While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull st ati ons, audib le
warning devices, and a fire alarm control panel with remote
notification capability—can provi de early warn ing of a develop
ing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association S tandard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the recommen
dations contained in the Guides for Proper Use o f System
Smoke Detectors, which are made available at no charge to all
installing dealers. These documents can be found at http://
www.systemsensor.com/html/applicat.html. A study by the
Federal Emergency Management Agency (an agency of the
United States government) indicated that smoke detectors
may not go off in as many as 35% of all fires. While fire al arm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A fire
alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behi nd walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a firstfloor or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ion
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires d evelop in dif ferent
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors incre ases at a predete r
mined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over t ime.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro
tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys
tem for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crip
pling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building .
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica
-
tion. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilep sy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsi
bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from st and by
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele
phone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan
dards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A main
tenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections
should be kept.
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ
ated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro
gramming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All compo
nents, circuits, system operations, or sof tware functions known
to be affected by a change must be 100% tested. In addit ion,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (non
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic com
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indicating device loops. Most devices cannot tol erate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subject ed to light
ning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Ser
vices Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi
cations, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal
contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han
dling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the inst al lati on, opera ting, and pr ogramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and rel iability depend upon prop er inst allatio n.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edict e p ar l e
ministere des Communications du Canada.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®,
VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of
Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft
Corporation.
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact T echnical Support with any questions about software and the appropriate version for
a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct /improve documentation
Section 1: General Information................................................................................................8
1.1: UL 864 Compliance.......................................................................................................................................8
1.2: About This Manual........................................................................................................................................8
1.2.1: Cautions and Warnings........................................................................................................................8
1.2.4: Shortcuts to Operating Functions......................................................................................................10
1.3: Introduction to the Control Panel ................................................................................................................10
Section 2: Use of the Controls...............................................................................................11
2.2: System Status Indicator LEDs.............................................................. .......................................................11
2.3: Control Keys................................................................................................................................................12
2.3.2: Signal Silence....................................................................................................................................13
2.3.3: System Reset .....................................................................................................................................13
3.2: Normal Mode of Operation .........................................................................................................................16
3.3: Fire Alarm Mode of Operation....................................................................................................................17
3.3.1: How the Control Panel Indicates a Fire Alarm..................................................................................17
3.3.2: How to Respond to a Fire Alarm.......................................................................................................17
3.3.3: Interpreting Fire Alarm Type Codes .................................................................................................18
3.4: Carbon Monoxide (CO) Alarm Mode of Operation....................................................................................20
3.4.1: How the Control Panel Indicates a CO Alarm ..................................................................................20
3.4.2: How to Respond to a CO alarm.........................................................................................................20
3.4.3: Interpreting CO Alarm/Supervisory Type ID Codes.........................................................................21
3.5: System Trouble Mode of Operation ............................................................................................................21
3.5.1: How the Control Panel Indicates a System Trouble..........................................................................21
3.5.2: How to Respond to a System Trouble...............................................................................................22
3.6: Security Alarm Mode of Operation.............................................................................................................23
3.6.1: How the Control Panel Indicates a Security Alarm...........................................................................23
3.6.2: How to Respond to a Security Alarm................................................................................................23
3.6.3: Interpreting Security Type Codes......................................................................................................24
3.7: Active Supervisory Signal Mode of Operation ...........................................................................................24
3.7.1: How the Control Panel Indicates an Active Supervisory ..................................................................24
3.7.2: How to Respond to an Active Supervisory .......................................................................................25
3.7.3: How to Interpret Supervisory Type Codes........................................................................................25
3.8: Pre-Alarm Warning Mode of Operation......................................................................................................26
3.8.1: How the Control Panel Indicates a Pre-Alarm Warning ...................................................................26
3.8.2: How to Respond to a Pre-Alarm Warning.........................................................................................27
3.9: Disabled Points Mode of Operation ............................................................................................................28
3.10: Non-Alarm Mode of Operation ....................................................... ..........................................................28
3.10.1: Purpose of Non-Alarm Points..........................................................................................................28
3.10.2: How the Control Panel Indicates an Active Fire Control................................................................29
3.10.3: How the Control Panel Indicates an Active Non-Fire Point .... .......................................................29
3.11: Active Trouble Monitor Mode of Operation..............................................................................................29
3.11.1: How the Control Panel Indicates an Active Trouble Monitor .........................................................29
3.11.2: How to Respond to an Active Trouble Monitor..............................................................................30
3.12: Output Circuit Trouble Mode of Operation...............................................................................................30
4.2: What is Read Status?........................ .................................. .................................. ........................................34
A.2: Releasing Zones (R0-R9)............................................................................................................................49
A.2.1: Purpose of Releasing Zones .............................................................................................................49
A.2.2: How to View Releasing Zone Selections .........................................................................................50
A.2.3: How Releasing Zones Operate .........................................................................................................50
A.3: Time, Date, and Holiday Functions............................................................................................................52
C.1: General Description.....................................................................................................................................60
C.3: Using the CRT-2 for Read Status ................................................................................................................62
C.3.4: Display Devices in Alarm or Trouble...............................................................................................63
C.3.5: Display All Programmed Points .......................................................................................................64
C.3.6: Step-through History .........................................................................................................................64
C.3.7: View All History...............................................................................................................................64
C.3.8: Step-through Alarm History .............................................................................................................64
C.3.9: View All Alarm History....................................................................................................................64
C.4: Using the CRT-2 for Alter Status ................................................................................................................64
C.4.6: Clear the Entire History Buffer................................. .. ......................................................................66
C.4.7: Set the Pre-Alarm for Alert or Action...............................................................................................67
Appendix D: Point and System Troubles Lists....................................................................68
D.1: Point (Device) Troubles ..............................................................................................................................68
D.2: System Troubles..........................................................................................................................................69
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864 9th Edition.
1.2 About This Manual
1.2.1 Cautions and Warnings
This manual contains cautions and warnings to alert the reader as follows:
CAUTION:
Information about procedures that could cause programming errors, runtime errors, or equipment
damage.
WARNING:
Indicates information about procedures that could cause irreversible damage to the control panel,
irreversible loss of programming data or personal injury.
1.2.2 Typographic Conventions
This manual uses the following typographic conventions as listed in below:
When you seeSpecifiesExample
text in small capsthe text as it appears in the
LCD display or on the control
panel
text in quotesa reference to a section or a
LCD menu screen
bold textIn body text, a number or
character that you enter
italic texta specific documentNFS-320 Installation Manual
a graphic of the keyIn a graphic, a key as it
appears on the control panel
Table 1.1 Typographic Conventions in this Manual
NOTE: In this manual, the term NFS-320 is used to refer to the NFS-320, NFS-320E, and
NFS-320C, NFS-320SYS and NFS-320SYS/E unless otherwise noted.
MARCHTIME is a selection that appears in the
LCD display; or Press the
“Read Status”; specifies the Read S tatus section
or menu screen
Press 1; means to press the number “1” on the
keypad
The table below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-NOT) provides the current
document revision. A copy of this document is included in every shipment.
Compatible Conventional Devices (Non-addressable)Document Number
Device Compatibility Document15378
Fire Alarm Control Panel (FACP) and Main Power Supply InstallationDocument Number
NFS-320/E/C Installation, Operations, and Programming Manuals
NFS-320C Canadian Applications Addendum
NFS-320SYS/E/C Installation Manual53717
SLC Wiring Manual51253
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming UtilityDocument Number
VeriFire® Tools CD help fileVERIFIRE-TCD
Power Supplies, Auxiliary Power Supplies & Battery ChargersDocument Number
General InformationIntroduction to the Control Panel
1.2.4 Shortcuts to Operating Functions
T o the left of each program function, you’ll find a keypad shortcut, which contains a
series of keypad entries required to access the program function. All shortcuts start
with the control panel in normal operation.
For example, the keypad shortcut to the left, shows how to enter the Read Status
function with the control panel in normal operation, as well as how to exit the
function.
1.3 Introduction to the Control Panel
The NFS-320 is a modular, intelligent Fire Alarm Control Panel (FACP) with features suitable for
most applications. Following is a list of operating features available.
•Alarm Verification selection, to reduce unwanted alarms, for intell igent detector points
•Positive Alarm Sequence (PAS) and Presignal per NFPA 72
•Silence Inhibit timer and Auto Silence timer for Notification Appliance Circuits (NACs)
•March time/temporal code for Notification Appliance Circuits (NACs)
•Programmable Signal Silence, System Reset, and Alarm Activate functions through monitor
modules
•Automatic time-of-day and day-of-week control functions, with holiday option
•Intelligent Sensing with nine field-adjustable Pre-Alarm levels with programmable
Control-By-Event (CBE)
•Operate automatic smoke or heat detector sounder base on action Pre-Alarm level, with
general evacuation on alarm level
•Security alarm point option with separate audible signal code
•Audible alarm signaling options
•Programmable Control-By-Event control of outputs from individual alarm or supervisory
addressable devices
•Networks with other FACPs and equipment for large applications.
You can also press this key to display multiple alarms or troubles. If more than one alarm or trouble
exists, the control panel displays the next alarm or trouble for 3 seconds (or until you press the
ACKNOWLEDGE/SCROLLDISPLAYkey), then displays the next alarm or trouble.
NOTE: If Local Control is set to “0” (NO), the FACP will not respond to ACKNOWLEDGE, and the
piezo will not sound.
2.3.2 Signal Silence
Use the SIGNALSILENCE key to silence the panel sounder and turn off all audio and visual devices
connected to Notification Appliance Circuits. When pressed, the control panel does the following:
•Turns off the panel sounder
•Turns off all silenceable output circuits
•Lights the SIGNALSSILENCED LED
•Sends a SIGNALSSILENCEDmessage to the History buffer and installed printers, CRT-2
terminals, and FDU-80 annunciators
Partial Signal Silence
When some active outputs are silenced and others remain constant, the SIGNALSSILENCED LED
will flash
NOTE: If Local Control is set to “0” (NO) or “2” (Partial Control), the FACP will not respond to
SIGNALSILENCE.
2.3.3 System Reset
Use the SYSTEMRESET key to reset the control panel. When pressed, the control panel does the
following:
•Clears ALL active inputs
•Interrupts resettable power
•Sends a “System Reset” message to the History buffer, and installed printers, CRT-2 terminals,
and FDU-80 annunciators
•Decouples from Noti•Fire•Net, if connected, for 60 seconds to allow Cooperative Control By
Event (CCBE) to clear.
If any alarm or trouble exists after you press the SYSTEMRESET key, all NACs, contr ol output s, and
panel audio and visual indicators will reactivate.
NOTE: Trouble conditions will not clear and re-report upon reset.
NOTE: If Local Control is set to “0” (NO), the FACP will not respond to SYSTEMRESET.
Use the DRILL key to manually activate all silenceable outputs and Notification Appliance Circuits.
To prevent accidental activation, you must press the
control panel does the following:
•Turns on all silenceable NACs
•Turns off the SIGNALSSILENCED LED
•Sends a Manual Evacuate message to the History buffer and installed printers, CRT-2
terminals, and FDU-80 annunciators
NOTE: If Local Control is set to “0” (NO) or “2” (Partial Control), the FACP will not respond to
DRILL.
DRILL key for 2 seconds. When pressed, the
2.3.5 Lamp Test
Use the LAMPTEST key to test the control panel LEDs and the panel sounder. When pressed and
held, the control panel does the following:
•Lights all control panel LEDs
•Turns on the panel sounder
•Lights all segments of the LCD display. When the LAMPTEST key is held for longer than five
seconds, the LCD will display the Software Revisions.
This section contains instructions for operating the control panel. Listed below are the topics
detailed in this section:
SectionRefer to Page
3.2, "Normal Mode of Operation"page 16
3.3, "Fire Alarm Mode of Operation"page 17
3.4, "Carbon Monoxide (CO) Alarm Mode of Operation"page 22
3.5, "System Trouble Mode of Operation"page 23
3.5, "System Trouble Mode of Operation"page 21
3.6, "Security Alarm Mode of Operation"page 23
3.7, "Active Supervisory Signal Mode of Operation"page 24
3.8, "Pre-Alarm Warning Mode of Operation"page 26
3.9, "Disabled Points Mode of Operation"page 28
3.10, "Non-Alarm Mode of Operation"page 28
3.11, "Active Trouble Monitor Mode of Operation"page 29
3.12, "Output Circuit Trouble Mode of Operation"page 30
3.13, "Operation of Special System Timers"page 32
3.14, "Waterflow Circuit Operation"page 33
3.15, "Style 6 and Style 7 Operation"page 33
This manual also contains information on operating the control panel in the appendixes, listed as
follows:
•Appendix A, “Special Zone Operation”, on page 49
•Appendix B, “Intelligent Detector Functions”, on page 58
•Appendix C.3, “Remote Terminal Mode Functions”, on page 62
•Appendix D, “Point and System Troubles Lists”, on page 68
WARNING:
When used for CO2 releasing applications, observe proper precautions as stated in NFPA 12. Do not
enter the protected space unless physical lockout and other safety procedures are fully completed.
Do not use software disable functions in the panel as lockout.
3.2 Normal Mode of Operation
The system operates in Normal mode when no alarms or troubles exist. In Normal mode, the
control panel displays a System Normal message as follows
•Sends an Alarm message to the LCD display, History buffer and installed printers, FDU-80
annunciators, and CRT-2s.
•Latches the control panel in alarm. (You can not return the control panel to normal operation
until you correct the alarm condition and reset the control panel)
•Initiates any Control-By-Event actions
•Starts timers (such as Silence Inhibit, Auto Silence)
•Activates the general alarm zone (Z00)
3.3.2 How to Respond to a Fire Alarm
If the control panel indicates a fire alarm, you can do the following:
•To silence only the panel sounder:
Press the ACKNOWLEDGE/SCROLLDISPLAY key. The local sounder will silence and the FIRE
ALARM LED will change from flashing to steady.
The control panel will send an acknowledge message to the LCD display, history buffer, and
installed printers, FDU-80 annunciators, and CRT-2s.
Page 18
Operation of the Control PanelFire Alarm Mode of Operation
Status banner
Time and date of the
Alarm Silenced
SIGNALS SILENCED
03:12P 011508 Tue
•To silence the panel sounder and any activated outputs that are programmed as silenceable:
Press the SIGNALSILENCE key . The FIREALARM LED and SIGNALSSILENCED LED light steady.
The control panel sends an Signal Silenced message to the History buffer and installed
printers, FDU-80 annunciators, and CRT-2s. The figure below shows a sample Alarm Silenced
message.
Figure 3.3 Sample Alarm Silenced Message
1.Check the Alarm message for the location and type of trouble.
2.Correct the condition causing the alarm.
3.When you finish correcting the alarm condition, press the
SYSTEMRESET key to return the
control panel to normal operation (indicated by the “System Normal” message). The control
panel sends a “System Normal” message to the LCD display, History buffer and installed
printers, FDU-80 annunciators, and CRT-2s.
3.3.3 Interpreting Fire Alarm Type Codes
The Type Code that displays in the Alarm message indicates the function of the point that initiates
the fire alarm. For example, a monitor module with a
PULLSTATION Type Code means that the
monitor module connects to a manual pull station. The table below lists the Type Codes that can
appear in an alarm message:
Type Code
Latching
(Y/N)
PurposeWhat it does
Monitor Modules
BlankYIndicates activation of a device with no descriptionLights FIREALARM LED and activates CBE
HEAT DETECTYIndicates activation of a conventional heat detectorLights FIREALARM LED and activates CBE
MONITORYIndicates activation of an alarm-monitoring deviceLights FIREALARM LED and activates CBE
PULL STATIONYIndicates activation of a manual fire-alarm-activating
device, such as a pull station.
RF MON MODULYIndicates activation of a wireless alarm-monitoring device Lights FIREALARM LED and activates CBE
RF PULL STAYIndicates activation of a wireless manual fire-alarm-
activating device, such as a pull station
SMOKE CONVENYIndicates activation of a conventional smoke detector
attached to an FZM-1
SMOKE DETECTYIndicates activation of a conventional smoke detector
attached to an FZM-1
WATERFLOWYIndicates activation a waterflow alarm switchLights FIREALARM LED and activates CBE
EVACUATE SWNPerforms Drill functionActivates all silenceable outputs
MAN. RELEASEYIndicates activation of a monitor module programmed to
a releasing zone to perform a releasing function.
MANREL DELAYYIndicates activation of a monitor module programmed for
a release output
SECOND SHOTNProvides second activation of releasing zone after soak
timer has expired.
CO MONITOR*YIndicates activation of a CO conventional detectorActivates CBE, does not light an indicator at
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED and activates CBE
Indicates ACTIVE and activates CBE
the control panel.
Detectors
SMOKE(ION)YIndicates activation of an ion smoke detectorLights FIREALARM LED and activates CBE
SMOKE(DUCT I)YIndicates activation of a duct ion smoke detectorLights FIREALARM LED and activates CBE
Fire Alarm Mode of OperationOperation of the Control Panel
Type Code
SMOKE(PHOTO)YIndicates activation of a photo smoke detectorLights FIREALARM LED and activates CBE
RF_PHOTOYIndicates activation of a wireless photoelectric smoke
SMOKE(DUCTL)YIndicates activation of a duct laser detectorLights FIREALARM LED and activates CBE
SMOKE(DUCTP)YIndicates activation of a duct photo smoke detectorLights FIREALARM LED and activates CBE
SMOKE(HARSH)*YIndicates activation of a HARSH smoke detectorLights FIREALARM LED and activates CBE
SMOKE(LASER)YIndicates activation of a laser smoke detectorLights FIREALARM LED and activates CBE
SMOKE(BEAM)YIndicates activation of a beam smoke detectorLights FIREALARM LED and activates CBE
SMOKE(DUCTL)YIndicates activation of a duct laser smoke detectorLights FIREALARM LED and activates CBE
AIR REFYIndicates activation of a laser air reference detector. L ights FIREALARM LED and activates CBE
HEATYIndicates activation of a 190oF intelligent thermal detector Lights FIREALARM LED and activates CBE
HEAT+YIndicates activation of a 190oF adjustable threshold
HEAT(ANALOG)Y135oF intelligent thermal sensorLights FIREALARM LED and activates CBE
HEAT (ROR)Y15oF per minute rate-of-rise detectorLights FIREALARM LED and activates CBE
SMOKE ACCLIMYIndicates activation of detector without freeze warningLights FIREALARM LED and activates CBE
SMOKE (ACCL+)YIndicates activation of a detector with freeze warningLights FIREALARM LED and activates CBE
SMOKE MULTI*YMulti sensor smoke detectorLights FIREALARM LED and activates CBE
PHOTO/CO*YIndicates activation of the Photo, Heat, or CO element of
PHOTO/CO
(P SUP)*
PHOTO/CO
(C SUP)*
*FlashScan mode only
Latching
(Y/N)
detector
intelligent thermal detector
a detector
YIndicates activation of the Photo, Heat or CO element of
a detector.
YIndicates activation of the Photo, Heat or CO element of
a detector.
PurposeWhat it does
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED for photo and heat,
no LED will light for a CO alarm. Photo and
heat will activate CBE, CO alarm activates
special function zone FC and sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
Lights FIREALARM LED for heat, no LED will
light for a CO alarm, supervisory LED will
light for photo alarm, heat and photo will
activate CBE, CO alarm activates special
function zone FC and sixth CBE zone only
(sixth CBE zone programmable via VeriFire
Tools)
Lights FIREALARM LED for heat and photo
alarms, will light supervisory LED for CO
alarm, photo and heat alarms will activate
CBE, CO alarm will activate sixth CBE zone
only (sixth CBE zone programmable via
VeriFire Tools)
Operation of the Control PanelCarbon Monoxide (CO) Alarm Mode of Operation
Status banner
Type Code of initiating device
Custom descriptor for
this device location
Device address
Time and date of trouble
Extended 12 character
custom label
ALARM: CO INTENSIVE CARE UNIT
EASTERN WING Z004 03:10P 011511 2M147
Zone
Status banner
Time and date of the
Alarm Silenced
SIGNALS SILENCED
03:12P 011511 Tue
3.4 Carbon Monoxide (CO) Alarm Mode of Operation
3.4.1 How the Control Panel Indicates a CO Alarm
When a CO alarm from a FCO-851 or monitor module with a CO monitor activates due to a CO
alarm event, the control panel does the following:
•Produces a pulsed audible tone (if the piezo is enabled)
•Displays a CO alarm event that indicates the type of device that activated the CO alarm
•Displays ALARM in the status banner on the LCD display, along with information specific to
the device, as shown below:
Figure 3.4 Sample CO Alarm Display
•Sends a CO alarm message to the LCD display, remote annunciators, History buffer, installed
printers, and CRT-2s.
•Latches the control panel in CO alarm. (You can not return the control panel to normal
operation until you correct the CO alarm condition and reset the control panel.)
•Initiates any Control-By-Event actions and activates special function zone FC.
If the control panel indicates a CO alarm, you can do the following:
•To silence only the panel sounder:
Press the ACKNOWLEDGE/SCROLLDISPLAY key. The local sounder will silence.
The control panel will send an acknowledge message to the LCD display, remote annunciators,
history buffer, installed printers, and CRT-2s
•To silence the panel sounder and any activated outputs that are programmed as silenceable:
Press the SIGNALSILENCE key. The SIGNALSILENCE LED will light steady.
The control panel sends an Signal Silenced message to the History buffer, installed printers, remote
annunciators, and CRT-2s. The figure below shows a sample Alarm silenced message.
Figure 3.5 Sample Alarm Silenced Message
1.Check the Alarm message for the location and type of trouble.
2.Correct the condition causing the CO alarm.
3.When you finish correcting the CO alarm condition, press the
control panel to normal operation (indicated by the “System Normal” message). The control
panel sends a “System Normal” message to the LCD display, History buffer, instal led printe rs,
FDU-80 annunciators, and CRT-2s.
SYSTEMRESET key to return the
Page 21
System Trouble Mode of OperationOperation of the Control Panel
3.4.3 Interpreting CO Alarm/Supervisory Type ID Codes
The Type Code that displays in the CO alarm message indicates the function of the point that
initiates the CO alarm. For example, a monitor module with a
the monitor module monitors a conventional CO Detector. The table below lists the Type Codes
that can appear in an alarm message:
COMONITOR Type Code means that
Type Code
Latching
(Y/N)
PurposeWhat it does
Monitor Modules
CO Monitor*YIndicates activation of a CO conventional detectorActivates CBE, CO alarm does not light an
indicator at the control panel.
Detectors
Photo/CO*YIndicates activation of the Phot o, Heat, or CO element of
a detector
Photo/CO (C Sup)*YIndicates activation of the Photo, Heat or CO element of
a detector.
Photo/CO (P Sup)*YIndicates activation of the Photo, Heat or CO element of
a detector.
*FlashScan mode only
Table 3.2 CO Alarm Type Codes
Activates CBE, CO alarm does not light an
indicator at the control panel.
Activation of the Heat or Photo elements
will light an indicator at the control panel.
Activation of the CO element will light the
SUPERVISORY LED. Activates the CBE
Activation of the Heat element will light an
indicator at the control panel.
Activation of a CO alarm will not light an
indicator at the control panel.
Activation of the Photo element will light the
SUPERVISORY LED. Activates the CBE
3.5 System Trouble Mode of Operation
3.5.1 How the Control Panel Indicates a System Trouble
The system goes into system trouble when the control panel detects an electrical fault. If no fire
alarms exist, the control panel does the following:
•Produces a pulsed audible tone
•Activates the Trouble relay (TB4)
•Flashes the SYSTEMTROUBLE LED
•Displays a Type Code that indicates the type of device with a trouble.
•Displays TROUBLE in the status banner on the LCD display as well as the type of trouble and
information specific to the device, as shown in
Figure 3.6 below.
•Sends a Trouble message to the LCD display, history buffer and installed printers, FDU-80
annunciators, and CRT-2s.
NOTE: If a fire alarm exists when a trouble exists, the SYSTEMTROUBLE LED lights, but the Alarm
message appears in the LCD display.
Typical Trouble message that appears on the LCD display:
Figure 3.6 Sample Trouble Message
3.5.2 How to Respond to a System Trouble
If the control panel indicates a trouble, you can do the following:
1.Press the ACKNOWLEDGE/SCROLLDISPLAY key to silence the panel sounder and switch the
SYSTEMTROUBLE LED from flashing to steady—regardless of the number of troubles, alarms,
security and supervisory signals.
NOTE: Pressing the SIGNALSILENCE key when only troubles exist, gives the same result as
pressing the ACKNOWLEDGE/SCROLLDISPLAY key.
2.The control panel sends an Acknowledge message to the History buffer and installed printers,
FDU-80 annunciators, and CRT-2s.
Figure 3.7 Sample Acknowledge Message
3.Check the trouble message for the location and type of trouble.
Figure 3.8 Sample Trouble Messages on CRT-2 or Printer
4.Correct the condition causing the trouble. If the trouble clears, the control panel sends a Clear
Trouble message to the History buffer and installed printers, FDU-80 annunciators, and
CRT-2s.
If all troubles clear and no supervisory signals or fire alarms exist, the control panel does the
following:
•Returns to Normal operation (indicated by the “System Normal” message)
•Sends a “System Normal” message to the LCD display, History buffer and installed printers,
FDU-80 annunciators, and CRT-2s
•Restores troubles automatically - even if troubles are not acknowledged
If multiple trouble conditions exist in the system, the LCD and optional CRT-2 and FDU-8 0
annunciators display automatically step through each trouble every 3 seconds in the following
order:
Security Alarm Mode of OperationOperation of the Control Panel
ACTIVE SECURITY INTENSIVE CARE UNIT
EASTERN WING Z004 03:17P 041511 2M147
Status Banner
Type Code
Custom descriptor for
this device location
Device address
Time and date of trouble
Zone
Press the ACKNOWLEDGE/SCROLLDISPLAY key and the display stops on the current trouble event
for 1 minute, then begins to automatically step through remaining troubles. To manually step
through remaining troubles, press the
ACKNOWLEDGE/SCROLLDISPLAY key.
Refer to Appendix D, “Point and System Troubles Lists”, on page 68 for explanations of troubles
that appear on the display.
3.6 Security Alarm Mode of Operation
3.6.1 How the Control Panel Indicates a Security Alarm
The system goes into Security mode when a monitor module point programmed with a Security
Type Code activates. If no fire alarm exists, the control panel does the following:
•Produces a warbling audible tone
•Turns on the Security relay (TB5)
•Flashes the SECURITY LED (blue)
•Displays a Type Code that indicates the type of security alarm being generated
•Displays ACTIVE in the status banner on the control panel, along with information specific to
the device
•Sends a Security message to the LCD display, History buffer, and in stalled printers, FDU-80
annunciators, and CRT-2s
•Sends a Security message to the proprietary receiver via the network, if applicable.
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALSSILENCED LED is
lighted), a Security alarm will resound the panel sounder.
A Typical security message that appears on LCD display:
Figure 3.9 Sample Security Alarm Message
3.6.2 How to Respond to a Security Alarm
A Security Type Code latches the control panel. To return the control panel to normal operation,
you must correct the condition causing the security condition, then reset the control panel. If the
control panel indicates a security alarm, take the following action:
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALSSILENCED LED is
lighted), a Security alarm will resound the panel sounder.
1.Press the ACKNOWLEDGE/SCROLL display key to silence the panel sounder and switch the
SECURITY LED from flashing to steady—regardless of the number of troubles, alarms,
supervisory, and security signals. The control panel sends a Security message to the History
buffer and installed printers, FDU-80 annunciators, and CRT-2s.
2.Correct the condition that activated the Security point.
Operation of the Control PanelActive Supervisory Signal Mode of Operation
ACTIVE TAMPER INTENSIVE CARE UNIT
EASTERN WING Z004 03:19P 041511 2M147
Status Banner
Type Code
Custom descriptor for
this device location
Device address
Time and date of trouble
Zone
Extended 12 character
custom label
3.When you finish correcting the Security condition, press the SYSTEMRESET key to return the
control panel to normal operation (indicated by the “System Normal” message). The control
panel sends a “System Normal” message to the LCD display, History buffer and installed
printers, FDU-80 annunciators, and CRT-2s.
3.6.3 Interpreting Security Type Codes
The Type Code that displays in the security alarm message indicates the type of security alarm
being generated by the monitor module that initiates the alarm. For example, a monitor module
with a Type Code of
below lists the Type Codes that can appear in a security alarm message.
Type Code
AREA MONITORYMonitors area surveillance equipment, such
SECURITYYMonitors security switches for tamperingLights SECURITY LED, activates CBE
SYS MONITORYMonitors critical equipment for securityLights SECURITY LED, activates CBE
Latching
(Y/N)
AREAMONITOR indicates an intruder in a protected premises area. The table
Monitor Modules
PurposeWhat it does
Lights SECURITY LED, activates CBE
as motion detectors
Table 3.3 Security Type Codes
3.7 Active Supervisory Signal Mode of Operation
3.7.1 How the Control Panel Indicates an Active Supervisory
The system goes into Supervisory mode when a monitor module point programmed with a
Supervisory type code activates. When a Supervisory point activates, the control panel does the
following:
•Produces a warbling audible tone
•Turns on the Supervisory relay (TB5)
•Flashes the SUPERVISORY LED (yellow)
•Displays one of the Type Codes listed in Table 3.4.
•Displays ACTIVE in the status banner on the control panel, along with information specific to
the device
•Sends a Supervisory message to the LCD display, History buffer, and installed printers,
FDU-80G annunciators, and CRT-2s
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALSSILENCED LED is
lighted), a Supervisory alarm will resound the panel sounder.
A Typical Supervisory message that appears on LCD display:
Active Supervisory Signal Mode of OperationOperation of the Control Panel
3.7.2 How to Respond to an Active Supervisory
If a Latching Supervisory Type Code Displays
Some Supervisory Type Codes latch the control panel (Refer to Table 3.4 for a list of these type
codes). To return the control panel to normal operation, you must correct the condition causing the
supervisory condition, then reset the control panel. Take the following action:
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALSSILENCED LED is
lighted), a Supervisory alarm will resound the panel sounder.
1.Press the ACKNOWLEDGE/SCROLL DISPLAY key to silence the panel sounder and switch the
SUPERVISORY LED from flashing to steady—regardless of the number of troubles, alarms, and
supervisory signals. The control panel sends a Supervisory message to the History buffer and
installed printers, FDU-80 annunciators, and CRT-2s.
2.Correct the condition that activated the supervisory point.
3.When you finish correcting the latching supervisory condition, press the
return the control panel to normal operation (indicated by the “System Normal” message). The
control panel sends a “System Normal” message to the LCD display, History buffer and
installed printers, FDU-80 annunciators, and CRT-2s.
If Non-latching Type Code Displays
SYSTEMRESET key to
Some Supervisory Type Codes do not latch the control panel. (Refer to Table 3.4 for a list of these
type codes). The control panel automatically returns to normal operation, when you correct the
condition that activates the supervisory point. If the control panel indicates a non-latching
supervisory point, take the following action:
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALSSILENCED LED is
lighted), a Supervisory alarm will resound the panel sounder.
1.Press the ACKNOWLEDGE/SCROLLDISPLAY key to silence the panel sounder and switch the
SUPERVISORY LED from flashing to steady—regardless of the number of troubles, alarms, and
supervisory signals. The control panel sends a Supervisory message to the History buffer and
installed printers, FDU-80 annunciators, and CRT-2s.
2.Correct the condition that activated the supervisory point.
3.The control panel automatically returns to normal operation (indicated by the “System
Normal” message) and the control panel sends a “System Normal” message to the LCD
display, History buffer and installed printers, FDU-80 annunciators, and CRT-2s.
3.7.3 How to Interpret Supervisory Type Codes
The Type Code that displays in the Supervisory message indicates the function of the point that
initiates the Supervisory. For example, a monitor module with a
monitor module connects to a tamper switch.
Operation of the Control PanelPre-Alarm Warning Mode of Operation
Type Codes that can appear in an Supervisory message:
Monitor Modules
Type Code
WATERFLOW SYIndicates supervisory condition for activated water flow switch Lights SUPERVISORY LED and activates CBE
RF SUPERVSRYNMonitors a radio frequency deviceLights SUPERVISORY LED and activates CBE
LATCH SUPERVYIndicates latching supervisory conditionLights SUPERVISORY LED and activates CBE
TRACK SUPERVNIndicates tracking supervisory conditionLights SUPERVISORY LED and activates CBE
SPRINKLR SYSYIndicates activation of sprinkler systemLights SUPERVISORY LED and activates CBE
TAMPERYIndicates activation of tamper switchLights SUPERVISORY LED and activates CBE
Latching
(Y/N)
PurposeWhat it does
Detectors
SUP.T(DUCTI)NIon detector that indicates supervisory (non-alarm) conditionLights SUPERVISORY LED and activates CBE
SUP.L(DUCTI)YIon detector that indicates supervisory (non-alarm) conditionLights SUPERVISORY LED and activates CBE
SUPT(DUCTL)NLaser detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUPL(DUCTL)YLaser detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.T(DUCTP)NPhoto detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.L(DUCTP)YPhoto detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUPT(PHOTO)NPhoto detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.L(PHOTO)YPhoto detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.T(ION)NIon detector that indicates supervisory (non-alarm) conditionLights SUPERVISORY LED and activates CBE
SUP.L(ION)YIon detector that indicates supervisory (non-alarm) conditionLights SUPERVISORY LED and activates CBE
SUP.L(LASER)YLaser detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.T(LASER)
PHOTO/CO (C SUP)*YIndicates activation of the Photo, Heat or CO element of a
PHOTO/CO (P SUP)*YIndicates activation of the Photo, Heat or CO element of a
*FlashScan mode only
N
Laser detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
Activation of a Heat or Photo elements will
detector.
detector.
light an indicator at the control panel.
Activation of the CO element will light the
SUPERVISORY LED. Activates the CBE
Activation of a Heat element will light an
indicator at the control panel.
Activation of a CO alarm will not light an
indicator at the control panel.
Activation of the Photo element will light the
SUPERVISORY LED. Activates the CBE
Table 3.4 Supervisory Type Codes
3.8 Pre-Alarm Warning Mode of Operation
3.8.1 How the Control Panel Indicates a Pre-Alarm Warning
The control panel activates a Pre-Alarm Warning if a detector exceeds the programmed Pre-Alarm
Alert or Action level. When a detector activates a Pre-Alarm, the control panel does the following:
•Pulses the panel sounder
•Flashes the PRE-ALARM LED
•Activates the Pre-Alarm zone (F9)
•Sends a Pre-Alarm message to the LCD display, History buffer and installed printers, FDU-80
annunciators, and CRT-2s
•Displays a pre alarm status banner, the Type Code of the detector, and the Pre-Alarm level
(Alert or Action) on the LCD display, along with information specific to the device as shown
in
Pre-Alarm Warning Mode of OperationOperation of the Control Panel
Detector programmed for a Pre-Alarm level of 4
Shows the detector has reached 55% of the
programmed Pre-Alarm level. The 55% is a
real-time display and tracks smoke levels
Status banner
Type Code
PREALM SMOKE(PHOTO) INTENSIVE CARE UNIT
EASTERN WING 055%/4 03:20P 011511 1D147
Custom descriptor for
this device location
Device address
Time and date of trouble
Extended 12
character
custom label
3.8.2 How to Respond to a Pre-Alarm Warning
Pre-Alarm Alert and Action Levels
The Pre-Alarm function is a programmable option which determines the system’s response to realtime detector sensing values above the programmed setting. Use the Pre-Alarm function if you
want to get an early warning of incipient or potential fire conditions. The Pre-Alarm function
provides one of two levels of Pre-Alarm as follows:
NOTE: For detailed information on Pre-Alarm applications, refer to the NFS-320 Programming
Manual.
•Alert – a non-latching condition that causes a Pre-Alarm when a detector reaches the
programmed Pre-Alarm level.
•Action – a latching condition that causes a Pre-Alarm when a detector reaches the programmed
Pre-Alarm level.
Responding to a Pre-Alarm Warning
The Pre-Alarm screen display is the same for both alert and action conditions. Following is a
sample screen for a Pre-Alarm message.
Figure 3.11 Sample of an Alert Pre-Alarm Message
An Alert Pre-Alarm automatically restores to normal when the detector sensitivity, programmable
to one of nine settings, drops below the programmed Alert level. Zone F09 automatically clears
when no Pre-Alarm conditions exist.
An Action Pre-Alarm latches until you reset the system - even if the detector sensitivity drops
below the Action level. Zone F09 activates - but Zone Z00 (general alarm) and the trouble and
alarm relays do not activate. The fifth zone programmed, not the first four, in the detector’s CBE
activates. A subsequent alarm condition for this detector clears the Action indication from the LCD
display.
Interpreting Pre-Alarm Type Codes
The Type Code that displays in the Pre-Alarm warning indicates the function of the point that
initiates the Pre-Alarm warning. Refer to the Detectors section of
can appear in a Pre-Alarm warning, and for descriptions of those Type Codes.
Operation of the Control PanelDisabled Points Mode of Operation
!
Disable message
Type Code of the disabled device
Address of the
disabled device
DISABL TAMPER INTENSIVE CARE UNIT
EASTERN WING 03:20P 011511 1M159
Custom descriptor for
this device location
Time and date of trouble
Extended 12 character
custom label
3.9 Disabled Points Mode of Operation
The control panel indicates disabled points by displaying a screen for each disabled detector,
monitor module, and control/relay module. Disabled points do not cause an alarm or any
Control-by-Event activity. If more than one point is disabled, the control panel automatically
displays by priority, mimicking the alarms.
CAUTION:
Disabling a zone disables all input and output devices associated with the zone if the zone is
in first zone “primary” mapped location.
When one or more points are disabled, the control panel does the following:
•Holds all disabled output points in the off-state
•Flashes the SYSTEMTROUBLE LED
•Lights the POINTDISABLED LED
•Sends a Disabled Point message to the LCD display, History buffer and installed printers,
FDU-80 annunciators, and CRT-2s
•Displays a message for each disabled point
3.10 Non-Alarm Mode of Operation
ACCESS MONTRNUsed for monitoring building accessActivates CBE
ACK SWITCHNPerforms Acknowledge functionSilences panel sounder, gives an
DRILL SWITCHNPerforms Drill functionActivates silenceable outputs
FIRE CONTROLNUsed for air handler shutdown, intended to override
NON-FIRENUsed for energy management or other non-fire
PAS INHIBITNInhibits Positive Alarm SequenceInhibits Positive Alarm Sequence
RESET SWITCHNPerforms Reset functionResets control panel
SIL SWITCHNPerforms Signal Silence functionTurns off all activated silenceable outputs
ABORT SWITCHNIndicates Active at the panelAborts activation of a releasing zone
Non-Alarm points are addressable monitor modules programmed with one of the Non-Alarm Type
Codes listed in
Table 3.5. Non-Alarm points, except Non-Fire, operate like monitored system
functions that can produce troubles—but with the differences shown in the following sections.
Monitor Modules
Type Code
Latching
(Y/N)
normal operating automatic functions
situations. Does not affect operation of the control panel
Table 3.5 Non-Alarm Type Codes
PurposeWhat it does
Acknowledge message on the panel LCD
Activates CBE, does NOT light an
indicator at the control panel
Activates CBE, does NOT light an
indicator at the control panel
Page 29
Active Trouble Monitor Mode of OperationOperation of the Control Panel
Status banner
Type Code
Zone affected by the Fire Control
ACTIVE FIRE CONTROL INTENSIVE CARE UNIT
EASTERN WING Z055 08:59a 011511 1M044
Status banner
Type Code
TROUBL TROUBLE_MON INTENSIVE CARE UNIT
EASTERN WING 09:38A 011511 1M044
Custom descriptor for
this device location
Device address
Time and date of trouble
Extended 12 character
custom label
3.10.2 How the Control Panel Indicates an Active Fire Control
Activation of a FIRECONTROL point causes the control panel to do the following:
•Initiate the monitor module Control-by-Event
•Send a message to the LCD display, History buffer and installed printers, FDU-80
annunciators, and CRT-2s
•Display an ACTIVE status banner and FIRECONTROL Type Code on the LCD display, along with
information specific to the device
Figure 3.13 Sample Fire Control Point Display
3.10.3 How the Control Panel Indicates an Active Non-Fire Point
Non-Fire point operation does not affect control panel operation, nor does it display a message at
the panel LCD. Activation of a Non-Fire point activates CBE—but does not cause any indication
on the control panel. For example, you can program a Non-Fire point to turn lights in a zone to a
lower setting when activated. In this case, when the point activates the control panel activates the
point’s CBE to turn the lights down without any audio or visual indication on the control panel.
3.11 Active Trouble Monitor Mode of Operation
3.11.1 How the Control Panel Indicates an Active Trouble Monitor
Trouble Monitor Points are monitor modules programmed with the following Type Codes:
Type Code
EQUIP MONITRNUsed for recording access to monitored equipment Activates CBE
POWER MONITRNUsed to monitor remote power supplies or other
TROUBLE MONNUsed to monitor remote power supplies or other
These types of monitor modules operate like monitored system functions that can produce
troubles—but with the following differences:
•The LCD display status banner displays ACTIVE as shown:
•The monitor module is non-latching: the module will return to normal when the trouble
condition no longer exists.
•The monitor modules activate Control-by-Event
Page 30
Operation of the Control PanelOutput Circuit Trouble Mode of Operation
•The panel trouble relay transfers (TB4)
3.11.2 How to Respond to an Active Trouble Monitor
If the control panel indicates an active Trouble Monitor Point, take the following action:
1.Press the ACKNOWLEDGE/SCROLLDISPLAY key to silence the panel sounder and switch the
SYSTEMTROUBLE LED from flashing to steady—regardless of the number of troubles, alarms,
and supervisory signals.
2.The control panel sends an Acknowledge message to the History buffer and installed printers,
FDU-80 annunciators, and CRT-2s. Check the trouble message for the location an d type of
trouble.
3.Correct the condition causing the trouble.
4.When the trouble condition is corrected, the panel will return to normal operation (indicated by
the “System Normal” message).
5.The control panel sends a “System Normal” message to the LCD display, History buffer and
installed printers, FDU-80 annunciators, and CRT-2s.
3.12 Output Circuit Trouble Mode of Operation
3.12.1 Overview
Output circuits include NACs, Control/Relay Modules, and Transponder Points. This section
contains a description of control panel operation for each type of output circuit.
•Four NACs are included on the control panel
•Control/Relay Modules connected to the control panel on an SLC
•Transponder Points: XPC-8 (CLIP only), or XP6-C (CLIP or FlashScan)
Trouble Type Codes for Control Modules and NAC Circuits
Type Code
CONTROLN NACSupervised NAC
RELAYNFORM-C relayRelay Output
BELL CIRCUITNNACSupervised NAC for notification appliance
STROBE CKTNNACSupervised NAC for notification appliance
HORN CIRCUITNNACSupervised NAC for notification appliance
AUDIBLE CKTNNACSupervised NAC for notification appliance
REL END BELLNNACSupervised NAC for notification appliance
blankNNACSupervised NAC for undefined device
RELEASE CKTNNACDirects outputs to perform a releasing function.
REL CKT ULCNNACDirects outputs to perform a release function as required by ULC.
REL AUDIBLENNACNAC, activated upon release
NONRESET CTL*NNACRelay output, unaffected by “System Reset” command
TELEPHONENNACStandard Telephone circuit
REL CODE BELL**NNACSupervised NAC (NFS-320 NAC only)
INSTANT RELENNACNAC, short = normal; supervised for open circuits and ground
ALARMS PENDNNACOutput that will activate upon receipt of an alarm condition, and
CONTROL NAC**NNACSupervised NAC
Silenceable
(Y/N)
ConfigurationDevice Function
faults. Always non-silenceable and switch-inhibited.
remain in the alarm state until all alarms have been
acknowledged.
Table 3.7 Control Module and NAC Circuit Trouble Type Codes (1 of 2)
Figure 3.2 Sample of a Control/Relay Module in Trouble Message
Page 32
Operation of the Control PanelOperation of Special System Timers
Silence Inhibit Timer set to 180 seconds
Auto Silence Timer set to 600 seconds
Alarm Verification Timer set to 30 seconds
SIL INH=180 AUTO=600 VERIFY=30 USA TIME
TERM=N AC-DLY=Y LocT BLINK=01 ST=4 ACS=N
3.12.4 How to Respond to a NAC or Control/Relay Trouble
If the control panel indicates an active NAC or Control/Relay Trouble, take the following action:
1.Press the ACKNOWLEDGE/SCROLLDISPLAY key to silence the panel sounder and switch the
SYSTEMTROUBLE LED from flashing to steady—regardless of the number of troubles, alarms,
and supervisory signals.
2.The control panel sends an Acknowledge message to the History buffer and installed printers,
FDU-80 annunciators, and CRT-2s. Check the trouble message for the location an d type of
trouble.
3.Correct the condition causing the trouble.
4.When the trouble condition is corrected, the panel will return to normal operation (indicated by
the “System Normal” message).
5.The control panel sends a “System Normal” message to the LCD display, History buffer and
installed printers, FDU-80 annunciators, and CRT-2s.
3.13 Operation of Special System Timers
3.13.1 What are System Timers?
There are user-programmable time delays for three specific functions: the Auto Silence Timer, the
Alarm Verification Timer, and the Silence Inhibit Timer.
Function Selection screen with system timer settings. For instructions on changing system
functions, refer to the NFS-320 Programming Manual.
Figure 3.3 shows a sample System
3.13.2 How to View System Timer Selections
You can use the Read Status Entry option (explained in Chapter 4) to view the current selection for
the System Timers. To do so, press the keys shown below in sequence:
The LCD display shows the current selections for System Functions, which includes the three
system timers.
Sample LCD display of a System Function screen with system timer selections:
Figure 3.3 Sample System Function Selection Screen
3.13.3 How System Timers Work
The control panel can operate with special system timers: Auto Silence Timer, Alarm Verification
Timer and Silence Inhibit Timer.
Auto Silence Timer
A timer that functions like pressing the SIGNALSILENCE key. When the Auto Silence Timer reaches
its programmed value (600-900 seconds), the control panel automatically shuts off all active
outputs programmed as silenceable.
Waterflow Circuit OperationOperation of the Control Panel
Alarm Verification Timer
A timer that directs the control panel to ignore a fire alarm for a smoke detector, programmed for
Alarm Verification, while the Alarm Verification Tim e r is counting.
Table 3.8 contains a summary
of how the Alarm Verification Timer works.
IfThe control panel does this
A second fire alarm occurs while the
Alarm Verification Timer is counting
The Alarm Verification Timer elapses and
a fire alarm still exists
The Alarm Verification T imer expires and
a fire alarm no longer exists
Ignores the Alarm Verification Timer
Activates the fire alarm
Increments the Alarm Verification counter (up to 99)
for the device and returns to normal operation
Table 3.8 Alarm Ve rification Timer Operation
Silence Inhibit Timer
A timer that disables the SIGNALSILENCE key function and inhibits reset during countdown for the
programmed time (0-300 seconds) when a fire alarm occurs. A Silence Inhibit Timer starts at the
first fire alarm. Subsequent alarms will not restart the timer until the alarm condition is completely
resolved and a panel reset is performed.
3.14 Waterflow Circuit Operation
If a monitor module programmed with a WATERFLOW Type Code initiates a fire alarm, the control
panel disables the
SIGNALSILENCE key and the Auto Silence Timer. Refer to the NFS-320
Installation Manual for information on Waterflow circuits.
3.15 Style 6 and Style 7 Operation
Style 6 and Style 7 are supervised methods of communicating with addressable devices. If the
control panel detects a trouble (open or short), it will attempt to drive both ends of the loop,
maintaining communication in an unsupervised method. The trouble will display on the panel as a
Style 6 trouble until you correct the condition. Style 7 configuration of the SLC requires the use of
ISO-X isolator modules.
This section contains instructions and sample screens to show how to access all Read Status
functions and menus. For information on Read Status using a CRT-2 refer to
“Remote Terminal Mode Functions”, on page 62.
4.2 What is Read Status?
Read Status is a control panel function that lets you view system program information—but not
change any programmed settings. The Read Status function lets you do the following:
•View Read Status information without entering a password.
•Enter and operate Read Status functions while the control panel provi des full fire protection.
•View Read Status information while a fire alarm or trouble condition exists.
NOTE: If a fire alarm or trouble occurs while you are in Read Status, the control panel
automatically exits Read Status operation and displays the new fire alarm or trouble.
4.2.1 Quick Reference Key Sequences
Appendix C.3,
For quick reference, in the left margin next to each Read Status option is a block that
shows the key sequence needed to view that option.
For example, the block to the left shows how to display the “Read Point” screen:
4.3 Entering Read Status
To enter Read Status, follow these steps:
1.From the “System Normal” screen, press the ENTER key. The control panel displays the
“Entry” screen as shown below;
2.From the “Entry” screen, press the 2 key. The control panel displays the “Read Status Options”
screen as shown below:.
Viewing and Printing a Read StatusRead Status Operation
4.4 Viewing and Printing a Read Status
To view or print Read Status information follow the instructions below:
OptionPressLets you
Read Point0 key, ENTERkeyView information for a detector, module, NAC or zone
Print Points1 key, ENTERkeyPrint information for all installed points in the system
Read History2 key, ENTERkeyDisplay the total number of events in the History buffer and step
through each event in sequence
Print History3 key, ENTERkeyPrint the contents of the History buffer (up to 800 events)
Read Alarm History4 key, ENTER keyView a display of the number of alarms in the Alarm History buffer ,
then scroll through each alarm event
Print Alarm History5 key, ENTERkeyPrint the contents of the Alarm History buffer (up to 200 events)
NOTE: If attempting to read a point that is not installed, the control panel displays “Not Installed”.
During all Read Status operations (except print operations) the control panel starts a 2-minute timer
each time you press a key . If the control panel does not de tect a key press for 2 minutes, the control
panel exits Read Status and returns to the “System Normal” display.
In Read Status, you can also do the following:
•Press the ESC key to delete the previous entry.
•Press the SYSTEM RESET key to abort Read Status.
4.4.1 How to View Read St atus of Devices, Zones, & System Settings
Overview
Read Point options 0, 2, and 4 in the Read Status Screen let you display and view information for
devices and zones programmed into the control panel, as well as view system and annunciator
settings. This section provides instructions and sample displays so you can view Read Status.
T opics covered in this section:
To view Read Status forRefer to
Intelligent Detectors “How to View Read Status for a Detector” on page 36
Control/relay and Monitor
modules
NAC“How to View Read Status for a NAC” on page 38
Software Zones (Z01-Z99)“How to View Read Status for a Software Zone (Z01-Z99)”
Special Zones (F0-F9)“How to View Read Status for a Special Zone (F0-F9)” on
Releasing Zones (R0-R9)“How to View Read Status for a Releasing Zone (R0-R9)”
System Functions“How to Read Status for System Functions” on page 40
Annunciator Selections“How to Read Status for Annunciator Selections” on
“How to View Read Status for a Control/Relay or Monitor
Module” on page 37
Alarm Verification selection:V on; * off
Multidetector selection:
A, B, C, or * (not selected)
Label for the detector
Current alarm reading (percent)
Alarm sensitivity level
Pre-Alarm sensitivity level
Device status
SLC Address (001-159)
D (detector)
SLC number (always 1)
NORMAL SMOKE (ION) INTENSIVE CARE UNIT
EASTERN WING Z002 001%A6 6 CV00 1D002
Default CBE zone selection
Alarm Verification Time
(in seconds)
How to Display the Total of Installed Devices
To view the total number of installed devices, enter the “Read Status” screen
by pressing the ENTER key, then 2, then A. A screen similar to the following
will appear:
How to Display a Point or Zone for Read Status
From the “Read Status” screen, press 0, then press the ENTER key to
display the “Read Point Entry” screen as shown below:
•To view a detector, press DETECTOR, detector SLC address, ENTER.
•To view a zone, press , zone number, ENTER.
•To view a monitor or control/relay module, press MODULE, module SLC address, ENTER.
•To view a NAC, press OUTPUT, two-digit address, (for example 01 for B01, etc.), ENTER.
When you select a device or a zone, the control panel displays information for the device or zone,
but does not send this information to the serial ports or the History buffer.
How to View Read Status for a Detector
From the “Read Status” screen, press 0, then press the ENTER
key. You can now view Read Status for a detector as follows:
press
DETECTOR, enter the three digit address, then press the
ENTER key. For example, to read the status of detector 1D002:
press
DETECTOR, enter address 002, then press the ENTER key.
The control panel now displays information about the detector,
as shown in
The display and descriptions of the fields are shown below:
Viewing and Printing a Read StatusRead Status Operation
SLC address
next device
previous device
Type Code (CONTROL)
Walk Test selection:
W selected for Walk Test
* not selected
Label for the module
Extended 12character
custom label
SLC Address (001-159)
M (module)
SLC number (always 1)
Switch Inhibit: I selected, * not selected
Device status
OFF CONTROL INTENSIVE CARE UNIT
DOORHOLDER#2 Z000 *O* 1M147
Default CBE zone selection
Silenceable: O = selected, * = not selected (default)
•Device Status The status of the detector: Normal, Alarm, or Test.
•Type Code The software Type Code that identifies the type of detector. (Refer to “Point
Programming” in the NFS-320 Programming Manual.)
•Default CBE Zone Selection This is the first zone in the 5 zone CBE list. Defaults are Zone
001 (Heat detectors) Zone 002 (Ion detectors) Zo ne 003 (Photo detectors) Zone 004 (Laser
detectors) Zone 005 (Multisensor). Values may differ depending on point programming.
•Current alarm reading (xxx%) The current alarm reading of the detector, as a percentage of
the alarm sensitivity setting.
•Alarm sensitivity level (Ax) The alarm sensitivity (x=1-9) entered in the Detector Sensitivity
Screen.
•Pre-Alarm sensitivity level The Pre-Alarm Sensitivity (1-9; 0 = Pre-Alarm not used) entered
in the Detector Settings Screen.
NOTE: Refer to “Detector Sensitivity Settings” in the NFS-320 Programming Manual for more
information on the Pre-Alarm and Alarm Sensitivity settings
•Cooperative Multi-Detector selection A smoke detector programmed to evaluate readings
from nearby detectors in making Alarm or Pre-Alarm decisions. Cooperative Multi-Detector
sensing also allows the combination of ionization with photoelectric technology in reaching an
alarm decision.
* – Multi-not used.
A – combines the detector’s alarm decision with the next SLC address above.
B – combines the detector’s alarm decision with the next SLC address below.
C – combines the detector’s alarm decision with the next SLC address above and the next SLC
address below.
•Alarm Verification (* or V)
* – Alarm Verification not programmed for this detector.
V – Alarm Verification enabled.
Alarm Verification is a user-defined global time function that can reduce the number of
nuisance alarms. Refer to page
page 33 for more information.
•Device SLC Address The SLC address of the detector.
How to View Read Status for a Control/Relay or Monitor Module
From the “Read Status” screen, press 0, then press the ENTER
key. You can now view Read Status for a monitor or a
control/relay module as follows: press
address, then press the
status of an FCM-1 module 1M147: press
then press the
information about the module as shown in
The display and descriptions of the fields are shown below:
Figure 4.2 Sample Control/Relay or Monitor Module Read Status Display
MODULE, enter the SLC
ENTER key. For example, to read the
MODULE, enter 147,
ENTER key. The control panel now displays
Figure 4.2.
Page 38
Read Status OperationViewing and Printing a Read Status
Device address
next device
previous device
Type Code (CONTROL)
Walk Test selection:
W selected for Walk Test
* not selected
Label for the NAC
Default zone selection
Address (01-04)B = NAC
Switch Inhibit: I selected, * not selected
Device status
Silenceable: O = selected, * = not selected (default)
OFF CONTROL FRONT HALLWAY NO. 2
Z000 *OW B02
•Device Status The status of the module: control/relay module [On (device active) OFF (device
not active] or monitor module (Normal, Alarm, or Test).
•Type Code The software Type Code that identifies the type of module. (Refer to “Point
Programming” in the NFS-320 Programming Manual.)
•CBE list Only the first zone in the device’s CBE list will be displayed.
•Device SLC Address The SLC address of the module.
•Switch Inhibit (control/relay module only) Displays whether the remote ON/OFF capability
of the device is inhibited. (I=on; *=off).
•Silenceable (control/relay module only) A selection that specifies if the device can be
silenced during an alarm by pressing the signal silence key. Possible values are:
* = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by trouble
O = silenceable, does not resound
NOTE: If the “Strobe” Type ID is used with System Sensor Strobe synchronization, F, U, B, T, or
O will silence the entire circuit, “*” will silence the horn portion only.
Walk Test (control/relay module only) A selection that specifies if the device will activate
during a Walk Test.
How to View Read Status for a NAC
From the “Read Status” screen, press 0, then press the ENTER
key. You can now view Read Status for a NAC as follows:
press
OUTPUT, enter the device address, then press the ENTER
key. For example, to read the status of NAC 0-2: press
OUTPUT, enter 02, then press the ENTER key. The control
panel now displays information for a NAC as shown in
Figure 4.3.
The display and descriptions of the fields are shown below:
•Device Status The status of the device: ON (device active) OFF (device not active).
•Type Code The software Type Code that identifies the type of NAC. Refer to “Appendix F Type Codes” in the NFS-320 Programming Manual.
•CBE List Only the first zone in the NAC’s CBE list will be displayed here.
•Device Address The address of the NAC (01-04)
•Switch Inhibit A selection for disabling the switch function for the control/relay or
transponder output circuit. (I=on; *=off).
Page 39
Viewing and Printing a Read StatusRead Status Operation
Software
Zone Number
next device
previous device
Zone label for zones 01-99
Custom zone label for the zone
entered in during program Change
Zone Number
Zone status (ON or OFF)
OFF SOFTWARE ZONE 3RD FLOOR CAFETERIA
Z07
Special
Zone Number
next device
previous device
Zone label for Special Function F8
Indicates Special Zone F8
Zone status (ON or OFF)
Code Type selection
for Special Zone F8
OFF CODING FUNCTION CODE TYPE
MARCH TIME F8
•Silenceable A selection that specifies if the device can be silenced during an alarm by pressing
the
SIGNALSILENCE key. Possible values are:
* = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by troubl
O = silenceable, does not resound
NOTE: If the “Strobe” Type ID is used with System Sensor Strobe synchronization, F, U, B, T,
or O will silence the entire circuit, “*” will silence the horn portion only.
•Walk Test A selection that specifies if the device will activate during a Walk Test.
How to View Read Status for a Software Zone (Z01-Z99)
From the “Read Status” screen, press 0, then press the ENTER
key. You can now view Read Status for a Software Zone as
follows: press Z, enter the zone number (01-99), then press the
ENTER key . For example, to read the status of Software Zone 07:
press Z, enter 07, then press the
now displays information for a Software Zone as shown below.
ENTER key. The control panel
Figure 4.4 Sample Software Zone Read Status Display
How to View Read Status for a Special Zone (F0-F9)
From the “Read Status” screen, press 0, then press the ENTER
key. You can now view Read Status for a Special Zone as
follows: press
ENTER key. For example, to read the status of Special Zone F8:
press
Z, enter F8, then press the ENTER key. The control panel
now displays information for a Special Zone as shown below
NOTE: The zone label depends on the type of Special Zone. For example, CODINGFUNCTION
CODETYPE for F8.
Figure 4.5 Sample Special Zone Read Status Display
Read Status OperationViewing and Printing a Read Status
Releasing
Zone Number
next device
previous device
Zone label for Releasing Function
Indicates Special Zone R0
Zone status (ON or OFF)
Selections for
Releasing Zone R0
OFF RELEASE FUNCT RELEASE CONTROL
DELAY=00 ABORT=ULI CROSS=N SOK=0000 R00
SIL INH=000 AUTO=000 VERIFY=30 USA TIME
TERM=N AC_DLY=Y LocT BLINK=01 ST=4 ACS=N
How to View Read Status for a Releasing Zone (R0-R9)
From the “Read Status” screen, press 0, then press the ENTER
key. You can now view the Read Status of a Releasing Zone as
follows: press Z, enter the zone number (R0-R9), then press the
ENTER key. For example, to read the status of Releasing Zone
R0, enter Z, enter R0, then press the
ENTER key. The control
panel now displays information for a Releasing Zone as shown
below.
Figure 4.6 Sample Releasing Zone Read Status Display
How to Read Status for System Functions
The “System Functions” screen specifies global settings for the
control panel. From the “Read Status” screen, press 0, then press the
ENTER key. You can now view Read Status for System Functions as
follows: press Z, enter S0, press the
sample display and description of items for the Read Status of System
Functions:
ENTER key. Shown below is a
ParameterDescriptionSettings
SIL INH=000Silence Inhibit timer in
seconds.
AUTO=000Auto Silence Timer in
seconds.
VERIFY=30 Alarm Verification Timer00 = no timer; 00-30 seconds.
USA TIMETime and date display
format
TERM=N Terminal supervision YES – To supervise the wiring of an
AC_DLY=NDelays AC loss reportingYES - AC loss reporting is delayed for
LocT One of three operating
modes of a PC or terminal
connected to the control
panel (through TB12 PC
Terminal)
000 = no timer; or the timer duration in
seconds up to 300.
000 = no timer; 600-900 seconds.
USA TIME or EUR TIME
FDU-80.
NO – No FDU-80 supervision.
approximately 3 hours.
NO - No AC loss delay.
LocT – terminal connected to control
panel and located in the same room
as the control panel.
LocM – terminal connected to control
panel but requires password for
operation.
RemT – terminal connected through a
modem for Read Status operations
only.
REGION=0 TBL.REMIND=2 ALA.SCROLL=Y
LOCAL CONTROL=1 IP ACCESS=0 DCC-MODE=N
S5
FLASHSCAN LIDET LIMOD
Y Y
S6
ParameterDescriptionSettings
BLINK=01The rate at which intelligent
control or monitor modules
blink during polling
ST=4NFPA wiring style operation
for the SLC
ACS=NUse ACS Selection Groups N – No annunciator selected or
BLINK=00: No blink
BLINK=01: Devices blink on
every poll.
BLINK=16: Devices blink every
16th poll.
4 – Style 4 SLC or
6 – both Style 6 and Style 7 SLC
Y – Select and display ACS Selection
Groups
Table 4.1 System Function Parameters (2 of 2)
How to Read Status for Annunciator Selections
Annunciator Selection screens specify the information that displays
on ACS annunciators. From the “Read Status” screen, press 0, then
press the
Functions as follows: press Z, enter S, enter annunciation selection
number (1-4), press the
Status of Annunciator Selection are shown below:
ENTER key. You can now view Read Status for System
ENTER key. Sample LCD displays for the Read
Figure 4.7 Annunciator Selection 1 Screen
To view the next three annunciator selection screens, press the (NEXTSELECTION) key.
Figure 4.8 Annunciator Selection 2 Screen
If UDACT=N, the control panel displays the Annunciator Selections 3 and 4 screen, addresses
A20-A32, as shown below
•SEC_RLY and SUP_RLY (0= turn on by Fire Alarm, 1= turn on by Security, 2= turn on by
Supervisory).
•BAT_SIZE (1= battery size is greater than 26 Ahr, 0= less t han 26 Ahr).
•C_DRILL (custom drill N= No custom drill, Y= Yes).
•TERM_DATA (0= LCD80 Terminal using 7 bit data, 1= LCD80 Terminal using 8 bit data).
•PRT_BAND (0= 2400, 1= 4800, 2= 9600).
Figure 4.13 System Function Selection 8 Screen
An Annunciator Selection screen shows the information that will display on the ACS annunciators.
The table below contains the ACS display selections.
1 through 9Programmable Annunciator #1 through #9
0Programmable Annunciator #10
A8 Systems points + Zo ne s 1- 5 6
BZones 57-99, 9 F zones, 8 R zones, 4 NAC
CLoop 1, Modules 1-64
DNot Used
ELoop 1, Modules 65-128
FNot Used
GLoop 1, Modules 129-159
HLoop 1, Detectors 1-64
INot Used
JLoop 1, Detectors 65-128
KNot Used
LLoop 1, Detectors 129-159
MNot Used
N8 Systems points + Zones 1-56, used for r em o te station co m m un icator (TM-4)
O8 Systems points + Zones 1-56, used for municipal box trip ou t pu t (T M -4)
Annunciator addresses 1 to 19 can be programmed to any one of the above selections. If there is a UDACT,
selections A-M will be sent to Annunciator addresses 20 to 32 respectively.
Table 4.2 ACS Selection Groups
An example of ACS selections in Annunciator Selection Screen 1:
Figure 4.14 Annunciator Selection Screen 1 Example
NOTE: An ACS selection marked with an asterisk (*) indicates no annunciator selection.
The figure above shows annunciator selections for addresses A1-A3 (addresses A4-A10, marked
with asterisks, are not selected)
Read Status OperationViewing and Printing a Read Status
next event
previous event
The number of events in the History buffer
EVENT HISTORY START
EVENTS IN HISTORY: 550
Time and date of the event
Type of trouble
Type of event
TROUBL IN SYSTEM GROUND FAULT
01:46P 011508 Tue
4.4.2 How to View Read Status for Event and Alarm History
Overview
The control panel maintains a History buffer of the last 800 events, each with a time and date
stamp. History events include the following:
•All alarms, troubles and operator actions, such as: Acknowledge, System Reset, Signal
Silence, Drill, and Walk Test.
•Programming entries (Program Change and Status Change, but not Read Status), along with a
number (0-9) indicating the programming submenu (for example, 0=Clear). For an example,
see
Figure 4.18.
You can view events from the Hist ory buffer in two forms: by displaying all events (option 2,
HIST=2) or by displaying alarm events only (option 4, ALARMHIST=4).
NOTE: The History buffer cont ai ns 800 events total, including the alarm events that display for
Alarm history. The control panel generates Alarm history from the alarm events that exist in the
800-event History buffer.
How to View Read Status for Event History
Option 2 (HIST=2) lets you view the total number of events in the History
buffer (up to 800 events), then view each event in chronological
sequence. From the “Read Status” screen, press 2, then press the
key to display the “Event History” screen. A sample of the Event History
screen is shown below:
ENTER
Figure 4.16 Sample Event History Display
To display events in the History buffer, do the following:
•Press the NEXTSELECTION key to step through each event from the first entry (oldest event
first) in the History buffer, or
•Press the PREVIOUSSELECTION key to step through each event from the most recent entry in the
History buffer.
NOTE: The NEXTSELECTION key will show the most recent event first, and then move to its
normal function of displaying the oldest events first.
Viewing and Printing a Read StatusRead Status Operation
Message specifies the
Program Change option used
Type of event
Time and date of the event
PROGRAM CHANGE 5=ZONE LABEL CHG
01:51P 011508 Tue
next event
previous event
The number of alarms in the History buffe
ALARM HISTORY START (ESCAPE TO ABORT)
ALARMS IN HIST: 073
Type Code of the device
that alarmed
Type of event
(ALARM)
SLC address of the
device that alarmed
Time and date of the alarm
ALARM: PULL_STATION INTENSIVE CARE UNIT
EASTERN WING Z004 03:10P 011508 1M147
A sample LCD display for a Program Change event:
Figure 4.18 Sample Program Change Event Display
How to View Read Status for Alarm History
Option 4 (ALARMHIST=4) lets you view the total number of alarms in
the History buffer (up to 200), then view each alarm in chronological
sequence. From the “Read Status” screen, press 4, then press the
key to display the “Event History” screen. A sample Alarm History
screen is shown below:
Figure 4.19 Sample Alarm History Display
ENTER
To display alarms in the buffer, do the following:
•Press the NEXTSELECTION key to step through each alarm from the first entry (oldest alarm
first) in the buffer, or
• Press the PREVIOUSSELECTION key to step through each alarm from the most recent entry in
the buffer
NOTE: The NEXTSELECTION key will show the most recent event first, and then move to its
normal function of displaying the oldest events first.
A sample display for an alarm event:
Figure 4.20 Sample Alarm Event Display
4.4.3 How to Print Points, Event and Alarm History
Overview
Read Point options 1, 3, and 5 in the “Read Status” screen let you pri n t po ints, event history, and
alarm history . This section contains instructions for printing, as well as sample point, event history,
and alarm history printouts.
NOTE: Before printing, make sure your control panel is connected to a compatible printer and
the printer is configured according to the manufacturer’s specifications, and that the correct baud
rate is selected at the panel.
Option 1 (PRNTPOINT=1) lets you print a list of all points programmed into
the system. From the “Read Status” screen, press 1, then press the ENTER
key to print a list of installed points. A sample Print Point screen is shown
below:
Figure 4.21 Sample Print Point Display
A sample printout of three points using the Print Point option:
How to Print Event History
Option 3 (HIST=3) lets you print a list of all events in the History buffer (up
to 800). From the “Read Status” screen, press 3, then press the ENTER key to
print a list of events. A sample History Print screen is shown below:
Figure 4.22 Sample History Print Screen
A sample printout of three events in history using the History Print option:
How to Print Alarm History
Option 5 (ALARMHIST=5) lets you print a list of alarm events in the History
buffer (up to 200). From the “Read Status” screen, press 5, then press the
ENTER key to print a list of alarm events. A sample Print Alarm History
screen is shown below:
Figure 4.23 Sample Print Alarm History Display
A sample printout of two alarm events in the History buffer using the Print Alarm History option.
Viewing and Printing a Read StatusRead Status Operation
HISTORY EMPTY (ESCAPE TO ABORT)
****************************************
ALARM HISTORY EMPTY (ESCAPE TO ABORT)
****************************************
4.4.4 How to View and Print Hidden Event and Alarm History
The control panel maintains a copy of the History buffer. For instance, if someone clears the
History buffer using Status Change programming option 4, the control panel retains a copy of the
History buffer. The copy of the preceding History buffer is called a Hidden History buffer and a
copy of the preceding Alarm History is called a Hidden Alarm History buffer.
If you attempt to view or print history and the control panel displays one of the screens shown
below you can use the options listed in the table below to view the contents of a Hidden History
buffer.
Figure 4.24 History Empty Display
Figure 4.25 Alarm History Empty Display
Options for viewing and printing Hidden History and Hidden Alarm History do not appear in the
LCD display when in Read Status. You can view and print the contents of these Hidden History
buffers using the options listed in the table below. You read and print Hidden History and Hidden
Alarm History the same way you read and print history using the options that appear on the “Read
Status” screen. The table also contains references to the sections that contain instructions for
reading and printing history.
ToPressRefer to
Read Hidden Alarm History“How to View Read Status for
Alarm History” on page 45
Print Hidden Alarm History“How to Print Alarm History” on
page 46
Read Hidden History“How to View Read Status for
Print Hidden History“How to Print Event History” on
This section contains information for operating the control panel as detailed in the topics listed
below:
SectionSpecial ZoneRefer to Page
A.2, "Releasing Zones (R0-R9)"R0-R9page 49
A.3, "Time, Date, and Holiday Functions"F5, F6, F7page 52
A.4, "NAC Coding"F8page 54
A.5, "Presignal and Positive Alarm
Sequence (PAS) Operation"
A.2 Releasing Zones (R0-R9)
A.2.1 Purpose of Releasing Zones
WARNING: When used for CO2 releasing applications, observe proper precautions as stated
in NFPA 12. Do not enter the protected space unless physical lockout and other safety
procedures are fully completed.
Do not use software disable functions in the panel as lockout.
F0page 55
The control panel provides ten Releasing Zones (R0-R9). These are special zones that you can use
for up to ten independent releasing operations. This section contains descriptions of each Releasing
Function option and an example of how Releasing Zone options work.
For instructions on programming Releasing Functions, refer to the NFS-320 Programming Manual.
Each Releasing Zone includes the following releasing options:
OptionDescription
Cross Zone Cross Zones let you program the control panel to activate a Releasing
Zone when two or more initiating devices are alarmed. Cross Zone
selections are:
Y Two or more detectors are alarmed that are mapped to one of the ten
Releasing Zones (R0-R9)
Z Two or more detectors are alarmed that are mapped to two different
Software Zones and mapped to one of the ten Releasing Zones (R0-R9).
H At least one smoke detector mapped to one of the ten Releasing Zones
(R0-R9) is alarmed and at least one heat detector mapped to the same
Releasing Zone as the smoke detector is alarmed.
N Cross Zones not used
Delay TimerSelect a 0–60 second delay before activating a zone.
AbortAn Abort Switch Type Code used to abort activation of a zone.
Manual ReleaseAllows immediate zone activation by overriding the abort function,
cross-zone function, and delay timer.
Soak Timer Automatically shuts off the releasing device after a preprogrammed period
of time. Select 0001-9999 seconds for a Soak Timer or 0000 seconds for
You can use the Read Status Entry option to view the current selections for a Releasing Zone. For
example, to view selections for Releasing Zone R1, press the keys in sequence:
A sample LCD display of a Releasing Function selected for Releasing Zone R1:
Figure A.1 Sample Read Status for a Releasing Zone
A.2.3 How Releasing Zones Operate
The figure below contains an illustrated example of how Releasing Zones work, using cross zone
selections with four detectors and a NAC mapped to Releasing Zone 1 (listed as ZR1 in the CBE
list).
Table A.2 lists the cross zone selections and the conditions that activate the Releasing Zone:
Figure A.2 Illustrated Example of Cross Zone Programming
Listing of each Cross Zone option and the conditions required to activate the Releasing Zone,
according to the example shown in
Cross Zone Selection
(Cross=)
Cross=NAn alarm from any initiating devices activates the releasing circuit.
Cross=YAn alarm from any two initiating devices activates the releasing circuit.
Cross=ZAn alarm from two initiating devices mapped to different Software Zones,
Cross=HActivation of heat detector 2D104 and one smoke detector (2D101,
Figure A.2.
Condition(s) Required to Activate the Releasing zone
but mapped to the same Releasing Zone.
• An alarm from 2D101 and 2D103 – detectors mapped to different
zones, but both list ZR1 in their CBE.
• An alarm from 2D102 and 2D104 – detectors mapped to different
zones, but both list ZR1 in their CBE.
• An alarm from 2D101 and 2D104 – detectors mapped to different
zones, but both list ZR1 in their CBE.
• An alarm from 2D102 and 2D103 – detectors mapped to different
zones, but both list ZR1 in their CBE.
Special Zone OperationTime, Date, and Holiday Functions
USA Time and Date format (default)
EUR Time and date format
TROUBL CONTROL MODULE ADDR 1M159
OPEN 03:48P 011508 1M159
TROUBL CONTROL MODULE ADDR 1M159
OPEN 15:48 150108 1M159
Status ON (ON time in effect)
Time Function status banner
Zone F5
ON time for
devices that list
F5
OFF time for devices
that list F5
Day-of-week selections
(H=holiday selected)
ON TIME FUNCTION TIME CONTROL
ON=07:00 OFF=15:00 DAYS=SMTWTF*H F05
A.3 Time, Date, and Holiday Functions
A.3.1 Overview
The control panel includes a real-time clock that displays the time-of-day, the date, and the
day-of-week. The clock includes a lithium battery backup. Time displays in a USA format (12-hour
time format with month/day/year) or a EUR (European) format as shown below:
Figure A.3 Sample USA and EUR Time/Date Formats
The control panel also provides Time Control zones F5 and F6 for time and date control functions
and zone F7 for holiday functions.
A.3.2 How to View Time Control Selections
You can use the Read Status Entry option to view the current selection for the Time function. To do
so, press the following keys in sequence:
or
NOTE: For instructions on programming the Time function, refer to the NFS-320 Programming
Manual.
The LCD display shows the current selections for the Time Control function. The figure below
shows a sample LCD display of a Time Control function:
Time, Date, and Holiday FunctionsSpecial Zone Operation
Status ON (holiday function not in effect)
Holiday Function status banner
Holiday selections (for zone F7)
ON HOLIDAY FUNCTION 12/15 **/** **/**
**/** **/** **/** **/** **/** **/**
A.3.3 How to View Holiday Function Selections
You can use the Read Status Entry option to view the current selection for the Holiday function. To
do so, press the following keys in sequence:
NOTE: For instructions on programming the Hol i da y fu nction, refer to the NFS-320
Programming Manual.
The LCD display in Figure A.5 gives an example of an LCD display of a Holiday function:
Figure A.5 Sample Read Status for Holiday Function
A.3.4 How Time Control and Holiday Functions Work
Time and Holiday activation occurs automatically and does not require operator intervention. All
outputs with a CBE list containing F5 or F6 activate within the times specified for the days of the
week listed in F5 or F6. All smoke detectors with a CBE list containing F5 or F6 switch to their
lowest sensitivity (AL:9) within the times specified for the days of the week listed in ZF5 or ZF6.
Refer to “Intelligent Sensing Applications” in the NFS-320 Programming Manual for details on
setting detector sensitivity.
Time Control is active for all days of the week listed in F5 or F6. Holidays listed in F7 are excluded
unless you list Holidays (H) in the day-of-week selection of F5 and F6 (shown in
Figure A.4). Enter
the time functions in a 24-hour format with the OFF time later than the ON time. After changing
programming using Time Control, always reset the control panel.
NOTE: You can turn a NONFIRE control point on and off, by listing zone F5 or F6 in the CBE list
of a control/relay module.
You can use Time Control zones F5 and F6 to program non-fire applications such as turning lights
on and off, setting a thermostat, and so on. For example, you can program zones F5 and F6 to
activate outputs at one time of day and deactivate outputs at later time, on specified days of a week.
Table A.3 contains descriptions of additional Time Control applications:
Application Requirement
Control day and night sensitivity of
intelligent, addressable detectors
Control a specific date of yearInput up to nine date in the Holiday selection screen
List zone F5 or F6 in the detector CBE. This
automatically sets the detector sensitivity to the
minimum setting (AL:9) during the day and
automatically returns detector sensitivity to
programmed sensitivity during the evening.
for Special Zone F7, then list zone F7 (Holiday) in the
CBE of a device.
A Coding selection is the Code Type that pulses when the control panel activates a NAC mapped to
Special Zone F8. Special Zone F8 provides seven coding selections (see
in the CBE of a NAC. To use a Code Type, program a NAC to list Zone F8 (reserved for a Code
Type) in the NAC CBE list.
NOTE: Control modules (FCM-1, FRM-1) cannot be coded.
The table below contains descriptions of the signals that correspond to each NAC Code Type:
Coding SelectionSignalNotes
March Time (default)120 PPM (pulses Per minute)Default selection for NACs mapped to F8.
Two-Stage Alert signal (20 PPM) or
General Alarm signal (T emporal
pattern)
California10 sec. On, 5 sec. Off, repeatsn/a
Temporal0.5 on, 0.5 off, 0.5 on, 0.5 off,
0.5 on, 1.5 off, repeats
Canadian Dual Stage
(3 minutes)
Canadian Dual Stage
(5 minutes)
System Sensor StrobeSynchronizes System Sensor ADA horn/strobes.
Gentex StrobeSynchronizes Gentex horns/strobes.
Alert signal (20 PPM)
Drill Switch activation switches
to Temporal pattern
Alert signal (20 PPM)
Drill Switch activation switches
to Temporal pattern
Alert signal – When an alarm occurs and not activated by
another zone, the output pulses at 20 PPM.
General Alarm signal – If not acknowledged within 5 minutes,
the control panel switches from 20 PPM to Temporal pattern.
Used as a standard general EVAC signal.
Same as Two-Stage except will only switch to second stage by
activation of Drill Switch three minute timer.
Same as Two-Stage except will only switch to second stage by
activation of Drill Switch five minute timer.
T able A.4) that you can list
Table A.4 F8 Code Types and Audio Signals
A.4.2 How to View Coding (F8) Selections
You can use the Read Status Entry option to view the current selecti on for the Coding function. To
do so, press the following keys in sequence:
NOTE: For instructions on programming the Coding function, refer to the NFS-320 Programming
Manual.
The LCD display shows the current selections for the Code T ype. Figure A.6 shows a sample LCD
display of a Code Type selection of March Time:
Presignal and Positive Alarm Sequence (PAS) OperationSpecial Zone Operation
Initial alarm
annunciation
Alarm activates outputs,
if panel is not reset.
If PAS=Y, alarm activates
outputs if not acknowledged
PAS (15s)
Presignal Delay Timer (60-180)
A.4.3 How to Respond to an Alarm with Coding
If an alarm occurs with a Coding selection, the control panel latches the control panel in alarm and
pulses outputs mapped to F8 at the pulse specified by the Coding selection (see
Table A.4). To
silence the outputs, press the SIGNALSILENCE key.
A.5 Presignal and Positive Alarm Sequence (PAS) Operation
A.5.1 Overview
This section describes the Presignal and PAS selection, and provides instructions on how to do the
following:
•View Presignal and PAS selections
•Respond to an alarm with Presignal
•Operate the control panel with a Presignal Delay Timer only
•Operate the control panel with a Presignal Delay Timer and PAS
A.5.2 What is Presignal and PAS?
Presignal is a feature that initially causes alarm signals to only sound in specific areas, monitored
by qualified persons. This allows delay of the alarm from 60 to180 seconds after the start of alarm
processing. The control panel Presignal feature provides two selections:
NOTE: Presignal differs from the Alarm Verification Timer which does not require human
intervention.
•A Presignal Delay Timer (60-180 seconds) that delays activation of all outputs with a CBE that
includes Special Zone F0.
•A PAS selection, in addition to the Presignal Delay Timer, that allows a 15-second time period
for acknowledging an alarm signal from a fire detection/initiating device. If the alarm is not
acknowledged within 15 seconds, all local and remote outputs activate immediately and
automatically.
You can use the Read Status Entry option to view the current selection for the Presignal function.
To do so, press the keys in sequence:
NOTE: For instructions on programming the Presignal function, refer to the NFS-320
Programming Manual.
The LCD display shows the current selections for the Presignal function. The figure below shows a
sample LCD display of a Presignal function selected for PAS and a Presignal Delay Timer of 60
seconds:
Figure A.8 Sample Read Status for Presignal Function
NOTE: If any monitor modules are programmed with a PASINHIBIT Type Code and a fire alarm
occurs, zone F0 goes false and aborts the Presignal Delay Timer.
A.5.4 How to Respond to an Alarm with Presignal Delay Timer (no P AS)
If an alarm occurs with a Presignal Delay Timer (60-180 seconds), the control panel displays the
type of device and the SLC address of the device causing the alarm. If a second alarm occurs during
the Presignal Delay Timer, the control panel aborts the Presignal Delay Timer and activates all
programmed outputs. A sample Alarm screen for a monitor module is shown below:
Figure A.9 Sample Alarm Display Screen
The FIREALARM LED flashes and the panel sounder pulses a steady tone. The control panel latches
until the alarm is corrected and you press the S
have the duration of the Presignal Delay Timer (60-180 seconds) to respond to the alarm before the
control panel automatically activates all outputs programmed to F0. You can take the following
actions:
•To silence the panel sounder and change the FIREALARM LED from flashing to steady, press
the
ACKNOWLEDGE/SCROLLDISPLAY key.
•To abort the Presignal Delay Timer, press the SYSTEMRESET key.
•T o manually activate all outputs programmed to F0, press the DRILL key. The Manual Evacuate
screen appears, the panel sounder pulses and the
steady. The Manual Evacuate screen and Alarm screen display alternately at 3-second
intervals.
YSTEM RESET key to reset the control panel. You
FIREALARM LED changes from flashing to
If the Presignal Delay Timer reaches its programmed value, without operator intervention, the
control panel activates all outputs programmed to F0.
A.5.5 How to Respond to an Alarm with Presignal Delay Timer
(PAS selected)
If an alarm occurs with a Presignal Delay Timer (60-180 seconds) and PAS selected, the control
panel displays an Alarm screen that shows the type of device and the SLC address of the device
causing the alarm. When an alarm comes from an initiating device with a CBE list that includes F0
(with PAS selected), the control panel delays the following outputs:
•System Alarm relay
•TM-4 Polarity Reversal Alarm output
•TM-4 Municipal Box output
NOTE: These outputs do not delay for Presignal operations without PAS selected.
If a second alarm occurs during the Presignal Delay Timer, the control panel aborts the Presignal
Delay Timer and activates all programmed outputs.
A sample Alarm screen for a monitor module:
Figure A.10 Sample Alarm Display Screen
The FIREALARM LED flashes and the panel sounder pulses a steady tone. The control panel latches
until the alarm is corrected and you press the S
have 15
seconds to acknowledge the alarm or the control panel automatically activates all outputs
YSTEM RESET key to reset the control panel. You
programmed to F0. If you acknowledge the alarm within 15 seconds, the control panel increases the
delay time to the full Presignal Delay Timer (60-180 seconds). You have the duration of the
Presignal Delay Timer to respond to the alarm before the control panel activates all outputs
programmed to F0. You can take the following actions:
•To increase the delay to the full programmed Presignal Delay Timer, press the
ACKNOWLEDGE/SCROLLDISPLAY key . The panel sounder goes silent and the FIREALARM LED
changes from flashing to steady.
•To abort the Presignal Delay Timer, press the SYSTEMRESET key.
•T o manually activate all outputs programmed to F0, press the DRILL key. The Manual Evacuate
screen appears, the panel sounder pulses and the
FIREALARM LED changes from flashing to
steady. The Manual Evacuate screen and Alarm screen display alternately at 3-second
intervals.
If the Presignal Delay Timer reaches its programmed value, without operator intervention, the
control panel activates all outputs programmed to F0.
NOTE: For instructions on selecting Intelligent Detector Functions, refer to the NFS-320
Programming Manual.
Descriptions for Intelligent Detector Functions
FunctionDescription
Analog DisplayThe control panel reads and displays analog information from the 318
Sensitivity Adjust Nine selections for manually setting intelligent detector alarm levels
Day/Night Sensitivity
Operation
Maintenance AlertWhen compensation reaches the limit of the amount of drift
Automatic Test
Operation
Type Code
Supervision
LED Control
Operation
Alarm Verification Timer
and Verification Counter
Operation
analog detectors (159 per SLC). The display shows the sensed air at
the detector as a percentage of the alarm threshold for each detector.
within the UL range. If using ionization detectors in duct applications, set Sensitivity Adjust to Level 1.
Refer to the NFS-320 Programming Manual for detector sensitivity
information.
Y ou can program the system to automatically force smoke detectors to
minimum sensitivity during the day. Refer to
Functions” on page 52.
compensation that can be safely applied, the control panel reports a
trouble condition, according to National Fire Alarm Code standards.
This condition also activates if the detector remains at very high or very
low measured air levels for an extended time.
The control panel performs an automatic test of each detector every
256 minutes. Failure to meet the test limits causes an Auto Test Fail
trouble.
The control panel monitors hardware device Type Codes for each
installed device at regular intervals (an interval can take up to 40
minutes for a full capacity system). If a mismatch of type compared to
the program occurs, the control panel generates a point trouble labeled
Invalid Type.
A global program selection to prevent detector LEDs from blinking as a
result of polling during normal operation. A typical application is a
sleeping area where a blinking light can distract people. As a standard
function, independent of this programming selection, the control panel
allows all LEDs to turn on in alarm.
The control panel performs alarm verification on programmed
intelligent smoke detectors. The Alarm Verification Timer is a global
program selection of 0–60 seconds (ULC installations can not exceed
30 seconds). Each detector includes a Verification Counter, which
displays the number of times that a detector entered verification but did
not time-out to alarm. The Verification Counter increments to 99 and
holds.
The control panel can communicate with a remote terminal or computer connected to the EIA-232
PC/Terminal port. Refer to the NFS-320 Installation Manual for installation information.
NOTE: See the NFS-320 Programming Manual for instructions on enabling the CRT.
This port may be set up for interactive operation or for monitoring only. Interactive operation
requires that all equipment be UL-listed under UL Standard for Safety UL 864 and be installed and
set up as directed under Local Terminal Mode (LocT) or Local Monitor Mode (LocM).
ITE (Information Technology Equipment) equipment listed under UL 1950 is allowed for ancillary
system monitoring when the system is installed and set up as directed under Remote Terminal
Mode (RemT).
C.2 Operating Modes
The control panel provides three operating modes for the CPU EIA-232 PC/Terminal port:
•Local Terminal - LocT
•Local Monitor - LocM
•Remote Monitor - RemM
You select the operating mo de during con trol panel programming (Global System Functions). For
more information, refer to the NFS-320 Programming Manual.
The following subsections outline the functions, password requirements, and additional
information for each operating mode.
C.2.1 Local Terminal Mode (LocT)
Functions, passwords, and special requirements of Local Terminal Mode (LocT) are:
Functions:Read Status, Alter Status, and Control Functions (Table C.1).
Passwords:User-defined password for Alter Status functions.
Requirements:The terminal must be mounted in a UL 864 listed enclosure or positioned to provide
Functions available with the Local Terminal Mode:
FunctionLets you...
Read Status
Alter Status
equivalent protection against unauthorized use.
• Display the status of an individual point (Detector, Module, or Zone).
• Display a list of all the points in Alarm or trouble.
• Display a list of all programmed points in the system.
• Step through the History buffer event by event.
• Display the entire History buffer.
• Disable/Enable an individual point.
• Change the sensitivity of a detector .
• Clear the verification counter of all detectors.
• Clear the entire History buffer.
• Set the Intelligent Sensing alert and action levels.
Functions, passwords, and special requirements of Local Monitor Mode (LocM) are:
Functions:Read Status, Alter Status, and Control Functions (Table C.2).
Passwords:User-defined password for Alter Status and Control functions.
Requirements:Password security feature for Control Functions eliminates the need for mounting the
CRT-2 in an enclosure.
Functions available with the Local Monitor Mode:
FunctionLets you...
Read Status
Alter Status
Control Functions
• Display the status of an individual point (Detector, Module, or Zone).
• Display a list of all the points in Alarm or trouble.
• Display a list of all programmed points in the system.
• Step through the History buffer event by event.
• Display the entire History buffer.
• Disable/Enable an individual point.
• Change the sensitivity of a detector.
• Clear the verification counter of all detectors.
• Clear the entire History buffer.
• Set the Intelligent Sensing alert and action levels.
• Acknowledge
• Signal Silence
• System Reset
•Drill
Table C.2 Local Monitor Mode Functions
C.2.3 Remote Terminal Mode (RemT)
Functions, passwords, and special requirements of Remote Terminal Mode (RemT) are:
Functions:Read Status only. See Table C.3.
Passwords:None
Requirements:Use with UL ITE-listed terminals, including personal computers with the VeriFire™
Tools or terminal emulation software. Intended for terminals connected through
modems, including FSK modems connected through a public switched telephone
network.
Remote Terminal AccessUsing the CRT-2 for Read Status
Rd Point=1, Rd Alm/Tbl=2, All Points=3, Hist:Step=4/All=5, Ala-Hist:Step=6/All=7
Functions available with the Remote Terminal Mode:
FunctionsLets you...
Read Status
Alter Status
Control Functions
• Display the status of an individual point (Detector, Module, or Zone).
• Display a list of all the points in Alarm or trouble.
• Display a list of all programmed points in the system.
• Step through the History buffer event by event.
• Display the entire History buffer.
•N/A
•N/A
Table C.3 Remote Terminal Mode Functions
C.3 Using the CRT-2 for Read Status
C.3.1 Overview
This section shows how to perform Read Status functions from a CRT-2.
NOTE: See the NFS-320 Programming Manual for instructions on enabling the CRT port.
For more information see the “Read Status” section of this manual.
FunctionLets you...
Read PointRead the status of any point in the system (detectors, modules, software
zones, and system parameters).
Alm/Tbl StatusDisplay a list of all devices in the system that are in Alarm or trouble.
Read All PointsDisplay a list of all points programmed in the system. This list will display the
History StepStep through the History buffer one event at a time.
History-AllSend the entire History buffer to the CRT, from the most recent event to the
status of all addressable detectors, modules, system parameters and
software zones.
oldest event.
Table C.4 Read Status Functions
C.3.2 Accessing Read Status Options
Access the Read Status function from the CRT-2 by following these steps.
1.Turn on the CRT-2, which is connected to the control panel.
2.Press the Read Status function key . The control panel displays the “Read Status” menu options:
From the Read Status menu, you can select options 1-7.
From the Read Status menu, select option 1 - Read Point. The CRT-2 displays the following:
Enter the following:.
NOTE: Press F5 to scroll forward through a list of devices. Press F6 to scroll back through a list
of devices.
1.Enter the first letter of the device, using upper case letters.
• Detector = “D”
• Module = “M”
• Zone = “Z”
• Special Function = “F”
• Releasing Zone = “R”
•E Zone = “E”
•L Zone = “L”
• System Parameter = “S”
2.Enter the address or number of the device.
3.Press “
ENTER”.
Example Read points for detectors 1D001 and 1D002 on SLC 1:
C.3.4 Display Devices in Alarm or Trouble
From the “Read Status” menu, select option 2 - Read Alarms/Troubles. The CRT-2 will display the
alarm and trouble history.
The semicolon, a control character in networking applications, separates the hour and minute of
events displayed from history. If events display as they occur, a colon separates the hour and
minute.
From the “Read Status” menu, select option 3 - Read All Points. The CRT-2 displays a list of the
status of all addressable detectors, modules, system parameters and software zones:
C.3.6 Step-through History
From the “Read Status” menu, select option 4 - History-Step. This option lets you step through all
history events one event at a time. Step through the history list one event at a time by pressing the
Next F5 or Prior F6 function keys.
C.3.7 View All History
From the “Read Status” menu, select option 5 - History ALL. The entire history of events will
display on the screen.
C.3.8 Step-through Alarm History
From the “Read Status” menu, select option 6 - Alarm-History:Step. This option lets you step
through the panel’s alarm history one event at a time by pressing the Next F5 or Prior F6 function
keys.
C.3.9 View All Alarm History
From the “Read Status” menu select option 7 - Alarm History All. This entire history of alarm
events will display on the screen, from most recent to oldest event.
C.4 Using the CRT-2 for Alter Status
C.4.1 Overview
This section shows how to Alter Status functions from a CRT-2.
NOTE: The panel must be in Local Terminal Mode (LocT ) or Lo cal Monitor Mode (LocM).
NOTE: See the NFS-320 Programming Manual for instructions on enabling the CRT port.
Using the CRT-2 for Alter StatusRemote Terminal Access
Enter Status CHange Password or Escape to Abort
Press <
ALTERSTATUS>
*****
Press <1><1><1><1><1><
ENTER>
1=Disable 2=Alarm/Prealarm 3=Clear Verification 4=Clear History 5=Alert/Action
Disable/Enable. Type D(nnn) / nMnnn / P(nn) / Z(nn) then Enter
STATUS CHANGE Dis/Ena point 8:29A Tue 01/15/08
Press <1><
ENTER>
Number
Address (01-159)
FunctionLets you...
DisableEnable or disable detectors or modules.
Alarm/Pre-AlarmChange the Alarm and Pre-Alarm levels of any addressable detector in the
system.
Clear Verification Clear the verification counter for all the addressable detectors in the system.
Clear HistoryClear the contents of the History buffer.
Set Action/AlertSet the Pre-Alarm for Alert or Action.
Table C.5 Alter Status Functions
C.4.2 Accessing Alter St atus Options
Access Alter Status function from the CRT-2 by following these steps.
1.Turn on the CRT-2 connected to the control panel.
2.Press the Alter Status function key. The control panel displays the Password screen.
3.Enter the Status Change Password. The factory default Status Change Password is 11111.The
password does not display on the CRT-2. Five asterisks will appear in place of the password.
The Alter Status Options menu appears.
From the Alter Status Options menu, you can select 1-5.
C.4.3 Enable or Disable Detectors, Modules or Zones
From the “Alter Status” menu select option 1 - Disable. Disable lets you enable or disable
detectors, modules, or zones.
Enter the following:
1.Enter the first letter to read one of the following, using upper case letters:
STATUS CHANGE Alarm/Prealarm level 08:29A Tue 01/15/08
D102 sens. at level 5, Prealarm at level 3, Enter AxPx to change, Esc. to Abort
D102 now set at new Alarm level 5 and new Pre-alarm level 2
Press <D><1><0><2><
ENTER><A><5><P><2><ENTER>
STATUS CHANGE Clear verify count 08:29A Tue 01/15/08
Press D to Disable (E to Enable); then press ENTER.
C.4.4 Change Alarm and Pre-Alarm Levels
This option lets you change the Alarm and Pre-alarm levels of any addressable detector in the
system. Follow these steps.
1.From the “Alter Status” menu select option 2 - Alarm/Pre-alarm.
2.Enter the address of the detector you wish to change. For example, change alarm and pre-alarm
levels for detector 102 on SLC 1 to Alarm Level 4 & Pre-alarm Level 2.
C.4.5 Clear Verification Counter
Clear verification lets you clear the verification counter for all the addressable detectors in the
system.
C.4.6 Clear the Entire History Buffer
Clear History lets you clear the entire History buffer.
There are a variety of point or system trouble types that may appear in a trouble message. The
tables below give lists of the troubles and indications of their cause.
D.1 Point (Device) Troubles
A message from the “Trouble Type” column in the following table will appear in the upper right corner of
the panel display when a point (device) trouble occurs. Use this table to help determine what the trouble is.
POINT TROUBLES
TROUBLE TYPE TROUBLE DESCRIPTIONACTION
AC FAILUREThe auxiliary power supply has lost AC power.Determine whether there is an AC power loss or whether
ADRFLTDetector and new sounder base address doesn’t match. Or the ACPS
ALIGNA beam detector is in configuration mode.No action is necessary, as the trouble will clear when the
BLOCKSomething has come between the detector’s beam and its reflector.Investigate and clear the blockage.
CHGFLT*The power supply’s battery charger is not working properly.Correct the fault.
CO 6MNThe CO (carbon monoxide) detection element on the detector has six
CO EXPThe CO (carbon monoxide) detection element on the detector has
CO TBLThe CO element on the detector is not working properly. (This trouble
DIRTY 1The detector is dirty and needs cleaningClean the detector.
DIRTY 2The detector requires cleaning immediate l y. It is a false alarm risk.Clean the detector immediately.
DISABLThe point has been disabled.Service and re-enable the point.
GNDFLTThere is a ground fault on the main or auxiliary power supply.Correct the fault.
HI BATThe auxiliary power supply’s battery charge is too high.Check the batteries for problems. Replace batteries if
INVREPThe device has returned a response to the panel that the panel did not
IR TBLThe infrared element is not working properly onthe detector. (This
LO BATThe auxiliary power supply’s battery is low.Check the batteries for problems. Replace batteries if
LO TEMPThe temperature read by a Heat+ or Acclimate™+ detector is too low. Raise the heat in the area of the detector.
LO VALThe detector chamber reading is too low; the detector is not operating
NO ANSThe device (module or detector) is not responding to the poll. Either the
NO SIGThe device (module or detector) is not responding to the poll. Either the
OPENThe module device has an open circuit on its supervised wiring.Check the connections from the module to the input or
PRLOSSThe output module or new sounder base lost power.Turn power back on.
PSFAILThe power supply is not working properly.Check the battery for problems. Replace battery if
SHORTThe module device has a short circuit on its supervised wiring.Check the connections from the module to the input or
TEST FThis detector has failed the FACP’s periodic detector test for alarm
*This trouble may be fire panel or backup battery related. Test and replace backup batteries if necessary.
address is incorrect.
months left to expiration. (This trouble generates in FlashScan mode
only. CLIP mode will generate a LO VAL error.)
reached the expiration date. (This trouble gen erates in FlashScan mode
only. CLIP mode will generate a LO VAL error.)
generates in FlashScan mode only. CLIP mode will generate a LO VAL
error.)
expect.
trouble generates in FlashScan mode only. CLIP mode will generate a
LO VAL error.)
properly. Or (CLI P Mode only) t he thermist ors, CO eleme nt, or inf ra-r ed
element on
experiencing a freeze warning.
device is not working or it is not connected properly.
device is not working or it is not connected properly.
capabilities.
the detector is not working properly, or they are
Table D.1 Point (Device) Troubles (1 of 2)
the power supply and wiring is correct.
Readdress the incorrect device.
configuration is complete. However, the detector will not
detect a fire while this trouble exists.
Replace the detector.
Replace the detector.
Replace the detector.
necessary.
Check the device for functionality, addressing and wiring.
Replace the detector.
necessary.
The detector must be removed and replaced by an
authorized service representative.
Determine whether the device is functional, and
connected and addressed properly on the SLC.
Determine whether the device is functional, and
connected and addressed properly on the SLC.
output device to which it is wired.
necessary.
output device to which it is wired.
The detector should be removed and replaced by an
THERMThe thermistors are not functioning properly on the detector. (This
VER HIThis detector, which has been programmed to participate in alarm
trouble generates in FlashScan mode only. CLIP mode will generate a
LO VAL error.)
verification, has gone into and come out of verification its programmed
limit without going into alarm. Either something is wrong with the
detector or there is a condition nearby (such as someone smoking) that
causes it to go into verification frequently.
Replace the detector.
Check the detector and the conditions nearby to
determine the problem.
Table D.1 Point (Device) Troubles (2 of 2)
D.2 System Troubles
A message from the “Trouble Type” column in the following table wil l appear in the panel display
when a system trouble occurs. Use this table to help determine the cause of the trouble.
SYSTEM TROUBLES
TROUBLE MESSAGE
TYPE
AC FAILThe main power supply has lost AC power.
ADV WALK TESTThere is an Advanced Walk Test in progress.No action is required.
ANNUN x NO ANSWERThe annunciator at address x is not responding.Determine whether the device is functional, and
ANNUN x TROUBLEThe annunciator at address x is in trouble.Determine if the ACS module is functi onal, correctly
AUXILIARY TROUBLEAn auxiliary device connected to the NFS-320 at J6 is
BASIC WALK TESTA Basic Walk Test is in progress.No action is required.
BATTERYThe main power supply’s battery charge is too high or
BAT.BACKUP RAMRAM battery backup is low. Replace battery.
CHARGER FAIL*The main power supply’s battery charger is not workin g
CORRUPT LOGIC EQUATThe database that houses the panel’s logic equations
DRILL ACTIVATEDDrill has been initiated.No action is required.
EPROM ERRORThe a pplication and/or boot code is c orrupt. Service is required.
EXCEEDED CONN. LIMITMore than two panels have been connected to a high-
EXTERNAL RAM ERRORThe external RAM test failed. Service is required.
GROUND FAULTA ground fault has occurred within the panel.Locate the ground fault and repair.
GROUND FAULT LOOP xThere is a ground fault on loop x. Locate the ground fault and repair.
HS-NCM SNIFFER ACTIVThe HS-NCM is in a diagnostic mode.No action is required.
INTERNAL RAM ERRORThe internal RAM test failed.Service is required.
LCD80 SUPERVISORYCommunication has been lost with the LCD-80.Check connections to the LCD-80 Annunciator.
LOADING.NO SERVICEA program or database download is in progre ss . The
MASTER BOX TROUBLEA TM-4 connected to a municipal box is in trouble.Reset the master box.
MASTER BOX NO ANSWER A TM-4 connected to a municipal box is not
*This trouble may be fire panel or backu p battery related. Test and replace backup batteries if necessary.
NCM COMM FAILURECommunication is lost between the NFS-320 and the
TROUBLE DESCRIPTIONACTION
Determine whether there is an AC power loss or
whether the power supply and wiring is correct.
connected and addressed prop erly.
installed, and configured prope rly.
in trouble or the cable is missing.
too low.
properly.
is corrupt. It must be re-downloaded, or all
programming must be cleared and re-e ntered.
speed network communications module.
panel is NOT providing fire protection during the
download. P
responding.
network communications module.
Check the wiring and source.
Check batteries, replace if necessary.
Correct the fault.
The database must be re-downloaded, or all
programming must be cleared and re-entere d .
Remove extra panel(s).
Proper authorities should be notif ied while a download
is in progress so that other means of fire protection
can be supplied.
Determine whether the device is functional and
connected properly.
Check to see if the NUP cable is properly installed
and the network communications module is
functional.
NETWORK FAIL PORT xCommunication lost between NCM Port x and
NETWORK INCOMPATIBLEThe brand of this panel is incompatible with this
NFPA 24HR REMINDERThis message occurs every day at 11 am if any
NO DEV. INST ON L1No devices are installed on the system.Install SLC and run autoprogram.
PANEL DOOR OPENThe panel door is open.Close door.
POWER SUPPLY COMM
FAIL
PROGRAM CORRUPTEDT he database that houses the panel’s programming is
PROGRAM MODE
ACTIVATED
RELEASE DEV. DISABLERel easing devices have been disabled.Enable the devices.
SELF TEST FAILEDDiagnostic test failed. Call Technical Services.
STYLE 6 POS. LOOP xThere is an open circuit on the positive side of loop x. Style 6 and Style 7 are supervised methods of
STYLE 6 NEG. LOOP xThere is an open circuit on the negative side of loop x. Style 6 and Style 7 are supervised methods of
STYLE 6 SHORT LOOP xStyle 6 and Style 7 are supervised methods of communicating with addressable devices. If the control panel
SYS INITIALIZA TIONThe devices are initializing.No action is required, as the trouble will clear when
TERMINAL SUPERVISORYThere is a communication error with the CRT-2.Check connections to the CRT-2 terminal.
UDACT NO ANSWERThe UDACT i s not responding.Determine whether the UDACT is functional, and
UDACT TROUBLEThe UDACT is in trouble.Determine if the UDACT is functional and wired
TROUBLE DESCRIPTIONACTION
corresponding node.
network.
troubles exist.
There has been a communication failure with the power
supply.
corrupt.
A user is currently accessing the panel’s programming
menus.
communicating with addressable devices. If the control panel detects a trouble (open), it will drive both ends of
the loop, maintaining communication in an unsupervised method. The latching trouble will display on the panel
as a Style 6 trouble until you correct the condition and press RESET. Style 7 configuration of the SLC r equires
the use of ISO-X modules.
communicating with addressable devices. If the control panel detects a trouble (open), it will drive both ends of
the loop, maintaining communication in an unsupervised method. The latching trouble will display on the panel
as a Style 6 trouble until you correct the condition and press RESET. Style 7 configuration of the SLC requires
the use of ISO-X modules.
detects a trouble (open or short), it will drive both ends of the loop, maintaining communication in an
unsupervised method. The latching trouble will display on the panel as a Style 6 trouble until you correct the
condition and press RESET. Style 7 configuration of the SLC requires the use of ISO-X modules.
Check wiring and verify the node is online.
Verify all nodes are branded for the same OEM.
Resolve any troubles on the system.
Service is required.
The database must be re-downloaded, or all
programming must be cleared and re-entere d .
Service is required.
No action is required / Exit the Programming mode.
initialization is completed. However, the devices will
not report off-normal events while this trouble exists.
connected and addressed prop erly.
correctly.
Table D.2 System Troubles
NOTE: A charger fail trouble can be charger or battery related. Batteries near the end of their
service life may not accept the periodic charge current required by UL 864 Ninth edition, and can
result in the panel displaying a charger fail. Batteries should be tested and replaced as necessary
before repairing or replacing the panel.
Abort49
Abort Active LED12
Acknowledge/Scroll Display control key12
Active Supervisory Signal24–26
panel indication24
response to25
Type Codes25
Alarm Verification Timer32, 58
Alarm. See Fire Alarm17
Analog Display58
Annunciator Selections, read status41
Auto Silence Timer32
Automatic Test Operation58
B
Battery Levels, read status43
C
Caution
Disabling a zone disables all input and out-
put...28
Coding
to view F8 selections54
Coding, NAC54
Control Keys12
Control Panel Keys and Indicators, illustration11
Control/Relay Module Trouble
panel indication31
response to32
Type Codes30
Control/Relay Module, read status37
Controls Active LED11
Cooperative Multi-Detector, read status37
Cross Zone49
Cross Zone Programming illustration51
CRT-2 and Read Status62
Accessing62
CRT-2 and Read Status. See Appendix C
D
Date Functions52
Day/Night Sensitivity Operation58
Delay Timer49
Detector
fire alarm type codes18, 21
Functions58
Read Status37
supervisory alarm type codes26
Disabled Points28
Discharge LED12
Drill control key14
F
Fire Alarm17–18
LED12
panel indication17
response to a17, 55
Fire Control Type Code, active point29
H
Hidden History, read status and print47
History, event and alarm, read status44
Holiday Functions52
to view selections53
I
Increment Number key14
ISO-X module33, 70
L
Lamp Test control key14
Latching Supervisory Type Code25
Latching/non-latching type codes. See particular
type code for definition.
LED Control Operation58
LEDs, table of11
Local Control setting and control keys13
LocM (Local Monitor)60, 61
LocT (Local Terminal Mode)60
Pre-Discharge LED12
Presignal and Positive Alarm Sequence (PAS)
response to Presignal Delay Timer alarm
(no PAS)
response to Presignal Delay Timer alarm
(PAS selected)
to view selections56
56
57
R
Read Status34–47
to enter34
to print45
alarm history46
event history46
points45
print hidden event and alarm history
47
print points46
to view35
annunciator selections41
battery levels43
detector information36
devices, zones, system settings35
event and alarm history44
point or zone information36
Releasing Zone (R0-R9)40
releasing zone selections
software zones39
Special Zone (F0-F9)39
System Functions40
total of installed devices36
using a CRT. See Appendix C
Recall Last Entry key14
Releasing Zone (R0-R9), read status40
Releasing Zones (R0-R9)49–51
Remote Terminal Access60–??
RemT, Remote Terminal Mode60, 61
S
Security Alarm23
panel indication23
response to a23
Security LED12
Sensitivity Adjust58
Shortcuts to Operating Functions10
Signal Silence control key13
Signals Silenced LED12
Silence Inhibit Timer32, 33
Soak Timer49
Software Zone (Z01-Z99), read status39
Special Zone Operation49–57
Special Zone, read status39
Supervisory LED12
Supplemental Documentation9
System Functions, read status40
System Normal Message16
System Reset control key13
System Timers32
Alarm Verification Timer32
Auto Silence Timer32
Silence Inhibit Timer32, 33
to view selections32
System Trouble21–23
panel indication21
response to22
System Trouble LED12
System Troubles69
T
Time Functions52
to view selections52
Timers. See System Timers32
Transponder Points30
Trouble Monitor29
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein,
Manufacturer warrants that the Products manufactured by it in its
Northford, Connecticut facility and sold by it to its authorized
Distributors shall be free, under normal use and service, from defects
in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The
Products manufactured and sold by Manufacturer are date stamped at
the time of production. Manufacturer does not warrant Products that
are not manufactured by it in its Northford, Connecticut facility but
assigns to its Distributor, to the extent possible, any warranty offered
by the manufacturer of such product. This warranty shall be void if a
Product is altered, serviced or repaired by anyone other than
Manufacturer or its authorized Distributors. This warranty shall also
be void if there is a failure to maintain the Products and the systems in
which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND
DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER
EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS,
TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY
MANUFACTURER INCLUDING WITHOUT LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR
ANY PA RTICULAR PURPOSE. MANUFACTURER SHALL NOT BE
LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY
ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,
COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer
with respect to its products and replac es all previous warranties and is
the only warranty made by Manufacturer. No increase or alteration,
written or verbal, of the obligation of this warranty is authorized.
Manufacturer does not represent that its products will preven t any loss
by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at
Manufacturer's discretion, each part returned by its authorized
Distributor and acknowledged by Manufacturer to be defective,
provided that such part shall have been returned to Manufacturer with
all charges prepaid and the authorized Distributor has completed
Manufacturer's Return Material Authorization form. The replacement
part shall come from Manufacturer's stock and may be new or
refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND
EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.