CN1500 KEYS AND FUNCTION............................................................................................................................................4
Process Mode...........................................................................................................................................................................5
How to Enter a Typical Process Profile...............................................................................................................................8
Controller Type (On/Off or PID):......................................................................................................................................10
Decimal Point Position.......................................................................................................................................................11
High Scale..........................................................................................................................................................................11
Engineering Units ..............................................................................................................................................................12
Controller type (On/Off or PID):.......................................................................................................................................14
Temperature Units..............................................................................................................................................................14
Engineering Units ..............................................................................................................................................................15
Input Range ( Current and Voltage)......................................................................................................................................16
Voltage Range (0-10vdc)..................................................................................................................................................16
Voltage Range ( Millivolt inputs).....................................................................................................................................17
Current Range....................................................................................................................................................................17
Correct Range Settings.......................................................................................................................................................17
Run Mode...............................................................................................................................................................................19
Hold Mode.............................................................................................................................................................................20
DISPLAYING PROCESS .........................................................................................................................................................21
Data Description ....................................................................................................................................................................22
External Control Relay Installation............................................................................................................................................23
Figure 3. Solid State relay hookup to a controller output......................................................................................................23
ERROR MESSAGES AND SOLUTIONS................................................................................................................................23
POWER .....................................................................................................................................................................................23
Figure 5. REAR VIEW OF CN1500 INSTRUMENT...........................................................................................................24
Typical @ 25 C and rated supply voltage unless otherwise specified.
INPUT TYPE:
i) J,K,T,E,R,S,B, thermistor, RTD
ii) 4-20milliamp loop current
iii) 0-10 vdc
iv) 0-100 millivolt
Cold junction error: +/- 0.5 C (10C to 45C)
Open thermocouple indication: ‘HELP’ displayed
ACCURACY:
Temperature resolution: 1C/1F, 0.1% of Full Scale
Voltage = 0.05% FS
Current = 0.05% FS
ANALOG TO DIGITAL CONVERSION
20,000 count A/D converter
Dual slope inte grating converter.
Conversion rate: Seven conversions/sec (typical)
DISPLAY
Red 7-segment LED display, 0.39 inch (10mm) height
Negative polarity indication
Over-range indication: HELP
Display test: Briefly indicates 8.8.8.8.8.8.8. on power up
SCAN RATE
Two channels per second
Channel display time: programmable from 1 - 999 seconds
PROPORTIONAL BAND: RESET:
0 - 100% of span 0.00 TO 50.00 repeats per minute
3
DESCRIPTION
The CN1500 series is a compact unit that offers the features of up to seven full blown PID controllers
in a single 1/8th DIN (cutout) enclosure. Careful design, high functionality and its compactness allows it
to offer unmatched cost/performance ratio of any controller in its class.
CN1500 series offers PID control for optimum process stability. Additionally, processes that do not
require tight control through complex tuning of PID parameters can be run under simple ON/OFF
control.
Programmable from the front keys, the unit will accept signals from many different types of transducers.
These include thermocouples, thermistors, RTD’s, 4-20ma loop current, 0-10vdc and 0-100mv etc.
(Check Model number for specific input types). Input signal for each zone is selected independently.
Scaling and offset allows current and voltage signals to be converted to engineering units. Additionally,
each zone has its own ramp/soak profile which can be tailored to its specific requirements. ON/OFF as
well as PID parameters (Rate, Reset and Proportional band) for each zone are also independent of each
other.
Each zone can be programmed for either heating or cooling. Setpoint deviation, positive as well as
negative, can be viewed by the push of a key.
The maximum and minimum readings for each zone are also captured. This feature can be helpful in
quality control or as a tool in fine tuning the PID parameters.
Any zone can be put on an indefinite hold anywhere along the process profile. Also, a manual mode for
setpoint entry is available. Using this feature, a setpoint can be entered without going into the program
mode and entering the entire ramp/soak profile for a given zone.
CN1500 KEYS AND FUNCTION
The five CN1500 keys have several functions packed into each key. These Functions are listed below.
* Pushing this key, while scanning, will place the display in a hold mode. The
SCN/HLD
Display will hold on the current display function until the key is pushed again.
RST/EXT
* If the unit is in a display hold mode, push this key to continue scanning
between controllers.
* This key is also used to exit Programming Mode, indicated by the word ‘SAVInG'
being displayed.
4
NOTE: HOLD mode places only the display on hold. Internally, all the enabled channels keep on
scanning and controlling. The HLD led comes on when the unit is placed in a hold mode.
* To select a controller, toggle this key until the unit displays the desired controller
CTR./SEL
* To enter programming mode, push and hold this key, on the desired
PROG
controller to be programmed, until the unit displays 'EntEr PASSCOdE'.
* Toggling this key will sequentially display process value for each controller. DATA
PROCESS
* If a controller is selected (by pushing CTR SEL key) before pushing this key , it will
DATA
SETPT
* This key's function is similar to the above (Process/Data) key except that it displays setpoint instead of process for each controller.
DIG
* In Programming Mode this key is used to select a digit to be increment or decremented.
RUN/STP
* This key functions only after a controller has been selected by pushing CTR. SELkey. It is used for displaying and changing the current status of selected
controller (RUNNING, HOLDING. STOPPED & ENTER SP). * In Programming Mode this key is used to increment or decrement a selected digit or to toggle between selections.
The LEDS on the front indicate the controller status. They are turned on when each controller is in auto
run (automatic ramping) or in manual setpoint entry mode. The HLD led indicates that the display is
being held on any one parameter (e.g. controller number 1's process value).
number.
cause the unit to display the following data for that controller: process value, soak time,
deviation, Min/Max readings and rate of process change.
DISPLAY MODES
The CN1500 can be programmed to display in one of the following modes:
Mode Display Description
PROCESS PrOCESS
SETPOINT SEtPt Displays only the setpoint value for each
controller.
(Only those controllers that are in run/hold mode)
PROCESS - SETPOINT Pr-StPt Displays Process as well as Setpoint Values for
each controller that is running a program.
SEE PROGRAMMING ON HOW TO SELECT ONE OF THE DISPLAY MODES.
PROCESS MODE
Process Display Mode sequentially displays the process value of each controller. Process value is
displayed, regardless of whether the controller is running or not. All the controllers that are enabled will
be displayed. The display time is as setup during programming.
Display only the process value for the controllers.
5
SETPOINT MODE
This mode displays ONLY the setpoint value for those controllers that are running. If NO controller is
running, the unit will scroll the message 'nO CntrL rUnnInG' on the display. Setpoints are displayed
for the programmed amount of display time.
PROCESS-SETPOINT MODE
This mode displays Process as well as Setpoint value for each controller that is in run/hold mode. If no
controller is running a profile, the unit will display only the process reading of the controllers that are
enabled. If any controllers are being run, then their process value is displayed followed by their
setpoint. The display period is as programmed during setup, for example, if display time is 10 seconds,
the process will be displayed for ten seconds, followed by setpoint for ten seconds.
PROGRAMMING MODES
Programming mode is used for configuring various parameters of the unit. This is accomplished by first
selecting the controller that needs to be programmed (by pushing the CTR SEL key), and then holding
in the CTR.SEL (Controller Select) key until the units displays 'EntEr PASSCOdE'. At this point,
pass code for the system can be entered. The entry code is a four digit number which keeps unauthorized
personnel from changing the system parameters. The front panel keys are each marked with a small
digit in the lower right corner. For the five keys there are five digits --- 1,2,3,4,5. The pass-code is a
combination of these digits and for CN1500 systems it is 3254.
If, at any time during programming, it is desired to exit, just push the RESET key twice (and hold it in
till the display reads ‘SAVInG’). First push takes you to the very beginning of the program mode
(display shows 'PrG CTr '), and the second push will exit. Display briefly reads 'SAVING' to indicate
that the data is being saved in nonvolatile memory.
As soon as the correct four digit pass-code is entered, the system is ready for programming. Once in
programming mode, one of the following selections can be made:
Display Description tuninG Enter PID parameters or hysteresis for ON/OFF control
VErIFYVerify a previously entered Ramp/Soak profile .
PrOFILEProgram a Ramp/Soak profile for a controller.
PrG CTrPrG SYSProgram System parameters
TUNING MODE:
Tuning mode is used for entering relay hysteresis (if controller is programmed for ON/OFF mode) or
Rate, Reset and Proportional Band (if the unit is set as a PID controller). This mode is selected in
SETUP mode by pushing PROG key while the unit is displaying 'tUnIng'. After this selection, the
unit will display any one of the following: 'Cntr 1', 'Cntr 2', 'Cntr 3', 'Cntr 4', 'Cntr 5', 'Cntr 6', or
'Cntr 7'. At this time any controller can be selected by pushing key. LED for selected controller
will flash (this provides an easy way to track the controller being programmed). After selecting a
controller, use PROG key to step through programming. To exit, push EXT key.
Program Controller parameters.
6
NOTE:‘TUNING’ mode can also be entered by pushing and holding ‘DATA’ key till the display
reads ‘TuninG’. Once in this mode, any controller can be selected by pushing key. (This procedure
can only be done from normal display mode and not frome SETUP). To exit, push & hold RESET key.
ON/OFF HYSTERESIS (DEAD-BAND)
This step is used for setting up controller deadband or hysteresis and is indicated by the message
‘Cntr db’ followed by the display of current deadband value. The flashing digit is the active digit.
Pushing key and keeping it pushed, will increment the digit. Releasing key and then pushing it
again will decrement the value ( key works as a toggle -- alternating between increment and
decrement). To change the next digit, first push the <DIG> key. This will advance the flashing to the
following digit. Use key to change the value. After the desired setting is displayed, push PROG
key. This will take you to the beginning of setup mode (or Tunning Mode)
NOTE: This step comes up for programming only if the unit is programmed to work as ON/OFF
controller. If not, Rate, Reset and Proportional Band are programmed.
ENTERING PID VARIABLES
PROPORTIONAL BAND
If PID mode is selected, then next parameter to be programmed is the proportional band. Proportional
band, also referred to as gain, determines the output in proportion to the error between setpoint and
actual process temperature. It is based on percent error of 1000 degrees if the display units are
Centigrade and 2000 degrees if units are Fahrenheit (or scaled for voltage/current inputs). For example,
if the proportional band is set to 5.0 and the units are Centigrade, then a process error of 50 degrees
between setpoint and temperature will result in an output that will be fully on.To enter a new value for
proportional band, use and <DIG> keys . Once the value has been entered, push PROG key.
RESET
Parameter programmed after proportional band is Reset. As with other functions, this is indicated by the
display first showing the message followed by current reset value. The message in this case is 'RESET'.
Again, use key in conjunction with <DIG> key to change the value.
Reset is used with proportional band to fine tune the controller. Proportional band alone will bring down
the error between setpoint and process up to a certain point only. To reset the differential left by
proportional band, the error is integrated slowly over time until setpoint and process coincide. This is
done by introducing the reset factor. After programming reset, push PROG key to program RATE.
RATE
Rate is the third factor in the PID control. This factor provides the anticipation for the control as to how
fast or slow process change is being realized. This factor is usually handy at start ups when, generally,
process tends to lag setpoint and a higher output is required. On entering rate mode, the display first
reads 'RAtE' followed by rate value. This value can be change by using and DIG keys.
VERIFY MODE:
The Verify function is used for checking a previously programmed ramp/soak profile. This mode is
selected by pushing PROG key while the unit is displaying 'VE
7
rIFY'. After this selection, the unit
will display one of the following: 'Cntr 1', 'Cntr 2', 'Cntr 3', 'Cntr 4', 'Cntr 5', 'Cntr 6', or 'Cntr 7'.
At this time any one of the controllers can be selected by pushing the key. After selecting a
controller, use PROG key to step through the profile. To exit Verify mode at any time, push EXT key.
Unlike exiting 'ProFILE' mode, exiting VERIFY at any point does not mark the end of a profile.
NOTE: Verify mode should only be used to check or change a previously programmed
parameter. DO NOT USE THIS MODE TO ENTER A NEW PROFILE. TO ENTER A
NEW RAMP/SOAK PROFILE, USE 'PrOFILE' MODE.
NOTE: Before verifying a profile, all Controllers must be in Stopped Mode. If not, the unit will
scroll the message 'StOP rUnnInG'
PROFILE MODE (ENTERING RAMP/SOAK):
This programming mode is used for entering process profile for a selected controller. Once in
programming mode (after entering pass-code), use key until the unit displays PrOFILE (for
ramp/soak ‘Profile’ ). Next, push the PROG key. The unit will display one of the following with each
push on key: CntrL 1, CntrL 2, CntrL 3, CntrL4, CntrL 5, CntrL 6 or CntrL 7). After
selecting the desired controller, push PROG key to select it. A profile can now be programmed in the
following manner:
NOTE: Before programming or checking a programmed profile the Controller Must Be in the
Stopped Mode. If not, the unit will scroll the message "STOP RUNNING'.
HOW TO ENTER A TYPICAL PROCESS PROFILE
Upon entering the process profile mode, the display will briefly read Strt SP (for ‘Start Setpoint’), and
then the current value of Starting setpoint. Use and <DIG > keys to enter a desired value. The
key increments and decrements the FLASHING digit, where as the <DIG> key selects the digit to
increment or decrement. Next, press SETUP key to go on to the next function.
At this point the display will briefly read SetPt 1 and then the current value of Setpoint #1. Use
and <DIG > keys to enter a desired value. Next, press ‘PROG’ key to go to the following function.
The display will now read EntEr t (for ‘Enter time’), and then show the current time value. Time
entered is the time that it takes to ramp to the set point (or soak time, if the previous and current setpoints are same). The value shown for time is in minutes. Use and <DIG > keys to enter the
desired value, and then press PROG key to go on to the next function.
Repeat the above steps to program setpoints #2 thru #7. Once all 7 segments have been programmed,
the display will revert back to beginning of Programming mode selection. If all the seven segments are
not desired, the program can be aborted at any segment by simply pushing the EXT key. The segment in
which the EXT key is pushed is the one that is considered to be the end of the program. During Verify
Program mode, that segment and all the following segments are labeled as ‘PrG End’.
NOTE:DO NOT PUSH 'EXT' KEY IN THE LAST SEGMENT OF YOUR RAMP/SOAK
PROFILE. AFTER ENTERING TIME FOR THE LAST SEGMENT GO TO THE NEXT
SEGMENT
AND THEN HIT THE EXIT KEY. THE UNIT MARKS THE SEGMENT BEING
DISPLAYED AT THE TIME OF PUSHING 'EXT' KEY AS THE END OF PROGRAM.
THEREFORE, MAKE SURE THAT THE UNIT IS IN THE SEGMENT THAT YOU WISH TO
BE CONSIDERED AS THE END OF PROGRAM BEFORE PUSHING 'EXT' KEY.
8
Loading...
+ 20 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.