FEATURES ....................................................................................................................................................... 9
The Function Switch should not be used as the sole means of disconnecting
WARINNG:
To avoid danger of electric shock, unplug from outlet when not in use and before
3
IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT:Read the safety precautions of this booklet carefully before attempting to assemble, install, operate or
maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with instructions could result in personal injury and/or property damage. If you are unsure
about anything regarding your fan or these instructions, please contact Omega Altise on 1300 795 572 in
Australia or (09) 415 6000 in New Zealand before operating your appliance.
• This unit is not intended for use by children or infirm person without supervision.
power. Always unplug the power cord before servicing or moving the appliance.
• The appliance shall be disconnected from its power source during service.
• Always operate the unit from a power source of equal voltage, frequency and rating as indicated on
the product identification plate.
• Always use a power outlet that is grounded.
• The refrigerant loop is sealed. Only a qualified technician should attempt to service.
• The unit is designed only for use with R-290(propane) gas as the designated refrigerant.
• R-290 (propane) is flammable and heavier than air.
• Do not operate with wet hands. Prevent water from spilling onto the unit.
• Do not immerse or expose the unit to rain, moisture or any other liquid.
• Do not leave the unit running unattended. Do not tilt or turn over the unit.
• Do not unplug while the unit is operating.
• Do not use an extension cord or an adapter plug.
• Do not put objects on the unit.
• Do not climb or sit on the unit.
• Do not insert fingers or other objects into the air outlet.
• Do not touch the air inlet or the aluminum fins of the unit.
• Do not operate the unit if it is dropped, damaged or showing signs of product malfunction.
• Do not clean the appliance with any chemicals.
• Ensure the unit is far away from fire, inflammable, or explosive objects.
• The unit shall be installed in accordance with national wiring regulations.
• The appliance shall be stored in a room without continuously operation sources (for example: open
flames, an operating gas appliance or an operating electric heater).
• The appliance shall be stored so as to prevent mechanical damage from occurring.
• Do not piece or burn, even after use.
• Be aware that refrigerants may not contain an odour.
• Pipework shall be protected from physical damage and shall not be installed in an unventilated space, if
that space is smaller than 12 m².
• Keep any required ventilation openings clear of obstruction.
• Any person who is involved with working on or breaking into a refrigerant circuit should hold a current
valid certificate from an industry-accredited assessment authority, which authorizes their competence
to handle refrigerants safely in accordance with an industry, recognized assessment specification.
• Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and
repair requiring the assistance of other skilled personnel shall be carried out under the supervision of
the person competent in the use of flammable refrigerants.
• The appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specified for operation.
cleaning. If the supply cord is damaged, it must be replaced by the manufacturer, its
Service Agent or similarly qualified persons in order to avoid a hazard. In order to avoid
overheating, do not cover the appliance. Do not use the appliance in the immediate
surrounding of a bath, shower or swimming pool.
OMEGA ALTISE
4
IMPORTANT SAFETY INSTRUCTIONS
WARNING: flammable materials
Service indicator, read technical manual
Operator’s manual; operating instructions
• This unit is not intended for use by children (including children) with reduced physical, sensory or
metal capabilities, or lack of experience and knowledge, unless they been given supervision or
instruction. Children being supervised not to play with the appliance.
• Pipework shall be protected from physical damage and shall not be installed in an unventilated
space, if that space is smaller than 9 m².
• WARNING: Do not pierce or burn. Be aware that refrigerants may not contain an odour.
• WANRING: Any person who is involved with working on or breaking into a refrigerant circuit should
hold a current valid certificate from an industry-accredited assessment authority, which authorizes
their competence to handle refrigerants safely in accordance with an industry, recognized
assessment specification.
• WANRING: Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under
the supervision of the person competent in the use of flammable refrigerants.
• The appliance shall be stored in a well-ventilated area where the room size corresponds to the
room area as specified for operation.
• WARNING: Do not use means to accelerate the defrosting process or to clean, other than those
recommended by the manufacture.
• Do not place the appliance less than 50cm of free space around it to allow for proper air
circulation.
• The installation of pipework shall be kept to a minimum. The pipework shall be protected from
physical damage. In case of field charge, the effect on refrigerant charge caused by the different
pipe length has to be quantified.
• The compliance with national gas regulations shall be observed.
• The refrigerant shall only be charged at the manufacturing location or charged on site.
• WARNING: Maximum refrigerant charge 170g of R290.
• Dusts connected to the appliance shall not contain a potential ignition source.
• WARNING: unventilated area where the appliance using flammable refrigerants is installed shall
be so constructed that should any refrigerant leak, it will no stagnate so as to create a fire or explosion
hazard.
• WARNING: The appliance shall be stored in a well-ventilated area where the room size
corresponds to the room area as specified for operation.
• WARNING: The appliance shall be stored in a room without continuously operating open flames
(for example an operating gas appliance) and or other potential ignition sources (for example an
operating electric heater, hot surfaces).
OMEGA ALTISE
5
IMPORTANT SAFETY INSTRUCTIONS
Repair to sealed components
• During repairs to sealed components, all electrical supplies shall be disconnected from the
equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary
to have an electrical supply to equipment during servicing, then a permanently operating form of
leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
• Particular attention shall be paid to the following to ensure that by working on electrical
components, the casing is not altered in such a way that the level of protection is affected. This shall
include damage to cables, excessive number of connections, terminals not made to original
specification, damage to seals, incorrect fitting of glands, etc.
• Ensure that seals or sealing materials have not degraded to the point that they no longer serve
the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in
accordance with the manufacturer’s specifications.
Repair to intrinsically safe components
• Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that
this will not exceed the permissible voltage and current permitted for the equipment in use.
• Intrinsically safe components are the only types that can be worked on while live in the presence
of a flammable atmosphere. The test apparatus shall be at the correct rating.
• Replace components only with parts specified by the manufacturer. Other parts may result in the
ignition of refrigerant in the atmosphere from a leak.
Cabling
• Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental effects.
• The check shall also take into account the effects of aging or continual vibration from sources
such as compressors or fans.
Detection of flammable refrigerants
• Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be
used.
• Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable
refrigerants, the sensitivity may not be adequate, or may need re-calibration.
• Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used.
Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant employed, and the appropriate percentage of gas (25 % maximum) is
confirmed.
• Leak detection fluids are also suitable for use with most refrigerants but the use of detergents
containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the
copper pipework.
• If a leak is suspected, all naked flames shall be removed/extinguished.
• If a leakage of refrigerant is found which requires brazing, all of the refrigerants shall be recovered
from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak.
Removal and evacuation
• When breaking into the refrigerant circuit to make repairs – or for any other purpose –
conventional procedures shall be used. However, for flammable refrigerants it is important that best
practice is followed since flammability is a consideration. The following procedure shall be adhered
to:
OMEGA ALTISE
6
IMPORTANT SAFETY INSTRUCTIONS
• Remove refrigerant.
• Purge the circuit with inert gas (optional for a2l).
• Evacuate (optional for a2l).
• Purge with inert gas (optional for a2l).
• Open the circuit by cutting or brazing.
• The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances
containing flammable refrigerants other than A2L refrigerants, the system shall be purged with
oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This process may need
to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant
systems.
• For appliances containing flammable refrigerants, other than A2L refrigerants, refrigerants purging
shall be achieved by breaking the vacuum in the system with oxygen-free nitrogen and continuing to
fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a
vacuum. This process shall be repeated until no refrigerant is within the system. When the final
oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to
enable work to take place. This operation is absolutely vital if brazing operations on the pipework are
to take place.
• Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and that
ventilation is available.
Charging procedures
• In addition to conventional charging procedures, the following requirements shall be followed:
• Ensure that contamination of different refrigerants does not occur when using charging
equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained
in them.
• Cylinders shall be kept in an appropriate position according to the instructions.
• Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
• Label the system when charging is complete (if not already).
• Extreme care shall be taken not to overfill the refrigerating system.
• Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The
system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test
shall be carried out prior to leaving the site.
Decommissioning
• Before carrying out this procedure, it is essential that the technician is completely familiar with the
equipment and all its detail. It is recommended good practice that all refrigerants are recovered
safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is
required prior to re-use of recovered refrigerant. It is essential that electrical power is available before
the task is commenced.
(a) Become familiar with the equipment and its operation.
(b) Isolate system electrically.
(c) Before attempting the procedure, ensure that:
• Mechanical handling equipment is available, if required, for handling refrigerant cylinders.
• All personal protective equipment is available and being used correctly.
• The recovery process is supervised at all times by a competent person.
• Recovery equipment and cylinders conform to the appropriate standards.
(d) Pump down refrigerant system, if possible.
OMEGA ALTISE
7
IMPORTANT SAFETY INSTRUCTIONS
(e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various
parts of the system.
(f) Make sure that cylinder is situated on the scales before recovery takes place.
(g) Start the recovery machine and operate in accordance with instructions.
(h) Do not overfill cylinders (no more than 80 % volume liquid charge).
(i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
(j) When the cylinders have been filled correctly and the process completed, make sure that the
cylinders and the equipment are removed from site promptly and all isolation valves on the
equipment are closed off.
(k) Recovered refrigerant shall not be charged into another refrigerating system unless it has been
cleaned and checked.
Labelling
• Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.
The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that
there are labels on the equipment stating the equipment contain flammable refrigerant.
• When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely.
Recovery
• When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are employed. Ensure that the correct number of cylinders for holding the total system
charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled
for that refrigerant (i.e., special cylinders for the recovery of refrigerant). Cylinders shall be complete
with pressure-relief valve and associated shut-off valves in good working order. Empty recovery
cylinders are evacuated and, if possible, cooled before recovery occurs.
• The recovery equipment shall be in good working order with a set of instructions concerning the
equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants
including, when applicable, flammable refrigerants. In addition, a set of calibrated weighing scales
shall be available and in good working order. Hoses shall be complete with leak-free disconnect
couplings and in good condition. Before using the recovery machine, check that it is in satisfactory
working order, has been properly maintained and that any associated electrical components are
sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
• The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and
especially not in cylinders.
• If compressors or compressor oils are to be removed, ensure that they have been evacuated to
an acceptable level to make certain that flammable refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only
electric heating to the compressor body shall be employed to accelerate this process. When oil is
drained from a system, it shall be carried out safely.
Warnings for Disposal
Refrigerant used for the air-conditioner are flammable. Therefore when the air-conditioner is scraped,
it shall be kept away from any fire source and be recovered by a special recovering company with
corresponding qualification other than be disposed by combustion, so as to prevent damage to the
environment or any other harm.
OMEGA ALTISE
MAXIMUM SUCTION/EXHAUST
SIDE WORKING PRESSURE
Maximum permissible
pressure side
Heat exchanger maximum
allowable pressure
8
IMPORTANT SAFETY INSTRUCTIONS
Correct Disposal of this product
This marking indicates that this product should not be disposed with other household wastes. To
prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle
it responsibly to promote the sustainable reuse of material resources. To return your used device,
please use the return and collection systems or contact the retailer where the product was
purchased. They can take this product for environmentally safe recycling.
TECHNICAL DETAILS
Model OAPC9W
Fan Speeds 2 settings
Cooling Capacity 9000 Btu/h (2.64 KW)
Cooling Rated Input Power 1.005KW
Cooling Rated Input Current 4.5A
Power Supply 220-240V/50Hz-60Hz
Refrigerant R290 , 170g
IP Code IPX1
0.7MPa/3.2MPa
pressure on the high/low
Sound Power Level
Net Weight 22.5Kg
Dimensions 315x310x698mm
3.2Mpa
3.2Mpa
≤64dB(A)
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.