SER-485-IC_0710 R2
22..
IInnffoorrmmaattiioonn –– UULL CCllaassss 11 DDiivv 22
1. Power, input /output (I/O) wiring must be in
accordance with Class 1 Division 2 wiring methods
[Article 501.10(B) of the National Electric code,
NFPA70] and in accordance with the local authority
having jurisdiction.
2. Maximum ambient air temperature 80°
3. WARNING – EXPLOSION HAZARD:
SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABLITY FOR CLASS 1, DIVISION 2.
4. WARNING – EXPLOSION HAZARD: WHEN IN
HAZARDOUS LOCATIONS, TURNING OFF
POWER BEFORE REPLACING OR WIRING
MODULES
5. WARNING – EXPLOSION HAZARD: DO NOT
DISCONNECT EQUIPMENT UNLESS POWER HAS
BEEN SWITCHED OFF OR THE AREA IS KNOWN
TO BE NON-HAZARDOUS.
6. WARNING – THIS APPARATUS IS SUITABLE FOR
USE IN CLASS 1 DIVISION 2, GROUPS A, B, C,
AND D, OR UNCLASSIFIED AREAS.
11.. CChheecckk ffoorr RReeqquuiirreedd HHaarrddwwaarree
SER-485-IC Serial Converter
This Quick Start Guide
Additional Items Required but not included
o A 10 to 48 VDC Power Supply, 0.2A.
o RS-232 cable. The converter is a DCE device.
o RS-422/485 Cable.
Quick Start Guide
SER-485-IC
Triple Isolated RS-232 to
RS-422/485 Converter
44..
IInnffoorrmmaattiioonn -- DDIIPP SSwwiittcchh
Communications Mode
33..
IInnffoorrmmaattiioonn –– FFrroonntt PPaanneell
Front Panel
Red, Flashes when RS-422/485
Red Flashes when RS-422/485
Red, ON When Power Applied
Receive Line Signal Detector (DCD)
Note: Pin 1, Pin 4, and Pin 6 are tied together internally.
Pin 7and Pin 8 are tied together internally.
RS-422/485 Terminal Block
Put
820 S. University Blvd. Suite 4E, Mobile, AL 36609
PH: 251-342-2164 · FAX: 251-342-6353
N-Tron Corp.
66..
PPoowweerr CCoonnnneeccttiioonn
Power Requirements:
10 – 48 VDC @ 0.2A
77..
RRSS--223322 CCoonnnneeccttiioonn
1. DB9 F is DCE, Pin 2(RD) is the converter’s RS-232
Data output. Pin 3 (TD) is the converter’s RS-232
Data input.
2. Pins 1, 4, and 6 (DCD, DTR, and DSR) are tied
together inside the converter.
3. Pins 7 and 8 (RTS and CTS) are tied together
inside the converter.
88..
WWiirriinngg EExxaammpplleess
Two Wire RS-485
99..
LLoooopp BBaacckk TTeesstt // TTrroouubblleesshhoooottiinngg
Configure for RS-485 Four wire, 9600 baud
Jumper terminals B to D and C to E
Connect a PC to the RS-232 port (see Step 7).
Using hyper terminal or similar program, connect to
the appropriate COM port (remember to set the
baud rate to 9600).Turn off hyper terminal local
echo
Transmit data. The same data should be returned.
LED Indicators: Power is ON when power is applied.
TD flashes when RS-422/485 data is sent. RD
flashes when RS-422/485 Data is received.
55..
RRSS--442222//448855 TTiimmee OOuutt
Pre-defined timeouts are set using switches 8 through 12.
Resistor selectable baud rates are set by inserting a through
hole resistor (R-11) on the circuit board.
Timeout selections are equal to one character time at the
indicated baud rate. Setting the converter to 9600 will
generally work at 9600 and higher baud rates. In RS-422
mode, timeouts are not required.
SER-485-IC_0710 R2
820 S. University Blvd. Suite 4E, Mobile, AL 36609
PH: 251-342-2164 · FAX: 251-342-6353
N-Tron Corp.