Pressure / differential pressure transmitter should be installed by
!
professional engineers or qualified technical personnel. The product
specifications and important information provided on the label
should be carefully read before installation and wiring operations.
Pressure / differential pressure transmitter is powered by an
!
external power supply. The power supply circuit should comply with
energy-limiting circuit by relevant standards, and pay attention to the
high voltage circuits that may exist.
The maximum static pressure overload has been stated on the
!
product label, the process maximum pressure should not exceed
the full span of sensor.
When using pressure / differential pressure transmitter in hazardous
!
areas, installation, use and maintenance should also comply with
the operation manual and relevant requirements of national
standards.
Attention please! Disassemble the instruments under the condition
!
of normal atmospheric pressure only.
Differential pressure transmitter is especially suitable for micro
pressure measurement of hydrostatic pressure such as filter and
equipment leakage test and improving accuracy.
For high-temperature steam measuring, cooling water should be preinjected in the condenser filling the tube more than half way. After the
steam pipes are stable, slowly open the shut-off valve to start
measuring.
For high-temperature steam measuring, cooling water should be preinjected into the guided pipe, After the steam pipes are stable, slowly
open the shut-off valve to start measuring.
The pressure tube should be tilted up 45°, the installation location
should be lower than the process pipeline. Isolation tank and multiple
shut-off valves should be used. Cooling liquid should be pre-injected
into the guiding pressure tube. The drain/vent valve should be opened
periodically, clearing the residual gas and liquid in the guiding pressure
tube to ensure accuracy.
The pressure tube should be tilted down 45°, the installation location
should be lower than the process pipeline. Isolation tank and multiple
shut-off valves should be used. Open the drain/vent valve periodically
to clear the residual gas and liquid in the guiding pressure tube to
ensure accuracy.
Page 3
The pressure tube should be tilted up 45°, the installation location
should be lower than the process pipeline. Isolation tank and multiple
shut-off valves should be used. Open the drain/vent valve periodically
to clear the residual gas and liquid in the guiding pressure tube to
ensure accuracy.
For sealed container level measurement, isolation tank and multiple shut-off
valves should be used. Open the drain/vent valve periodically to clear the
residual gas and liquid in the guiding pressure tube to ensure accuracy.
When single flange diaphragm system is used for sealed container
level measurement, Isolation tank and multiple shut-off valves should
be used, open the drain/vent valve periodically, clear the residual gas
and liquid in the guiding pressure tube to ensure accuracy.
!
Pipe mounting bent bracket Plate mounting bent bracket Pipe mounting flat braket
For open container level measurement, media compatibility should be
considered, install on location where the liquid level and temperature
changes stably to improve accuracy.
Picture 1Picture 2
Picture 1: The length of pressure transmitter thread should be longer
than the depth of the thread to ensure the seal of head face gasket is
effective.
Picture 2: The length of pressure transmitter thread should be shorter
than the depth of the thread to ensure the seal of root gasket is
effective.
Page 4
1. Inspect port and fitting to ensure that both are free of contaminants
and excessive burrs and nicks.
2. Apply a stripe of an anaerobic liquid pipe sealant around the male
threads leaving the first two threads uncovered. If no liquid sealant is
available, wrap PTFE tape 1-1/2 turns in a clockwise direction, viewed
from the pipe end, leaving the first two threads uncovered.
Labe l
Brown/1
White/2
3
4
Blue/3
2
1
Black/4
Power supply+ is connected with transmitter terminal 1/brown
1
+
-
13
2
cable.
Signal+ is connected with transmitter terminals 4/black cable.
2
Signal- is connected with power supply-.
3
3: Screw finger tight into the port.
4: Wrench tighten the fitting 1.5 to 3 Turns Past Finger Tight, TPFT.
Consider final orientation position of display, as to not exceed the
recommended TPFT. Total thread engagement should be 3.5 to 6
turns.
Choose gasket according to medium features and temperature range,
pay attention to the bolt balance lock.
It is recommended to use an independent linear direct-current power
supply. Verify that the combined loop resistances (signal cable, display
meter, and other equipment) are not to high, so that the voltage
supplied to the pressure transmitter meets the normal operating
requirements.
Standard current signal output: 12-30VDC.
Using cable with shielded twisted-pair signal has the best effect. To
avoid ground loop, shielded layer adopts single-end grounded.
Transient is effective only in the case of good grounding.
protection
Metal shell and internal grounding terminals are used to the
nearest ground directly.
Range can be adjusted with LCD
buttons. For detailed operation,
please refer to instructions.
Choose gaskets which meet the health standards, to avoid excessive
locking clamp and squeeze gasket and diaphragm and cause
measuring error.
Lab leTwo w ires
1Power +
2
3
4Power -
Please make an adjustment after installation because the
mounting position will affect zero setting.
The vessel is absolutely empty (No pressure or medium on the
measuring diaphragm, the vessel connect to the atmospheric air).
Power connection please refer to LCD function instructionskeyboard shortcuts-PV=0.
Please set PV=0 after three weeks of installation to ensure the
best accuracy.
Set PV=0 each year.
!
Fill the vessel with medium (fill to the required level).
The static pressure value should be within the minimum and the
maximum pressure range.
Power connection please refer to LCD function instructions .
Page 5
Please refer to LCD function instructions.
Requi res no ma int ena nce .
Please notice the following when cleaning:
Use washing agent which will not damage the instruments.
Prevent the process diaphragm from mechanical damage, eg: the
mechanical damage caused by sharp objects.
Mechanical cleaning of metal diaphragm is prohibited.
Do not point the nozzles to the diaphragm directly when doing
internal cleaning by pressure washer.
Do not store outside.
Keep dry and dust-free.
Do not expose to the corrosive medium.
Avoid solar radiation.
Avoid mechanical shock and vibration.
Storage temperature: -40-85℃.
Maximum relative humidity: 95%.
This pressure transmitter conforms to 2014/30/EU EMC standard and bears
the CE mark.
Users need to ensure that all equipment conform to all the applicable
standards.
Remove all media from surfaces of the pressure transmitter.
Always refer safety data sheet for proper personal protection
equipment when handling dangerous medium!
Please adopt proper package to avoid damage in transportation.
The instrument is not restrained by WEEE instruction 2002/96/EG
and laws of relevant countries.
Please pass the instrument to specialized recycling companies
other than local recycling points.
Page 6
Prior to commissioning, use the display module to setup all the parameters according to the site configuration.
The display module of products with LCD can be viewed
through the lenses.
Adjustments to operating parameters can be done by removing
the protective cover. When commissioning is complete, replace
cover, taking care not to cross thread, and tighten snugly by
hand.
For ex ample , fa ctory settin g param eters ; press ure range -10- 10 0kPa, d ispla y unit mA, operate in the atm osphe re.
Set PV=0
Measuring
Interface
5.557
mAmA
ZS
+
Press at the same
time at least 5 seconds
Successful
interface
5.557
PV=0
Release at
the same time
ZS
+
4mA re-range w ith pr ess ure
Measuring
Interface
5.457
mAmA
Z
Press first, then press ,
then press + at the same
time at least 5 seconds
Z
M
M
Z
M
Successful
interface
Release + at
the same time
5.457
4mA OK
Finish
interface
5.457
mA
Finish
interface
4.000
mA
20mA re-r ang e wit h pressur e
Press first, then press m,
Measuring
Interface
then press + at the same
time for at least 5 seconds
5.457
mAmA
Facto ry re set
Me tho d 1:
Measuring
Interface
S
Press more
than 5 seconds
5.457
mAmA
Me tho d 2:
Measuring
Interface
Power off
5.457
mAmA
S
M
S
Successful
interface
5.457
RECOVERY
Successful
interface
5.457
20mA O K
S
Release ,then
Z
press more
than 2 seconds
Z
Press . Then power
on and wait about 5
seconds
Release + at
the same time
Successful
interface
Successful
interface
M
S
Release
Processing
Release
Processing
Finish
interface
20.000
mA
Finish
Z
interface
5.457
mA OK
Finish
Z
interface
5.457
mA OK
Page 7
Measuring Interface
Measuring
Interface
5.457
mA
M
Confirm and enter the next menu
%
Percenta ge
PV
Process vari able
mA
Current
Current parameters
mAD I SP
M
Confirm and enter the next menu
Current parameters
kPaU
M
Confirm and enter the next menu
Current parameters
-10.00
LRV
M
Confirm and enter the next menu
Current parameters
100.00
UR V
M
Confirm and enter the next menu
Z
Enter settings
Z
Enter settings
Z
Enter settings
Z
Enter settings
Set parameters
SET
mAD IS P
Set parameters
SET
U
kPa
confirm and choose the next parameter
Display modified
parameters
-10.00
LRV
Z
confirm and choose the next parameter
Display modified
parameters
100.00
UR V
Z
确认参数
S
Modify parameters
S
Modify parameters
S
Modify parameters
S
Modify parameters
Display modified
parameters
SET
D I SP
Display modified
parameters
SET
M aP
U
Display modified
parameters
-10.01
LRV
Display modified
parameters
100.01
UR V
Z
%
S
kPa
M a
P
bar
psi
mmHg
mmH2O
mH2O
inH2O
ftH2O
inHg
mHg
TORR
mbar
g/cm2
kg/cm2
Pa
ATM
mm
m
-19 999-99 999
-19 999-99 999
Z
confirm and choose the next parameter
Current parameters
0.0100
DA MP S
M
Confirm and enter the next menu
mA L IN ER
M
Confirm and enter the next menu
Current parameters
Z
Enter settings
Z
Enter settings
Z
Enter settings
Display modified
parameters
S
Modify parameters
0.0100
DA MP S
Set parameters
SETSET
mA L IN ER
Set parameters
S
Modify parameters
S
Modify parameters
Display modified
parameters
0.0101
DA MP S
Display modified
parameters
mA
SETSET
ALARM NO ALARM NO ALARM H
M
Confirm and enter the next menu
Z
confirm and output calibration current
Current parameters
Z
Enter settings
FIX\ C NOFIX\ C NO
M
Exit and back to measuring interface
Set parameters
SET
S
Modify parameters
3.8000
FIX\ C
mA
0-1 00S
LINER
NO Non e
H . 20 8 mA
L 3 8 mA .
NO (n one )
3.8 000 mA
4.0 000 mA
8.0 000 mA
12. 000 mA
16. 000 mA
20. 000 mA
20. 800 mA
Squar root
Linearity
Page 8
Disp lay hidden menus
Current
parameters
5.457
m A
Shut off power. Wait
one second. Press
and then power on
M
Running
interface
Successful
interface
Re le ase
M
Fin ish
int er fa ce
5.457
CLK WAIT
Z
Confirm and enter the next menu
m A
Current
parameters
1.0000
DE NSITY
M
Conf ir m and e nt er th e ne xt menu
Current
parameters
1.0000
HE IG HT m
Current
parameters
1.0000
PITO T K
M
Conf ir m and e nt er the ne xt menu
Z
Enter settings
Z
Enter settings
Z
Enter settings
1.0000
DE NSITY
Display selected
parameters
1.0000
HE IG HT m
Display modified
parameters
1.0000
PITO T K
S
Modify parameters
Z
Confirm and enter the next menu
S
Modify parameters
Z
Confirm and enter the next menu
S
Modify parameters
Z
Confirm and enter the next menu
Display modified
parameters
1.0001
DE NSITY
Display modified
parameters
1.0001
HE IG HT m
Display modified
parameters
1.0001
PITO T K
0 0 001-9 9999.
0 0 001-9 9999.
0 0 001-99 999.
Current
parameters
10.000
CUTOF F %
M
Conf ir m and e nt er the ne xt menu
Current
parameters
GAUGE
M
Conf ir m and e nt er the ne xt menu
Z
Enter settings
Z
Enter settings
Display modified
parameters
10.000
CUTOF F %
Set parameters
S
Modify parameters
S
Modify parameters
10.001
CUTOF F %
SETSET
GAUGE
Display modified
parameters
Display modified
parameters
ABSOLUTE
0-9 9.999
GAUGE
gauge,
differential
ABSOLUTE absolute
pressure
Page 9