Omega Products CSBASE00 User Manual

ENHANCED MODULAR CONTROLLER SERIES MASTER
CSMSTR
l Provides Enhanced Features For Data Acquisition
Or Multi-Zone Pid Control Applications
l Webserver Provides Worldwide Access to
l Virtual HMI Offers Built-In PC-Based
SCADA Functionality
l Performs Hierarchical Control of Other Modules
in the Modular Controller Series
l Stores Module Configuration Information,
and Automatically Reprograms Replaced Modules
l Extensive Built-In Driver List Allows Easy
Data Mapping to PLCs, PCs, and SCADA Systems
l Independent Serial Ports Provide Virtually
Unlimited Integration Methods
l 10 Base-T/100 Base-Tx Ethernet Connection
Provides Networking Capability
l Supports up to 16 Modular Controller
Series Modules
l Compactflash
®
Slot Allows Process Data to be
Logged Directly to CSV Files
CSMSTRSX shown smaller than actual size.
The CSMSTR is programmed with Crimson 2.0 software for Windows® 2000 or later platforms. The software is an easy to use, graphical interface which provides a means of communication configuration, as well as commissioning and calibration of new systems.
Automation Controllers and HMI
The Model CSMSTR is a communications and control platform designed for use with Modular Controller Series slave modules. The CSMSTR uses a proprietary high speed serial protocol to communicate, via backplane connection, with up to 16 slave modules. Through the same connection, the Master also provides power to the modules.
When powered up, the CSMSTR automatically identifies and addresses connected slave modules. By storing the configuration information of all of the modules, the CSMSTR is able to automatically configure modules if they are replaced.
The Master provides high-speed RS232/422/485 communication ports and an Ethernet port for connection to PCs, PLCs, and SCADA systems. An extensive list of master and slave protocol drivers are available to allow the CSMSTR to share and exchange variable data with external devices. The 10 Base-T/100 Base-TX Ethernet port can also be used to connect and share data with other devices at high speeds. The virtual HMI feature allows you to create and control an HMI from any networked PC. An onboard CompactFlash slot provides storage for the Master’s built-in data logger.
The design of the Modular Controller Series high density packaging and DIN rail mounting saves time and panel space. The controller snaps easily onto standard top hat (T) profile DIN rail.
SPECIFICATIONS
Power: 24 Vdc ± 10% 400 mA min. (1 module) 3.5 Amps
max. (16 modules + Expansion Card) Must use Class 2 or SELV rated power supply
Communications: USB/PG Port: Adheres to USB specification 1.1
(Device only using Type B connection) Serial Ports: Format and Baud Rates for each port are
individually software programmable up to 115,200 baud RS232/PG Port: RS232 port via RJ12 COMMS Ports: RS422/485 port via RJ45,
and RS232 port via RJ12 DH485 TXEN: Transmit enable; open collector,
VOH=15 Vcd, VOL=0.5 V @ 25 mA max Ethernet Port: 10 BASE-T / 100 BASE-TX RJ45 jack is
wired as a NIC (Network Interface Card)
LEDs: STS: Status LED indicates condition of master TX/RX: Transmit/Receive LEDs show serial activity
Ethernet: Link and activity LEDs CF: CompactFlash LED indicates card status
and read/write activity
Memory: On-Board User Memory: 4MB of non-volatile flash memory On-Board SDRAM: CSMSTRSX=2MB; CSMSTRGT=8MB
Memory Card: Compactflash type II slot for type I and type II cards
1
Real-Time Clock: Typical accuracy is less than one minute per month drift. Crimson
2.0’s SNTP facility allows synchronization with external servers
Battery: Lithium coin cell (included). Typical lifetime of 10 years at 25°C (77°F) A “battery low” system variable is available so that the programmer can choose specific action(s) to occur when the battery voltage drops below its nominal voltage.
Environmental Conditions: Operating Temperature Range:
0 to 50°C (32 to 122°F)
Storage Temperature Range:
-30 to 70°C (-22 to 158°F)
Operating and Storage Humidity:
80% max relative humidity, non-condensing, from 0 to 50°C (32 to 122°F)
Vibration According to IEC 68-2-6: 5 to 150 Hz, in X, Y, Z direction for
1.5 hours, 2 g’s Shock According to IEC 68-2-27:
Operational 25 g, 11 msec in 3 directions
Altitude: Up to 2000 meters Construction: Case body is burgundy
high impact plastic and stainless steel. Installation category I, pollution degree 2
Power Connection: Removable wire clamp screw terminal block
Wire Gage Capacity: 24 AWG to 12 AWG Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m) Mounting: Snaps onto standard DIN style
top hat (T) profile mounting rails according to EN50022 -35 x 7.5 and -35 x 15
Certifications and Compliances: Safety: UL Listed, File #E302106,
UL508, CSA 22.2 No. 14-M05 Listed by Und. Lab. Inc. to U.S. and Canadian safety standards IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for measurement, control, and laboratory use, part 1
Electromagnetic Compatability: Emissions and Immunity to EN 61326:
Electrical equipment for measurement, control and laboratory use
Immunity to Industrial Locations*:
Electrostatic discharge EN 61000-4-2 Criterion A2; 4 kV contact discharge; 8 kV air discharge; Electromagnetic RF fields EN 61000-4-3 criterion A 10 V/m; Fast transients (burst) EN 61000-4-4 Criterion A; 2 kV power; 2 kV signal; Surge EN 61000-4-5 Criterion A; 1kV L-L,2 kV L&N-E power; RF conducted interference EN 61000-4-6 Criterion A; 3 V/rms
Emissions: Emissions EN 55011 class A Weight: 456.4 g (15.1 oz)
*Notes:
1. Criterion A: Normal operation within specified limits.
2. This device was designed for installation in an enclosure. To avoid electrostatic discharge to the unit in environments with static levels above
4 kV, precautions should be taken when the device is mounted outside an enclosure. When working in an enclosure (ex. making adjustments, setting jumpers etc.), typical anti-static precautions should be observed before touching the unit.
To Order Visit omega.com/csmstr for Pricing and Details
MODEL NO. MASTER MODULE DESCRIPTION
CSMSTRSX Modular controller master with multiple protocol converter,
CSMSTRGT Modular controller master with multiple protocol conversion,
SFCRM2MC Modular controller crimson programming software,
ACCESSORIES
MODEL NO. DESCRIPTION
G3CF064M 64 MB compact flash card
G3CF256M 256 MB compact flash card
G3CF512M 512 MB compact flash card
CBLPROG0 Programming cable for CS, G3, and paradigm CBLUSB00 USB programming cable for G3, DSP and modular
PSDR0100 Mini power supply 1A PSDR0200 Mini power supply 2A PSDR0400 Mini power supply 4A RSRSTP00 Rail stops (qty 2) CSTERM00 Replacement termination plug CSBASE00 Replacement base CSTERM00 Replacement termination plug
MODULES
MODEL NO. MODULE DESCRIPTION
CSDIO14R 8-inputs 6 relay outputs CSDIO14S 8-inputs 6 solid state outputs CSINV800 8-channel ±10 V input module CSINI800 8-channel 0(4) to 20 mA input module CSOUT400 4-channel analog output CSPID1R0 Single loop module, relay outputs CSPID1RA Single loop module, relay outputs, analog output CSPID1RM Single loop module, relay outputs, heater current input CSPID1S0 Single loop module, solid state outputs CSPID1SA Single loop module, solid state out. Analog output CSPID1SM Single loop module, solid state, heater current input CSPID1TA Single loop module, triac outputs, analog output CSPID2R0 Dual loop module, relay outputs CSPID2RM Dual loop module, relay outputs, heater current input CSPID2S0 Dual loop module, solid state outputs CSPID2SM Dual loop module, solid state outputs, heater current input CSPID2T0 Dual loop module, triac outputs CSPID2TM Dual loop module, triac outputs, heater current input CSRTD600 6-channel input, RTD CSSG10RA Single loop, 1 strain gage input, relay outputs, analog out CSSG10SA Single loop, 1 strain gage input, solid state out, analog out CSSG11RA Single loop, 2 strain gage input, relay outputs, analog out CSSG11SA Single loop, 2 strain gage input, solid state out, analog out CSTC8000 8-channel thermocouple module
Comes complete with termination plug, terminal power block, lithium cell battery, and operator’s manual. Ordering Example: CSMSTRSX, controller, SFCRM2MC, software, G3CF512M, 512 MB flash card, PSDR0100, power supply, CSDIO14R, module.
data logger, web server , virtual HMI up to QVGA (320X240) size and expansion slot.
data logger, web server, full VGA virtual HMI (640X480) size and expansion slot with increased DRAM
manual and download cable
(industrial grade 2 million write cycles)
(industrial grade 2 million write cycles)
(industrial grade 2 million write cycles)
controller, type A-B
2