Omega CN9400 User Manual

®
User ’s Guide
http://www.omega.com
e-mail: info@omega.com
CN9400
Dual Display Autotune Temperature Controller

INDEX

SAFETY INFORMATION A1 FUNCTIONS MENU A3
QUICK START
Quick Start Set-up 1a
INTRODUCTION 2
The controllers 2
OVERVIEW 3
Installation 3 Set-up 3 Autotune 3 Cycle-time 4
SET-UP 5
Power-up 5 Select input sensor 5 Select display units 5 Allocate output device 5 Enter initial configuration 5 Set main setpoint 5
MENU NAVIGATION 6
Using program mode 6
AUTOTUNE 7
Tune program 7 Tune at setpoint program 8
PROPORTIONAL CYCLE-TIME 9
Cycle-time selection methods 9 Cycle-time recommendations 9 Autotune calculated cycle-time 9
PROGRAMMER 11
Ramp-Soak 11
SECOND SETPOINT (SP2) 12
SP2 as an alarm 12 SP2 subsidiary mode 13 SP2 as a proportional output 13 SP2 alarm condition table 13 SP2 alarm annunciator 13
ERROR MESSAGES 14
Recommendations 14 Autotune data in
IMPROVING CONTROL ACCURACY 15
Using
ChEK
FUNCTION LIST 16
Level 1 16 Level 2 18 Level 3 19 Level 4 21
OUTPUT OPTIONS 22 ADVANCED SETTINGS 23
Heat Cool strategy 23 Calibration to other instrument 24 Linear input calibration 25
MECHANICAL INSTALLATION 27
DIN panel cut-outs 27 Minimum spacing 27 Mounting 28
ELECTRICAL INSTALLATION 29
General requirements 29 Connection diagrams 30
INPUT/SENSOR SELECTION 31 SPECIFICATION 32 WARRANTY INFORMATION Inside back cover
tECH
accuracy monitor 15
14
Index
A2A1

SAFETY INFORMATION

INSTALLATION
Designed for use: UL873 - only in products where the acceptability is determined by Underwriters Laboratories Inc. EN61010-1 / CSA 22.2 No 1010.1 - 92 To offer a minimum of Basic Insulation only. Suitable for installation within Catagory II and III and Pollution Degree 2.
SEE ELECTRICAL INSTALLATION P29 & P30
It is the responsibility of the installation engineer to ensure this equipment is installed as specified in this manual and is in compliance with appropriate wiring regulations.
CONFIGURATION
All functions are front selectable, it is the responsibility of the installing engineer to ensure that the configuration is safe. Use the program lock to protect critical functions from tampering.
ULTIMATE SAFETY ALARMS
Do not use SP2 as the sole alarm where personal injury or damage may be caused by equipment failure.
Safety Information

FUNCTIONS MENU

nonE; LEV 3; LEV 2; ALL
LEVL 4
Security lock
LOCK
Disable program auto-exit
PROG NO.AL DIS.S DER.S
*
Auto; StAY
USER-PROTECTED SETTINGS
Off; on
Disable -AL- alarm display
Display averaging
*
dir; 1 to 32 (6)
0.1 to 1.0 x dEr.t (0.5)
Derivative sensitivity
Range of Adjustment shown in red under description. If applicable, factory settings shown in bold.
* Note: Dual Relay and Dual SSd Output Options
Models CN9411 and CN9422 have their outputs pre-configured. (see page 22)
Setpoint 1 Output indicator (green)
Process temperature (PV) or Function (green)
Setpoint temperature (SP) or Option (orange)
Setpoint 2 Output indicator (red)
nonE; rlY; SSd
SP1 output device
LEVL 3
LEVL 2
Functions Menu
LEVL 1
Level C only visable
when COMMS Option fitted
KEY ✱ ▼ OR ✱ ▲ TOGETHER TO CHANGE LEVELS OR OPTIONS
LEVL C
SP1.D
CONFIGURE OUTPUT SAFETY SETTINGS CALIBRATION PERFORMANCE DATA
0 to 100% read only
Read SP1 output %
SP1.P
oFF; on; tunE; ParK; At.Sp
Autotune or Park
TUNE
PROGRAM ENTRY
0 to 255
Instrument address
ADDR
A3
nonE; SSd; rlY (read only)
SP2 output device
SP2.D BURN REU.D REU.L SPAN ZERO CHEK READ TECH UER RSET
0 to 100% proportional
SP1 manual output %
HAND PL.1 PL.2 SP2.A SP2.B DISP HI.SC LO.SC INPT UNIT
MANUAL ADJUSTMENTS SP2 MODES RANGING CONFIGURE INPUT
0.1 deg to 25% sensor f/s
SP1 Prop band (gain)/hyst
BAND INT.T DER.T DAC CYC.T OFST SP.LK SPRR SPRN SOAK SET.2 BND.2 CYC.2
1200: 2400: 4800:
Baud rate
BAUD DATA DBUG
COMMS SETTINGS
Sensor burn-out
mode only
Limit SP1 output %
(10°C/18°F)
Integral time (reset)
9600: 19k2
Data format
uP.SC; dn.SC; 1u.2d; 1d.2u
100 to 0%
Off; 0.1 to 60 min (5 min)
18n1:18E1:18O1
1r.2d; 1d.2d; 1r.2r; 1d.2r
Reverse outputs
100 to 0%
Limit SP2 output %
Off; 1 to 200 sec (25 sec)
Derivative time (rate)
SP1 SETTINGS
Off; on
Tx/Rx activity
1n.2n; 1i.2n; 1n.2i; 1i.2i
Reverse O/P LEDs
nonE; dV.hi; dV.Lo; bAnd;
FS.hi; FS,Lo; Cool
Main SP2 mode
0.5 to 5.0 x bAnd (1.5)
Derivative approach
0.0 to 25% sensor f/s
Span adjustment
nonE; LtCH; hold; Lt.ho;
nLin
Second SP2 mode
(20 sec)
On.off; 0.1 to 81 sec
Cycle time or on/off
sensor full scale
0.0 to 25%
Zero Adjustment
1 or 0.1 degree
Display resolution
(In.t = off)
0 to 50% x bAnd
Offset (manual reset)
Off; on
Set Monitor
sensor full scale
0.0 Sensor max to
Set scale maximum
Off; on
Setpoint lock (SP1)
Read Monitor
Set scale minimum
Setpoint Ramp rate
KEY ▼ ▲ TO VIEW FUNCTIONS
VAr; hi; lo deg
full scale
0.0 Sensor min to sensor
CtA; Ctb; Ct1; Ct2; Ct3;
Read Tune Data
nonE
Select input sensor
Ct4; oS1; uS; oS2
Consult unit
Software version
PSi; Ph; rh; SEt
nonE; °C; °F; bAr;
Select display units
RESET
nonE; ALL
QUICK START ENTRY
0 to 9990 deg/hour
PROGRAMMER SETTINGS SP2 SETTINGS
On; off; hold
Ramp off/on
Off; 0 to 1440 min
Soak time
Adjust SP2 setpoint
full scale
+/– sensor full scale or
0.1 deg to 100% sensor
SP2 prop band/Gain/Hyst
f/s (2°C/3.6°F)
SP2 Cycle on/off
On.off; 0.1 to 81 sec
INSTRUMENT ADJUSTMENTS
To enter or exit program mode: Press ▲ ▼ together for 3 seconds To scroll through functions: Press ▲ or ▼ To change levels or options: Press ✱ ▲ together or ✱ ▼ together To view setpoint: Press To increase setpoint: Press ✱ ▲ together To decrease setpoint: Press ✱ ▼ together To reset an alarm or fault condition: Press ▲ ▼ together briefly
Notes: If in difficulty by becoming “lost” in program mode, press and
together for 3 seconds to return to display mode, check the INSTRUMENT ADJUSTMENTS above and try again.
When in program mode, after 60 seconds of key inactivity the display will revert to either or, if the initial configuration has been completed, the measured value. Any settings already completed will be retained.
INPT
NONE
2 Select unit.
Press and hold and use the or buttons to scroll
through the unit selection list until the correct unit is displayed. Release the buttons. The display will read selected unit e.g.
Press ▲ once The display will now read
3 Select SP1 (Main setpoint output device)
Note: Dual Relay and Dual SSd Output Options
Models CN9411 and CN9422 have their outputs pre-configured. (see page 22)
Press and hold and use the or buttons to select
SSd
or
rLY
as required.
The controller will now read selected output device e.g.

Quick Start

QUICK START
1b
4 To enter initial configuration into
controller memory
Press and hold both and buttons for 3 seconds.
The upper display will now alternate
ParK
and measured variable (temperature) (eg. 23)
ParK
is displayed because a setpoint has not yet been entered as shown by the lower display
To display setpoint
Press and hold The displays will now read
unit
(eg. °C) and
0
To enter setpoint
Press and hold and use button to increase or
button to decrease the reading and scroll to required setpoint value. (The digit roll-over rate increases with time).
THE CONTROLLER IS NOW OPERATIONAL
WITH FACTORY SETTINGS
Note: For precise control of an application the controller
may need to be TUNED. Please study section headed FUNCTIONS and OPTIONS before moving to the section on AUTOTUNE.
UNIT
*C
SPI.D
NONE
SPI.D
SSD
PARK
0
*C
0

Introduction

INTRODUCTION
The CN9400 is a 1/16 DIN dual display, dual output miniature controller with PID control strategy.
Control can be optimised with a single shot autotune either on initial warm-up or at setpoint. The second setpoint can be configured in a variety of alarm modes or PID Heat-Cool strategy. A programmer offers a single ramp to setpoint with a choice of timed soak period before switching off the output.
Control of non temperature processes is achieved by the provision of linear input ranges and scaling in commonly used engineering units.
Serial communication is available as an option, and the easy to use CN9-SW is a graphic WINDOWS
TM
based software package designed for PC supervision of up to 32 instruments, for remote adjustment, configuration, cloning, saving and retrieving settings to files and logging and charting in real time.
CN9-SW uses the MODBUS®protocol via either a fully isolated RS232 or RS485 link depending on the number of instruments and the transmission distances involved in the application.
A users manual is supplied with the comms option. For more information contact OMEGA. For details, see rear cover.
It is suggested that users read the OVERVIEW section of this manual before any installation or setting-up procedures are undertaken.
Note: The controller will not be operational until either the
QUICK-START or SET-UP procedure has been completed.
NB: Please note that in program mode, functions
are shown in the upper display (green) and options in the lower display (orange)
2
CN9400
TUNE
PARK

Overview

OVERVIEW
INSTALLATION
The Model CN9400 controller is designed to be mounted in a 1/16 DIN panel cut-out. See the INSTALLATION section.
SET-UP
After installation the controller requires programming with the following information:
Type of Input Sensor Operating unit (C or F etc) Type of Output Device Temperature Setpoint
Note: The controller will not be operational until this
information is entered.
When the above information has been programmed into the controller it will be operational with the following factory PID (proportional band, integral time, derivative time) settings.
Proportional band/Gain 10°C/18°F Integral time/Reset 5 mins Proportional cycle-time 20 secs Derivative time/Rate 25 secs DAC Derivative approach control 1.5
AUTOTUNE
To precisely control an application the controller will need to be ‘tuned’ using the built-in ‘AUTOTUNE’ feature. Autotune ‘teaches’ the controller the main characteristics of the process and ‘learns’ by cycling the output on and off. The results are measured and used to calculate optimum PID values which are automatically entered in the controller memory.
During AUTOTUNE the optimum cycle-time is calculated but is not automatically implemented. The cycle-time requires manual acceptance unless pre-selected.
To ensure good control over a wide range of applications two versions of the Autotune program are provided, TUNE and TUNE AT SETPOINT.
The TUNE method normally achieves the best results. Starting with the load cool, tuning occurs during warm-up preventing overshoot. This method of tuning is recommended.
The TUNE AT SETPOINT method is used for specialist applications. eg. Heat-cool, multizones and processes below 100°C/200°F. During the tuning cycle some overshoot occurs because the tuning cycle is at set point. The DAC setting is not re-calculated.
3
Overview
CYCLE-TIME
The choice of cycle-time is influenced by the external switching device or load. e.g. contactor, SSR, Valve. A setting that is too long for the process will cause oscillation and a setting that is too short will cause unnecessary wear to an electro-mechanical switching device.
Cycle-time selection methods
The following methods of cycle-time selection may be used:
Autotune calculated
After Autotune has been run and completed the calculated cycle­time can be manually accepted or adjusted to suit the switching device. For selection method see Select Autotune Calculated
Cycle-time.
Pre-select autotune cycle-time
The controller can be programmed to automatically accept the calculated Autotune cycle-time. For selection method see Pre-
Select Automatic Acceptance of Any Autotune Cycle-time.
Pre-select before autotune
The controller can be programmed manually with any cycle-time between 0.1 and 81 sec. This cycle-time will not be changed by any
Autotune functions. For selection method see Pre-Select Cycle­time Before Autotune.
Factory set
To use the 20 sec factory set cycle-time no action is needed whether Autotune is used or not.
Further information can be programmed into the controller, see
SECOND SETPOINT, RANGING AND SETPOINT LOCK, IMPROVING CONTROL ACCURACY
Functions and options
The facilities of the controller are selected from the multi-level menu using the front panel mounted buttons.
Note: It is advisable to study this section before any
programming is undertaken.
Each level within the multi-level menu offers different functions, see FUNCTIONS MENU for menu of main functions. Each function has a range of user selections or options, see FUNCTION LIST for functions and options details.
The controller has two modes, program mode and operating mode. When in program mode the controller can be programmed with settings and functions to suit the application. When in operating mode the controller uses the setting and functions entered in the program mode to control the application and also displays both the process variable and setpoint temperatures. For full details on how to program the controller see VIEWING AND SELECTING
FUNCTIONS.
Note: In this manual the letter k is represented by the
character
K
4

Set-up

SET-UP
5
This section details the four step initial configuration that enables control with factory PID settings to start, once the setpoint has been entered.
POWER-UP
On power-up the controller will display the self test sequence and brief display blanking
1 SELECT INPUT SENSOR
Press and hold and use either the or buttons to scroll through the sensor selection (see table p.31). When the correct sensor is displayed, release the buttons. The controller will now display selected sensor type e.g.
2 TO SELECT °C/°F
Press and release the button, the controller will now display
Press and hold the button and using the button select °C, °F, Bar, PSI, Ph, Rh or SEt as required. Release the buttons when the correct unit is displayed.
The controller will now display
unit
and e.g. ºC
3 TO SELECT SP1
(Main setpoint output device)
Note: Dual Relay and Dual SSd Output Options Models
CN9411 and CN9422 have their outputs pre­configured. (see page 22)
Press and release the button, the controller will now display Press and hold the button and using the button select
SSd
or
rLY
as required. Release the buttons when the correct device is displayed. The controller will now display
SPI.d
and selected output device e.g.
SSd
.
4 To enter initial configuration into
controller memory
Press and hold both and buttons for 3 seconds.
The upper display will now alternate
ParK
and measured variable (temperature) (eg. 23)
ParK
is displayed because a setpoint has not yet been entered as shown by the lower display
TO SET THE MAIN SETPOINT
To display the setpoint, press and hold the button. °Cand
0
or °Fand 32will be displayed. Press and hold the button. Press to increase or to decrease the setpoint. The main setpoint LED will flash indicating that SP1 output is ON. The controller will now be set with the factory PID settings.
INPT
NONE
SP1>D
NONE
SP1>D
SSD
INPT
TCS
UNIT
NONE
UNIT
*C
PARK
0

Menu Navigation

MENU NAVIGATION
To change an option value or setting
Press and hold the button, then press to increase or to decrease the value or select the next option.
Note: Check the new option value before moving to
another function or exiting program mode.
To change levels
Press and hold to scroll through the functions until
LEUL
is displayed. Release to display current level. Press and hold the button, then press to increase or to decrease the level. Release buttons when required level is obtained.
To exit program mode
Press and hold both and buttons for at least 3 seconds.
Note: Control commences with any new instructions now entered in the memory.
REMINDER OF INSTRUMENT ADJUSTMENTS
Press ▲ ▼ together for 3 seconds for program entry or exit. Press ▲ or ▼ to scroll through functions. Press ✱ ▲ together or ✱ ▼ together to change levels or alter options. Note: If in difficulty by becoming “lost” in program mode,
press and together for 3 seconds to return to display mode, check the Menu Navigation summary above and try again.
The facilities of the controller are selected from the multi-level menu using the front panel mounted buttons. Each level within the multi-level menu offers different functions, see FUNCTIONS MENU page A3. Each function has a range of user selections or options, see FUNCTION LIST pages 16–22
In operating mode, the upper (green) display reads process temperature (PV) and the lower (orange) display reads setpoint temperature (SP). When in program mode, settings of each function, shown in the upper display, can be made by selecting an appropriate option from the lower display.
USING PROGRAM MODE
Note: The controller will auto-exit program mode after
60 seconds of inactivity.
To enter program mode from normal operating mode
Press and hold both and buttons for at least 3 seconds. Release the buttons together and the controller will now display the function and option (setting of that function), e.g.
To view function on the same level and display current option
Press or button once to view the next function. Press and hold or buttons to scroll through functions. The current option or function value is shown in the lower display.
6
TUNE
OFF

Autotune

AUTOTUNE
Select the most appropriate method of Autotune , Tune or Tune at Setpoint, to suit the application.
Note: The proportional cycle-time can be pre-selected
before starting Autotune, see PROPORTIONAL CYCLE-TIME.
The TUNE program should be run with the load cool. The output is cycled at 75% of the setpoint value to avoid any overshoot during the tuning cycle. The warm-up characteristics are monitored and set DAC which minimises overshoot on subsequent warm-ups.
The TUNE AT SETPOINT program is recommended:
when the setpoint is below 100°C/200°F, where TUNE’s tuning cycle at 75% setpoint may be too close to ambient to produce good results;
when the process is already hot and the cooling rate is slow;
when controlling multi-zone or heat-cool applications;
to re-tune if the setpoint is changed substantially from previous Autotune.
Note: dAC is not re-tuned by TUNE AT SETPOINT.
TUNE PROGRAM
Enter program mode
and from the display
press and hold and press once,
the controller will now display
Exit program mode.
The TUNE program will now start. The upper display will
alternate between
tune
and the process temperature as it climbs to setpoint. The lower display will read the setpoint value e.g.
Note: During tuning, the main setpoint (SP1) LED will flash.
Temp
Setpoint
Cycle
75% SP
Start
TUNE
TUNE
Tuning DAC
PID
1
1
/4 on/off tuning
cycles
New PID values entered
Time
(100% output)
7
TUNE
OFF
TUNE
ON
TUNE
232
Autotune
The TUNE AT SETPOINT program will now start. The upper display will alternate
tune
and the process temperature.
The lower display will read the setpoint value.
Note: During tuning the main setpoint (SP1) LED will flash.
When the TUNE AT SETPOINT program is complete the upper alternating display stops and only the process temperature is displayed. The PID values are entered automatically. The process temperature will rise to setpoint and control should be stable. If not, this may be because optimum cycle time is not automatically implemented. To set the cycle time see PROPORTIONAL CYCLE-TIME.
When the TUNE program is complete the upper alternating display stops and only the process temperature is displayed. The PID values are entered automatically. The process temperature will rise to setpoint and control should be stable. If not, this may be because optimum cycle time is not automatically implemented. To set the cycle time see PROPORTIONAL CYCLE-TIME.
TUNE AT SETPOINT PROGRAM
Enter program mode and select
And from the display select
Exit program mode.
Temp
Setpoint
Start
TUNE
Tuning
PID
1
3
/4 on/off tuning
cycles
New PID values entered
Time
(100% output)
AT.SP
Overshoot
during tuning
Prop band
REMINDER OF INSTRUMENT ADJUSTMENTS
Press ▲ ▼ together for 3 seconds for program entry or exit. Press ▲ or ▼ to scroll through functions. Press ✱ ▲ together or ✱ ▼ together to change levels or alter options. Note: If in difficulty by becoming “lost” in program mode,
press and together for 3 seconds to return to display mode, check the Menu Navigation summary above and try again.
8
TUNE
OFF
TUNE
AT.SP
Loading...
+ 26 hidden pages