Omega Products DP3409 Installation Manual

Page 1
omega.com
®
®
User’s Guide
http://www.omega.com
e-mail: info@omega.com
DP3409 SERIES
Universal T emperature & Pr ocess
Indicator
Page 2
omega.com
®
®
OMEGAnet®On-Line Service Internet e-mail
http://www.omega.com info@omega.com
Servicing North America:
USA:
ISO 9001 Certified
Canada:
For immediate technical or application assistance:
USA and Canada:
Mexico and Latin America:
Benelux:
One Omega Drive, Box 4047 Stamford, CT 06907-0047 Tel: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com
976 Bergar Laval (Quebec) H7L 5A1 Tel: (514) 856-6928 FAX: (514) 856-6886 e-mail: info@omega.ca
Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA Customer Service: 1-800-622-2378 / 1-800-622-BEST Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA
Tel: (95) 800-826-6342 FAX: (95) 203-359-7807 En Espan˜ol: (95) 203-359-7803 e-mail: espanol@omega.com
SM
SM
SM
Servicing Europe:
Postbus 8034, 1180 LA Amstelveen, The Netherlands Tel: (31) 20 6418405 FAX: (31) 20 6434643 Toll Free in Benelux: 0800 0993344 e-mail: nl@omega.com
Czech Republic:
France:
Germany/Austria:
United Kingdom:
ISO 9002 Certified
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
ul. Rude armady 1868, 733 01 Karvina-Hranice Tel: 420 (69) 6311899 FAX: 420 (69) 6311114 Toll Free: 0800-1-66342 e-mail: czech@omega.com
9, rue Denis Papin, 78190 Trappes Tel: (33) 130-621-400 FAX: (33) 130-699-120 Toll Free in France: 0800-4-06342 e-mail: france@omega.com
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany Tel: 49 (07056) 3017 FAX: 49 (07056) 8540 Toll Free in Germany: 0130 11 21 66 e-mail: info@omega.de
One Omega Drive, River Bend Technology Centre Northbank, Irlam, Manchester M44 5EX, United Kingdom Tel: 44 (161) 777-6611 FAX: 44 (161) 777-6622 Toll Free in the United Kingdom: 0800-488-488 e-mail: info@omega.co.uk
Page 3
GETTING STARTED
This manual is divided into 5 sections which contain all the information needed to install, configure, set up and operate the instrument. Each section is identified clearly by a symbol as shown below.
Displays and Controls
Displays and function keys
LED Indication
Error Messages
Operator Mode (Level 1)
Operator menus for:
Standard Indicator – Totalizer/Batch Controller – Maximum/Minimum/Average Indicator
8
Set Up Mode (Level 2)
Alarm trip points
Totalizer functions
Configuration Mode (Levels 3 and 4)
Accessing the configuration levels
Level 3 – Hardware assignment and input type – Alarm types and hysteresis – Operator functions and totalizer setup – Digital input and serial communications
Level 4 – Ranges and passwords
Installation
Siting
Mounting
Electrical connections
Symbol Identification and Section Contents
1
Page 4
CONTENTS
1 DISPLAYS AND FUNCTION KEYS ................................................................ 3
1.1 Introduction .............................................................................................. 3
1.2 Use of Function Keys .............................................................................. 4
1.3 LED Alarms and Indicators ..................................................................... 5
1.4 Error Messages ....................................................................................... 6
2 OPERATOR MODE ......................................................................................... 7
2.1 Introduction .............................................................................................. 7
2.2 Operating Page – Standard .................................................................... 8
2.3 Operating Page – Totalizer ..................................................................... 9
2.4 Operating Page – Math Functions ........................................................ 11
3 SET UP MODE ............................................................................................... 13
3.1 Introduction ............................................................................................ 13
3.2 Set Up Level .......................................................................................... 14
4 CONFIGURATION MODE ............................................................................. 18
4.1 Introduction ............................................................................................ 18
4.2 Accessing the Configuration Mode ....................................................... 18
4.3 Basic Hardware and Configuration (Level 3)........................................ 20
4.3.1 Hardware Assignment and Input Type ...................................... 20
4.3.2 Alarms ........................................................................................ 22
4.3.3 Operator Functions and Totalizer Set Up ................................. 24
4.3.4 Digital Input and Serial Communications .................................. 26
4.4 Ranges and Passwords (Level 4) ......................................................... 28
5 INSTALLATION ............................................................................................. 31
5.1 Siting .................................................................................................... 31
5.2 Mounting ................................................................................................ 33
5.3 Electrical Connections........................................................................... 35
5.4 Relays, Arc Suppression and Outputs.................................................. 35
5.4.1 Relay Contact Ratings ............................................................... 35
5.4.2 Arc Suppression......................................................................... 35
2
5.4.3 Logic Output ............................................................................... 35
5.4.4 Control or Retransmission Analog Output ................................ 35
Page 5
1 DISPLAYS AND FUNCTION KEYS
Information.
The fold-out page inside on the back cover of this
manual shows all the frames in the programming levels. Space is provided on the page for writing the programmed setting or selection for each frame.
1.1 Introduction – Fig. 1.1
The instrument front panel display, function keys and LED indicators are shown in Fig. 1.1.
Display
888888
Function Keys
Parameter Advance
Raise
Lower
A1
A2
A3
Alarm LEDs (invisible when off)
Multi-function Key
Fig. 1.1 Front Panel Display, Function Keys and Indicators
3
Page 6
…1 DISPLAYS AND FUNCTION KEYS
1.2 Use of Function Keys – Fig. 1.2
A – Raise and Lower Keys
100.0 100.1
99.9
Use to change/set a parameter value…
B – Parameter Advance Key
LEVEL1
100.1
Use to advance to the next frame within a level…
+ –
LEVEL1
Frame 1 (top of level)
Frame 2
or…
…move between levels
LEVELx
100.1
or…
200.2
300.3
400.4
…select the top (LEVEL) frame from within a level
LEVEL2
Press and hold
Note. This key also stores any changes made in the previous frame
C – Multi-function Key
CodE
0
Use to view a parameter setting or selection…
Fig. 1.2 Use of Function Keys
4
or…
…select individual characters in a frame
123456
Page 7
1 DISPLAYS AND FUNCTION KEYS…
1.3 LED Alarms and Indicators
Alarm LEDs
LED Status
All Flashing
• Indicator is in the Configuration Mode – see Section 4.2.
A1, A2 and A3
A1
A2
A3
Alarm 1 Alarm 2
Alarm 3
• Flash when Alarm is active (off when inactive).
• Lit constantly when Alarm 1 is an active latched alarm which has been acknowledged
Fig. 1.3 LED Alarms and Indicators
5
Page 8
…1 DISPLAYS AND FUNCTION KEYS
1.4 Error Messages
Display Error/Action
Calibration error
CAL.Err
Turn power off and on again (if the error persists, contact the Supplier).
Configuration error
CFG.Err
The configuration and/or setup data for the instrument is corrupted. Turn power off and on again (if error persists, check configuration/setup settings).
A to D Converter Fault
A.d. Err
The analog to digital converter is not communicating correctly.
To Clear Display
Press the
Press the
Turn power off and on again. If error persists, contact the
key
key
9999
DPt.Err
Process Variable Over/Under Range
Option board error
Communications to the option board have failed.
Supplier
Restore valid input
Contact the Supplier
6
Page 9
2 OPERATOR MODE
2.1 Introduction
Operator Mode (Level 1) is the normal day-to-day mode of the instrument. Frames displayed in Level 1 are determined by the indicator functions which are
selected during configuration of the instrument – see Section 4.
Note. Only the operating frames relevant to the configured functions are
displayed in Operator Mode.
The three indicator functions are:
Standard Indicator page 8
Indicator with Totalization page 9
Indicator with Max./Min./Average page 11
7
Page 10
…2 OPERATOR MODE
2.2 Operating Page – Standard (Level 1)
2145.3
UN-ACK
CodE
Process Variable
Normally displayed in engineering
2145.3
units.
To view the process variable in
27.6
•1
Global Alarm Acknowledge (latch alarms only)
UN-ACK. – alarm unacknowledged ACK. – acknowledged
Security Code
Enter the correct code to access the setup level
electrical units, press the
key.
(Level 2).
------
[0 to 9999]
LEVEL1
•1 Only displayed if there is an active latch alarm.
Level 1
Note. To select this frame from anywhere in this
level, press the
key for a few seconds.
8
Page 11
2 OPERATOR MODE…
2.3 Operating Page – Totalizer (Level 1)
These frames are only displayed if the totalizer function is enabled in the configuration level – see Section 4.3.3
2145.3
ACK-n
123456
rSt-n
•1
•1
Process Variable
To view the input value (in electrical units), press the
key.
Global Alarm Acknowledge (latch alarms only)
UN-ACK. – alarm unacknowledged ACK. – acknowledged
Totalizer Value
When this frame is selected, the current counter status is displayed (
Stop/Start
t–GO or t-StOP).
t–GO – start totalizer t-StOP – stop totalizer
Reset
rSt-Y – reset totalizer rSt-n – do not reset totalizer
To reset the totalizer, select the
Continued on next page.
•1 Totalizer stop/go and reset from these frames can be disabled – see Section
4.3.3. A digital input can also be used to start/stop or reset the totalizer – see
key.
rSt-Y. then press
Section 4.3.4
9
Page 12
…2 OPERATOR MODE
2.3 Operating Page – Totalizer (Level 1)
PrESEt
000000
Select Digit
PrEdEt
999999
Select Digit
•2
Preset Total
This is the value the batch total is set to when it is reset
•1
[000000 to 999999 flow units]
Predetermined Total
When the predetermined total is reached, the batch total is reset (with wrap on) or stops (wrap off), depending on the wrap setting – see Section 3.2.
•1
[000000 to 999999 flow units]
CodE
Security Code
Enter the correct code to access the setup level.
------
[0 to 9999]
LEVEL
•1 The predetermined value should be greater than the preset value when the totalizer is counting up and lower than the preset value when the totalizer is counting
Level 1
Note. To select this frame from anywhere in
this level, press the
key for a few seconds.
down.
•2 Only displayed if enabled in the configuration level – see Section 4.3.3.
10
Page 13
2 OPERATOR MODE…
2.4 Operating Page – Max./Min./Average Functions (Level 1)
Note. It is possible to have totalizer and math functions together.
Process Variable
2145.3
To view the input value (in electrical units), press
UN-ACK
A 140.5
rSt-n
•1
the
Global Alarm Acknowledge (latch alarms only)
key.
UN-ACK. – alarm unacknowledged ACK. – acknowledged
Average Value
This is the mean average value of the process variable input, since the average was reset.
rSt-Y – reset rSt-n – do not reset
To reset the average value, select
rSt-Y then press
the
key.
H150.2
Continued on next page.
•1 This frame can be disabled – see Section 4.3.3. The average value is reset automatically on power-up and can also be reset
from a digital input – see Section 4.3.4. The reset function in this frame can be disabled – see Section 4.3.3.
11
Page 14
…2 OPERATOR MODE
…2.4 Operating Page – Math Functions (Level 1)
H150.2
rSt-n
L130.8
rSt-n
•1
•1
Maximum Value
This is the maximum value of the process variable since the maximum was reset.
rSt-Y – reset rSt-n – do not reset
To reset the maximum value, select press the
Minimum Value
This is the minimum value of the process variable since the minimum was reset.
rSt-Y – reset rSt-n – do not reset
key.
rSt-Y then
To reset the minimum value, select press the
CodE
------
LEVEL1
•1 This frame can be disabled – see Section 4.3.3.
Security Code
Enter the correct code to access the setup level.
[0 to 9999]
Level 1
Note. To select this frame from anywhere in this
level, press the
key.
key for a few seconds.
rSt-Y then
12
The average value is reset automatically on power-up and can also be reset from a digital input – see Section 4.3.4.
The reset function in this frame can be disabled – see Section 4.3.3.
Page 15
3 SET UP MODE
3.1 Introduction
To access the Setup Level (Level 2), the correct password must be entered in the
8
security code frame (
Level 1 –
Operating Level
Security
Code
LEVEL1
CodE x
CodE) in Level 1– see Fig. 3.1.
LEVEL2
A1xx
Correct
Password
A2xx
A3xx
123456
t-GO
SEC.tot
Level 2 – Set Up
Alarm 1 Trip Point
Alarm 2 Trip Point
Alarm 3 Trip Point
Batch Total
Totalizer Stop/Go
Secure Total/Reset
PrESEt
PrEdEt
A xxxx
H xxxx
L xxxx
0AdJ
Fig. 3.1 Accessing the Set Up Level (Level 2)
Preset Batch Total Predetermined Batch
Total Average Value
Maximum Value
Minimum Value
Offset Adjustment
13
Page 16
8
3.2 Set Up Level (Level 2)
…3 SET UP MODE
LEVEL2
A1.hP
100.1
A1. HYS
•1
•2
Level 2
Note. To select this frame from anywhere in
this level, press the
Alarm 1 Trip Point
Alarm type:
A1.hP = High process alarm A1.LP = Low process alarm A1.HL = Latched high process alarm A1.LL = Latched low process alarm
[In engineering units]
Alarm 1 Hysteresis Value
key for a few seconds.
A2.LP
A2. HYS
A3.hP
12.5
200.2
27.9
•1
•2
[In engineering units]
Alarm 2 Trip Point
Alarm type
[In engineering units]
Alarm 2 Hysteresis Value
[In engineering units]
Continued on next page.
•1 Not displayed if the alarm is disabled ('NONE' selected) – see Section 4.3.2.
•2 Only displayed if custom alarm hysteresis is selected – see Section 4.3.2
14
Page 17
…3.2 Set Up Level (Level 2)
3 SET UP MODE…
8
A3.hP
300.3
A3 HYS
34.6
123456
•1
•2
•3
•4
Alarm 3 Trip Point
Alarm type
[In engineering units]
Alarm 3 Hysteresis Value
[In engineering units]
Totalizer Value
rSt-Y – reset rSt-n – do not reset
rSt-n
•3
To reset the maximum value, select press the
Totalizer Stop/Go
key.
rSt-Y then
t-GO
t–GO . – start totalizer t-StOP. – stop totalizer
t-StOP
Setting to the predetermined value. Setting to the totalizer at its present value.
SEC.tOt
Continued on next page
•1 Not displayed if the alarm is disabled ('NONE' selected) – see Section 4.3.2
t-GO starts the totalizer counting towards
t-StOP holds
•2 Only displayed if custom alarm hysteresis is selected – see Section 4.3.2
•3 Only displayed if enabled in the configuration level – see Section 4.3.3
•4 A digital input can also be used to reset the batch total.
15
Page 18
8
…3.2 Set Up Level (Level 2)
…3 SET UP MODE
SEC.tOt
456789
rSt-n
PrESEt
•1
•2
Secure Total
The secure total is independent of the batch total value. When 999999 or 000000 is reached, the total is reset and then continues counting.
Total
Reset
rSt-Y. – reset totalizer rSt-n. – do not reset totalizer
To reset, select
Preset Batch Total
This is the value the batch total is set to when it is reset.
rSt-Y. then press the key.
[000000 to 999999]
000000
PrEdEt
•2
999999
A140.5
•1 Only displayed if enabled in the configuration level – see Section 4.3.3.
Predetermined Batch Total
When this value is reached the batch total either resets (with wrap on) or stops (wrap off) – see Section 4.3.3.
[000000 to 999999]
Continued on next page.
•2 The preset value must be lower than the predetermined value when counting up, and greater than the predetermined value when counting down.
16
Page 19
…3.2 Set Up Level (Level 2)
3 SET UP MODE…
8
A140.5
rSt-n
H150.2
rSt-n
•1
•2
Average Value
This is the mean average value of the process variable input since the average was reset.
rSt-Y. – reset rSt-n. – do not reset
To reset, select
Maximum Value
This is the maximum value of the process variable since the maximum was reset.
rSt-Y. – reset rSt-n. – do not reset
To reset, select
rSt-Y. then press the key.
rSt-Y. then press the key.
L130.8
rSt-n
O.AdJ
1.0
•2
Minimum Value
This is the minimum value of the process variable since the minimum was reset.
rSt-Y. – reset rSt-n. – do not reset
To reset , select
Offset Adjustment
An offset can be applied to the process variable input to enable spot calibration or the removal of system errors.
[±10% of engineering range]
rSt-Y. then press the key.
•1 The average value i s reset automatically on power-up and can also be reset from a digital input – see Section 4.3.4.
•2 The maximum and minimum values are reset automatically on power-up and can also be reset from a digital input – see Section 4.3.4.
17
Page 20
4 CONFIGURATION MODE
4.1 Introduction
The Configuration Mode comprises two levels (3 and 4) as shown in Fig. 4.2. Configuration Level 3 is divided into four frames. For most simple applications, it is
only necessary to set up the parameters in the first frame.
Note.
When in the configuration level:
All the LED indicators flash.
All relays and logic outputs are turned off.
The analog output reverts to 0% (4mA) output level.
4.2 Accessing the Configuration Mode – Fig. 4.1
To access the Configuration Mode, set the security switch to the 'Configure' position (Levels 1 and 2 cannot be accessed from this setting). When the configuration parameters are programmed, reset the security switch to the 'Normal' position and the operating page is displayed automatically .
Normal
Configure
18
Fig. 4.1 Accessing the Configuration Mode
Page 21
4 CONFIGURATION MODE…
Level 3
Hardware
Configuration
Alarms and
Set Points
Custom Operator
Settings
LEVEL3
A 1KC0
b 1KC0
C 1KC0
d 1KC0
E 0000
F 0000
G 0000
H 0000
J 0000
K 0000
L 0000
N 0000
LEVEL4
ENG HI
ENG LO
rEt HI
rEt LO
CNt HI
CUtOFF
PASSrd
Level 4
Engineering Range High
Engineering Range Low
Retransmission Range High
Retransmission Range Low
Totalizer Count High
Totalizer Count Cut-off
Set Up Password
Digital Input and
Serial Comms.
P 0000
r 0000
S 0000
t 0000
Fig. 4.2 Configuration Levels
Addr.
MODBUS Address
19
Page 22
…4 CONFIGURATION MODE
4.3 Basic Hardware and Configuration (Level 3) – Fig. 4.3
4.3.1 Hardware Assignment and Input Type
LEVEL3
A 1KC0
B 1KC0
C 1KC0
d 1KC0
Level 3
Note. To select this frame from anywhere in this
level, press the
'ABCD' Settings
The first character (A, B, C or D) identifies the parameter to be changed. The current setting is indicated by a flashing letter. Parameter options are shown in Fig. 4.3.
key for a few seconds.
A = Hardware configuration b = Input type and range C = Temperature units d = No. of decimal points
Note. The temperature ranges default to their
maximum values when the input type is changed.
E 1203
Continued on page 22.
Information.
Count High Calculation
actual engineering flow rate
Convert flow rate into units/sec =
units/sec
Count High = resultant must be >0.001 and <99.999pps.
Counter factor is the engineering value of the least significant digit shown on the totalizer display – see Section 4.3.3.
Totalizer Count Pulse
The totalizer count pulse is on for a preset time of 250ms and off for a minimum
of 250ms.
counter factor
flow range time units (in seconds)
20
Page 23
4 CONFIGURATION MODE…
A 1KC0
A – Hardware Configuration
50Hz/60Hz Relay 1 Relay 2* Relay 3* Logic O/P Analog O/P
Source Source Source Source Source
1 A Alarm 1 Alarm 2 Alarm 3 TCP** PV 2 b Alarm 1 Alarm 2 Alarm 3 TWP** PV 3 C TCP** Alarm 1 Alarm 2 TWP** PV 4 D TWP** Alarm 1 Alarm 2 TCP** PV 5 E Alarm 1 Alarm 2 Alarm 3 TCP** PV Average
U Custom Custom Custom Custom Custom TCP = Totalizer Count Pulse TWP = Totalizer Wrap Pulse PV = Process Variable
* Only available if the appropriate option board is fitted. ** Pulse energizes assigned relay
B – Input Type and Range Configuration
b 1KC0
Display
b T/C Type B
E T/C Type E
J T/C Type J K T/C Type K n T/C Type N
r T/C Type R
S T/C Type D
t T/C Type T
P PT100 RTD
C – Temperature Units
Display
C 1KC0
Display Temperature Units
C Degrees C* F Degrees F* 0 No temperature units
* Temperature inputs only
1 0 to 20 mA 2 4 to 20 mA 3 0 to 5 V 4 1 to 5 V 6 0 to 50 mV 7 4 to 20 mA (square root lineariser)
U Custom Configuration
d 1KC0
Display
0 xxxx 1 xxx . x 2 xx . xx 3 x . xxx 4 x . xxxx
D – Process Variable Display Decimal Places
Fig. 4.3 Hardware Configuration and Input/Output Ranges
21
Page 24
…4 CONFIGURATION MODE
4.3.2 Alarms – Figs. 4.4 and 4.5
Note. Relays assigned to alarms are de-energized in the alarm state.
E 0000
F 0000
J 0000
G 0000
H 0000
'EFGH' Settings
The first character (E, F, G or H) identifies the parameter to be changed. The current setting is indicated by a flashing letter. Parameter options are shown in Fig. 4.5.
E = Alarm 1 type F = Alarm 2 type G = Alarm 3 type H = Alarm hysteresis
Continued on page 24.
Hysteresis
Hysteresis
Process Variable
Alarm on Alarm off
Information.
For latch alarms the relay remains de-energized until acknowledged in
Level 1 (or by a digital input)
High Process
Low Process
Fig. 4.4 Alarm Action
Trip point
Alarm on Alarm off
22
Page 25
4 CONFIGURATION MODE…
E 0000
E – Alarm 1 Type
Display
0 None 1 High Process 2 Low Process 3 High Latch 4 Low Latch
F – Alarm 2 Type
F 0000 G 0000
Display
0 None 1 High Process 2 Low Process 3 High Latch 4 Low Latch
Display
0 None 1 High Process 2 Low Process 3 High Latch 4 Low Latch
G – Alarm 3 Type
h 0000
Display
0 None 1 0.1% 2 0.2% 3 0.5% 4 1.0% 5 2.0% 6 5.0%
U Custom
H – Alarm Hysteresis
Value in % of engineering range
Value in engineering units
Fig. 4.5 Alarm Set Up
Note. When custom
alarm hysteresis is selected, the alarm hysteresis values are set individually in the
Level – see Section 3.2
Set Up
23
Page 26
…4 CONFIGURATION MODE
4.3.3 Operator Functions and Totalizer Set Up – Fig. 4.6
J 0000
K 0000
P 0000
L 0000
n 0000
'JKLN' Settings
The first character (J, K, L or N) identifies the parameter to be changed. The current setting is indicated by a flashing letter. Parameter options are shown in Fig. 4.6.
J = Totalizer set-up K = No. of decimal places for totalizer L = Operator level frame enable n = Operator level functions enable/disable
Continued on page 26.
24
Page 27
4 CONFIGURATION MODE…
J 0000
Display
0Off 1 Count Up, Wrap Off 2 Count Up, Wrap On 3 Count Down, Wrap Off 4 Count Down, Wrap On
J – Totalizer Set Up
L – Operator Level Frame Enable
K 0000
Display
0 xxxxxx 1 xxxxx.x 2 xxxx.xx 3 xxx.xxx 4 xx.xxxx 5 x.xxxxx
K – Totalizer Display Decimal Places
L 0000
Display Max/Min Values Average Value Preset/Predetermined
Displayed Displayed Values Displayed
0No No No 1 Yes No No 2 Yes Yes No 3 No Yes Yes 4No No Yes 5 Yes No Yes 6 Yes Yes Yes
This frame determines which frames appear in the operating page (Level 1)
N – Operator Level Math Function & T otalizer Control Enable
n 0000
Display Totalizer Stop/Go Totalizer Reset Max./Min./Average
0No No No 1 Yes No No 2 No Yes No 3 Yes No Yes 4 No Yes Yes 5 Yes Yes Yes
This frame determines which functions the operator can control
Fig. 4.6 Totalizer Set Up and Operator Functions
25
Page 28
…4 CONFIGURATION MODE
4.3.4 Digital Input and Serial Communications – Figs. 4.7 and 4.8
P 0000
r 0000
LEVEL4
S 0000
t 0000
'PRST' Settings
The first character (P, R, S or T) identifies the parameter to be changed and the current setting is indicated by a flashing letter. Parameter options are shown in Fig. 4.8.
P = Digital input function r = Analog input filter S = Serial communications configuration t = Serial communications parity
Note. For custom settings contact the local
distributor.
Continued on page 28.
Reset
1 Totalizer Reset
Stop
Go
2 Totalizer Stop/Go
Max
Min
3 Average Max/Min Reset
Information.
Digital input options 1, 2, 3 and 5 are edge-triggered to enable the front
4 Front Panel Lock out
5 Alarm Acknowledge
Lock Unlock
Acknowledge
26
panel keys to change the function when the digital input is operational.
Fig. 4.7 Digital Function Configuration
Page 29
4 CONFIGURATION MODE…
P 0000 r 0000
P – Digital Input Function
Display
0 None 1 Totalizer Reset 2 Totalizer Stop/Go 3 Average, Max/Min Reset 4 Front Panel Lockout 5 Alarm Acknowledge
S 0000 t 0000
Display Baud Rate, 2/4 Wire
0Off 1 2400, 2 Wire 2 2400, 4 Wire 3 9600, 2 Wire 4 9600, 4 Wire
S – Serial Communication Configuration
Display
0 0 seconds 1 1 second 2 2 seconds
5 5 seconds A 10 seconds B 20 seconds C 40 seconds D 60 seconds
Display
0 None 1 Odd 2 Even
R – Analog Input Filter
T – Serial Communication Parity
Note. Settings for options P, S and T are only available if the
appropriate option board is fitted.
Fig. 4.8 Digital Function and Serial Communications Configurations
27
Page 30
…4 CONFIGURATION MODE
4.4 Ranges and Passwords (Level 4)
LEVEL4
ENG HI
100.0
ENG LO
Level 4
Note. To select this frame from anywhere in this
level, press the
Engineering (Display) Range
High Value
•1
[–9999 to 99999]
Low Value
key for a few seconds.
•1
0.0
CNt HI
Continued on next page…
•1 The engineering range high and low values are automatically set to the maximum allowed value when thermocouple or RTD is selected in the configuration level – see Section 4.3.1. This value can be modified if required.
[–9999 to 99999]
28
Page 31
4 CONFIGURATION MODE…
…4.4 Ranges and Passwords (Level 4)
Retransmission Range
The retransmission range defines the engineering range to be retransmitted.
rEt HI
rEt LO
CNt HI
100.0
100.0
High (20mA output)
•1
[–9999 to 99999 (in engineering units)]
Low (4mA output)
•1
[–9999 to 99999 (in engineering units)]
Continued on next page…
•1 The retransmission range high and low values are automatically set to the maximum allowed value when thermocouple or RTD is selected in the configuration level – see Section 4.3.1. This value can be modified if required.
29
Page 32
…4 CONFIGURATION MODE
…4.4 Ranges and Passwords (Level 4)
CNt HI
1.00
cut.oFF
100.0
•1
•1
Totalizer Count High
This frame determines the count corresponding to the full-scale input.
[0.000 and 99.999 pulses/second]
Cut-Off
This frame sets the lowest flow value at which the totalizer is to stop counting.
[In engineering units]
PASSrd
0
•2
Addr.
1
•1 Only displayed if enabled in the configuration level – see Section 4.3.3.
Set Up Password
This password enables access to the set up level (level 2).
[0 to 9999]
MODBUS Address
This frame sets the MODBUS address.
[1 to 99]
•2 Only available if the appropriate option board is fitted.
30
Page 33
5 INSTALLATION
5.1 Siting – Figs. 5.1 and 5.2
Close to Sensor
Sensor
At Eye Level
Avoid Vibration
Fig. 5.1 Siting – General Requirements
31
Page 34
…5 INSTALLATION
…5.1 Siting – Figs. 5.1 and 5.2
Temperature Limits
Humidity Limits
55°C Max.
0°C Min.
0 to 90% RH
Environmental Limits
Use Screened Cable
IP65/NEMA-3
(front panel)
IP20
(rear)
+
32
Fig. 5.2 Environmental Requirements
Page 35
5 INSTALLATION…
5.2 Mounting – Figs. 5.3 and 5.4
The instrument is designed for panel mounting (see Fig. 5.4). Overall dimensions are shown in Fig. 5.3.
Dimensions in inches (mm)
0.28 (7.1)
4.68 (119)
1.57 (40) 3.11 (79)
1.76
(44.6)
0.11 (2.7)
1.89
+ 0.6
(45 )
– 0
1.77
+ 0.02 – 0
3.78 (96)
+ 0.03
3.62
– 0
+ 0.8
(92 )
– 0
Panel cut-out
0.55 (14)
Fig. 5.3 Overall Dimensions
0.55
(14)
33
Page 36
…5 INSTALLATION
…5.2 Mounting – Figs. 5.3 and 5.4
Cut a suitable hole in the panel (see Fig. 5.3)
1
2
Insert the instrument into the panel cut-out
Fit the retaining clamp
3
over the instrument case
34
Push the retaining clamp firmly
4
against the panel
Fig. 5.4 Mounting Details
Page 37
5 INSTALLATION…
EC Directive 89/336/EEC
In order to meet the requirements of the EC Directive 89/336/EEC for EMC regulations, this product must not be used in a non­industrial environment.
5.3 Electrical Connections – Figs. 5.5 and 5.6
Warning. Before making
any connections, ensure that the power supply, any powered control circuits and high common mode voltages are switched off.
5.4.3 Logic Output
18V DC at 20mA Min load 900 Isolated from Analog Input (not
isolated from Retransmission Output). Dielectric strength – 500V d.c. for 1 minute.
5.4.4 Control or Retransmission Analog Output
Max. load 15V (750 at 20mA) Isolated from Analog Input (not
isolated from Logic Oouput). Dielectric strength - 500V d.c. for
Note. If it is not possible to avoid strong electrical and magnetic fields, screened cables within earthed/grounded metal conduit must be used.
5.4 Relays, Arc Suppression and Outputs
5.4.1 Relay Contact Ratings
Relay contacts are rated at:
115/230V AC at 5A (non-inductive) 250V DC 25W max.
5.4.2 Arc Suppression - Fig. 5.5
Arc suppression components are fitted to relays 2 and 3 only. If relay 1 is
1 minute.
Terminal Block
11 7
10 9 8
NC
Load Load
Switched
C
Suppression
component
Supply
NO
(B9303)
required to switch inductive loads, the arc suppression component supplied must be fitted across the contacts used.
Fig. 5.5 Fitting Arc Suppression
Components
35
Page 38
…5 INSTALLATION
Logic Output (18V at 20mA max.)
Analog Input (see below)
+
123456789101112
13
Not
Used
750 max. load
14
RTD1
15
Digital
Input
+
Analog Output
Transmitter PSU
+
18
17
C
Relay
Output 2
+
16
+
N/O
19
N/C
1
Relay
Output 1
N/C
CN/O
21
20
+
RS485
TX
Relay Output 3
22 23
RS485
or
N/O
85 to 265V a.c.
N
L
+
1A
24
C
RS485
2
+
RX
C
24V d.c.
N/C
Note 1. The Analog Output and Logic Output use a common positive
terminal, capable of driving both outputs simultaneously.
Note 2. Fit arc suppression components if switching inductive loads.
T/C millivolts and volts
1
2
+
3
3-lead
RTD
rd
3
lead
RTD –
RTD
+
2-lead RTD
and resistance
RTD –
RTD –
RTD +
Milliamps
**100
+
4
* Using internal transmitter power supply
** Use 100 shunt resistor provided with instrument
* Milliamps
**100
Tx
+
2-wire transmitter
36
Fig. 5.6 Electrical Connections
Page 39
CUSTOMER CONFIGURATION LOG
LEVEL4
LEVEL3
A 1KC0
A B C D
E 0000
E F
J 0000
J K
P 0000
G H
L N
ENG HI
ENG LO
rEt HI
rEt LO
CNt HI
CUtOFF
PASSrd
P R
S T
Addr.
Page 40
CUSTOMER SETUP LOG
LEVEL1
CodE
8
LEVEL2
A1xx
A2xx
A3xx
xxxxxx
t-GO
SEC.tot
PrESEt
PrEdEt
A xxxx
H xxxx
L xxxx
0AdJ
Instrument Serial Number:
Page 41
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 37 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal three (3) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY / DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY
RETURNS, please have the following information available BEFORE contacting OMEGA:
1. Purchase Order number under which the
product was PURCHASED,
2. Model and serial number of the product
under warranty, and
3. Repair instructions and/or specific problems
relative to product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 1998 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied,
photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
FOR NON-WARRANTY REPAIRS, OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of the products, and
3. Repair instructions and/or specific problems relative to the product.
consult
Page 42
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
TEMPERATURE
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD & Thermistor Calibrators & Ice Point References Recorders, Controllers & Process Monitors Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
Transducers & Strain Gauges Load Cells & Pressure Gauges Displacement Transducers Instrumentation & Accessories
FLOW/LEVEL
Rotameters, Gas Mass Flowmeters & Flow Computers Air Velocity Indicators Turbine/Paddlewheel Systems Totalizers & Batch Controllers
pH/CONDUCTIVITY
pH Electrodes, Testers & Accessories Benchtop/Laboratory Meters Controllers, Calibrators, Simulators & Pumps Industrial pH & Conductivity Equipment
DATA ACQUISITION
Data Acquisition & Engineering Software Communications-Based Acquisition Systems Plug-in Cards for Apple, IBM & Compatibles Datalogging Systems Recorders, Printers & Plotters
HEATERS
Heating Cable Cartridge & Strip Heaters Immersion & Band Heaters Flexible Heaters Laboratory Heaters
ENVIRONMENTAL MONITORING AND CONTROL
Metering & Control Instrumentation Refractometers Pumps & Tubing Air, Soil & Water Monitors Industrial Water & Wastewater Treatment pH, Conductivity & Dissolved Oxygen Instruments
M2937/0299
Loading...