NOVUS TP506 User Manual

EXPLODED VIEW OF THE TRANSMITTER
PRODUTOS ELETRÔNICOS LTDA
NOVUS PRODUTOS ELETRÔNICOS LTDA.
Rua Ramiro Barcelos 157, CEP 90035-004 - Porto Alegre - RS - Brazil
Tel.: 55-51-284-3600 Fax: 225-7306
55-51-
E-mail: info@novus.com.br
PRESSURE TRANSMITTERS - SERIES 506
OPERATION MANUAL
CHARACTERISTICS Excitation Voltage (Vexc.): 11 to 33 Vdc Maximum Load Impedance (RLmax): RLmax = (Vexc.-11V)/20mA Accuracy< 1.0% of FS for ranges between 7 and 10 bar < 0.5% of FS E 10 and 60 bar including non-linearity, hysteresis and repeatability. Overload: 2 times measuring range limited to 80 bar. Rupture pressure: 3 times 90 bar. Weight: 70 grams
SPECIFICATIONS Operating Temperature: -40 to 80 °C Thermal Deviation: <0.04% of FS/°C between 7 and 60 bar Thermal Sensitivity: < 0.015% of FS/°C Dinamic Response: < 5ms Compatibility: gases and ;liquids compatible with ceramic and stainless steel. Process Connection: external thread ¼ - 18NPT (basic model) Electrical Connector: DIN 43650-A Connector Protection Class: IP65
Electromagnetic Compatibility: CE conformity to EC directive 89/336 (EMC): Electrostatic Discharge (IEC 1000-4-2):8kV on air, 4kV on contacts, no falilure. High Frequence electromagnetic radiation: ENV 50140 10V/m from 80 to 1GHz. Fast transients (burst): IEC 801-4, 2kV, no failure. Magnetic fields: EN 61000-4-8, 50Hz 30A/m, no failure. Conducted interference: EN 55022; 0.15 to 30MHz, no effect. Radiation from housing: 30 to 1000Hz, no effect at 10 meters.
for ranges between
measuring range limited to
1.405 (AISI 303)
COVERFIXING SCREW
TRANSMITTERSEALCONNECTOR
ELECTRICAL CONNECTIONS
VOLTAGE
SOURCE
VVDCDC
1
2
8888
LOAD
3
CONNECTOR
DIN
The Voltage Source in the upper circuit must have a voltage defined as to allow an Excitation Voltage range on the transmitter within the 11 to 33 Vdc limit.
The LOAD element in this circuit corresponds to the pressure meter. This can be a digital indicator, a controller, a recorder, etc. The LOAD maximum impedance can be calculated in relation to the voltage applied, according to the equation below:
(VDC - 11V)
RLmax=
____________
20mA
The 4 to 20mA output signal is the current flowing through the transmitter. 4mA corresponds to the lower pressure limit and 20mA corresponds to the upper pressure limit. These limits are shown in the pressure transmitter label .