1
⁄8 DIN Dual Display,
Temperature, Process
and Strain PID Controllers
TM
CNi8D Series
FM
APPROVED
U Embedded Ethernet
Connectivity (Optional)
U Dual Display with Bright
Color-Changing Feature
U Programmable
Digital Filter
U 2 Control or Alarm
Outputs (Choice of DC
Pulse, Solid State
Relays, Mechanical
Relays, Analog Voltage
and Current)
U Full Autotune PID Control
U Built-In Excitation
U Front Removable
The OMEGATM CNi8DH and
CNi8DV are high-quality, highly
accurate single loop autotune PID
temperature and process controllers
for 1⁄8 DIN (92 x 45 mm) horizontal
or vertical panel cutouts. Both
devices feature the same state-ofthe-art technology, uncompromising
accuracy, and quality backed by an
extended 5-year warranty.
The CNi8DH and CNi8DV are
simple to configure and use, while
providing tremendous versatility and
a wealth of powerful features.
The CNi8DH and CNi8DV come
standard with your choice of
2 control or alarm outputs in almost
any combination: solid state relays
rated at 0.5 A @ 120/240 Vac;
Form “C” SPDT relays rated at
3 A @ 120/240 Vac; pulsed 10 Vdc
output for use with an external SSR;
or analog output (0 to 10 Vdc or
0 to 20 mA) selectable for control or
retransmission of the process value.
CNi8DH33, shown smaller than actual size.
The universal temperature and
process instrument (CNi8 models)
offer a selection of 10 thermocouple
types as well as 2-, 3- or 4-wire
RTDs, process voltage and current.
The CNi8DH and CNi8DV are ideal
controllers for use with transmitters
and amplified transducers. Built-in
excitation is standard (24 Vdc
@ 25 mA). The units handle
0 to 20 mA process current and
process voltage in 3 scales:
0 to 100 mV, 0 to 1V, and 0 to 10V.
As with all iSeries devices, the process
value display can be programmed
to change color between GREEN,
AMBER, and RED at any setpoint
or alarm point. The LEDs displaying
the process value on the CNi8DH
(horizontal
digits of any 1⁄8 DIN controller.
The strain/process instrument
(model iS) meters and controllers
measure inputs from load cells,
pressure transducers, and most any
strain gage sensor. Input ranges
include 0 to 100 mVdc; -100 mVdc
to 1 Vdc; 0 to 10 Vdc in addition to
0 to 20 mA. Excitation for transducers
of 5 V and 10 V is standard.
The highly recommended networking
and communications options include
direct Ethernet LAN connectivity
with an embedded Web server, and
serial communications. The C24
serial communications option
includes both RS232 and RS485
which can be selected from the
menu as well as both a
1
⁄8 DIN) are the largest
CNiS8DV33, shown
smaller than actual size.
straightforward ASCII protocol.
The C4EIT option includes Ethernet
and RS485 ASCII on 1 device.
The iSeries, with the network
options, are designed for easy
integration with popular industrial
automation and control programs
as well as Microsoft Visual Basic
and Excel®. OMEGA provides
free configuration software which
makes it fast and easy to get up
and running with many applications.
Available for download off the
Internet.
TM
®
at any
setpoint
Totally
Programmable
Color
Displays
PATENTED
1

17.78 (0.700)
109.86
(4.325)
The i/8 Series controllers feature plug/removable
connectors and a sturdy panel mounting sleeve with
adjustable thumb nuts for easy secure installation.
Dimensions: mm (inch)
22.9 (0.90)
104 (4.10)
Options
Ordering
Suffix Description
-AL Limit alarm version (alarms only,
no PID control)
-SM Simplified menu (on/off control or
alarms, no PID)
*2
*3
Network Options
-EIT Ethernet with embedded
Web server
-C24 Isolated RS232 and RS485/422,
300 to 19.2 Kb*
-C4EIT
Ethernet with embedded Web
server + isolated RS485/422 hub
for up to 31 devices*
1
1
Power Supply
Standard power input:
90 to 240 Vac, 50 to 400 Hz
(no entry required)
-DC 20 to 36 Vdc, 24 Vac*
1
Factory Setup
-FS Factory setup and configuration
Software (Requires Network Option)
Omega-Enterprise- Logging/Alarming/Monitoring with
Gateway Integration Capabilities
*1“-DC”, “-C24”, and “-C4EIT” not available with excitation.
*2 Analog output is not available with “-AL” units.
*3“-SM” option not available on CNiS strain models.
To Order
Model No. Output 1 Output 2
Dual Display Horizontal with 2 Control Outputs
CNi8DH33 Relay Relay
CNi8DH34 Relay DC pulse
CNi8DH44 DC pulse DC pulse
CNi8DH43 DC pulse Relay
CNi8DH42 DC pulse 0.5 A SSR
CNi8DH22 0.5 A SSR 0.5 A SSR
CNi8DH23 0.5 A SSR Relay
CNi8DH24 0.5 A SSR DC pulse
CNi8DH53 Analog Relay
CNi8DH54 Analog DC pulse
CNi8DH52 Analog 0.5 A SSR
Dual Display Vertical with 2 Control Outputs
CNi8DV33 Relay Relay
CNi8DV34 Relay DC pulse
CNi8DV44 DC pulse DC pulse
CNi8DV43 DC pulse Relay
CNi8DV42 DC pulse 0.5 A SSR
CNi8DV22 0.5 A SSR 0.5 A SSR
CNi8DV23 0.5 A SSR Relay
CNi8DV24 0.5 A SSR DC pulse
CNi8DV53 Analog Relay
CNi8DV54 Analog DC pulse
CNi8DV52 Analog 0.5 A SSR
Strain/Process Input, Dual Display Horizontal with
2 Control Outputs
CNiS8DH33 Relay Relay
CNiS8DH44 DC pulse DC pulse
CNiS8DH43 DC pulse Relay
CNiS8DH42 DC pulse 0.5 A SSR
CNiS8DH22 0.5 A SSR 0.5 A SSR
CNiS8DH23 0.5 A SSR Relay
CNiS8DH24 0.5 A SSR DC pulse
CNiS8DH53 Analog Relay
CNiS8DH54 Analog DC pulse
CNiS8DH52 Analog 0.5 A SSR
Strain/Process Input, Dual Display Vertical
with 2 Control Outputs
CNiS8DV33 Relay Relay
CNiS8DV44 DC pulse DC pulse
CNiS8DV43 DC pulse Relay
CNiS8DV42 DC pulse 0.5 A SSR
CNiS8DV22 0.5 A SSR 0.5 A SSR
CNiS8DV23 0.5 A SSR Relay
CNiS8DV24 0.5 A SSR DC pulse
CNiS8DV53 Analog Relay
CNiS8DV54 Analog DC pulse
CNiS8DV52 Analog 0.5 A SSR
Comes with complete operator’s manual.
Ordering Examples: CNi8DH43, horizontal
pulse control and relay. CNi8DV53,
with analogue output and relay. CNiS8DH22,
horizontal controller with 2 SSR outputs.
1
1
⁄8 DIN dual display with
⁄8 DIN dual display vertical controller
1
⁄8 DIN dual display
2

TM
Common Specifications
Universal Temperature and
Process Input (DPi/CNi Models)
Accuracy: ±0.5°C temp; 0.03% rdg
Resolution: 1°/0.1°; 10 µV process
Temperature Stability:
RTD: 0.04°C/°C
TC @ 25°C (77°F): 0.05°C/°C
Cold Junction Compensation
Process: 50 ppm/°C
NMRR: 60 dB
CMRR: 120 dB
A/D Conversion: Dual slope
Reading Rate: 3 samples/s
Digital Filter: Programmable
Display: 4-digit 9-segment LED
10.2 mm (0.40"); i32, i16, i16D, i8DV
21 mm (0.83"); i8 10.2 mm (0.40") and
21 mm (0.83"); i8DH RED, GREEN,
and AMBER programmable colors
for process variable, setpoint and
temperature units
Input Types: Thermocouple, RTD,
analog voltage, analog current
Thermocouple Lead Resistance:
100 Ω max
Thermocouple Types (ITS 90):
J, K, T, E, R, S, B, C, N, L (J DIN)
RTD Input (ITS 68): 100/500/1000 Ω
Pt sensor, 2-, 3- or 4-wire; 0.00385 or
0.00392 curve
Voltage Input: 0 to 100 mV, 0 to 1V,
0 to 10 Vdc
Input Impedance: 10 MΩ for 100 mV
1 MΩ for 1 or 10 Vdc
Current Input: 0 to 20 mA (5 Ω load)
Configuration: Single-ended
Polarity: Unipolar
Step Response: 0.7 sec for 99.9%
Decimal Selection:
Temperature: None, 0.1
Process: None, 0.1, 0.01 or 0.001
Setpoint Adjustment:
-1999 to 9999 counts
Span Adjustment:
0.001 to 9999 counts
Offset Adjustment: -1999 to 9999
Excitation (Not Included with
Communication): 24 Vdc @ 25 mA
(not available for low-power option)
Universal Strain and Process
Input (DPiS/CNiS Models)
Accuracy: 0.03% reading
Resolution: 10/1µV
Temperature Stability: 50 ppm/°C
NMRR: 60 dB
CMRR: 120 dB
A/D Conversion: Dual slope
Reading Rate: 3 samples/s
Digital Filter: Programmable
Input Types: Analog voltage and current
Voltage Input: 0 to 100 mVdc,
-100 mVdc to 1 Vdc, 0 to 10 Vdc
Input Impedance: 10 MΩ for 100 mV;
1 MΩ for 1V or 10 Vdc
Current Input: 0 to 20 mA (5 Ω load)
Linearization Points: Up to 10
Configuration: Single-ended
Polarity: Unipolar
Step Response: 0.7 sec for 99.9%
Decimal Selection: None, 0.1, 0.01
or 0.001
Setpoint Adjustment:
-1999 to 9999 counts
Span Adjustment: 0.001 to 9999 counts
Offset Adjustment: -1999 to 9999
Excitation (Optional In Place Of
Communication): 5 Vdc @ 40 mA;
10 Vdc @ 60 mA
Control
Action: Reverse (heat) or direct (cool)
Modes: Time and amplitude proportional
control; selectable manual or auto PID,
proportional, proportional with integral,
proportional with derivative and anti-reset
Windup, and on/off
Rate: 0 to 399.9 s
Reset: 0 to 3999 s
Cycle Time: 1 to 199 s; set to 0 for on/off
Gain: 0.5 to 100% of span; setpoints 1 or 2
Damping: 0000 to 0008
Soak: 00.00 to 99.59 (HH:MM), or OFF
Ramp to Setpoint:
00.00 to 99.59 (HH:MM), or OFF
Auto Tune: Operator initiated from
front panel
Control Output 1 and 2
Relay: 250 Vac or 30 Vdc @ 3 A (resistive
load); configurable for on/off, PID and ramp
and soak
Output 1: SPDT, can be configured as
alarm 1 output
Output 2: SPDT, can be configured as
alarm 2 output
SSR: 20 to 265 Vac @ 0.05 to 0.5 A
(resistive load); continuous
DC Pulse: Non-isolated; 10 Vdc @ 20 mA
Analog Output (Output 1 Only):
Non-isolated, proportional 0 to 10 Vdc or
0 to 20 mA; 500 Ω max
Output 3 Retransmission:
Isolated Analog Voltage and Current
Current: 10 V max @ 20 mA output
Voltage: 20 mA max for 0 to 10 V output
Network and Communications
Ethernet: Standards compliance
IEEE 802.3 10 Base-T
Supported Protocols:
TCP/IP, ARP, HTTPGET
RS232/RS422/RS485: Selectable from
menu; both ASCII and MODBUS protocol
selectable from menu; programmable
300 to 19.2 Kb; complete programmable
setup capability; program to transmit
current display, alarm status, min/max,
actual measured input value and status
(All
i/8, i/16, i/32 DIN)
RS485: Addressable from 0 to 199
Connection: Screw terminals
Alarm 1 and 2 (Programmable)
Type: Same as output 1 and 2
Operation: High/low, above/below,
band, latch/unlatch, normally open/
normally closed and process/deviation;
front panel configurations
Analog Output (Programmable):
Non-isolated, retransmission 0 to 10 Vdc
or 0 to 20 mA, 500 Ω max (output 1 only);
accuracy is ± 1% of FS when following
conditions are satisfied: input is not scaled
below 1% of input FS, analog output is not
scaled below 3% of output FS
General
Power: 90 to 240 Vac ±10%, 50 to 400
*, 110 to 300 Vdc, equivalent voltage
Hz
Low Voltage Power Option: 24 Vac
12 to 36 Vdc for DPi/CNi/DPiS/CNiS;
20 to 36 Vdc for dual display, ethernet
and isolated analog output from qualified
safety approved source
**,
Isolation
Power to Input/Output: 2300 Vac
per 1 minute test
For Low Voltage Power Option:
1500 Vac per 1 minute test
Power to Relay/SSR Output:
2300 Vac per 1 minute test
Relay/SSR to Relay/SSR Output:
2300 Vac per 1 minute test
RS232/485 to Input/Output:
500 Vac per 1 minute test
Environmental Conditions:
All Models: 0 to 55°C (32 to 131°F)
90% RH non-condensing
Dual Display Models:
0 to 50°C (32 to 122°F), 90% RH
non-condensing (for UL only)
Protection:
DPi/CNi/DPiS/CNiS32,16,16D, 8C:
NEMA 4X/Type 4 (IP65) front bezel
DPi/CNi/DPiS/CNiS8, 8DH, 8DV:
NEMA 1/Type 1 front bezel
Approvals: UL, C-UL, CE per
2014/35/EU, FM (temperature
units only)
Dimensions
i/8 Series: 48 H x 96 W x 127 mm D
(1.89 x 3.78 x 5")
i/16 Series: 48 H x 48 W x 127 mm D
(1.89 x 1.89 x 5")
i/32 Series: 25.4 H x 48 W x 127 mm D
(1.0 x 1.89 x 5")
Panel Cutout
i/8 Series: 45 H x 92 mm W
(1.772 x 3.622"),
i/16 Series: 45 mm (1.772") square,
1
⁄16 DIN
i/32 Series: 22.5 H x 45 mm W
(0.886 x 1.772"),
Weight
i/8 Series: 295 g (0.65 lb)
i/16 Series: 159 g (0.35 lb)
i/32 Series: 127 g (0.28 lb)
No CE compliance above 60 Hz.
*
** Units can be powered safely with 24 Vac
power, but no certification for CE/UL are claimed.
1
⁄8 DIN
1
⁄32 DIN
3