PRINCIPLE OF OPERATION
he transducer is a force balance device in which a coil is suspended in the field of a magnet by a flexure. Current flowing
T
through the coil generates axial movement of the coil and flexure. The flexure moves against the end of a nozzle, and creates
a back pressure in the nozzle by restricting air flow. This back pressure acts as a pilot pressure to an integral booster relay.
Consequently, as the input signal increases (or decreases, for reverse acting), output pressure increases proportionally.
Zero and span are calibrated by turning easily accessible adjusting screws on the front face of the unit. The zero adjustment
causes the nozzle to move relative to the flexure. The span adjustment is a potentiometer that limits the flow of current
through the coil. A thermistor circuit in series with the coil provides temperature compensation.
MOUNTING
The transducer can be mounted at any angle, but should be
calibrated after mounting. For maximum output pressure
stability, it should be mounted vertically in a vibration free
location or such that the vibration is isolated to the X and Z
axis as shown in
Pipe: Due to its light weight , the transducer may be sup-
ported by the piping used for the supply and output.
Panel: (with access to rear of panel) Attach transducer
(See Fig. 3), to panel using two 10-32 screws and two
threaded mounting holes on the back of the unit.
Figure 3.
A
Panel: (with no access to rear of panel) Attach bracket
(
see Fig 1 and 3), to transducer using two 10-32 screws
on the back of the unit and mount bracket to panel using
four 8-32 screws.
AIR CONNECTIONS
•Supply Air must be instrument quality air regulated
between the minumum and maximum specified on the
nameplate of the transducer.
•Instrument quality air consists of :
a A dew point less than 35˚F
b No particles larger than three microns
c Maximum oil content of 1 ppm
•All unused ports must be plugged.
Supply: Connect supply to the1/4" NPT ports marked “IN” on the base of the transducer. Avoid getting pipe sealant inside
the piping or transducer.
Output: Connect output to the 1/4" NPT ports marked “OUT” on the base of the transducer. The pipe plugs may be removed
from the two auxiliary output ports for a pressure gauge or as an alternative output port.
Figure 1
3
Page 4
A
M4110/0519 IP211, EP211 SERIES
RODUCT CERTIFICATIONS
P
FACTORY MUTUAL
INTRINSIC SAFETY: The (I/P Models I/P211-X15-ISF and I/P211-X27-ISF) transducers are rated intrinsically safe by FM for:
- CLASS I, DIVISION 1, GROUPS A,B,C,D T6, Ta=40˚C HAZARDOUS LOCATIONS when installed in accordance with
interconnection drawing 990-440-000, and the specific barrier models.
NOTICE: The above ratings only apply when installed per Interconnection Diagram 990-440-000
- Nonincendive for CLASS I, DIVISION II, GROUPS A, B, C, D.
ANADIAN STANDARDS ASSOCIATION
C
INTRINSIC SAFETY:
The I/P (I/P211-X15-ISC and I/P211-X15-ISC) are rated intrinsically safe by CSA for: Class I Groups A,
B, C, and D; Class II Groups E, F, and G; and Class III, when connected through certified diode safety barriers in accor-
dance with Interconnection diagram, 990-440-000
ELECTRICAL CONNECTIONS
PRECAUTIONS TO BE OBSERVED DURING INSTALLATION
The Transducers were tested at the EMC Test Centre, Dunfermline, Fife, KY11 5LB to the Electromagnetic
Compatibility Directive effective January 1, 1996. The relevant EMC specifications tested were the following: EN
50081-1 (1992) and EN 50082-1 (1992). A Technical Construction File, Serial #107 was written and Certificate of
Conformity issued by a Competent Body.
EN 50081-1 (1992): Test results confirmed that no precautions need to be observed during installation regarding electromagnetic emissions from the I/P & E/P 211 Transducers.
EN 50082-1 (1992): The following precautions should be taken during installation to maintain the advertised accuracy
specifications for the Transducers. The input wiring to the transducer should be isolated from other high voltage transient
wiring. The momentary switching on and off of nearby relays, motors, or other high capacitive or inductive loads can have a
minor effect on the terminal based linearity specification (1.0% of span, standard range models). Any change in output
pressure is minimal and momentary, and is considered to be within its performance capabilities. Use of a ferrite bead collar on
the input wires entering the transducer is recommended should installation next to high electromagnetic interference be
necessary.
Connect electrical signal to the wires exiting from the side of transducer through the 1/2" NPT conduit fitting.
For DIRECT ACTING: (where increasing the input signal increases output pressure), connect the positive input signal to the
black transducer lead, and the negative to the white transducer lead.
For REVERSE ACTING: (where increasing the input signal decreases output pressure), connect the positive input signal to the white transducer lead, and the negative to the black transducer lead. Agency Approved Models may also be operated in either
mode.
4
Page 5
4110/ IP211, EP211 SERIES0519
M
ALIBRATION
C
Once the transducer has been mounted, and air supply connections finished, the unit’s calibration must be checked before
placing into service.
Note: input percentage refers to the following examples:
If 4 to 20 mAIf 0 to 10 VDCIf 0 to 5 VDCIf 1 to 5 VDC
1. Apply the 0% input signal to unit and adjust the “Zero” adjusting screw to the low setpoint output. Turn screw counterclockwise to increase output. If there is no change in output, keep turning adjustment screw counter-clockwise until
output begins to rise. It is imperative that the output pressure be closely monitored as turning the zero screw excessively could damage the flexure.
2. Apply the 100% signal to unit and adjust “Span” adjusting screw until output is at the high setpoint.
3.
IMPORTANT: On I/P (Current) input models, turn the “Span” adjusting screw counter-clockwise to increase output. On
E/P (Voltage) input models, turn the “Span” adjusting screw clockwise to increase the output pressure.
4. Repeat steps 1& 2 until unit is calibrated.
Reverse Acting
1. Apply the 0% input signal to unit and adjust "Zero" adjusting screw until output reaches the high output pressure set-
point. Turn counter-clockwise to increase.
2. Apply the 100% input signal to unit and adjust "Span" adjustment until output pressure is at the low setpoint.
IMPORTANT: On I/P (Current) input models, turn the “Span” adjusting screw clockwise to increase output. On E/P
(Voltage) input models, turn the “Span” adjusting screw counter-clockwise to increase the output pressure.
3. Repeat steps 1& 2 until unit is calibrated.
5
Page 6
A
M4110/0519 IP211, EP211 SERIES
FIGURE 2
BLACK
WHITE
E / P SCHEMATIC
121 Ω
RV1
R1
100 Ω @ 25°C
J2
COIL
300 Ω
J1
BLACK
WHITE
I / P SCHEMATIC
RV1
100 @ 25°CΩ
68 Ω
R1
121 Ω
R2
RT1
J2
J1
COIL
300 Ω
SIGNAL IMPEDANCE
The input impedance will vary depending upon the potentiometer setting of the “SPAN (RV1)”, (SEE FIG. 2). The I/P circuit design
consists of a resistor and potentiometer in parallel with the coil/flexure. The E/P circuit utilizes a potentiometer in series with the
coil/flexure. The following are some of the nominal impedences that would be measured across the signal leads of the average
calibrated transducer. These values are helpful when determining power requirements and for trouble-shooting.
Transducer remains at start up no
matter the input signal3.
4110/ IP211, EP211 SERIES0519
M
) Plugged or blocked orifice.
1
2) Supply pressure too low.
1) Zero set too low.
2) Electrical connection has opened or
wrong type of signal applied.
A
1) Remove orifice screw and clean
orifice with wire or pin <0.009"
diameter
2) Supply pressure must be at least 5
PSIG above the 100% output.
1) Turn zero adjustment counter-
clockwise until output pressure
increases then follow calibration
procedure.
2) Check electrical connections to
insure that there is a correct input
signal reaching the transducer.
Transducer works in reverse.
(Pressure goes down when input
signal goes up.)
Output Pressure same as supply
Pressure with no signal effect.
Wires connected in reverse
Pneumatic connections reversed or
supply and output both connected to
“IN” ports.
Insure wiring is connected per Electrical
Connection section.
Insure supply is connected to port
marked “IN” and output is connected to
port marked “OUT”.
Note: If you experience an unusual problem that is not described in this section, or if troubleshooting procedures will not
restore the unit to normal operation, please contact Omega.
7
Page 8
A
M4110/0519 IP211, EP211 SERIES
Figure 3
8
Page 9
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from
date of purchase. OMEGA's WARRANTY adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA's customers receive maximum coverage on each
product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA's Customer Service Department will issue an
Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to
be defective, it will be repaired or replaced at no charge. OMEGA's WARRANTY does not apply to defects resulting from any
action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper
repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows
evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper
specification; misapplication; misuse or other operating conditions outside of OMEGA's control. Components in which wear is not
warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes
responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products
in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts
manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL
IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are
exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is
based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10
CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any
Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way,
OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will
indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in
such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY
PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA'S
CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be
marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the
following information available BEFORE contacting
OMEGA:
1. P urchase Order number under which the product
was PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords
our customers the latest in technology and engineering.
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the
prior written consent of OMEGA ENGINEERING, INC.
FOR NON-WARRANTY REPAIRS, consult OMEGA for
current repair charges. Have the following information
available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST
of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems
relative to the product.
Communications-Based Acquisition Systems
Data Logging Systems
Wireless Sensors, Transmitters, & Receivers
Signal Conditioners
Data Acquisition Software
HEATERS
Heating CableCartridge & Strip HeatersImmersion & Band HeatersFlexible HeatersLaboratory Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
Metering & Control InstrumentationRefractometersPumps & TubingAir, Soil & Water MonitorsIndustrial Water & Wastewater TreatmentpH, Conductivity & Dissolved Oxygen Instruments
M4110/0519
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.