AND FUNCTION KEYS
Information.
The fold-out page inside on the back cover of this
manual shows all the frames in the programming
levels. Space is provided on the page for writing the
programmed setting or selection for each frame.
1.1Introduction – Fig. 1.1
The instrument front panel display, function keys and LED indicators are shown in
Fig. 1.1.
Display
888888
Function Keys
Parameter Advance
Raise
Lower
A1
A2
A3
Alarm LEDs
(invisible
when off)
Multi-function Key
Fig. 1.1 Front Panel Display, Function Keys and Indicators
3
Page 6
…1DISPLAYS AND FUNCTION KEYS
1.2Use of Function Keys – Fig. 1.2
A – Raise and Lower Keys
100.0 100.1
99.9
Use to change/set a parameter value…
B – Parameter Advance Key
LEVEL1
100.1
Use to advance to the next
frame within a level…
+
–
LEVEL1
Frame 1
(top of level)
Frame 2
or…
…move between levels
LEVELx
100.1
or…
200.2
300.3
400.4
…select the top (LEVEL) frame
from within a level
LEVEL2
Press and
hold
Note. This key also stores any changes made in the previous frame
C – Multi-function Key
CodE
0
Use to view a parameter setting or selection…
Fig. 1.2 Use of Function Keys
4
or…
…select individual characters in a frame
123456
Page 7
1DISPLAYS AND FUNCTION KEYS…
1.3LED Alarms and Indicators
Alarm LEDs
LEDStatus
All Flashing
• Indicator is in the Configuration Mode – see Section 4.2.
A1, A2 and A3
A1
A2
A3
Alarm 1
Alarm 2
Alarm 3
• Flash when Alarm is active (off when inactive).
• Lit constantly when Alarm 1 is an active latched alarm which has
been acknowledged
Fig. 1.3 LED Alarms and Indicators
5
Page 8
…1DISPLAYS AND FUNCTION KEYS
1.4Error Messages
DisplayError/Action
Calibration error
CAL.Err
Turn power off and on again (if the
error persists, contact the
Supplier).
Configuration error
CFG.Err
The configuration and/or setup
data for the instrument is
corrupted. Turn power off and on
again (if error persists, check
configuration/setup settings).
A to D Converter Fault
A.d. Err
The analog to digital converter is
not communicating correctly.
To Clear Display
Press the
Press the
Turn power off and
on again. If error
persists, contact the
key
key
9999
DPt.Err
Process Variable Over/Under
Range
Option board error
Communications to the option
board have failed.
Supplier
Restore valid
input
Contact the Supplier
6
Page 9
2OPERATOR MODE
2.1Introduction
Operator Mode (Level 1) is the normal day-to-day mode of the instrument.
Frames displayed in Level 1 are determined by the indicator functions which are
selected during configuration of the instrument – see Section 4.
Note. Only the operating frames relevant to the configured functions are
When this frame is selected, the current counter
status is displayed (
Stop/Start
t–GO or t-StOP).
t–GO – start totalizer
t-StOP – stop totalizer
Reset
rSt-Y – reset totalizer
rSt-n – do not reset totalizer
To reset the totalizer, select
the
Continued on next page.
•1 Totalizer stop/go and reset from these frames can be disabled – see Section
4.3.3.
A digital input can also be used to start/stop or reset the totalizer – see
key.
rSt-Y. then press
Section 4.3.4
9
Page 12
…2OPERATOR MODE
2.3Operating Page – Totalizer (Level 1)
PrESEt
000000
Select Digit
PrEdEt
999999
Select Digit
•2
Preset Total
This is the value the batch total is set to when it is reset
•1
[000000 to 999999 flow units]
Predetermined Total
When the predetermined total is reached, the batch
total is reset (with wrap on) or stops (wrap off),
depending on the wrap setting – see Section 3.2.
•1
[000000 to 999999 flow units]
CodE
Security Code
Enter the correct code to access the setup level.
------
[0 to 9999]
LEVEL
•1 The predetermined value should be greater than the preset value when the
totalizer is counting up and lower than the preset value when the totalizer is counting
Level 1
Note. To select this frame from anywhere in
this level, press the
key for a few seconds.
down.
•2 Only displayed if enabled in the configuration level – see Section 4.3.3.
This is the mean average value of the process
variable input, since the average was reset.
rSt-Y – reset
rSt-n – do not reset
To reset the average value, select
rSt-Y then press
the
key.
H150.2
Continued on next page.
•1 This frame can be disabled – see Section 4.3.3.
The average value is reset automatically on power-up and can also be reset
from a digital input – see Section 4.3.4.
The reset function in this frame can be disabled – see Section 4.3.3.
11
Page 14
…2OPERATOR MODE
…2.4Operating Page – Math Functions (Level 1)
H150.2
rSt-n
L130.8
rSt-n
•1
•1
Maximum Value
This is the maximum value of the process variable
since the maximum was reset.
rSt-Y – reset
rSt-n – do not reset
To reset the maximum value, select
press the
Minimum Value
This is the minimum value of the process variable
since the minimum was reset.
rSt-Y – reset
rSt-n – do not reset
key.
rSt-Y then
To reset the minimum value, select
press the
CodE
------
LEVEL1
•1 This frame can be disabled – see Section 4.3.3.
Security Code
Enter the correct code to access the setup level.
[0 to 9999]
Level 1
Note. To select this frame from anywhere in this
level, press the
key.
key for a few seconds.
rSt-Y then
12
The average value is reset automatically on power-up and can also be reset
from a digital input – see Section 4.3.4.
The reset function in this frame can be disabled – see Section 4.3.3.
Page 15
3SET UP MODE
3.1Introduction
To access the Setup Level (Level 2), the correct password must be entered in the
8
security code frame (
Level 1 –
Operating Level
Security
Code
LEVEL1
CodE x
CodE) in Level 1– see Fig. 3.1.
LEVEL2
A1xx
Correct
Password
A2xx
A3xx
123456
t-GO
SEC.tot
Level 2 – Set Up
Alarm 1 Trip Point
Alarm 2 Trip Point
Alarm 3 Trip Point
Batch Total
Totalizer Stop/Go
Secure Total/Reset
PrESEt
PrEdEt
A xxxx
H xxxx
L xxxx
0AdJ
Fig. 3.1 Accessing the Set Up Level (Level 2)
Preset Batch Total
Predetermined Batch
Total
Average Value
Maximum Value
Minimum Value
Offset Adjustment
13
Page 16
8
3.2Set Up Level (Level 2)
…3SET UP MODE
LEVEL2
A1.hP
100.1
A1. HYS
•1
•2
Level 2
Note. To select this frame from anywhere in
this level, press the
Alarm 1 Trip Point
Alarm type:
A1.hP = High process alarm
A1.LP = Low process alarm
A1.HL = Latched high process alarm
A1.LL = Latched low process alarm
[In engineering units]
Alarm 1 Hysteresis Value
key for a few seconds.
A2.LP
A2. HYS
A3.hP
12.5
200.2
27.9
•1
•2
[In engineering units]
Alarm 2 Trip Point
Alarm type
[In engineering units]
Alarm 2 Hysteresis Value
[In engineering units]
Continued on next page.
•1Not displayed if the alarm is disabled ('NONE' selected) – see Section 4.3.2.
•2Only displayed if custom alarm hysteresis is selected – see Section 4.3.2
14
Page 17
…3.2Set Up Level (Level 2)
3SET UP MODE…
8
A3.hP
300.3
A3 HYS
34.6
123456
•1
•2
•3
•4
Alarm 3 Trip Point
Alarm type
[In engineering units]
Alarm 3 Hysteresis Value
[In engineering units]
Totalizer Value
rSt-Y – reset
rSt-n – do not reset
rSt-n
•3
To reset the maximum value, select
press the
Totalizer Stop/Go
key.
rSt-Y then
t-GO
t–GO . – start totalizer
t-StOP. – stop totalizer
t-StOP
Setting to
the predetermined value. Setting to
the totalizer at its present value.
SEC.tOt
Continued on next page
•1Not displayed if the alarm is disabled ('NONE' selected) – see Section 4.3.2
t-GO starts the totalizer counting towards
t-StOP holds
•2Only displayed if custom alarm hysteresis is selected – see Section 4.3.2
•3Only displayed if enabled in the configuration level – see Section 4.3.3
•4A digital input can also be used to reset the batch total.
15
Page 18
8
…3.2Set Up Level (Level 2)
…3SET UP MODE
SEC.tOt
456789
rSt-n
PrESEt
•1
•2
Secure Total
The secure total is independent of the batch total value.
When 999999 or 000000 is reached, the total is reset
and then continues counting.
Total
Reset
rSt-Y. – reset totalizer
rSt-n. – do not reset totalizer
To reset, select
Preset Batch Total
This is the value the batch total is set to when it is reset.
rSt-Y. then press thekey.
[000000 to 999999]
000000
PrEdEt
•2
999999
A140.5
•1 Only displayed if enabled in the configuration level – see Section 4.3.3.
Predetermined Batch Total
When this value is reached the batch total either resets
(with wrap on) or stops (wrap off) – see Section 4.3.3.
[000000 to 999999]
Continued on next page.
•2 The preset value must be lower than the predetermined value when
counting up, and greater than the predetermined value when counting down.
16
Page 19
…3.2Set Up Level (Level 2)
3SET UP MODE…
8
A140.5
rSt-n
H150.2
rSt-n
•1
•2
Average Value
This is the mean average value of the process variable
input since the average was reset.
rSt-Y. – reset
rSt-n. – do not reset
To reset, select
Maximum Value
This is the maximum value of the process variable
since the maximum was reset.
rSt-Y. – reset
rSt-n. – do not reset
To reset, select
rSt-Y. then press thekey.
rSt-Y. then press thekey.
L130.8
rSt-n
O.AdJ
1.0
•2
Minimum Value
This is the minimum value of the process variable since
the minimum was reset.
rSt-Y. – reset
rSt-n. – do not reset
To reset , select
Offset Adjustment
An offset can be applied to the process variable input to
enable spot calibration or the removal of system errors.
[±10% of engineering range]
rSt-Y. then press thekey.
•1 The average value i s reset automatically on power-up and can also be reset
from a digital input – see Section 4.3.4.
•2 The maximum and minimum values are reset automatically on power-up and
can also be reset from a digital input – see Section 4.3.4.
17
Page 20
4CONFIGURATION MODE
4.1Introduction
The Configuration Mode comprises two levels (3 and 4) as shown in Fig. 4.2.
Configuration Level 3 is divided into four frames. For most simple applications, it is
only necessary to set up the parameters in the first frame.
Note.
When in the configuration level:
•All the LED indicators flash.
•All relays and logic outputs are turned off.
•The analog output reverts to 0% (4mA) output level.
4.2Accessing the Configuration Mode – Fig. 4.1
To access the Configuration Mode, set the security switch to the 'Configure'
position (Levels 1 and 2 cannot be accessed from this setting). When the
configuration parameters are programmed, reset the security switch to the 'Normal'
position and the operating page is displayed automatically .
Normal
Configure
18
Fig. 4.1 Accessing the Configuration Mode
Page 21
4CONFIGURATION MODE…
Level 3
Hardware
Configuration
Alarms and
Set Points
Custom Operator
Settings
LEVEL3
A 1KC0
b 1KC0
C 1KC0
d 1KC0
E 0000
F 0000
G 0000
H 0000
J 0000
K 0000
L 0000
N 0000
LEVEL4
ENG HI
ENG LO
rEt HI
rEt LO
CNt HI
CUtOFF
PASSrd
Level 4
Engineering
Range High
Engineering
Range Low
Retransmission
Range High
Retransmission
Range Low
Totalizer Count
High
Totalizer Count
Cut-off
Set Up Password
Digital Input and
Serial Comms.
P 0000
r 0000
S 0000
t 0000
Fig. 4.2 Configuration Levels
Addr.
MODBUS Address
19
Page 22
…4CONFIGURATION MODE
4.3Basic Hardware and Configuration (Level 3) – Fig. 4.3
4.3.1Hardware Assignment and Input Type
LEVEL3
A 1KC0
B 1KC0
C 1KC0
d 1KC0
Level 3
Note. To select this frame from anywhere in this
level, press the
'ABCD' Settings
The first character (A, B, C or D) identifies the
parameter to be changed. The current setting is
indicated by a flashing letter. Parameter options are
shown in Fig. 4.3.
key for a few seconds.
A=Hardware configuration
b=Input type and range
C=Temperature units
d=No. of decimal points
Note. The temperature ranges default to their
maximum values when the input type is changed.
E 1203
Continued on page 22.
Information.
Count High Calculation
actual engineering flow rate
Convert flow rate into units/sec =
units/sec
Count High =resultant must be >0.001 and <99.999pps.
Counter factor is the engineering value of the least significant digit shown on
the totalizer display – see Section 4.3.3.
Totalizer Count Pulse
The totalizer count pulse is on for a preset time of 250ms and off for a minimum
* Only available if the appropriate option board is fitted.
**Pulse energizes assigned relay
B – Input Type and Range Configuration
b 1KC0
Display
bT/C Type B
ET/C Type E
JT/C Type J
KT/C Type K
nT/C Type N
rT/C Type R
ST/C Type D
tT/C Type T
PPT100 RTD
C – Temperature Units
Display
C 1KC0
DisplayTemperature Units
CDegrees C*
FDegrees F*
0No temperature units
* Temperature inputs only
10 to 20 mA
24 to 20 mA
30 to 5 V
41 to 5 V
60 to 50 mV
74 to 20 mA (square root lineariser)
UCustom Configuration
d 1KC0
Display
0xxxx
1xxx . x
2xx . xx
3x . xxx
4x . xxxx
D – Process Variable
Display Decimal Places
Fig. 4.3 Hardware Configuration and Input/Output Ranges
21
Page 24
…4CONFIGURATION MODE
4.3.2Alarms – Figs. 4.4 and 4.5
Note. Relays assigned to alarms are de-energized in the alarm state.
E 0000
F 0000
J 0000
G 0000
H 0000
'EFGH' Settings
The first character (E, F, G or H) identifies the
parameter to be changed. The current setting is
indicated by a flashing letter. Parameter options are
shown in Fig. 4.5.
E=Alarm 1 type
F=Alarm 2 type
G=Alarm 3 type
H=Alarm hysteresis
Continued on page 24.
Hysteresis
Hysteresis
Process
Variable
Alarm on
Alarm off
Information.
For latch alarms the relay remains de-energized until acknowledged in
Level 1 (or by a digital input)
High Process
Low Process
Fig. 4.4 Alarm Action
Trip point
Alarm on
Alarm off
22
Page 25
4CONFIGURATION MODE…
E 0000
E – Alarm 1 Type
Display
0None
1High Process
2Low Process
3High Latch
4Low Latch
F – Alarm 2 Type
F 0000G 0000
Display
0None
1High Process
2Low Process
3High Latch
4Low Latch
Display
0None
1High Process
2Low Process
3High Latch
4Low Latch
G – Alarm 3 Type
h 0000
Display
0None
10.1%
20.2%
30.5%
41.0%
52.0%
65.0%
UCustom
H – Alarm Hysteresis
Value in % of
engineering range
Value in engineering units
Fig. 4.5 Alarm Set Up
Note. When custom
alarm hysteresis is selected,
the alarm hysteresis values are
set individually in the
Level – see Section 3.2
Set Up
23
Page 26
…4CONFIGURATION MODE
4.3.3Operator Functions and Totalizer Set Up – Fig. 4.6
J 0000
K 0000
P 0000
L 0000
n 0000
'JKLN' Settings
The first character (J, K, L or N) identifies the
parameter to be changed. The current setting is
indicated by a flashing letter. Parameter options are
shown in Fig. 4.6.
J=Totalizer set-up
K=No. of decimal places for totalizer
L=Operator level frame enable
n=Operator level functions enable/disable
Continued on page 26.
24
Page 27
4CONFIGURATION MODE…
J 0000
Display
0Off
1Count Up, Wrap Off
2Count Up, Wrap On
3Count Down, Wrap Off
4Count Down, Wrap On
This frame determines which functions the operator can control
Fig. 4.6 Totalizer Set Up and Operator Functions
25
Page 28
…4CONFIGURATION MODE
4.3.4Digital Input and Serial Communications – Figs. 4.7 and 4.8
P 0000
r 0000
LEVEL4
S 0000
t 0000
'PRST' Settings
The first character (P, R, S or T) identifies the
parameter to be changed and the current setting is
indicated by a flashing letter. Parameter options are
shown in Fig. 4.8.
Note. Settings for options P, S and T are only available if the
appropriate option board is fitted.
Fig. 4.8 Digital Function and Serial Communications Configurations
27
Page 30
…4CONFIGURATION MODE
4.4Ranges and Passwords (Level 4)
LEVEL4
ENG HI
100.0
ENG LO
Level 4
Note. To select this frame from anywhere in this
level, press the
Engineering (Display) Range
High Value
•1
[–9999 to 99999]
Low Value
key for a few seconds.
•1
0.0
CNt HI
Continued on next page…
•1 The engineering range high and low values are automatically set to the
maximumallowed value when thermocouple or RTD is selected in the
configuration level – see Section 4.3.1. This value can be modified if
required.
[–9999 to 99999]
28
Page 31
4CONFIGURATION MODE…
…4.4Ranges and Passwords (Level 4)
Retransmission Range
The retransmission range defines the engineering
range to be retransmitted.
rEt HI
rEt LO
CNt HI
100.0
100.0
High (20mA output)
•1
[–9999 to 99999 (in engineering units)]
Low (4mA output)
•1
[–9999 to 99999 (in engineering units)]
Continued on next page…
•1 The retransmission range high and low values are automatically set to the
maximumallowed value when thermocouple or RTD is selected in the
configuration level – see Section 4.3.1. This value can be modified if
required.
29
Page 32
…4CONFIGURATION MODE
…4.4Ranges and Passwords (Level 4)
CNt HI
1.00
cut.oFF
100.0
•1
•1
Totalizer Count High
This frame determines the count corresponding to the
full-scale input.
[0.000 and 99.999 pulses/second]
Cut-Off
This frame sets the lowest flow value at which the
totalizer is to stop counting.
[In engineering units]
PASSrd
0
•2
Addr.
1
•1 Only displayed if enabled in the configuration level – see Section 4.3.3.
Set Up Password
This password enables access to the set up level
(level 2).
[0 to 9999]
MODBUS Address
This frame sets the MODBUS address.
[1 to 99]
•2 Only available if the appropriate option board is fitted.
30
Page 33
5INSTALLATION
5.1Siting – Figs. 5.1 and 5.2
Close to Sensor
Sensor
At Eye Level
Avoid Vibration
Fig. 5.1 Siting – General Requirements
31
Page 34
…5INSTALLATION
…5.1Siting – Figs. 5.1 and 5.2
Temperature Limits
Humidity Limits
55°C
Max.
0°C
Min.
0 to 90% RH
Environmental Limits
Use Screened Cable
IP65/NEMA-3
(front panel)
IP20
(rear)
+
32
Fig. 5.2 Environmental Requirements
Page 35
5INSTALLATION…
5.2Mounting – Figs. 5.3 and 5.4
The instrument is designed for panel mounting (see Fig. 5.4). Overall dimensions
are shown in Fig. 5.3.
Dimensions in inches (mm)
0.28 (7.1)
4.68 (119)
1.57 (40)3.11 (79)
1.76
(44.6)
0.11 (2.7)
1.89
+ 0.6
(45 )
– 0
1.77
+ 0.02
– 0
3.78 (96)
+ 0.03
3.62
– 0
+ 0.8
(92 )
– 0
Panel
cut-out
≥ 0.55 (14)
Fig. 5.3 Overall Dimensions
≥0.55
(14)
33
Page 36
…5INSTALLATION
…5.2Mounting – Figs. 5.3 and 5.4
Cut a suitable hole in the panel (see Fig. 5.3)
1
2
Insert the instrument into the panel
cut-out
Fit the retaining clamp
3
over the instrument
case
34
Push the retaining clamp firmly
4
against the panel
Fig. 5.4 Mounting Details
Page 37
5INSTALLATION…
EC Directive 89/336/EEC
In order to meet the requirements
of the EC Directive 89/336/EEC for
EMC regulations, this product
must not be used in a nonindustrial environment.
5.3Electrical Connections –
Figs. 5.5 and 5.6
Warning. Before making
any connections, ensure that the
power supply, any powered control
circuits and high common mode
voltages are switched off.
5.4.3Logic Output
18V DC at 20mA
Min load 900Ω
Isolated from Analog Input (not
isolated from Retransmission
Output). Dielectric strength –
500V d.c. for 1 minute.
5.4.4Control or Retransmission
Analog Output
Max. load 15V (750Ω at 20mA)
Isolated from Analog Input (not
isolated from Logic Oouput).
Dielectric strength - 500V d.c. for
Note. If it is not possible to
avoid strong electrical and
magnetic fields, screened cables
within earthed/grounded metal
conduit must be used.
5.4Relays, Arc Suppression
and Outputs
5.4.1Relay Contact Ratings
Relay contacts are rated at:
115/230V AC at 5A (non-inductive)
250V DC 25W max.
5.4.2Arc Suppression - Fig. 5.5
Arc suppression components are fitted
to relays 2 and 3 only. If relay 1 is
1 minute.
Terminal Block
117
1098
NC
LoadLoad
Switched
C
Suppression
component
Supply
NO
(B9303)
required to switch inductive loads, the
arc suppression component supplied
must be fitted across the contacts
used.
Fig. 5.5 Fitting Arc Suppression
Components
35
Page 38
…5INSTALLATION
Logic Output
(18V at 20mA max.)
Analog Input
(see below)
+
–
123456789101112
13
Not
Used
✝ 750Ω max. load
14
RTD1
15
–
Digital
Input
+
Analog
Output ✝
Transmitter PSU
+
18
17
C
Relay
Output 2
–
+
16
+
N/O
–
19
N/C
1
Relay
Output 1
N/C
CN/O
21
20
+
RS485
TX
Relay Output 3
2223
–
RS485
or
N/O
85 to 265V a.c.
N
–
–
L
+
1A
24
C
RS485
2
+
RX
C
24V d.c.
N/C
Note 1. The Analog Output and Logic Output use a common positive
terminal, capable of driving both outputs simultaneously.
Note 2. Fit arc suppression components if switching inductive loads.
T/C
millivolts
and volts
1
–
2
+
3
3-lead
RTD
rd
3
lead
RTD –
RTD
+
2-lead RTD
and resistance
RTD –
RTD –
RTD +
Milliamps
–
**100Ω
+
4
* Using internal transmitter power supply
** Use 100Ω shunt resistor provided with instrument
* Milliamps
**100Ω
–
Tx
+
2-wire
transmitter
36
Fig. 5.6 Electrical Connections
Page 39
CUSTOMER CONFIGURATION LOG
✍
LEVEL4
LEVEL3
A 1KC0
ABCD
E 0000
EF
J 0000
JK
P 0000
GH
LN
ENG HI
ENG LO
rEt HI
rEt LO
CNt HI
CUtOFF
PASSrd
PR
ST
Addr.
Page 40
CUSTOMER SETUP LOG
LEVEL1
CodE
8
✍
LEVEL2
A1xx
A2xx
A3xx
xxxxxx
t-GO
SEC.tot
PrESEt
PrEdEt
A xxxx
H xxxx
L xxxx
0AdJ
Instrument Serial Number:
Page 41
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship
for a period of 37 months from date of purchase. OMEGA Warranty adds an additional one (1)
month grace period to the normal three (3) year product warranty to cover handling and
shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written
request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or
replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of
the purchaser, including but not limited to mishandling, improper interfacing, operation outside of
design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit
shows evidence of having been tampered with or shows evidence of having been damaged as a
result of excessive corrosion; or current, heat, moisture or vibration; improper specification;
misapplication; misuse or other operating conditions outside of OMEGA’s control. Components
which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability
for any damages that result from the use of its products in accordance with information
provided by OMEGA, either verbal or written. OMEGA warrants only that the parts
manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER
WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR
IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY
WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE
HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth
herein are exclusive, and the total liability of OMEGA with respect to this order, whether
based on contract, warranty, negligence, indemnification, strict liability or otherwise,
shall not exceed the purchase price of the component upon which liability is based. In
no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a
“Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or
(2) in medical applications or used on humans. Should any Product(s) be used in or with any
nuclear installation or activity, medical application, used on humans, or misused in any way,
OMEGA assumes no responsibility as set forth in our basic WARRANTY / DISCLAIMER language,
and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability
or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department.
BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN
AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN
ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the
outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to
prevent breakage in transit.
FOR WARRANTY
RETURNS, please have the
following information available BEFORE
contacting OMEGA:
1. Purchase Order number under which the
product was PURCHASED,
2. Model and serial number of the product
under warranty, and
3. Repair instructions and/or specific problems
relative to product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible.
This affords our customers the latest in technology and engineering.
photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in
whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
FOR NON-WARRANTY REPAIRS,
OMEGA for current repair charges. Have the
following information available BEFORE
contacting OMEGA:
1. Purchase Order number to cover the COST of
the repair,
2. Model and serial number of the products, and
3. Repair instructions and/or specific problems
relative to the product.
Data Acquisition & Engineering Software
Communications-Based Acquisition Systems
Plug-in Cards for Apple, IBM & Compatibles
Datalogging Systems
Recorders, Printers & Plotters