-Air
Dew point: -40.0 °C and 100.0 °C
measurement errors can be discarded
through the soft ware’ s OFFSET parameter.
A minimum of 15 seconds. No more than 30
minutes (1800 s)
ve RP SMA (Plug) connector for
128 (Advanced Encryption
Standard).
The product is suitable for applications that
60 x 70 x 35 mm + antenna 105 mm + sensor
37.2 mm
configuration environme nt
It configures, reads and displays data on the
screen.
OR TEMPERATURE AND HUMIDITY – INSTRUCTIONS MANUAL V1.0x A
1 INTRODUCTION
RHT-Air comes with a high precision and stability sensor to measure both
temperature and relative humidity. Because it operates with a
microprocessor, it can be fully configured through it s USB and IEEE 8 02.15.4
interfaces, using Modbus RTU commands. The software DigiConfig enables
for all the eq uipment’s res ources to be configured.
RHT-Air can be configured to display the temperature and Relative Humidity
measured or even, the temp erature and the Dew Point
RHT-Air should be connected (via wireless) to an AirGate-Modbus so that
its registers can be read whenever it is in operation.
1.1 IDENTIFICATION
The following elements appear in the front part of the equipment:
Fig. 1 – RHT-Air main screen
Communication Indicator (COM): It signals that the device is receiving data
from the Modb us network.
Button (Programming): This button is used to configure the Modbus
address, the Update Interv al and screen changes.
Temperature: Room temperature measured by the equipment.
Relative Humidity: Relative Humidity measur e me nt.
2 SPECIFICATIONS
Equipment’s operat ing
temperature
Electromagnetic
compatibility
Sensor’s me asurement
range
Precision of
measurements
Resolution of
measurements:
Response time
(Sensor)
Interval bet ween updates
Power supply
Connections
Wireless
RTH-Air = from -10 °C to 70 °C
EMC: EN61326-1:2006 CISPR11/EN55011,
EN61000-4-2, EN61000-4-3, EN61000-4-4,
EN61000-4-6, EN61000-4-8
Temperature: -40.0 °C to 100.0 °C.
Relative Humidity (RH): 0.0 to 100.0 % RH.
(No Condensat ion)
See Fig. 3.
Note:
Temperature: 0.1 °C. 14 bits (16383 levels)
Relative Humidity (RH): 0.1 %. 12 bits (4095
Temperature: Up to 30 s in slow moving air.
Humidity: Up to 8 s in softly moving air (20 to
12 Vdc to 30 Vdc, consumption < 100 mA or
Lithium batt ery of 3.6 Vcc (1/2 AA), internal.
• Internal USB Device (Miniconfiguration and firmware update.
• Groo
antenna.
•
Power supply connector.
• Maximum transmission power of 25,11
mW (14 dBm).
• Maximum Range: 500 meters line-of-sight
in open field.
• Receptor sensibility - 92 dBm.
• Operation band ISM 2.4 GHz.
• DSSS Technology -
Spread Spect rum.
• OQPSK Modulation -
Phase Shift Keying.
• 15 operation channels .
• AES-CBC-
Fig. 2 – RHT-Air’s second screen
Communication Address: Programmed value to identify the Modbus
network equipment. Programmable betw een
NOVUS AUTOMATION 1/8
require a level of protection of up to IP65.
Electronic module box: IP65; Sensor capsule:
Configurati on Software Windows®.
Menus in Portuguese, English or Spanish.
and
Level of protecti on
.
Dimensions
Weight 171 grams / 40 grams (cable)
DigiConfig software
Certifications CE, ANATEL (0172-13-7089)
2.1 PRECISION OF MEASUREMENTS AND OPERATIONAL LIMITS OF SENSORS:
Fig. 3 - Precision of the humidity and temperature measurement
3 MECHANICAL INSTALATION
RHT-Air was designed to be attached to walls. By removing the equipment’s
cover, users will have access to two molding holes of the base, as shown in
Fig. 4. The equipment should be attached with the sensor capsule
facing downwards in order to ensure precision and the specified level
or protection.
Fig. 4 - RHT-Air mounting holes and measures
4 CONFIGURATION
4.1 CONFIGURATION VIA USB INTERFACE
Initially, the first conf iguration must be done through USB interface.
• Remove the four set screws of the front panel of the equipment RHT-Air,
taking the necessary precaution not to apply force on the internal connector
of the electronic circ ui t.
• In order to configure it through a USB interface, connect the cable as
shown below. The external power cord should not be used during the
configuration.
5 ELECTRICAL INSTALLATION
5.1 EXTERNAL POWER SUPPLYING
Fig. 6 below shows RHT-Air’s necessary electrical connection. Terminals
1 and 2 are to be used in the electrical connection and terminals 3 and 4
Fig. 5 - RHT-Air Measurements
NOVUS AUTOMATION 2/8
are not used.
1 - VDC Power Supply Black wire
2 + VDC Power Supply White Wire
3 Not used Blue wire
4 Not used Brown Wire
RHT-Air
• After removing the front panel, change the position of the jumper (J1) to
“BAT” so that it can be supplied through the battery. Replace the front
panel, by placing the four set screws, taking the necessary precaution
not to apply force on the internal connector of the electronic circuit.
Fig. 6 - Electrical wiring
• RHT-Air is manufactured with the jumper (J1) set in the position “EXT”
for external power supply .
5.1.1 RECOMENDATIONS FOR INSTALLATION
• Conductors of small electric signals must be separated from activation
conductors or higher current or power in the system’s plan, if possible in
grounded electroducts.
• The instrument’s supply must come from a network proper for
instrumentation.
• In control and monitoring applications, it is essential to consider what
may happen when any part of t he system fails.
• The use of RC FILTERS (47 Ω and 100 nF, series) in parallel with
contactor and solenoid coi ls, etc. is recommended.
5.2 BATTERY POWER SUPPLY
RHT-Air can be supplied by an internal battery whenever the equipment is
not energized by the electrical grid. Below are guidelines on how to proceed
for supplyin g power with a battery:
• Remove the four set screws of the front panel of the equipment RHT-Air,
taking the necessary precaution not to apply force on the internal connector
of the electronic circ ui t.
5.2.1 REPLACING THE INTERNAL BATTERY
It is possible to check the battery’s charge through register “29”. A full y charged
battery typically has a power above 3.6 V. As you use the RHT-Air, the power
of the battery will gradually decrease. It is recommended that you check the
value of registry “29" regularly so that when it reaches below 3.3 V, the battery
can be replaced.
Note: Even when the power is below 100 %, the equipment will operate
normally.
Only suitable replacement battery for this product is:
• Remove the four set screws of the front panel, taking the necessary
precaution not to apply force on the internal connector of the electronic
circuit. After removing the front panel, replace the battery, taking the
necessary precaution not to to uch the electronic circuit.
MANUFACTURER: OMNICELL
MODEL: ER14250HD
• Insert a new battery and replace the front panel carefully, placing the
four molding screws.
6 CONFIGURATION / OPERATION
NOVUS AUTOMATION 3/8
The application DigiConfig is a Windows® software used for configuring
RHT-Air. In order to install it, please run the file “DigiConfigSetup.exe” from
the CD that comes with the equipment and follow the inst ructions therein.
DigiConfig comes with an unabridged help tutorial, containing all the
necessary information for you to use it. If you want to use help tutorial, start
the applicat ion and select t he "Help” menu or press "F1".
If you do not have the CD that comes with the equipment, go to
www.novusautomation.com
manual guides.
Users will receive the fully calibrated adjustment-free equipment. The original
configuration is s hown below :
(Communication address) = 246
Time (Update interval) = 60
to get the DigiConfig installer and the additional