ENGINEERING UNITS (C/F)........................................................................................................................................... 10
THERMOCOUPLE TYPE SELECTION: ............................................................................................................................... 12
As Process Limit:...................................................................................................................................................... 13
As Rate Limit:........................................................................................................................................................... 13
SELECTION OF LIMIT 4 AS PROCESS OR DEVIATION LIMIT: ........................................................................................... 13
As Process Limit:...................................................................................................................................................... 13
As Deviation Limit:................................................................................................................................................... 13
EXTERNAL CONTROL RELAY INSTALLATION FOR RAMP/SOAK OPERATION..................................... 17
Figure 3. Solid State relay hookup for controller output......................................................................................... 17
VARIOUS CONTROLLER MODES........................................................................................................................... 17
CONTROLLER RUN MODE............................................................................................................................................. 17
CONTROLLER HOLD MODE .......................................................................................................................................... 17
PROCESS ALARMS.....................................................................................................................................................19
OPEN COLLECTOR OPTION............................................................................................................................................ 20
Figure 5. Open Collector Hookup Example............................................................................................................ 20
HOW TO RESET ELAPSED TIME...................................................................................................................................... 21
HIGH AND LOW PEAKS ............................................................................................................................................ 21
HOW TO RESET HIGH &LOW PEAK READINGS.............................................................................................................. 21
SIGNAL CONNECTION.............................................................................................................................................. 23
(for 220 Vac units only 0.25Amp.@ 240Vac (resistive load))
2 open collector transistors @ 50ma. sink each
ACCURACY:
• Temperature resolution: 1 C/1 F, 0.1C for Thermistor
• 0.1% of Full Scale (Base metal T/C), 0.5% others
ANALOG TO DIGITAL CONVERSION:
• 4 1/2 Digit (20000 count) A/D conversion.
• Dual slope integrating converter.
• Conversion Rate: 7 /sec. typical
POWER REQUIREMENTS:
• 120Vac, 0.2 Amp. @ 60 Hz
DIMENSIONS:
• Case: 7.55"W x 6.29"H x 4.05"D
•
IP65 rated plastic enclosure
• Weight: 2.63 lb. (1.19kg.)
• Enclosure: All Plastic enclosure—IP65 Ingress Protection
DISPLAY:
• Red 7-segment LED display, 0.39 inch (10mm) digit height
• Negative polarity indication
• Out of range indication: HELP
• Display Test: Briefly displays 8.8.8.8.8.8.8. on power up
RELIABILITY:
• Calibration: NIST traceable
• Recalibration: Recommended at 12 months interval
4
Page
DESCRIPTION
The CN1501 series is a highly versatile temperature controller which offers the ease of an ON/OFF
controller combined with the precision of a PID controller. Selectable heat/cool mode allows the unit to be
used for either heating (direct acting) or cooling (reverse acting).
The unit has the capability of accepting five different ramp and soak programs, each one with up to ten
segments. Separate pass-codes are required for selecting or entering a program. This keeps the operators
from making any inadvertent changes. Manual hold feature allows for an indefinite hold any where along the
ramp/soak profile. Also offered is a manual set-point entry mode for a quick 'ramp to set-point' function. This
eliminates entering a complete ramp/soak program.
Maximum and minimum temperature readings are constantly tracked and can be helpful in quality control or
monitoring unattended processes (e.g. overnight).
Various process parameters monitored by the system may be displayed by pushing the appropriate keys on
the front panel, e.g. (Rate, Peak etc.). The respective parameter will be displayed as long as the key is kept
pressed. Alternately, if the key is pressed and then released, the unit will display a particular parameter
briefly and then go back to temperature display mode.
The CN1501 Series supports six outputs: 4 relay outputs for process limits and 2 solid state outputs for
timers. Process limit relays may be operated in two different modes:
1. Non-latching mode, in which the relays reset automatically as soon as the temperature
falls below the limit (minus the relay dead-band).
2. Latching mode, in which the relays stay energized even after the temperature falls below
the programmed limit. In this mode the relays will stay on until manually reset.
THERMOCOUPLE OR RTD SELECTION
CN1501 instruments ordered for Thermocouples or RTD’s can be programmed through the front panel keys
to work with one of these specific inputs (Input type or options depends on Model number ordered).
When CN1501 is first turned on, a ‘display segment test’ is done by briefly displaying 8.8.8.8.8.8.8.,
followed by the software revision number (rEn X.XX) and input signal type.
J (R,S,B, rtd 385, Thermistor, J tC (r, S, B, rtd 385, tHrStor,
Millivolt, Voltage, Current) Lo VoLt, HI VoLt, CurrEnt)
K (rtd 392) Cr.AL tC (rtd 392)
T t tC
E E tC
Factory default thermocouple/RTD selection can be obtained as explained below:
How to Reset and Program Thermocouple Type (or RTD)
A CN1501-TC that is calibrated for a J, K, T, or E type thermocouple or an RTD model may be
programmed for a specific thermocouple, or RTD (385/392) type, by going into SETUP mode (Look under
‘SETUP’). Alternately, a thermocouple/RTD may be selected by turning
in the appropriate key (see Figure 1). This procedure also clears the memory and programs factory default
values for limits, rate time-base etc. Therefore, after performing Power-up reset, various parameters such as
limits, ramp and soak profiles, rate time base etc., must be re-programmed. However, if done in SETUP
Input type Display shows:
On power to the unit while holding
5
Page
mode, no programmed parameters such as limits, ramp & soak profiles etc. are erased from the memory. It is mode, no programmed parameters such as limits, ramp & soak profiles etc. are erased from the memory. It is
recommended that thermocouple (RTD) selection be done in SETUP. Power-up reset should be performed if
it is suspected that program memory may have been corrupted due to power surge, noise on electrical lines
etc.
FIGURE 1. Thermocouple/RTD Selection Keys
Memory Clear only
E t/c
K t/c, RTD392,
T t/c
J (R, S or B) t/c,
RTD385 , Thermistor
KEYInput Type Selected
DATA J (R, S or B , RTD 385)
Thermistor
STOP K (RTD 392)
RUN T
TIMER E
RESET Memory cleared – no
factory default values
. programmed.
NOTE: All keys, except RESET, clear
memory and program necessary factory
default values. RESET key clears memory
only and programs no default values.
However, previous thermocouple type is
retained.
DISPLAY MODES
The CN1501 can be programmed to display in one of the following three modes:
Mode Display Description
PROCESS PrOCESS
SETPOINT SE
PROCESS - SETPOINT P
Setpoint value.
SEE SETUP ON HOW TO SELECT ONE OF THE DISPLAY MODES.
tPt Displays only the setpoint value.
r-StPt Alternately displays Process as well as
Displays only the process value.
RETAINING USER SETTINGS ON POWER DOWN
CN1501 saves all the programmed parameters in an EEPROM (electrically erasable programmable read only
memory). An EEPROM stores the programmed parameters even when the power is removed from the unit.
However, it is important to note that if the parameters are being changed during setup, they must be saved in
the EEPROM by
SETUP. If parameters are
will be lost ( the unit will, however, maintain the old values).
pressing and holding the ‘RESET’ key (till SAVING is displayed) as described under
NOT saved and the power is removed from the unit, any newly changed values
6
Page
FLOW CHART
PROGRAM LIMITS
PROGRAM LIMIT1
PROGRAM LIMIT2
Configure Limit3 as
Process or Rate
PROGRAM LIMIT3
Configure Limit4 as
Process or Deviation
PROGRAM LIMIT4
SETUP
PROGRAM
CONTROLLER
Type of Control ---
PID or ON/OFF
If ON/OFF, Enter
Controller Deadband
If PID Mode, Enter
Proportional Band
If PID Mode, Enter
RESET
If PID Mode,
Enter RATE
VERIFY
SELECT PROG NO.
PROG1, PROG2, ETC.
START SETPT
ENTER SETPT1
ENTER TIME
ENTER SETPT2
Verify
segment 2
thru 9
PROFILE
SELECT PROG NO.
PROG 1, PROG2, ETC
START SETPT
ENTER SETPT1
ENTER TIME
ENTER SETPT2
Program
segment 2
thru 9
Select Timer Modes
0,1 or 2
PROGRAM TIMER1
PROGRAM TIMER2
RELAY DEADBAND
Limit1 Normally open
or closed
Limit2 Normally open
or closed
Limit3 Normally open
or closed
Limit4 Normally open
or closed
DEGREE ‘C’
OR ‘F’
DISPLAY TIME
DISPLAY OPTION
HEAT/COOL
RATE
TIMEBASE
COLD JUNCTION
CALIBRATION
INPUT
CALIBRATION
ENTER SETPT10
ENTER TIME
Back to
SETUP
ENTER SETPT10
ENTER TIME
Back to
SETUP
Limits Latching or
Non-Latching
Audio Alarm ON or
OFF
INPUT
SIGNAL TYPE
Back to
SETUP
Page
7
'RAMP & SOAK PROFILE' SELECTION
CN1501 has the capability of five different ramp and soak profiles. Each
of these programs can have up to ten segments. The desired profile can be
selected by going into SETUP mode and entering the correct pass-code.
To enter setup, push and hold SETUP key till the display starts scrolling
the message 'EnTER PASCOdE'. At this point two different pass-code
options are available. One is to get into ramp/soak or system
programming and the other is
& soak profile. To get into selection mode, enter pass-code '4523' (also
look under SETUP). On accepting the pass-code, the unit will scroll the message 'SELECt PROG nO.'
followed by the indication of active program number. The display format for program number is 'ProG x'
(where x = the program number, which can be from 1 to 5). To select an alternate program, push ‘^ENTv’
key. After making the selection, push RESET key to indicate so. Doing so will also exit program selection
mode.
selection of an already programmed ramp
SETUP MODE
Setup is used for configuring various parameters of CN1501 unit. These
parameters include entering ramp/soak profiles, verifying temperature
profiles, entering limits, timers, dead-bands etc.
Entering and Exiting Setup Mode:
To get into setup mode, press and hold SETUP key. The display will
show ELPSd t and then the value of elapsed time. Keep holding-in ‘SETUP’ key till the display shows
‘SETUP’ and scrolls the message 'EntEr PASSCOdE'.
To return from SETUP to normal display/run mode, simply push and
down the ‘RESET’ key. On exiting, the display will briefly show
'SAVING' to indicate that the new data is being saved in nonvolatile
memory (key should be held in until the word ‘SAVING’ shows up on the
display). Setup mode is also exited automatically if no key action is
detected for about 5 minutes.
How To Increase/Decrease Programmable Values in Setup
Once a parameter is displayed (e.g. 01234), the ‘^Ent v’ key can then be used for increasing or decreasing
the value of the flashing digit. For incrementing, push and
‘^Ent v’ key and immediately push it (and
till the desired digit starts flashing. Again, use ‘^Ent v’ key to change its value.
hold in) again. To move on to the next digit, push ‘<DIG>’ key
hold in ‘^Ent v’ key. To decrement, release
Passcode Entry:
Passcode entry is a four digit number which keeps unauthorized personnel
from changing the unit’s parameters. Front panel keys are each marked
with a small digit in the lower right corner. For the five keys there are five
digits --- 1,2,3,4,5. Pass-code is a combination of these digits and for
CN1501 units, passcode for
pass-code to program
entering the correct pass-code are allowed. Anytime a wrong digit is entered, the display will read HELP. If
correct pass-code is not entered within three attempts, the system will exit SETUP and return to normal
selection of ramp/soak programs is 4523. The
new ramp/soak profiles, limits , controller parameters , etc. is 3254. Three attempts at
hold
8
Page
display mode. To make another attempt, you have to get into setup again by
holding in ‘SETUP’ key.
As soon as correct four digit pass-code is entered, the unit is ready for setup.
At this point the unit will display ‘PrG Ctr’ (for 'Program Controller'). All
the options available for programming at this point are:
The unit starts with 'Program Controller’ as the active mode (displaying PrG Ctr). To select any other
mode, push ‘^Ent v’ key. Once the desired mode is displayed, push ‘SETUP’ key to select it.
‘PROGRAM
’
'PROGRAM CONTROLLER' MODE
Selecting ON/OFF or PID Control
On entering Program Controller mode, the very first step lets you program the type of control i.e. simple
ON/OFF or PID. The display will read ‘Pid Ctr’ (for PID control) or ‘On-OFF’ (for ON/OFF control).
Push ^ENTv key to make alternate selection. Push SETUP key to go to the next step.
NOTE: The next step depends on whether PID or ON/OFF control was selected. If PID mode is selected,
then the next three steps programmed are Proportional band, Reset and Rate. For ON/OFF mode, controller
deadband is programmed.
Entering ON/OFF Variable
On/Off Hysteresis (Dead-Band)
Controller dead-band (hyteresis) determines how tight a control around
setpoint is achieved. A smaller number results in a tighter control. This
function is indicated by the message ‘CntL db’ followed by the value of
previously programmed dead-band. The flashing digit is the active digit.
Pushing ^ENTv key and keeping it pushed, will increment the digit. Releasing ^ENTv key and then
pushing it again will decrement the value (^ENTv key works as a toggle -- alternating between increment
and decrement). To change the next digit, first push the <DIG> key. This will advance the flashing to the
following digit. Use ^ENTv key to change the value. After the desired setting is displayed, push SETUP
key. This will take you to the next step.
NOTE: This step comes up for programming only if the unit is programmed to work as ON/OFF
controller. If not, Rate, Reset and Proportional Band are programmed.
Entering PID Variables
Proportional band
If PID mode is selected, then next parameter to be programmed is the proportional band. Proportional band,
also referred to as gain, determines the output in proportion to the error between setpoint and actual process
temperature. It is based on percent error of 1000 degrees if the display units are Centigrade and 2000 degrees
if units are Fahrenheit (or scaled for voltage/current inputs). For example, if the proportional band is set to
5.0 and the units are Centigrade, then a process error of 50 degrees between setpoint and temperature will
result in an output that will be fully on.To enter a new value for proportional band, use ^ENTv and <DIG>
keys . Once the value has been entered, push SETUP key.
9
Page
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.