United Kingdom: One Omega Drive, River Bend Technology Centre
ISO 9002 CertifiedNorthbank,
Irlam, Manchester
Tel: 44 (161) 777-6611FAX: 44 (161) 777-6622
Toll Free in the United Kingdom: 0800-488-488
e-mail: info@omega.co.uk
®
OMEGAnetSMOn-Line Service Internet e-mail
http://www.omega.com info@omega.com
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that
apply. OMEGA is constantly pursuing certification of its products to the European New Approach
Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts
no liability for any errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
This manual is intended for use in support of installation, commissioning
and configuration of the 1/32-DIN Temperature Indicator.
The procedures described in this manual should be undertaken only by
personnel competent and authorized to do so.
CAUTION:
Read This Manual!!
!
THE INTERNATIONAL HAZARD SYMBOL IS INSCRIBED ADJACENT TO
THE REAR CONNECTION TERMINALS. IT IS IMPORTANT TO READ
THIS MANUAL BEFORE INSTALLING OR COMMISSIONING THE UNIT.
2
Table of Contents
Page
Section 1 - Installation - Panel-Mounting
1.1 Unpacking the Instrument5
1.2 Installing the Instrument in the Mounting Panel6
1. Remove the Instrument from its packing. A panel gasket and a “no tools
required” fixing strap are supplied. Retain the packing for future use (e.g.
moving the Instrument to a different site).
2. Examine the delivered items for damage or deficiencies. If any are found,
notify the carrier immediately. Check that the Product Code on the label
affixed to the Instrument housing corresponds to that ordered.
FIGURE 1-1Main Dimensions
FIGURE 1-2Panel Cut-out Dimensions
5
1. 2INSTALLING THE INSTRUMENT IN THE MOUNTING PANEL
CAUTION: Do not remove the front panel gasket from the Instrument, as
this may cause inadequate clamping of the Instrument to the mounting
panel. Ensure that this gasket is not distorted and that the Instrument is
positioned squarely against the mounting panel. Apply pressure to the front
panel bezel only.
Instrument
6
Installation - Wiring Connections
dc Pulse
Line Supply
FIGURE 2-1Rear Terminal Connections
NOTE: Terminals 7 & 8 are dedicated to those units which a dc Pulse output was ordered. If a
single output relay unit was ordered, the relay is wired between pins 9 & 10.
7
2.1MAINS (LINE) SUPPLY
This version of the Instrument will operate on a 96 - 264V AC 50/60Hz
mains (line) supply. The power consumption is approximately 4W.
CAUTION: This equipment is designed for installation in an enclosure
which provides adequate protection against electric shock. Local
regulations regarding electrical installation should be rigidly observed.
Consideration should be given to prevention of access to the power
terminations by unauthorized personnel. Power should be connected via a
two-pole isolating switch (preferably situated near the Instrument) and a 1A
fuse, as shown in Figure 2-2.
FIGURE 2-2Mains (Line) Supply Connections
If the contacts of the relay output(s) are used to carry mains (line) voltage, it
is recommended that the relay contacts mains (line) supply should be
switched and fused in a similar manner but should be separate from the
Instrument mains (line) supply.
2.2LOW VOLTAGE (24V AC/DC) SUPPLY - OPTION
This version of the Instrument will operate on 12 - 24V AC 50/60Hz or 12 30V DC supply . The power consumption is approximately 4W. The
connections are shown in Figure 2-3; these should be made via a two-pole
isolating switch and a 315mA slow-blow (anti-surge Type T) fuse.
8
FIGURE 2-3Low Voltage AC/DC Supply Connections
2.3THERMOCOUPLE INPUT
The correct type of thermocouple extension leadwire or compensating cable
must be used for the full distance between the Instrument and the thermocouple, ensuring that the correct polarity is observed throughout.
NOTE: Do not run the thermocouple cables adjacent to power-carrying
conductors. If the wiring is run in a conduit, use a separate conduit for the
thermocouple wiring. If the thermocouple is grounded, this must be done at
one point only. If the thermocouple extension lead is shielded, the shield
must be grounded at one point only.
2.4RTD INPUTS
The compensating lead should be connected to Terminal 3. For two-wire
RTD inputs, Terminals 2 and 3 should be linked. The extension leads should
be of copper and the resistance of the wires connecting the resistance
element should not exceed 5 ohms per lead (the leads should be of equal
length).
2.5DC INPUTS
DC (mV) inputs are connected to Terminals 2 and 3 in the polarity shown in
Figure 2-1; DC (V) inputs are connected to the same terminals with the
same polarity but require an external attenuator. DC (mA) inputs are connected to Terminals 3 and 4 in the polarity shown in Figure 2-1 with Terminals 2 and 4 linked externally.
2.6RELAY OUTPUTS (OUTPUT 2 & OUTPUT 3)
The contacts are rated at 2A resistive at 120/240V AC.
9
2.7dc PULSE OUTPUT (OUTPUT 1)
This output produces a time-proportioned non-isolated DC signal (0 - 10V
nominal, into 500Ω minimum).
2.8RS485 COMMUNICATIONS
The “A” terminal (Terminal 12) on the Instrument should be connected to
the “A” terminal on the master device; the “B” terminal (Terminal 11) on the
Instrument should be connected to the “B” terminal on the master device.
This instrument uses standard RS485 devices, isolated from all other inputs
and outputs. The devices present a 1/4-unit load to the RS485 line. Generally, termination will not be required but may be necessary for line lengths
greater than 100 metres. Where termination is necessary, it is recommended that a 120Ω resistance in series with a 0.1µF capacitor be used at
each end of the line (see Figure 2-4).
FIGURE 2-4RS485 Line Termination
10
Instrument
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.