The NuTone central cleaning system consists of a power unit, PVC tubing and fittings, wall inlets, a flexible hose and various
cleaning attachments.
The power unit is designed to be wall-mounted away from the living area of the home and connected to the living area by means
of permanently installed in-wall tubing, fittings and inlets.
Generally, an installation will require 3 to 4 inlets and 16 to 20 feet of tubing per inlet. It is suggested that a floor plan be used to
more accurately determine the quantity of materials needed.
Use the following examples as an aid in planning the installation in either new or existing construction. You should be able to
adapt the examples shown to your specific home layout.
THE RANCH STYLE HOUSE
Here the power unit is mounted in the
garage. The intake and exhaust tubing,
the only exposed tubing in the installation,
EXHAUST
runs up the garage wall and into the attic.
The trunk line runs horizontally through the
attic from the power unit to the farthest inlet
location. Branch lines spread throughout
the attic, connecting the trunk line to the
inlet tubing. Each inlet tube is threaded
vertically through an inside wall. Located in
hallways and in large rooms, the inlets are
placed to provide maximum access to all
POWER
UNIT
INTAKE
cleaning areas. See figure at right.
AH0003A
THE TWO-STORY HOUSE
A double-trunk line system is commonly used in two-story
houses. In the installation shown at right, the power unit
is mounted in the basement. The intake tubing runs up
the basement wall and connects to the main trunk line,
which runs along the unfinished basement ceiling. Two
first-floor inlets are connected to the basement trunk line
by vertical inlet lines run through interior walls. In the
center of the house, a vertical branch line runs from the
basement trunk line, through stacked closets, up into the
attic. A second trunk line runs across the attic and two
branch lines connect to inlet lines which are dropped
down through upstairs interior walls. See figure at right.
THE SPLIT-LEVEL HOUSE
AH0005A
TRUNK LINE
VERTICAL
BRANCH
LINE
INTAKE
POWER
UNIT
BRANCH LINE
INLETS
AT TIC
TRUNK
LINE
EXHAUST
BASEMENT
TRUNK LINE
INLET LINE
INLET
LINE
INLE
Like the two-story house, the split level
installation commonly calls for a two-level
trunk line. Here, the power unit is located
in the garage. The intake tubing runs
exposed up the garage wall and into the
ground level section's attic. Two branch
lines connect this part of the trunk line
to inlet lines which are dropped inside
interior walls. A vertical branch line runs
to the upstairs attic, where the trunk line
branches into a T-shape. This trunk line
connects to two upstairs inlet lines and
to one inlet line which drops through an
upstairs wall and down into the third-level
utility room to service this entire level. See
figure at right.
AH0004A
EXHAUST
BRANCH
VERTICAL
BRANCH
LINE
TRUNK
LINE
POWER
UNIT
INTAKE
BRANCH
LINE
INLET
LINES
INLET
LINE
INLET
4
SYSTEM PLANNING AND LAYOUT (CONT'D)
!
!
WARNING
Do not install outdoors. When performing
installation, servicing or cleaning the unit, it is
recommended to wear safety glasses and gloves.
LOCATING THE POWER UNIT
• Locate the power unit away from the general living area in
an accessible location for cleaning and maintenance.
• When planning the installation of PP7001 power unit,
remember it is equipped with an inlet to service a garage,
basement, utility room, etc., wherever it is located.
• Locate the power unit within 6 feet of a grounded electrical
outlet. The power unit requires a 120 VAC power source.
• Do not locate the power unit close to a source of extreme
heat (i.e.: water heater) or in an area with a high ambient
temperature (i.e.: attic, furnace room).
• If the power unit is located in a closet or a small utility
room, make sure the area is well-ventilated (e.g.: with door
louvers).
• Exhausting the power unit to the outside is recommended
for optimal performance. The exhaust should not be vented
into a wall, a ceiling or a concealed space in the house.
The exhaust line should be vented outside the home using
a Model 393 or CI330 wall caps.
TUBING AND
WALL INLET LOCATIONS
Locate inlets on interior walls, choosing central locations
which allow several rooms to be cleaned from a single inlet
using a 30-foot long hose.
The tubing installation should consist of a main trunk line
running from the farthest wall inlet to the power unit location,
with branch lines running to each additional inlet. Keep all
tubing lines as straight as possible and use as few fittings as
possible.
Beginning at the area farthest from the power unit, choose
a tentative inlet location. Measure 30 feet from the proposed
inlet location to the farthest corner of the rooms to be cleaned
by that inlet to determine if inlet location is proper. If working
from blueprints (or building plans drawn at 1⁄4" = 1 ft. scale),
use a 7½" chain as your guide to determine inlet locations.
Locate inlets within six feet of an electrical receptacle to
allow use of optional current-carrying hose.
Be sure inlets will not be blocked by doors or furniture.
Be sure inlets will not interfere with electrical, plumbing or
other mechanical installations.
Move tentative inlet location if necessary. Use the same
procedure to determine each additional inlet location,
always working toward the power unit.
GENERAL INSTALLATION GUIDE
WARNING
When applicable local regulations comprise more restrictive installation and/or certification requirements,
the aforementioned requirements prevail on those of this document and the installer agrees to conform to
these at his own expenses.
TOOL LISTING
Depending on your installation, you may require the use of these tools. The power tools are recommended to make your installation
proceed quickly. Also, plan a mask when cutting ducting (PVC dust) and gloves when using glue.
Before you cut a length of tube,
accurately measure the length you
need. Allow 5/8” of tubing for inserting
into fittings and 1½” for placing into
flexible tubing. Cut the plastic tubing
with a hacksaw, making sure that the
cut is exactly square. (You can use a
tube cutter if one is available.) Use
wire cutters or tin snips to cut flexible
tubing. The 8” lengths of flexible tubing
supplied with each inlet should not be
cut. See figure at right.
AR0016
Use a small knife to remove any burrs
from the inside of the tube. You can
also use steel wool to remove burrs.
The burrs must be removed or they
may impede air flow of form clogs by
snagging hair and carpet thread. See
figure at right.
AR0017
5
GENERAL INSTALLATION GUIDE (CONT'D)
WORKING WITH
PLASTIC TUBING (CONT'D)
CUTTINGTHE TUBING(CONT'D)
Next, use a file to slightly bevel the
outside of the tube so that it will easily
slide into the fitting. Use steel wool or
a light grained sandpaper to buff the
surface of the tube which will be glued.
This will clean the tube and assure a
good seal. See figure at right.
MAKINGA JOINT
Insert the tube into the fitting,
aligning the two parts as they
will be installed. Mark the tube
and the fitting so that you can
quickly realign the joint. See
figure at right.
Apply cement only to the
outside of the tube. Dab the
cement generously in an
inch-wide band. Insert the
tube into the fitting with the
alignment marks a quarter turn
apart, and then quickly push
and turn the fitting to align the
marks and spread the cement.
Allow one minute for the joint to
dry. You may also use electrical
tape or duct tape to further seal
the joint. See figure at right.
AR0018
AR0019
CEMENTING FLEXIBLE TUBING
Make sure the ends of the flexible tubing are even—trim if
necessary. When you join flexible tubing to plastic tubing or to
an inlet mounting plate, apply cement to both the inside of the
flexible tubing and the outside of the plastic tubing or mounting
plate tubing ring. Twist the two pieces as you join them to
evenly spread the glue. Allow five minutes for the cement to set
in flexible tubing. You may also use electrical tape or duct tape
to further seal the joint.
SECURE WIRETO T UBING
The low-voltage power wiring
is run along with the tubing. To
insure that the wire is secure
and will not hang-up in a wall,
use electrical tape to attach
the wire to the tubing. Tape
the wire approximately every
12-18 inches. See figure at
right.
AO0011
AO0010
6
INSTALLATION IN NEW CONSTRUCTION
WALL INLET ROUGH-IN
Once the locations for the wall inlets have been determined, mount all inlet brackets.
Choose the appropriate mounting bracket for the inlet being installed. (See chart below.)
To locate a bracket on a wall stud, measure approximately 18" up from finished floor level. (Height may vary according to
individual preference.)
CI399X
MODELS CF361 & CF361F
(FOR USEWITH 360 INLET)
Refer to figure below. Nail bracket to the side of the stud so
that the front edge of the bracket is flush to the front of the
stud. (The bracket may also be nailed to the front edge of
the stud. See face mounting illustrated. For face mounting,
use locating tabs on bracket for proper alignment.)
MODEL CF361 & CF361F
SIDE
MOUNTING
23/8"
AD0059A
FACE
MOUNTING
13
/16"
1
MODELS CF329 (FOR USEWITH 330 INLETS)
When using Model CF329, glue elbow to
mounting plate. Attach to stud as shown in
figure at right.
AD0015
Refer to figure below. Remove cardboard from plaster guard
frame. Using four (4) provided screws, attach the appropriate
flanged fitting and inlet seal to back of inlet.
Replace cardboard in plaster guard frame
AD0060
7
INSTALLATION IN NEW CONSTRUCTION (CONT'D)
!
INSTALLING THE TUBING
Use the following installation guidelines when installing tubing.
B Start tubing installation at farthest inlet and work toward the
power unit.
C Tubing run to the power unit should be as straight as
possible.
D When assembling sections with elbows and tees, make sure
the curve in the fitting is aligned so that the air flows toward
the power unit.
E Branch lines should always join the trunk line from above
or from the same level. Never join a branch line from an
angle below the trunk line.
I Refer to figure at right. Cut tubing,
keeping cut square.
AR0016
F Refer to figure at right. Run
low voltage wiring (Model
376UL) and secure wiring
to tubing as tubing is
installed. Model CF380
Pipe Support can be used
to support long runs of
tubing (position near joists)
and to clip wire along tubing.
Secure tubing to joists or
studs. Leave approximately
6" of wire for connection to
each inlet.
G Cut a 2½" diameter hole in sole plate, header or stud
AE0040
directly in line with opening of inlet bracket fitting. See figure
below for center line dimensions.
MODEL CF361 MOUNTING
2½” DIA. HOLE
3
2
SIDE MOUNTING
AD0055A
THROUGH SOLE PLATE
”
/8
13
1
/16
MODEL CF329 MOUNTING
2”
FACE MOUNTING
”
THROUGH SOLE PLATE
13
”
1
/16
13
”
1
/16
13
1
FACE MOUNTING
2½” DIA. HOLE
”
/16
J Refer to figure at right. Remove
burrs from both inside and outside
of tubing.
AR0017
K Before cementing, pre-assemble section to inlet fitting,
check for proper length.
L Refer to figure at right Apply PVC
cement (Model 379) to outside of
tubing. Coat tubing approximately 1"
back. Take care to keep cement
from inside of tube.
AR0020
M Refer to figure at right. Insert tubing
into fitting with a twisting motion to
evenly spread cement. Be sure
tubing is firmly seated in fitting.
AO0012
N If fittings have been attached to tubing at the end opposite the
inlet bracket, be sure alignment is proper before cement sets.
H Refer to figure below. Measure length of tubing needed to
connect inlet to trunk line. Allow approximately 3⁄4" of tubing
for inserting into fittings.
INCLUDE FITTING RECESS
3/4”
(19 mm)
FITTING
AD0017A
IN MEASUREMENT
TUBING MEASUREMENT
PVC TUBING
(19 mm)
FITTING
3/4”
O Refer to figure at right. Tape wire
to tubing to hold in place and insert
through hole in inlet bracket.
AD0018
P Connect each inlet line and branch line into main trunk line.
Complete low voltage wiring as main trunk line is continued
back to power unit.
WARNING
When tubing is run through the wall stud, sole
plate, headers or else where building materials will
be attached, place a nail plate (Model 378) over that
area (on both sides if necessary) to prevent nails
from piercing tubing.
8
INSTALLATION IN NEW CONSTRUCTION (CONT'D)
WALL INLET INSTALLATION
MODEL 360 WALL INLET
(CF361
B Remove the cardboard plaster guard.
C Refer to figure at right.
For some drywall or panel
construction, the plaster frame
will extend beyond the finished
wall. In this case, remove
plaster frame from mounting
bracket by removing mounting
screws.
NOTE: When using the model CF361 and CF361F inlet
INLET MOUNTING
AND CF361F ROUGH-INS)
AR0045
bracket on walls thinner than 1⁄2", use a 1⁄4" spacer
(not furnished) between the wall and the inlet bracket.
See figure below. Spacer may be made from plywood,
Masonite™, etc. Contact cement may be used to hold
spacer in place during assembly. Configuration of
spacer may vary depending upon installation.
BRACKET
SPACER
1/4"
WALL LESS THAN
1
/2" THICK.
MODEL 330 WALL INLET (CF329 ROUGH-IN)
B Refer to figure at right. Connect
2-conductor low-voltage wire
to terminal screws on back of
wall inlet.
C Align inlet mounting holes with
holes in mounting plate.
D Refer to figure at right. Place
inlet into mounting plate and
secure with two provided
screws.
INLET
AE0024A
MOUNTING
PLATE
21/4"
AD0057A
D Refer to figure at right.
31/4"
PLASTER
GUARD
HOLE
Connect 2-conductor low voltage wire to terminal
screws on back of wall inlet.
AE0040
E Guide excess wire back through the hole in inlet bracket and
B Fasten the mounting plate onto a stud. Locate the lower hole
on the mounting plate marked “Wire Trap” and use a zip tie
to secure the wire to the back of the mounting plate at the
10” mark.
C Position the assembled wire plug through the top hole in the
mounting plate. Secure the plug to the mounting plate tab as
shown. This will keep it secure and out of harm’s way during
drywalling and finishing.
D Run the wire to the adjacent electrical box. If the
wire is to run through a stud, drill a hole directly
on the center of the stud and run the wire through.
Strip 6 inches of outer sheathing from this end of the wire and
place the wire into the electrical box through a strain relief.
Ensure the strain relief is tightened against the outer sheathing
(do not over tighten). Leave 1/2” of sheathing inside the outlet
box. Fold the 6” of black and white wires into the outlet box.
Leave the wires to be connected by the electrician when the
outlet receptacle is being installed.
E Once drywall and finishing have been completed, pull the
plug off the tab and snap into the opening on the back of the
new ElectraValve®. Ensure the plug is securely locked into
the position as shown. Attach the low voltage wires to the
screw contacts.
B
Ta b
Wire
Trap
D
C
1/2” Outer
Sheathing
CAUTION
Power tools such as routers are not recommended
for use with the inlet installation, as removal of
drywall with these devices may cause damage to
the mounting plate and/or inlet plug.
F Insert the valve into the mounting plate and secure the valve
to the mounting plate with the screws provided.
WARNING
All location and installation direct connect
electrified wall valves must conform with all local
and municipal building codes.
E
F
Low Voltage Wires
Valve
locking
tabs
AE0050A
10
C1358 SUPERVALVE™ WALL INLET & ROUGH-IN KIT
!
AL0008A
SAFETY INSTRUCTIONS
FOR HOUSEHOLD USE ONLY. INSTALL ONLY ON A NOMINAL 120 V, 60 Hz, 7 A SUPPLY
PROTECTED BY A MAXIMUM 15 A OVERCURRENT PROTECTIVE DEVICE.
THE PIN CONNECTOR ON THIS TYPE A WALL VALVE IS INTENDED FOR USE ON
A NOMINAL 120 V, 60 Hz, 7 A SUPPLY ONLY. IT IS REQUIRED TO BE WIRED BY A
QUALIFIED ELECTRICIAN AND IS REQUIRED TO CONFIRM
TO LOCAL ELECTRICAL CODES.
WARNING
Do not operate on wet surfaces!
NEW CONSTRUCTION
Install BUILDING WIRE CONDUCTORS (1) through the approved type electrical CONNECTOR (2) (supplied) until they
B
protrude approximately six inches from connector. Seat connector firmly into the opening atop the WIRING COMPARTMENT (4).
Insert and secure LOCKING TAB (3).
C Splice wires from INLET VALVE RECEPTACLE (7) to the protruding building wire conductors with no. 31 TWIST-ON WIRE
CONNECTORS (8) (not supplied).
NOTE: WHITE wire to WHITE wire and BLACK wire to BLACK wire.
D Feed LOW VOLTAGE RELAY WIRES (5) through opening in the LVT COVER PLATE (6) and connect to the two contact screws
of INLET VALVE FACE PLATE (9).
E Push Inlet Valve face plate (10) into MOUNTING PLATE (11 ). At the same time, push ELECTRICAL CONDUCTORS (12) and
connectors (8) into WIRING COMPARTMENT (4). Back out the two screws that hold the wiring compartment in place. Slip
upper FINISHED WALL CLIP (13) under the screw\heads and tightly fasten both wiring compartment and upper finished wall
clip (13) with MOUNTING SCREWS (supplied).
F Install the lower FINISHED WALL CLIP (14) with screws (supplied).
G Secure Inlet Valve face plate (10) to mounting plate (11) using the two supplied color matched SCREWS (15).
No. LR 61865 No. 27Z2
®
FINISHED CONSTRUCTION
After pipe, low voltage relay control wire, electrical building wires and opening in wall has been cut:
B Remove mounting plate NAILING FLANGE (16). Use a hack saw or score with razor knife along dotted line and snap off.
C Repeat step B (from NEW CONSTRUCTION).
D Install modified mounting plate with short 90° ELL glued in position into wall opening.
E Repeat steps C - G (from NEW CONSTRUCTION).
11
INSTALLATION IN EXISTING CONSTRUCTION
LOCATING ACCESS KEYS IN
EXISTING CONSTRUCTION
Unless your home is a ranch-style house where a single trunk
line can run directly through the attic or basement, you should
first investigate your house to find the key to running your
tubing from level to level. Look for an accessible area free from
obstructions that will accommodate the 2" tubing.
If you understand how your existing home is constructed, it can
be relatively easy to find access routes to run the tubing. Refer
again to the illustrations on page 4 as you consider your home
construction.
Some of the keys you might find in your home are illustrated
here.
STACKED CLOSETSORLAUNDRY CHUTE
Many homes will have an upstairs closet located directly
above a downstairs closet. It is easy to run the tubing from
one floor level to another inside these stacked closets. In these
installations the tubing is often left exposed inside the closets.
See figure below. A laundry chute could also provide access
from basement to upper floors. You may also want to consider
running exposed tubing through cabinets or cupboards.
Use the following procedures for installation in existing
construction. Wall inlets in existing construction may be
accessed from below (basement or crawl space) or from above
(attic). Instructions apply to either method.
Starting from farthest wall inlet location, install each inlet as
described below. Working back toward power unit, connect
each inlet line and branch line into main trunk line. See page
24. Complete low voltage wiring as main trunk line is continued
back to power unit. Mount power unit and complete wiring. See
pages 27-29.
AVOIDING IN-WALL OBSTACLES
The tubing which connects the inlet into the trunk line is
threaded through interior partition walls. After you’ve chosen an
inlet location, make sure the wall doesn’t contain some hidden
obstacle which will prevent you from running tubing to the inlet.
ELECTRICAL WIRING
The insulation in these walls will prevent you from running
tubing through them.
EXTERIOR WALLS
Wiring may not obstruct your tubing, but you should always
make sure that tubing does not damage the wiring. Electrical
outlets and wall switches are signs of wiring.
D0019
COLD-AIR RETURN
A cold-air return often provides a straight run from basement
to other levels of the house. See figure below. The ductwork is
easily cut for access. Seal around the tube when completing
the installation.
AD0061
DUCTWORK
Avoid choosing a section of wall that contains ducting. If you
see signs of ductwork—such as floor or ceiling registers—
move your inlet location to another section of the wall.
PLUMBING
Plumbing may or may not prevent you from running tubing
through a wall. If you must choose a plumbing wall for an inlet
location, be extremely careful when making a cutout in the wall.
WALL STUDS
Make sure your location is between wall studs. Locate studs by
tapping walls, looking for electrical outlet (usually fastened to
studs), or noticing finishing nails in the floor molding.
INSTALLING THE INLET TUBING
When your planning is complete, you will have to determine
where all the inlets and the power unit will be located. You have
also mapped out the location of your trunk line and found the
access you need to run vertical tubing from one level of your
house to another level. You should have acquainted yourself
with the methods of joining plastic tubing and acquired the
tools you’ll need to install your NuTone Central Vacuum System.
Now, you can begin installation.
The first step to install the inlet tubing which connects the wall
inlets to the branch lines. As explained before, the inlet lines
run inside interior walls. You will find access to these walls
through your attic or basement. Briefly, you want to find the
exact location in the wall, drill an access hole through the wall
plate or header, and insert the tubing into the wall cavity.
This part of your installation requires close observation and
careful measurements. Take your time and make sure you
accurately line up your access holes with the locations you’ve
chosen for your wall inlets.
12
INSTALLATION IN EXISTING CONSTRUCTION (CONT'D)
INSTALLING THE INLET TUBING (CONT'D)
LOCATING ATTIC ACCESS HOLES
Drill the access holes directly above the inlet location. To
accurately locate the access hole, you must find the space
between wall studs where the inlet is to be located. Observe the
area around the inlet location. Look for references you might be
able to find in the attic: electrical wiring, ductwork, doorways,
etc. Measure and note the distance from these references to
the inlet location.
Enter the attic and find the inlet wall. Have a helper downstairs
knock on the top of the wall right above the inlet location; locate
the general area by following the sound. Most likely, you will
have to clear away insulation. Ask your helper to continue
knocking until you locate the area between wall studs directly
above the inlet location.
Next, measure the
thickness of the wall. Mark
the exact center of the wall
where you will drill the
access hole. Remember
that the access hole must
be placed exactly in the
center of the wall.
LOCATING BASEMENT ACCESS HOLES
To locate access holes in
the basement, remove the
toe molding or baseboard
at the base of the inlet
wall. Carefully loosen the
molding or baseboard
by inserting the blade of
a putty knife behind it.
Force another putty knife
between the first knife
and the baseboard or
wall. Gently hammer a
cold chisel between the
two knife blades, prying the loosened molding away from the
baseboard or the baseboard away from the wall.
Directly below the inlet
location, drill a 1/16”
reference hole through the
floor into the basement.
(If you’re drilling through
carpet, use an awl to
slightly open the weave.
This will keep the carpet
from wrapping itself around
the drill bit.) Insert a piece
of scrap wire or a clothes
hanger into the reference
hole so you can easily find
the hole in the basement.
Drywall
AR0021A
AR0022
AR0023
Drywall
Wall Plate
Once you’ve found the location in the partition wall, you must
center the access hole in the middle of the wall. Measure half
the thickness of the wall and mark the center of the wall where
you will drill the access hole. If you cannot see the plate, you
can determine this measurement from upstairs. At the nearest
doorway, measure the thickness of the wall, including the
baseboard.
In the basement measure a distance equal to half the thickness
of the wall, using the reference hole as a starting point.
DRILLINGTHE ACCESS HOLES
Once you are certain that
you’ve located the center
of the wall directly above
the inlet location, use a
2½” hole saw to cut the
access hole through the wall
plate or header and into
the wall cavity. (A 1/2” drill
is recommended.) Remove
the drill from the hole
AR0024
carefully.
Now, use a flashlight to
inspect the wall cavity
through the access hole.
Make sure no hidden
obstacles will interfere
with the tube installation.
(If this inspection reveals
an obstacle, find a new
inlet location.) Repeat this
procedure in your attic
or basement until your
access holes are drilled.
AR0025
ASSEMBLINGTHE INLET TUBING
Once you’ve drilled the access holes, you assemble the inlet
tubing and insert it into the wall cavity. Refer to “Working With
Plastic Tubing” on pages 5-6 before you begin to assemble the
inlet lines.
Select a section of plastic
tubing and an 8” section
of the flexible inlet tubing.
Apply cement to the
outside of the plastic
tubing and to the inside of
the flexible tubing. Join the
two pieces together and
allow 5 minutes for them
to dry.
AO0013
13
INSTALLATION IN EXISTING CONSTRUCTION (CONT'D)
INSTALLING THE INLET TUBING (CONT'D)
ASSEMBLINGTHE INLET TUBING(CONT'D)
Cut a piece of low voltage
wire which is long enough
for the complete inlet line,
allowing 6” for connections
to the inlet wall plate.
Secure the wire to the
tubing with electrical tape.
AO0014
Tuck the 6” wire lead inside
the flexible tubing so that
it will not snag inside the
wall.
AO0015
If space permits, you
can assemble the entire
inlet line by joining two
sections of tubing with
a stop coupling before
dropping the assembly
into the access hole.
(Remember to only glue
the outside of the tubing
when joining two pieces of
PVC tubing.) Oftentimes,
tight attic spaces require
you to begin your drop and
then join the second section of tubing. Of course, the order of
assembly, and the length of tubing required depend on your
attic space and your wall height.
Whatever the case, insert
the completed inlet line
into the access hole and
thread it down inside the
wall. The inlet line should
be long enough so that it
extends above the joists
in the attic; at this height, it
can be easily connected to
the branch and truck lines.
When cutting the inlet
tubing to length, remember
that your inlet will be placed at 18” above the floor.
AO0016
AO0017
For a basement installation,
assemble the tubing to
the inlet flexible tubing in
the same way and insert
it into the access hole.
A basement inlet line
is necessarily shorter
because it must only reach
18” from the floor to the
inlet. Most of the time,
basement inlet lines are
more easily installed by
two people after the inlet
hole has been cut in the
interior wall. See “Wall Inlet
Installation.”
Complete all your inlet lines, and then proceed to your inlet
installations.
AO0018
WALL INLET INSTALLATION
The wall inlet design allows you to work outside the wall—
where assembly is easy and all the parts you need are
accessible. First, you make a cutout into the wall and locate the
flexible tubing attached to the inlet line which you previously
threaded into the wall. Then, you attach the flexible tubing to
the inlet mounting plate, assemble the other inlet parts, and
make the wiring connections. You place the inlet assembly into
the wall cutout, sandwiching the wall between the inner and
outer parts, and secure the inlet tightly to the wall with two
screws.
Assemble and install the wall inlet as shown in the illustrations
and as explained in the next few pages. Be careful and patient
as you make your first cutout and install your first inlet by
following the procedure step by step—the other inlets will be
easy to install in very little time.
MAKINGTHE WALL INLET CUTOUT
The wall inlet should be
located 18” on-center from
the floor and directly in line
with the attic or basement
inlet tubing hole you have
already drilled in the wall
plate or header. the wall
inlet cutout must be exactly
3 7⁄8” high by 2 7⁄8” wide. It
is crucial that you make an
accurate cutout, and we
have supplied a template
to help you.
14
INSTALLATION IN EXISTING CONSTRUCTION (CONT'D)
e
e
WALL INLET INSTALLATION (CONT'D)
MAKINGTHE WALL INLET CUTOUT (CONT'D)
Place the template against
the wall so that it is 18”
on-center from the floor.
Use a level along the top
edge of the template to
make sure it is square to
the wall. Mark your wall
for the cutout by tracing
around the inside of the
template. Then use your
pencil to mark the screw
hole locations through
punched holes at the top
and bottom of the template.
Remove the template from
the wall.
AR0027
3/8”
Use an awl or icepick to
punch pilot holes where
you marked the two hole
locations. Now, drill two
3⁄8” diameter holes, using
the pilot holes as the
centers. Locate and drill
these holes exactly as
marked with the template.
Also drill four pilot holes
in the four corners of the
marked area. Make sure
these holes are located
inside the marked line.
Then, using a utility knife,
score along the inside of
the marked line. For plaster
walls, score the plaster
deeply, being careful to
stay inside the marked line.
Next, use a keyhole saw
or a sabersaw to make the
cutout. Again, be extremely
careful to cut along the
inside of the marked line.
CAUTION
When cutting into
plaster walls, make
sure the plaster is firm
and secure around
the cutout area.
AR0028A
AR0032A
AR0033A
DIA.
HOLES
Pilot holes must b
inside marked line
Cut
along
inside
of marked
line
ATTACHINGTHE INLET MOUNTING PLATE
Reach through the inlet
hole and locate the inlet
tubing. Raise it up inside
the wall until you locate
the inlet tubing. If the inlet
is connected from the
basement, have a helper
insert the inlet tubing into
the access hole until you
can see the flexible tubing.
Then, pull the flexible
tubing through the inlet
hole and remove the low
voltage wiring from inside
the tube. If the end of the flexible tubing is not even, trim it so
that it is exactly even.
Now, remove the nail
flange (used for new
construction) from the inlet
mounting plate. Use pliers
to bend this flange along
the scored lines until you
can break it off.
Apply cement to both the
inside of the flexible tubing
and to the outside of the
mounting plate’s tube ring.
Insert the mounting plate’s
tube ring in the flexible
tubing and twisting the
pieces as you join them
to spread the cement, and
align the mounting plate in
a vertical position.
Hold the assembly in place for a few minutes as the cement
sets; allow 5 minutes for the cement to completely dry.
Now, strip the ends of the two low voltage wires, and then
connect the wires to the screw terminals on the back of the
inlet cover. Make sure the wires are tightly secured under the
terminal screws.
AO0041
15
AO0038
Nail Flang
AO0039A
AO0040
AO0042
INSTALLATION IN EXISTING CONSTRUCTION (CONT'D)
WALL INLET INSTALLATION (CONT'D)
ATTACHINGTHE INLET MOUNTING PLATE (CONT'D)
When the wiring is complete, assemble the inlet cover to the
tube guard and mounting plate. Insert the top screw through
the entire inlet assembly until the screw engages the mounting
plate.
AO0043
COMPLETING INLET ASSEMBLY
Once you have attached the
mounting plate to the flexible
tubing, pull the low voltage wire
through the top wiring hole in
the mounting plate.
AR0034
Insert the bottom screw into
the inlet cover and through the
other parts. Give the screw a
few turns until it firmly engages
in the mounting plate. Now,
level and slightly lower the
assembly. Make sure the wall is
sandwiched between the inner
and outer parts—you’ll be able
to feel if mounting plate is firmly
centered on the inside of the
AO0047
wall.
Hold the inlet in place and
gradually tighten down each
screw a little bit at a time. (If you
completely tighten down one
screw at a time, the mounting
plate may pull away from the
wall at the loose end and slip
back into the cutout.)
AR0035
Complete all your wall inlet installations in this manner. If your
cutouts are accurate, each wall inlet will install more quickly
and easily.
INSTALLINGTHE INLET
When you place the inlet into
the wall cutout, the mounting
plate and tube guard slip inside
the wall; the inlet cover remains
on the outside.
Holding the inlet assembly
between your thumbs and
fingers, angle the bottom of the
mounting plate into the cutout.
Push the assembly downward
until you have clearance at the
top of the cutout.
Push the top of the mounting
plate into the cutout and lift the
assembly upward until the top
screw seats in the predrilled
hole. At this point, the wall
should be sandwiched between
the mounting plate and the
frame plate.
INLET
AE0024A
AO0044
AO0045
AO0046
MOUNTING
PLATE
360 SERIES INLETS
(CF361 OR CF361F ROUGH-IN)
NOTE: If 330 wall inlet is being used refer to Model 330 Series
Wall Inlet on next page.
B If area is clear, cut an inlet opening in the wall approximately
18" above the floor. Make sure wall opening and 2½" tube
hole line up (see figure below).
31/16 "
29/16 "
21/2"
18"
AD0062
16
INSTALLATION IN EXISTING CONSTRUCTION (CONT'D)
e
360 SERIES INLETS
(CF361 OR CF361F ROUGH-IN) (CONT'D)
NOTE: If the wall for mounting the Model 360 inlet is less than
1⁄2", a spacer must be used. See figure below as a
guide.
INLET MOUNTING
BRACKET
SPACER
1/4"
WALL LESS THAN
1
/2" THICK.
F Attach the low voltage wires
to terminal screws on back
of wall inlet (see figure at
right). If using 361 Rough-in
with CI370 Series Inlets,
refer to instructions on page 7,
step D, shown in its figure.
AO0071
21/4"
AD0057A
C Cut a length of tubing that will extend from inlet opening to a
31/4"
PLASTER
GUARD
HOLE
point below floor level (or above ceiling level in attic
installation). Tape low voltage wire to tube and insert tube
through predrilled hole to a level opposite the wall opening.
FLANGED
FITTING
D Apply cement to tube and
install flanged wall fitting.
Make sure fitting is well
seated and sealed (see
LOW
VOLTAGE
WIRING
figure at right).
AD0064A
E Remove plaster frame from mounting bracket. Pull low
voltage wire through hole in bracket and insert bracket into
cutout. Secure bracket to flanged fitting with 4 screws
provided. Be sure seal is secure between flange fitting and
mounting bracket (see figure below).
G Insert wall inlet into bracket
and secure with the two
screws provided (see figure
at right).
AR0047
MODEL 330 SERIES
WALL INLET INSTALLATION
(CF329 ROUGH-IN)
1/4"
(6 mm)
7
/8"
B Make cutout according to
dimensions in figure at right.
AD0020A
C Refer to figure at right. Break
off nail plate at scored line.
3
(98 mm)
1/4"
(6 mm)
3
/4"
2
(70 mm)
3/8
" (10 mm) DIA.
3/8
" (10 mm) DIA.
3
/8"
1
(35 mm)
Nail Flang
AD0063
AO0039A
MOUNTING
D Refer to figure at right. Glue
elbow to mounting plate,
PLATE
ELBOW
place assembly into cutout,
and attach elbow to tubing
inside the wall.
MOUNTING
HOLE (2)
AD0021A
17
INSTALLATION IN EXISTING CONSTRUCTION (CONT'D)
MODEL 330 SERIES
INLET
EXTENSION
MOUNTING
BRACKET
CUT TO
LENGTH
EXTENSION
SLEEVE
FLOOR
INLET
9
/16"
2
WALL
INLET
WALL INLET INSTALLATION
(CF329 ROUGH-IN) (
E Make sure mounting holes are exactly at top and bottom.
F Connect 2-conductor low voltage wire to terminal screws on
back of wall inlet.
G Refer to figure at right.
Align inlet mounting holes with
mounting plate holes, place
inlet into mounting plate, and
secure with provided screws.
NOTE: If CF382S shorter radius elbow is used, it may be
necessary to use the short mounting screw to avoid
interference with elbow.
CONT'D)
INLET
AE0024A
MOUNTING
PLATE
FLOOR INLET INSTALLATION IN
NEW & EXISTING CONSTRUCTION
MODEL 360 SERIES INLETS (361 ROUGH-IN)
B Refer to both figures below. After floor inlet location has been
selected, cut a 3 ¹⁄16" x 2 9⁄16" square hole in floor. Center line
of inlet must be located at least 2½" from wall to allow cover
to be opened when hose is inserted.
TOP VIEW
9
/16"
2
1
3
/16"
AD0067A
SIDE VIEW
AD0068A
C Determine direction of tubing and attach appropriate flanged
MOLDING
21/2" MIN.
APPROX.
fitting to mounting bracket with four (4) screws supplied. Be
sure mounting bracket flange does not interfere with tubing
and seal is securely in place.
WALL
MOUNTING BRACKET
FLANGE
D Refer to figure
at right. Position
bracket with
FLOOR
SUB-FLOOR
frame and flanged
fitting assembly
into cutout from
below and secure
to sub-floor.
AD0069A
E Refer to figure at
right. Large end of
Model 399
extension sleeve
should be cut
to length to allow
proper seating of
inlet against floor
or carpet.
F Refer to figure at
FLANGED
FITTING
AD0070A
right. Pull
low-voltage
2-conductor wire
through mounting
bracket and attach
to terminal screws
on back of floor
inlet. Cement
extension sleeve
to Model 360 inlet.
Insert extension
TUBING
sleeve through
vinyl gasket in
AD0071A
mounting bracket
and firmly seat into flanged fitting.
G For convenience of operation, floor inlet should be installed
to open back toward wall.
H Refer to figure of step D. Secure floor inlet in place with two
screws.
31/16"
FRAME
SEAL
FLANGED
FITTING
MOUNTING
BRACKET
FLANGE
EXTENSION SLEEVE
BRACKETFLANGED FITTING
18
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.