1
For Temp. Units
8 DIN Dual Display, Temperature, Process and Strain PID Controllers
TM
CNi8D Series
FM
APPROVED
U Embedded Ethernet
Connectivity (Optional)
U Dual Display with Bright
Color-Changing Feature
U Programmable
Digital Filter
U 2 Control or Alarm
Outputs (Choice of DC Pulse, Solid State Relays, Mechanical Relays, Analog Voltage and Current)
U Full Autotune PID Control U Built-In Excitation
U Front Removable
The OMEGATM CNi8DH and CNi8DV are high-quality, highly accurate single loop autotune PID temperature and process controllers for 1⁄8 DIN (92 x 45 mm) horizontal or vertical panel cutouts. Both devices feature the same state-of­the-art technology, uncompromising accuracy, and quality backed by an extended 5-year warranty.
The CNi8DH and CNi8DV are simple to configure and use, while providing tremendous versatility and a wealth of powerful features.
The CNi8DH and CNi8DV come standard with your choice of 2 control or alarm outputs in almost any combination: solid state relays rated at 0.5 A @ 120/240 Vac; Form “C” SPDT relays rated at 3 A @ 120/240 Vac; pulsed 10 Vdc output for use with an external SSR; or analog output (0 to 10 Vdc or 0 to 20 mA) selectable for control or retransmission of the process value.
CNi8DH33, shown smaller than actual size.
The universal temperature and process instrument (CNi8 models) offer a selection of 10 thermocouple types as well as 2-, 3- or 4-wire RTDs, process voltage and current. The CNi8DH and CNi8DV are ideal controllers for use with transmitters and amplified transducers. Built-in excitation is standard (24 Vdc @ 25 mA). The units handle 0 to 20 mA process current and process voltage in 3 scales: 0 to 100 mV, 0 to 1V, and 0 to 10V.
As with all iSeries devices, the process value display can be programmed to change color between GREEN,
AMBER, and RED at any setpoint
or alarm point. The LEDs displaying the process value on the CNi8DH (horizontal digits of any 1⁄8 DIN controller.
The strain/process instrument (model iS) meters and controllers measure inputs from load cells, pressure transducers, and most any strain gage sensor. Input ranges include 0 to 100 mVdc; -100 mVdc to 1 Vdc; 0 to 10 Vdc in addition to 0 to 20 mA. Excitation for transducers of 5 V and 10 V is standard.
The highly recommended networking and communications options include direct Ethernet LAN connectivity with an embedded Web server, and serial communications. The C24 serial communications option includes both RS232 and RS485 which can be selected from the menu as well as both a
1
8 DIN) are the largest
CNiS8DV33, shown
smaller than actual size.
straightforward ASCII protocol. The C4EIT option includes Ethernet and RS485 ASCII on 1 device.
The iSeries, with the network options, are designed for easy integration with popular industrial automation and control programs as well as Microsoft Visual Basic and Excel®. OMEGA provides free configuration software which makes it fast and easy to get up and running with many applications. Available for download off the Internet.
TM
®
at any
setpoint
Totally Programmable Color Displays
PATENTED
1
17.78 (0.700)
109.86 (4.325)
The i/8 Series controllers feature plug/removable
connectors and a sturdy panel mounting sleeve with
adjustable thumb nuts for easy secure installation.
Dimensions: mm (inch)
22.9 (0.90)
104 (4.10)
Options Ordering
Suffix Description
-AL Limit alarm version (alarms only,
no PID control)
-SM Simplified menu (on/off control or
alarms, no PID)
*2
*3
Network Options
-EIT Ethernet with embedded
Web server
-C24 Isolated RS232 and RS485/422,
300 to 19.2 Kb*
-C4EIT
Ethernet with embedded Web server + isolated RS485/422 hub for up to 31 devices*
1
1
Power Supply
Standard power input:
90 to 240 Vac, 50 to 400 Hz (no entry required)
-DC 20 to 36 Vdc, 24 Vac*
1
Factory Setup
-FS Factory setup and configuration Software (Requires Network Option) Omega-Enterprise- Logging/Alarming/Monitoring with
Gateway Integration Capabilities
*1“-DC”, “-C24”, and “-C4EIT” not available with excitation. *2 Analog output is not available with “-AL” units. *3“-SM” option not available on CNiS strain models.
To Order
Model No. Output 1 Output 2 Dual Display Horizontal with 2 Control Outputs CNi8DH33 Relay Relay CNi8DH34 Relay DC pulse CNi8DH44 DC pulse DC pulse CNi8DH43 DC pulse Relay CNi8DH42 DC pulse 0.5 A SSR CNi8DH22 0.5 A SSR 0.5 A SSR CNi8DH23 0.5 A SSR Relay CNi8DH24 0.5 A SSR DC pulse CNi8DH53 Analog Relay CNi8DH54 Analog DC pulse CNi8DH52 Analog 0.5 A SSR Dual Display Vertical with 2 Control Outputs CNi8DV33 Relay Relay CNi8DV34 Relay DC pulse CNi8DV44 DC pulse DC pulse CNi8DV43 DC pulse Relay CNi8DV42 DC pulse 0.5 A SSR CNi8DV22 0.5 A SSR 0.5 A SSR CNi8DV23 0.5 A SSR Relay CNi8DV24 0.5 A SSR DC pulse CNi8DV53 Analog Relay CNi8DV54 Analog DC pulse CNi8DV52 Analog 0.5 A SSR
Strain/Process Input, Dual Display Horizontal with 2 Control Outputs
CNiS8DH33 Relay Relay CNiS8DH44 DC pulse DC pulse CNiS8DH43 DC pulse Relay CNiS8DH42 DC pulse 0.5 A SSR CNiS8DH22 0.5 A SSR 0.5 A SSR CNiS8DH23 0.5 A SSR Relay CNiS8DH24 0.5 A SSR DC pulse CNiS8DH53 Analog Relay CNiS8DH54 Analog DC pulse CNiS8DH52 Analog 0.5 A SSR
Strain/Process Input, Dual Display Vertical with 2 Control Outputs
CNiS8DV33 Relay Relay CNiS8DV44 DC pulse DC pulse CNiS8DV43 DC pulse Relay CNiS8DV42 DC pulse 0.5 A SSR CNiS8DV22 0.5 A SSR 0.5 A SSR CNiS8DV23 0.5 A SSR Relay CNiS8DV24 0.5 A SSR DC pulse CNiS8DV53 Analog Relay CNiS8DV54 Analog DC pulse CNiS8DV52 Analog 0.5 A SSR
Comes with complete operator’s manual. Ordering Examples: CNi8DH43, horizontal
pulse control and relay. CNi8DV53, with analogue output and relay. CNiS8DH22, horizontal controller with 2 SSR outputs.
1
1
8 DIN dual display with
8 DIN dual display vertical controller
1
8 DIN dual display
2
TM
Common Specifications
Universal Temperature and Process Input (DPi/CNi Models)
Accuracy: ±0.5°C temp; 0.03% rdg Resolution: 1°/0.1°; 10 µV process Temperature Stability: RTD: 0.04°C/°C TC @ 25°C (77°F): 0.05°C/°C
Cold Junction Compensation Process: 50 ppm/°C NMRR: 60 dB CMRR: 120 dB A/D Conversion: Dual slope Reading Rate: 3 samples/s Digital Filter: Programmable Display: 4-digit 9-segment LED
10.2 mm (0.40"); i32, i16, i16D, i8DV 21 mm (0.83"); i8 10.2 mm (0.40") and 21 mm (0.83"); i8DH RED, GREEN, and AMBER programmable colors for process variable, setpoint and temperature units
Input Types: Thermocouple, RTD, analog voltage, analog current
Thermocouple Lead Resistance: 100 Ω max
Thermocouple Types (ITS 90):
J, K, T, E, R, S, B, C, N, L (J DIN) RTD Input (ITS 68): 100/500/1000 Ω
Pt sensor, 2-, 3- or 4-wire; 0.00385 or
0.00392 curve Voltage Input: 0 to 100 mV, 0 to 1V,
0 to 10 Vdc Input Impedance: 10 MΩ for 100 mV 1 MΩ for 1 or 10 Vdc
Current Input: 0 to 20 mA (5 Ω load) Configuration: Single-ended Polarity: Unipolar Step Response: 0.7 sec for 99.9% Decimal Selection:
Temperature: None, 0.1 Process: None, 0.1, 0.01 or 0.001
Setpoint Adjustment:
-1999 to 9999 counts Span Adjustment:
0.001 to 9999 counts
Offset Adjustment: -1999 to 9999
Excitation (Not Included with Communication): 24 Vdc @ 25 mA
(not available for low-power option)
Universal Strain and Process Input (DPiS/CNiS Models)
Accuracy: 0.03% reading Resolution: 10/1µV Temperature Stability: 50 ppm/°C NMRR: 60 dB CMRR: 120 dB A/D Conversion: Dual slope Reading Rate: 3 samples/s Digital Filter: Programmable Input Types: Analog voltage and current Voltage Input: 0 to 100 mVdc,
-100 mVdc to 1 Vdc, 0 to 10 Vdc
Input Impedance: 10 MΩ for 100 mV; 1 MΩ for 1V or 10 Vdc
Current Input: 0 to 20 mA (5 Ω load) Linearization Points: Up to 10 Configuration: Single-ended Polarity: Unipolar Step Response: 0.7 sec for 99.9% Decimal Selection: None, 0.1, 0.01
or 0.001 Setpoint Adjustment:
-1999 to 9999 counts
Span Adjustment: 0.001 to 9999 counts Offset Adjustment: -1999 to 9999 Excitation (Optional In Place Of
Communication): 5 Vdc @ 40 mA;
10 Vdc @ 60 mA
Control
Action: Reverse (heat) or direct (cool) Modes: Time and amplitude proportional
control; selectable manual or auto PID, proportional, proportional with integral, proportional with derivative and anti-reset Windup, and on/off
Rate: 0 to 399.9 s Reset: 0 to 3999 s Cycle Time: 1 to 199 s; set to 0 for on/off Gain: 0.5 to 100% of span; setpoints 1 or 2 Damping: 0000 to 0008 Soak: 00.00 to 99.59 (HH:MM), or OFF Ramp to Setpoint:
00.00 to 99.59 (HH:MM), or OFF Auto Tune: Operator initiated from
front panel
Control Output 1 and 2
Relay: 250 Vac or 30 Vdc @ 3 A (resistive
load); configurable for on/off, PID and ramp and soak
Output 1: SPDT, can be configured as alarm 1 output
Output 2: SPDT, can be configured as alarm 2 output
SSR: 20 to 265 Vac @ 0.05 to 0.5 A (resistive load); continuous
DC Pulse: Non-isolated; 10 Vdc @ 20 mA Analog Output (Output 1 Only):
Non-isolated, proportional 0 to 10 Vdc or 0 to 20 mA; 500 Ω max
Output 3 Retransmission: Isolated Analog Voltage and Current
Current: 10 V max @ 20 mA output Voltage: 20 mA max for 0 to 10 V output
Network and Communications
Ethernet: Standards compliance
IEEE 802.3 10 Base-T Supported Protocols:
TCP/IP, ARP, HTTPGET RS232/RS422/RS485: Selectable from
menu; both ASCII and MODBUS protocol selectable from menu; programmable 300 to 19.2 Kb; complete programmable setup capability; program to transmit current display, alarm status, min/max, actual measured input value and status
(All
i/8, i/16, i/32 DIN)
RS485: Addressable from 0 to 199 Connection: Screw terminals
Alarm 1 and 2 (Programmable)
Type: Same as output 1 and 2 Operation: High/low, above/below,
band, latch/unlatch, normally open/ normally closed and process/deviation; front panel configurations
Analog Output (Programmable):
Non-isolated, retransmission 0 to 10 Vdc or 0 to 20 mA, 500 Ω max (output 1 only); accuracy is ± 1% of FS when following conditions are satisfied: input is not scaled below 1% of input FS, analog output is not scaled below 3% of output FS
General
Power: 90 to 240 Vac ±10%, 50 to 400
*, 110 to 300 Vdc, equivalent voltage
Hz Low Voltage Power Option: 24 Vac
12 to 36 Vdc for DPi/CNi/DPiS/CNiS; 20 to 36 Vdc for dual display, ethernet and isolated analog output from qualified safety approved source
**,
Isolation
Power to Input/Output: 2300 Vac
per 1 minute test For Low Voltage Power Option: 1500 Vac per 1 minute test Power to Relay/SSR Output: 2300 Vac per 1 minute test Relay/SSR to Relay/SSR Output: 2300 Vac per 1 minute test RS232/485 to Input/Output: 500 Vac per 1 minute test Environmental Conditions: All Models: 0 to 55°C (32 to 131°F) 90% RH non-condensing Dual Display Models: 0 to 50°C (32 to 122°F), 90% RH non-condensing (for UL only) Protection: DPi/CNi/DPiS/CNiS32,16,16D, 8C:
NEMA 4X/Type 4 (IP65) front bezel DPi/CNi/DPiS/CNiS8, 8DH, 8DV: NEMA 1/Type 1 front bezel Approvals: UL, C-UL, CE per 2014/35/EU, FM (temperature units only)
Dimensions i/8 Series: 48 H x 96 W x 127 mm D
(1.89 x 3.78 x 5") i/16 Series: 48 H x 48 W x 127 mm D (1.89 x 1.89 x 5") i/32 Series: 25.4 H x 48 W x 127 mm D (1.0 x 1.89 x 5")
Panel Cutout i/8 Series: 45 H x 92 mm W
(1.772 x 3.622"), i/16 Series: 45 mm (1.772") square,
1
16 DIN i/32 Series: 22.5 H x 45 mm W (0.886 x 1.772"),
Weight i/8 Series: 295 g (0.65 lb)
i/16 Series: 159 g (0.35 lb) i/32 Series: 127 g (0.28 lb)
No CE compliance above 60 Hz.
* ** Units can be powered safely with 24 Vac
power, but no certification for CE/UL are claimed.