Notifier NFS-320, NFS-320E, NFS-320C, NFS2-640/E Installation Manual

Page 1
Fire Alarm Control Panel
NFS-320/E/C
Installation Manual
Document 52745 7/1/14 Rev:
P/N 52745:M2 ECN 13-838
M2
Page 2
2 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi­cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi­oelectriques depassant les limites applicables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriF ire® , and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of
Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2014 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 3
Page 4
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 5
Table of Contents
Section 1: About This Manual..................................................................................................7
1.1: Standards and Other Documents....................................................................................................................7
1.2: UL 864 Compliance.......................................................................................................................................8
1.2.1: Products Subject to AHJ Approval......................................................................................................8
1.3: Related Documents........................................................................................................................................8
1.4: Cautions and Warnings ..................................................................................................................................9
1.4.1: Typographic Conventions....................................................................................................................9
Section 2: System Overview.................................................................................................. 10
2.1: System Description......................................................................................................................................10
2.1.1: Standard Features ..............................................................................................................................10
2.1.2: Options ..............................................................................................................................................11
2.1.3: System Limitations............................................................................................................................11
2.2: System Components ....................................................................................................................................11
2.2.1: Standard Equipment ..........................................................................................................................11
2.2.2: Control Panel Circuit Board .............................................................................................................11
2.2.3: Main Power Supply CPS-24/E ..........................................................................................................12
2.2.4: Circuit Board Components ................................................................................................................13
2.2.5: System Cabinet..................................................................................................................................15
2.3: Compatible Equipment ...............................................................................................................................16
Section 3: Installation.............................................................................................................18
3.1: Preparing for Installation .............................................................................................................................18
3.1.1: Standards and Codes..........................................................................................................................18
3.2: Installation Checklist ...................................................................................................................................19
3.3: Mounting a Cabinet .....................................................................................................................................20
3.4: Installing Option Boards..............................................................................................................................20
3.5: Connecting the Power Cables......................................................................................................................22
3.5.1: Overview ...........................................................................................................................................22
3.5.2: Connecting the Control Panel to AC Power......................................................................................23
3.5.3: Checking AC Power ..........................................................................................................................23
3.5.4: Installing and Connecting the Batteries ............................................................................................24
3.5.5: External DC Power Output Connections...........................................................................................24
3.5.6: Accessories DC Power Output Connections .....................................................................................25
3.6: NAC Connections and Releasing Circuits...................................................................................................26
3.6.1: Stat-X Devices...................................................................................................................................27
3.7: Output Relay Connections...........................................................................................................................27
3.8: Backup-Alarm Switches .............................................................................................................................28
3.9: UL Power-limited Wiring Requirements.....................................................................................................29
3.9.1: Labeling Modules and Circuits..........................................................................................................30
3.10: Installing EIA-485 Devices .......................................................................................................................30
3.11: Installing Remote Printers and/or CRT......................................................................................................30
3.11.1: Custom Cable Fabrication ...............................................................................................................30
3.11.2: Installing and Configuring the PRN Series Printer .........................................................................31
3.11.3: Installing and Configuring a CRT-2................................................................................................32
3.11.4: Connecting Multiple Printers, CRTs, or CRT/PRN Combination ..................................................33
3.12: Wiring a Signaling Line Circuit (SLC)......................................................................................................34
3.13: Connecting a PC for Off-Line Programming ............................................................................................35
Section 4: Applications ..........................................................................................................36
4.1: Overview......................................................................................................................................................36
4.2: Devices Requiring External Power Supervision..........................................................................................36
4.3: NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit)..................................37
4.4: Central Station Fire Alarm System Canadian Requirements.......................................................................39
4.5: NFPA 72 Proprietary Fire Alarm Systems...................................................................................................40
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 5
Page 6
Table of Contents
4.6: Fire/Security Applications ..........................................................................................................................40
4.6.1: General Operation..............................................................................................................................40
4.6.2: Installing a Security Tamper Switch..................................................................................................41
4.6.3: Receiving Unit ...................................................................................................................................41
4.6.4: Programming .....................................................................................................................................41
4.6.5: Wiring for Proprietary Security Alarm Applications ........................................................................42
4.7: Releasing Applications ................................................................................................................................43
4.7.1: Overview............................................................................................................................................43
4.7.2: Programming .....................................................................................................................................43
4.7.3: Wiring ................................................................................................................................................43
4.7.4: Connecting a Releasing Device to the Control Panel ........................................................................44
4.7.5: Connecting a Releasing Device to the FCM-1 Module.....................................................................46
4.7.6: Connecting a Releasing Device to the FCM-1-REL .........................................................................47
4.7.7: Connecting an NBG-12LRA Agent Release-Abort Station ..............................................................48
Section 5: Testing the System .............................................................................................. 50
5.1: Acceptance Test ...........................................................................................................................................50
5.2: Periodic Testing and Service........................................................................................................................50
5.3: Operational Checks......................................................................................................................................50
5.4: Battery Checks and Maintenance.................................................................................................................51
Appendix A: Power Supply Calculations ............................................................................. 52
A.1: Calculating AC Branch Circuit Current......................................................................................................52
A.2: Calculating the System Current Draws ......................................................................................................52
A.2.1: Calculating the Maximum Secondary Power Fire Alarm Current Draw..........................................55
A.3: Calculating the Battery Requirements ........................................................................................................56
A.3.1: Calculating the Battery Capacity ......................................................................................................56
A.3.2: Calculating the Battery Size .............................................................................................................57
Appendix B: Electrical Specifications ..................................................................................58
B.1: Electrical Specifications..............................................................................................................................58
B.2: Wire Requirements......................................................................................................................................60
Index ........................................................................................................................................ 62
6 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 7

Section 1: About This Manual

1.1 Standards and Other Documents

This Fire Alarm Control Panel complies with the following NFPA standards:
•NFPA 12 CO
• NFPA 12A Halon 1301 Extinguishing Systems
• NFPA 13 Sprinkler Systems
• NFPA 15 Water Spray Systems
• NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems
• NFPA 17 Dry Chemical Extinguishing Systems
• NFPA 17A Wet Chemical Extinguishing Systems
• NFPA 72 Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected Premises Unit (requires Notifier UDACT/UDACT-2).
• NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems.
• NFPA 72 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems (requires TM-4).
• NFPA 72 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems
• NFPA 72 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems (Protected Premises Unit).
• NFPA 2001 Clean Agent Fire Extinguishing Systems
The installer should be familiar with the following documents and standards:
• NFPA 72 Initiating Devices for Fire Alarm Systems
• NFPA 72 Inspection, Testing and Maintenance for Fire Alarm Systems
• NFPA 72 Notification Appliances for Fire Alarm Systems
Extinguishing Systems
2
Underwriters Laboratories
• UL 38 Manually Actuated Signaling Boxes
• UL 217 Smoke Detectors, Single and Multiple Station
• UL 228 Door Closers - Holders for Fire Protective Signaling Systems
• UL 268 Smoke Detectors for Fire Protective Signaling Systems
• UL 268A Smoke Detectors for Duct Applications
• UL 346 Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 Audible Signaling Appliances
• UL 521 Heat Detectors for Fire Protective Signaling Systems
• UL 864 Standard for Control Units for Fire Protective Signaling Systems
• UL 1481 Power Supplies for Fire Protective Signaling Systems
• UL 1971 Visual Signaling Appliances
• UL 1076 Proprietary Burglar Alarm Systems
• UL 2017 Standard for General-Purpose Signaling Devices and Systems
• UL 2572 Standard for Mass Notification Systems
• UL 60950 Safety of Information Technology Equipment
Underwriters Laboratories of Canada (ULC)
• Standard CAN/ULC-S527-M99
• CAN/ULC-S524-M91 Standard for the Installation of Fire Alarm Systems
Other
• EIA-485 and EIA-232 Serial Interface Standards
• NEC Article 300 Wiring Methods
• NEC Article 760 Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction
• C22.1-98 The Canadian Electrical Code, Part 1
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 7
Page 8
About This Manual UL 864 Compliance

1.2 UL 864 Compliance

1.2.1 Products Subject to AHJ Approval

This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition.
The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications. Operation of the NFS-320/E/C with products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
• For a complete list of all peripherals that can be used with this fire alarm control panel (FACP), and which of those peripherals have not received UL 864, 9th Edition certification and may only be used in retrofit applications, see Section 2.3, “Compatible Equipment”, on page 16.

1.3 Related Documents

Table 1.1 below provides a list of documents referenced in this manual, as well as documents for selected other compatible devices. The document series chart (DOC-NOT) provides the current document revision. A copy of this document is included in every shipment.
Compatible Conventional Devices (Non-addressable) Document Number
Device Compatibility Document 15378
Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number
NFS-320/E/C Installation, Operations, and Programming Manuals NFS-320C Canadian Applications Addendum
SLC Wiring Manual 51253
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming Utility Document Number
VeriFire® Tools CD help file VERIFIRE-TCD
Power Supplies, Auxiliary Power Supplies & Battery Chargers Document Number
ACPS-2406 Installation Manual 51304
ACPS-610 Instruction Manual 53018
APS-6R Instruction Manual 50702
APS2-6R Instruction Manual 53232
CHG-120 Battery Charger Manual 50641
FCPS-24S6/FCPS-24S8 Field Charger/Power Supply Manual 51977
Networking Document Number
52745, 52746, 52747
52745CDN
High-Speed Network Communication Module 54014
High-Speed Noti•Fire•Net Instruction Manual 54013
Noti•Fire•Net Manual, Network Version 5.0 & Higher 51584
ONYXWorks™ Workstation Hardware & Software Application: Installation and Operation Manual 52342
ONYXWorks™ NFN Gateway (PC Platform) Installation & Operation Manual 52307
Table 1.1 Reference Documentation (1 of 2)
8 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 9
Cautions and Warnings About This Manual
!
!
ONYXWorks™ NFN Gateway (Embedded Platform) Installation & Operation Manual 52306
NCM-W/F Installation Document 51533
NCS ONYX® Network Control Station Manual, Network Version 4.0 & Higher 51658
NCA-2 Network Control Annunciator Manual 52482
NCA Network Control Annunciator Manual 51482
System Components Document Number
Annunciator Control System Manual 15842
ACM-8R Annunciator Control Module Manual 15342
FDU-80 Remote Annunciator Manual 51264
LCD-80 Liquid Crystal Display Annunciator 15037
LCD2-80 Liquid Crystal Display Annunciator 53242
LDM Series Lamp Driver Annunciator Manual 15885
SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712
DPI-232 Direct Panel Interface Manual 51499
TM-4 Installation Document (Reverse Polarity Transmitter) 51490
UDACT Manual (Universal Digital Alarm Communicator/Transmitter) 50050
UDACT-2 Manual (Universal Digital Alarm Communicator/Transmitter) 54089
FireVoice-25/50 & FireVoice-25/50ZS Manual 52290
FirstCommand Emergency Communication System LS10001-001-NF-E
RA100Z Remote LED Annunciator Installation Document I56-0508
FSA-8000 Intelligent Aspiration Sensing Technology Document I56-3903
FWSG Wireless Manual LS10036-000NF-E
Table 1.1 Reference Documentation (2 of 2)

1.4 Cautions and Warnings

This manual contains cautions and warnings to alert the reader as follows:
CAUTION:
Information about procedures that could cause programming errors, runtime errors, or equipment damage.
WARNING:
Indicates information about procedures that could cause irreversible damage to the control panel, irreversible loss of programming data or personal injury.

1.4.1 Typographic Conventions

NOTE: The term NFS-320 is used in this manual to refer to the NFS-320, and the NFS-320E
and the NFS-320C, unless otherwise noted.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 9
Page 10

Section 2: System Overview

2.1 System Description

The NFS-320/E/C control panel is a modular, intelligent fire alarm control panel (FACP) with an extensive list of powerful features. The control panel uses the CPS-24/E integral power supply with battery charger. This is mounted in its cabinet to create a complete fire alarm control system. The panel supports FlashScan® and CLIP mode; the board provides an integral signaling line circuit (SLC) that can support up to 318 addressable points (159 detectors and 159 monitor/control modules). The panel is networkable, and can be monitored across a network by other networked panels.
Modular devices mount in the cabinet or in auxiliary backboxes to provide additional circuits. This system is available in either a 120 VAC or 240 VAC configuration. Cabinetry can be ordered in black or in red. The NFS-320/E/C chassis is removable, allowing work to be done outside the cabinet.

2.1.1 Standard Features

• Uses Notifier’s VIEW® early warning fire detection and the FlashScan® or Classic Loop Interface Protocol (CLIP) families of detectors and modules
• Integral power supply with battery charger
• Four standard Notification Appliance Circuits (NAC), Class A or B
• Alarm, Trouble, Supervisory and Security relays
• Support for 32 annunciator addresses, with 10 special annunciator groups
• Supports Style 4, Style 6, Style 7 SLC loops
• Releasing service using on-board NACs or FCM-1 modules
• Logic Equations
• Display scroll selection
• Alarm verification supervisory indication (NYC)
• Supervisory duct detectors
• Supports ONYX® Intelligent Sensing algorithms
• Network operation
• Battery charger supports 18 to 200 amp hour sealed lead-acid batteries
• EIA-485 connections for wiring ACS annunciators (including LDM custom graphic annunciators), TM-4 transmitter
• EIA-232 connections for printer, CRT, printer/CRT, or network operation
• VeriFire Tools® off-line programming utility
• Autoprogram feature for faster device programming
• The control panel provides 6 amps of usable output power in an alarm condition; it provides 3 amps of usable output power in normal or continuous operating conditions
• Diagnostic LEDs and switches
• Ground fault detection (0 ohm impedance)
• Battery and battery-charger supervision, voltage-monitoring, and current-monitoring
• Disconnect of deeply-discharged battery (low battery disconnect)
• Programmable for strobe synchronization
• QWERTY silicone-rubber keypad with a 2x40 LCD display and eight indicator LEDs
• Mass Notification System compatible
10 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 11
System Components System Overview

2.1.2 Options

Refer to Section 2.2 “System Components” for descriptions of the various optional modules.
• Optional devices include: Wire and Fiber versions of the NCM or HS-NCM connection to the Noti•Fire•Net and High­Speed Noti•Fire•Net, UDACT/UDACT-2 Universal Digital Alarm

2.1.3 System Limitations

System expansion must take into consideration the following:
1. The physical limitations of the cabinet configuration.
2. The electrical limitations of the system power supply.
3. The capacity of the secondary power source (standby batteries). (Note that batteries larger than 26 AH will require a separate battery backbox.)

2.2 System Components

2.2.1 Standard Equipment

The standard, factory-assembled NFS-320/E/C system includes the following components:
• The control panel with integral power supply, and cabinet. NFS-320 (120V operation) or NFS­320E (220-240V operation), and CPS-24/E. NFS-320/E is the “control panel” itself and the heart of the system; it ships with a grounding cable, battery interconnect cables, and document kit. CPS-24/E mounts directly on the control panel. The system ships pre-installed in its cabinet.
Communicator/Transmitter, and ACM-8R remote relay module to increase point capacity.
• Optional annunciators connected through the EIA-485 interface allow remote system monitoring.
NOTE: The CPS-24/E is an integral part of the NFS-320 and is not available separately.
• A primary display KDM-R2 keypad/display.
Batteries are ordered separately; refer to Appendix A.3 “Calculating the Battery Requirements” for system current-draw calculations.
Up to two option boards can be installed within the FACP’s cabinet; additional optional peripherals can be mounted in auxiliary backboxes. Refer to Section 2.3, “Compatible Equipment” for equipment listed for use with this FACP.

2.2.2 Control Panel Circuit Board

The control panel electronics are contained in NFS-320 and its built-in power supply. The printed circuit board incorporates a signaling line circuit (SLC) and the central processing unit; the power supply has an integral battery charger. A keypad/display unit is installed over the power supply as shown Figure 2.1. Wiring is shown in Figure 2.2, “NFS-320 and Power-Supply: Wiring Connections” and Figure 2.3, “NFS-320 and Power-Supply: Jumpers, LEDs and Switches”.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 11
Page 12
System Overview System Components
320door_open.wmf
Figure 2.1 NFS-320/E/C System, Shown
with Door Open

2.2.3 Main Power Supply CPS-24/E

The main power supply is an integral part of the NFS-320/E/C and mounts directly over the control panel’s circuit board. It provides a total of 3.9 A (7.4 A in alarm) and contains an integral battery charger. This can be used for many functions including:
• Powering the NFS-320/E/C
• Powering a variety of UL-listed 24 VDC notification appliances from four built-in NAC outputs
• Providing up to 1.25 A of resettable power for four-wire smoke detectors
See Figure 2.2, “NFS-320 and Power-Supply: Wiring Connections” and Figure 2.3, “NFS-320 and Power-Supply: Jumpers, LEDs and Switches” for details.
• Providing up to 1.25 A of non-resettable power for external devices such as the TM-4 Transmitter Module
• Providing auxiliary 24 VDC power @ 0.5 A and 5 VDC power @ 0.15 A
• Fuse: 8 amps, 250 V, 5 x 20 mm, Fast Acting, ceramic, p/n 12117
12 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 13
System Components System Overview
TB13 - SLC Loop #1
(supervised, power-
limited)
(Figure 3.18)
TB11 - EIA-485 ACS Mode Connection (supervised)
TB11 - EIA-485 Terminal Mode Connection (supervised)
(Figure 3.14 on page 30)
TB10 - DC Power
(24 VDC power-limited)
Resettable
Non-resettable
(See Figure 3.6 on page 24)
TB12 - EIA-232 Printer Connection (Figure 3.15 on page 31)
TB12 - EIA-232 PC/Terminal Connection (CRT)
(Figure 3.16 on page 32)
J1 - Network/Service Connection (NUP)
(power-limited, supervised)
J2 - USB A VeriFire Tools Connection
J3 - USB B VeriFire Tools Connection
TB8 - NAC#2
All NAC Circuits: power-
limited, supervised
(Figure 3.9 on page 26)
TB9 - NAC#1
TB7 - NAC#3
TB6 - NAC#4
Output Relays - power-limited only if connected to a power-limited
source. (See Figure 3.11 on page 27 for details.)
TB5 -
Supervisory Relay
Security Relay
TB4 -
Alarm Relay
Trouble Relay
J5 - Security Tamper Switch
J6 - Auxiliary Trouble Input
J7 - KDM-R2
Connection
CPU320-KAPS-
Figure 2.2 NFS-320 and Power-Supply: Wiring Connections
TB3 - Battery Connection
(over-current protected, non-power-limited)
TB1 - AC Power Connection (non-
power-limited)
Hot
Neutral
Earth
Ground
(+) (-)
TB2 - Secondary Power Auxiliary Outputs
(power-limited)

2.2.4 Circuit Board Components

The following three figures illustrate the location of the various connections, switches, jumpers and LEDs on the NFS-320 and its power supply. Figure 2.2 shows wiring connections; Figure 2.3 shows jumpers, LEDs and switches. See Section 3 “Installation” for larger images and more details. (Larger images are referenced on these drawings.)
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 13
Page 14
NAC
LEDs
Disable - Enable Switches
for Backup Alarm
(Figure 3.12 on page 28)
LED10 – SLC Loop
Ground Fault LED
LED5 - Supervisory LED
LED7 - Pre-Alarm LED
LED6 - Security LED
LED3 - Point Disabled LED
LED2 - Signals Silenced LED
LED4 - System Trouble LED
LED8 - Fire Alarm LED
LED1 - Power-on LED (AC or battery)
System Switches - ‘No
Keyboard Operation’
SW5 - Acknowledge
SW6 - Silence
SW7 - Reset
CPU320-KAPS-291809.wmf, CPU2-640-
JP1 - SLC Ground
Fault Jumper
SW1 - Ground Fault Detection Enable/Disable
LED3 - Earth Fault LED (general board ground fault)
Figure 2.3 NFS-320 and Power-Supply: Jumpers, LEDs and Switches
LED5 - +24V Aux LED
LED6 - +5V Aux LED
LED6 - +5V Aux LEDLED1 - Logic Power LED
LED2 - Trouble LED
LED4 - AC Power LED
F4- AC Fuse
System Overview System Components
14 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 15
System Components System Overview

2.2.5 System Cabinet

The control panel is factory installed in its backbox. The lockable door is hinged on the left and opens a full 180 degrees. Mounting methods include surface-mounting or semi-flush mounting on a wall between 16 inch (40.64 cm) on-center studs. A trim ring option is available for semi-flush mounting.
External measurements:
• Backbox: 18.12 in. (46.025 cm) width;
18.12 in. (46.025 cm) height;
5.81 in. (14.76 cm) depth.
When using trim ring TR-320, mount backbox with at least 1 inch (2.54 cm) between wall surface and front of backbox, to allow door to open fully past the trim ring. The TR-320 molding width is
0.905 in. (2.299 cm).
Additional Options
The NFS-320/E/C control panel provides space for one or two additional option boards to be installed, as shown in Figure 3.3 on page 21. The NFS-320C fulfills ULC annunciation requirements; see NFS-320C Canadian Applications Addendum for details. A variety of compatible annunciators are available with their own backboxes; see Section 2.3, “Compatible Equipment”.
• Door: 18.187 in. (46.195 cm) width;
18.40 in. (46.736 cm) height;
0.75 in. (1.905 cm) depth.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 15
Page 16
System Overview Compatible Equipment
!
Continued on next page...

2.3 Compatible Equipment

These are the most common devices at time of publishing; the most complete list of compatible intelligent SLC loop devices is provided in the SLC Wiring Manual; for conventional non­addressable equipment see the Device Compatibility Document. These devices are UL and ULC listed unless marked otherwise (in parentheses next to the product). Other control panels and their equipment can also be connected in a network, via Noti•Fire•Net version 5.0 or the High-Speed Noti•Fire•Net; refer to the Noti•Fire•Net Version 5.0 & Higher Installation Manual or High-Speed Noti•Fire•Net Installation Manual for details. For products documented separately, see Section 1.3 “Related Documents”.
WARNING: UL 9th Edition Compliance
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of the NFS-320/E/C with products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ). Peripheral devices in the second list were listed under UL 8th Edition and may only be used in retrofit applications (see Section 1.2, “UL 864 Compliance”, on page 8).
Notifier Compatible Equipment
NOTE: Products marked with a checkmark “” have not received UL 864 9th Edition
certification and may only be used in retrofit applications (see Section 1.2, “UL 864 Compliance”, on page 8)
NOTE: The wireless option is not suitable for ULC.
Electronic Equipment
A77-716B End-of-Line Resistor Assembly Acclimate Plus™ FAPT-751, FAPT-851 Combination
Photoelectric/Heat Detector
ACM-24AT Annunciator Control Module ACM-48A Annunciator Control Module ACM-8R Annunciator Control Module ACPS-610 Addressable Charger/Power Supply AEM-24AT Annunciator Expander Module AEM-48A Annunciator Expander Module AKS-1B Annunciator Key Switch APS2-6R Auxiliary Power Supply B200S Addressable sounder base B200SR Sounder base B501 Intelligent base B501BH Sounder base B501BH-2 Sounder base, steady tone B501BHT-2 Sounder base, temporal tone B710LP/B210LP Intelligent detector base BAT-12120 Battery 12-volt, 12 amp-hour BAT-12180 Battery 12-volt, 18 amp-hour BAT-12250 Battery 12-volt, 25 amp-hour BAT-12260 Battery 12-volt, 26 amp-hour BAT-12550 Battery 12-volt, 55 amp-hour BAT-12600 Battery 12-volt, 60 amp-hour BX-501 Intelligent Detectors/Sensors Base CCM-1 Communication Converter Module CMX-1 Addressable Control Module CMX-2 Addressable Control Module CPU-320/E Control Panel Circuit Board CPX-551 Ionization Smoke Detector CPX-751 Intelligent Ionization Smoke Detector CRT-2 Video Display Monitor with Keyboard DHX-501, DHX-502 Duct Detectors DNR/W Intelligent Non-Relay Photoelectric Duct Detector DPI-232 Direct Panel Interface FCM-1 NAC Module FCM-1-REL Control Module FCO-851 IntelliQuad PLUS Multi-Criteria Fire/CO Detector FCPS-24S6/S8 Field Charger Power Supply FDM-1 Dual Monitor Module FDRM-1 Dual Monitor/Dual Relay
FDU-80, FDU-80G Remote Fire Annunciator FDX-551 Intelligent Thermal Sensor FMM-1 Monitor Module FMM-101 Mini Monitor Module FRM-1 Relay Module FSA-8000 FAAST Intelligent Aspiration Detector FSB-200 Single-ended beam smoke detector. FSB-200S Single-ended beam smoke detector with
sensitivity testing
FSC-851
IntelliQuad Multi-Criteria Smoke Detector
FSD-751P Photoelectric Duct Detector FSD-751PL Low-flow Duct Detector FSD-751RP Photoelectric Duct Detector with alarm relay FSD-751RPL Low-flow Duct Detector with alarm relay FSH-751 HARSH™ Smoke Detector FSI-751, FSI-851 Ion Detector FSL-751 VIEW® Low Profile Laser Detector FSM-101 Pull Station Monitor Module FSP-751, FSP-851 Photo Detector FSP-751T, FSP-851T Photo/Thermal Detector FSP-851R/DNR Remote Test Capable Photoelectric Smoke
Detector
FST-751, FST-851 Thermal Detector FST-751R, FST-851R Thermal Detector (rate of rise) FST-851H High Temperature Detector FWSG Wireless Gateway. FWD-200P Wireless photo detector for use with the FWSG
Wireless Gateway. FWD-200ACCLIMATE Wireless Acclimate detector for use with the FWSG Wireless Gateway. FWH-200FIX135 Wireless, fixed-temperature heat detector for use with the FWSG Wireless Gateway. FWH-200ROR135 Wireless, rate-of-rise heat detector for use with the FWSG Wireless Gateway.FW-MM Wireless Monitor Module for use with the FWUIDDJ.
FTM-1 Telephone Module FZM-1 Monitor and Zone Interface Module HPX-751 Intelligent HARSH™ Detector HS-NCM-MF High-Speed Network Communications Module
(Multi-Mode Fiber) HS-NCM-MFSF High-Speed Network Communications Module (Multi-Mode Fiber to Single-Mode Fiber)HS-NCM-SF High-Speed Network Communications Module (Single-Mode
16 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 17
Compatible Equipment System Overview
Fiber) HS-NCM-W High-Speed Network Communications Module (Wire) HS-NCM-WMF High-Speed Network Communications Module (Wire to Multi-Mode Fiber) HS-NCM-WSF High-Speed Network Communications Module (Wire to Single-Mode Fiber)
ISO-X Loop Fault Isolator Module KDM-R2 Keypad/Display Unit LCD-80 Liquid Crystal Display Annunciator LCD2-80 Liquid Crystal Display Annunciator LDM-32 Lamp Driver Module LDM-E32 Lamp Driver Module LDM-R32 Lamp Driver Module LPX-751 VIEW® Low Profile Laser Detector (CLIP) MMX-1 Addressable Monitor Module MMX-101 Addressable Mini Monitor Module MMX-2 Addressable Monitor Module N-ELR Assortment ELR Pack with Mounting Plate NBG-12 Series Manual Pull Station NBG-12LRA Agent Release-Abort Station NBG-12LX Addressable Manual Pull Station NBG-12LXP Portuguese-labeled Addressable Manual Pull
Station NBG-12LXSP Spanish-labeled Addressable Manual Pull Station
NCA-2 Network Control Annunciator NCM-F Network Communications Module (Fiber)
NCM-W Network Communications Module (Wire) NCS Network Control Station NFV-25/50 Notifier FireVoice-25/50 ONYXWorks Graphical Workstation PRN-6 80-Column Printer R-120 120 Ohm End-of-Line Resistor R-2.2K 2.2K End-of-Line Resistor R-27K 27K End-of-Line Resistor R-470 470 End-of-Line Resistor R-47K 47K End-of-Line Resistor RM-1 Remote Microphone RM-1SA Remote Microphone RPT-485F EIA-485 Repeater (Fiber) RPT-485W EIA-485 Repeater (Wire) RPT-485WF EIA-485 Repeater (Wire/Fiber) SCS-8, SCE-8 Smoke Control Station SCS-8L, SCE-8L Smoke Control Lamp Driver SDX-551 Intelligent Photoelectric Detector SDX-751 Intelligent Photoelectric Detector STS-1/STS-200 Security Tamper Switch TM-4 Transmitter Module UDACT Universal Digital Alarm Communicator Transmitter UDACT-2 Universal Digital Alarm Communicator/Transmitter XP10-M Ten Input Monitor Module XP6-C Supervised Control Module XP6-MA
Six Zone Interface Module
XP6-R Six Relay Control Module
Backboxes, Chassis, Dress Panels, etc.
ABF-1B Annunciator Flush Box ABF-1DB Annunciator Flush Box with Door ABF-2B Annunciator Flush Box ABF-2DB Annunciator Flush Box with Door ABF-4B Annunciator Flush Box ABM-16AT Annunciator Blank Module ABM-32A Annunciator Module Blank ABS-1B Annunciator Surface Box
ABS-1TB Annunciator Surface Box ABS-2B Annunciator Surface Box ABS-4D Annunciator Surface Box ABS-8RB Annunciator Backbox for ACM-8R NFS-LBB Battery Box NFS-LBBR Red Battery Box VP-2B 2” Filler Dress Plate
System Sensor Equipment
A2143-00 End of Line Resistor Assembly EOLR-1 End-of-Line Resistor Assembly
Retrofit Equipment: Compatible Notifier Equipment Listed Under Previous Editions of UL 864
NOTE: The products in this list have not received UL 864 9th Edition certification and may only be used in retrofit applications (see Section 1.2, “UL 864 Compliance”, on page 8).
ACM-16AT Annunciator Control ModuleACM-32A Annunciator Control ModuleACPS-2406 Auxiliary Charger/Power SupplyAEM-16AT Annunciator Expander ModuleAEM-32A Annunciator Expander ModuleAPS-6R Auxiliary Power SupplyBGX-101L Addressable Manual Pull StationCHG-120 Battery Charger FCPS-24 Field Charger Power SupplyIPX-751 Advanced Multi-Sensor Intelligent DetectorNCA Network Control Annunciator P-40 Keltron PrinterP40-KITB Dress plate for Keltron Printer
PRN-4, PRN-5 80-Column PrintersRA400 Remote AnnunciatorRA400Z Remote Annunciator with diodeXP5-C Transponder Control ModuleXP5-M Transponder Monitor ModuleXPC-8 Transponder Control ModuleXPDP Transponder Dress Panel XPM-8 Transponder Monitor ModuleXPM-8L Transponder Monitor ModuleXPP-1 Transponder ProcessorXPR-8 Transponder Relay Module
NOTE: The FWSG Wireless Gateway as part of the wireless network has been tested for compliance with the Federal Communications Commission (FCC) requirements of the United States Government. This product has not been evaluated for use outside the USA. Use of this system outside the USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this product may be legally used outside the USA.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 17
Page 18

Section 3: Installation

!
!

3.1 Preparing for Installation

Choose a location for the fire alarm system that is clean, dry, and vibration-free with moderate temperature. The area should be readily accessible with sufficient room to easily install and maintain it. There should be sufficient space for cabinet door(s) to open completely.
Carefully unpack the system and inspect for shipping damage. Count the number of conductors needed for all devices and find the appropriate knockouts. (Refer to Section 3.9 “UL Power-limited Wiring Requirements” for selection guidelines.)
Before installing the fire alarm system, read the following:
• Review the installation precautions at the front of this manual, including temperature and humidity limits for the system (Page 3).
• All wiring must comply with the National and Local codes for fire alarm systems.
• Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a separate battery cabinet; this space is for internal battery installation.
• Review installation instructions in Section 3.2 “Installation Checklist”.
CAUTION:
Make sure to install system components in the sequence listed below. Failure to do so can damage the control panel and other system components.
WARNING:
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits. Use static-suppressive packaging to protect electronic assemblies removed from the unit.

3.1.1 Standards and Codes

In addition, installers should be familiar with the following standards and codes:
• NEC Article 300 Wiring Methods.
• NEC Article 760 Fire Protective Signaling Systems.
• Applicable Local and State Building Codes.
• Requirements of the Local Authority Having Jurisdiction.
• C22.1-98 The Canadian Electrical Code, Part 1.
• CAN/ULC-S5524-01 Standard for the Installation of Fire Alarm Systems.
18 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 19
Installation Checklist Installation
Location for 1 or 2 option boards
Figure 3.1 NFS-320/E/C in Cabinet
Top two mounting holes
Two lower mounting holes are behind batteries.

3.2 Installation Checklist

Table 3.1 provides an installation checklist for installing, wiring, and testing the NFS-320/E/C system. It has references to installation information included in manuals listed in Section 1.3 “Related Documents”.
Seq Task Refer to
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Mount the cabinet backbox to the wall. Section 3.3 “Mounting a Cabinet”
If adding option boards such as such as wire and/or fiber version of the NCM/HS-NCM or TM-4:
• Remove keypad.
• Install option boards
• Replace keypad
Optional: Install auxiliary power supply and/or external battery charger; set backup-alarm switches.
Connect AC wiring, place batteries into backbox without connecting them, and run cable to optional power supplies, DC power outputs, NACs, and relays.
CAUTION: Do not apply AC or DC power at this time.
Optional: Install output devices such as a printer, or CRT terminal.
Wire annunciators and network connections. Relevant product manuals
Wire the Signaling Line Circuits. Section 3.12 “Wiring a Signaling Line Circuit (SLC)”
Terminate wire shielding as instructed. SLC Wiring Manual
Apply AC power to the control panel by placing the external circuit breaker to the ON position. Do NOT connect batteries.
Check AC power. Table 3.2 in Section 3.5 “Connecting the Power Cables”
Connect the batteries using interconnect cable, P/N 75560 and 75561.
Program the control panel. NFS-320/E/C Programming Manual and VeriFire Tools
Field test the system. Section 5 “Testing the System”
Section 3.4 “Installing Option Boards”, Section 1. “Remove and re-install KDM-R2 as shown in Figure 3.2. It may be convenient to do some basic field­wiring before reinstalling KDM-R2.”, and Section 3.4 “Installing Option Boards” Also see option board documentation for board-specific details.
Auxiliary power manuals, Section 3.8 “Backup-Alarm Switches”
Section 3.5 “Connecting the Power Cables”
Section 3.11 “Installing Remote Printers and/or CRT”
Online Help.
Table 3.1 Installation Checklist
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 19
Page 20
Installation Mounting a Cabinet
!

3.3 Mounting a Cabinet

This section provides instructions for mounting the NFS-320/E/C backbox to a wall. The NFS­320/E/C is assembled with a removable chassis that can be removed to provide easier access to the backbox’s mounting holes, or to allow the electronics to be worked on outside the cabinet.
Follow these guidelines when mounting the backbox:
• Locate the backbox so that the top edge is 66 inches (1.6764 m) above the surface of the finished floor.
• Access to the cabinet shall be provided in accordance with NFPA 90, article 110.33.
• Allow sufficient clearance around cabinet for door to swing freely. (See Section 2.2.5 “System Cabinet”.)
• Use the four holes in the back surface of the backbox to provide secure mounting. (See Figure 3.1 on page 19.)
• Mount the backbox on a surface that is in a clean, dry, vibration-free area.
CAUTION:
Unless you are familiar with the placement of components within this backbox, only use the knockout locations provided for conduit entry.
Follow the instructions below:
1. Mark and pre-drill holes for the top two keyhole mounting bolts (0.25 inch, 0.635 cm). Use mounting hardware appropriate for the mounting surfaces; see UL 2017 Pull-Test Requirements.
2. Select and punch open the appropriate knock-outs. (For selection guidelines, see Section 3.9 “UL Power-limited Wiring Requirements”.)
3. Using the keyholes, mount the backbox over the two screws.
4. Mark the location for the two lower holes, remove the backbox and drill the mounting holes.
5. Mount the backbox over the top two screws, then install the remaining fasteners. Tighten all fasteners securely.
6. Feed wires through appropriate knockouts.

3.4 Installing Option Boards

The NFS-320/E/C ships fully assembled with in its cabinet. One or two option boards can be mounted inside the NFS-320 cabinet, under the keypad, as shown in Figure 3.3. Option boards that can be installed internally include the wire and/or fiber versions of the NCM or HS-NCM, TM-4, and UDACT or UDACT-2. See Section 2.3, “Compatible Equipment” for a complete list. When installing option boards, temporarily remove the KDM-R2 keypad/display unit to provide full access to hardware connections. It may be convenient to do some basic field-wiring before reinstalling KDM-R2.
NOTE: UDACT or UDACT-2 only:
If using UDACT or UDACT-2 inside the cabinet, do not install a second option board. See the UDACT Manual or UDACT-2 Manual for instructions on using the mounting bracket.
20 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 21
Installing Option Boards Installation
Figure 3.2 Removing and Reinstalling KDM-R2
320_assembly_tech_pubs_5 -2.wmf
Figure 3.3 Installing Option Boards
320_assembly_tech_pubs_3-2.wmf
!
1. Remove and re-install KDM-R2 as shown in Figure 3.2. It may be convenient to do some basic field-wiring before reinstalling KDM-R2.
2. Lay the first option board over the four stand-offs already installed on the CPU, so that the holes and stand-offs align.
3. If attaching a second option board, use its standoffs to secure the first option board, then lay the second option board over the standoffs. Two sizes of standoffs are shipped with the option boards; select standoffs that allow sufficient clearance for electronics on the lower option board.
4. Secure the top option board with four #4-40 screws (supplied).
5. Re-attach KDM-R2.
CAUTION:
It is critical that all mounting holes of the NFS-320/E/C are secured with a screw or standoff to insure continuity of Earth Ground.
NOTE: It may be convenient to field-wire the SLC loop before installing any option boards, and to make wiring connections on the first option board before installing a second option board in front of it.
Installing a Transmitter Module TM-4
TM-4 is power-limited. Connections are on TB10 nonresettable output and TB11 EIA-485 ACS Mode. Refer to the Transmitter Module TM-4 installation document for installation details.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 21
Page 22
Installation Connecting the Power Cables
!
!
Network Communications Module
If networking two or more control panels or network control annunciators, each unit requires a Network Communications Module (NCM) or a High-Speed Network Communications Module (HS-NCM); wire and fiber versions are available for each. The wire and/or fiber versions of the NCM or HS-NCM can be installed in any standard option-board position (see Section 3.4, “Installing Option Boards”; the default position is immediately to the right of the control panel.
1. Mount the NCM/HS-NCM in the selected position and screw firmly in place.
2. Connect J1 on the control panel to J3 on the NCM or J6 of the HS-NCM using the network cable provided (P/N 75556) as described in the NCM Installation Document and the HS-NCM Installation Document. Do not connect two NCM/HS-NCMs via NUP ports (“NUP to NUP”).
3. When installing the NCM: Connect Channel A and/or Channel B as described in the NCM Installation Document.
When installing the HS-NCM: Connect Channel A to Channel B as described in the HS- NCM Installation Document.
NOTE: See the Noti•Fire•Net Manual or the High-Speed XLS-NET Manual and NCM Installation Document or the HS-NCM Installation Document for wiring diagrams and system configuration
information. See the BMP-1 Product Installation Drawing if considering mounting the module behind blank module plate in a dress plate or annunciator backbox.
NOTE: Over-bending fiber-optic cable can damage it. Do not exceed a 3 inch (7.62 cm) minimum bend radius.
NOTE: NCM hardware is not compatible with HS-NCM hardware and should not be mixed on the same network.

3.5 Connecting the Power Cables

WARNING:
Remove all power sources to equipment while connecting electrical components. Leave the external, main power breaker OFF until installation of the entire system is complete.
WARNING:
Several sources of power can be connected to the control panel. Before servicing the control panel, disconnect all sources of input power including the battery. While energized, the control panel and associated equipment can be damaged by removing and/or inserting cards, modules, or interconnecting cables.

3.5.1 Overview

Complete all mounting procedures and check all wiring before applying power. Electrical connections include the following:
• Primary AC power source – 120 VAC, 50/60 Hz, 5.0 A from line voltage source (with NFS­320E use 220-240 VAC, 50/60 Hz, 2.5 A). Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 12 AWG (3.31
2
mm
) wire (maximum) with a 600-volt rating.
• Secondary power source – 24 VDC from batteries, installed in the control panel (or in an optional battery cabinet). Secondary (battery) power is required to support the system during loss of primary power.
22 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 23
Connecting the Power Cables Installation
TB1 - AC Power Connection
Hot
Neutral
Ground
(Earth)
Figure 3.4 CPS-24/E:
AC Power Connections
CPS-24_TB1.wmf
!
• External power sources – 24 VDC power for Smoke Detectors (4 wire), NACs, and Annunciators.
• Auxiliary power source – 24 VDC power @ 0.5 A and 5 VDC power @ 0.15 A from TB2 on the CPS-24/E.
See Appendix B “Electrical Specifications” for details and overall installation guidelines.

3.5.2 Connecting the Control Panel to AC Power

Connect primary power as follows (see Figure 3.4):
1. Turn off the circuit breaker at the main power distribution panel.
2. Open the hinged insulating cover on TB1.
3. Connect the service ground to terminal marked Ground (Earth).
4. Connect the primary neutral line to terminal marked NEUTRAL and the primary Hot line to terminal marked HOT.
5. Close the hinged insulating cover over TB1.

3.5.3 Checking AC Power

Table 3.2 contains a checklist for checking the system with AC power applied:
CAUTION:
While checking AC power, make sure batteries are not connected. Follow the sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is Step 10.
Component Status
Control panel circuit board
Each option board In an unconfigured system, the yellow Trouble indicator may come on for approximately 10 seconds after
Each auxiliary power supply
The green AC Power indicator on; the system Trouble indicator on because batteries are not connected.
applying AC power.
The yellow Trouble indicator comes on because batteries are not connected.
Table 3.2 AC Power Checklist
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 23
Page 24
Installation Connecting the Power Cables
!
!
COM
COM +5V AUX
+24V AUX
TB3 - Battery Connection
Battery (-)Battery (+)
Figure 3.5 CPS-24/E:
DC Power Connections
Non-resettable
Power
CPU-320-DCOut.wmf
Resettable
Power
Figure 3.6 Power Supply DC Outputs - TB10

3.5.4 Installing and Connecting the Batteries

w
WARNING:
Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention.
WARNING:
Do not connect the Battery Interconnect Cables (P/N 75560 and 75561) at this time. Make this connection AFTER initial system primary powerup. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is Step 11.
Batteries are installed in the control panel cabinet or in a separate battery cabinet which can be mounted below the control panel or up to 20 feet (6.096 m) away from the control panel, in conduit in the same room.
Connect the battery as follows (see Figure 3.4 above):
1. Install batteries into bottom of cabinet or into separate battery cabinet.
2. Connect the red cable from TB3(+) on the CPS-24/E power supply to the positive (+) terminal of one battery.
3. Connect the black cable from TB3(–) on the CPS-24/E power supply to the negative (–) terminal of the other battery.
4. Connect the remaining cable between the negative (-) terminal on the first battery to the positive (+) terminal on the second battery.

3.5.5 External DC Power Output Connections

Terminal TB10 provides two (2) power outputs, resettable and non-resettable. Each output is power-limited. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is part of Step 4.
24 VDC Resettable Power Circuit (Four-Wire Smoke Detectors). The power supply provides a single 24 VDC filtered, power-limited, resettable power circuit for devices that require resettable power (such as four-wire smoke detectors). This circuit is power-limited, but must be supervised. To provide supervision, install a UL-listed end-of-line power supervision relay (such as the EOLR-1) after the last device. Connect the power supervision relay normally open contact in series with an Initiating Device Circuit (IDC). The four-wire power circuit energizes the power supervision relay. When you reset the system, the control panel removes power from these terminals for approximately 15 seconds.
24 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 25
Connecting the Power Cables Installation
!
24V - Blue Wire
COM - Black Wire
5V - Red Wire
COM - Black Wire
AMPS24_TB2access.wmf
Connect external field wires to the power supply terminals TB10 RESET(+) and (–) to provide up to 1.25 A of current for powering four-wire smoke detectors. See Figure 3.6 above. TB2 (on CPS-
24), TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
24 VDC Non-resettable Power Circuit The power supply provides one 24 VDC filtered, power-limited, non-resettable power output, capable of up to 1.25 A. Use this circuit to power devices that require low-noise 24 VDC power (such as Notifier annunciator model ACM-24AT or the transmitter module TM-4).
Connect external field wires to power supply terminals TB10 NONRESET (+) and (–) to provide up to 1.25 A of non-resettable current for powering external devices such as annunciators. See Figure 3.6 above. TB2 (on CPS-24), TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
CAUTION:
During system reset, power remains at terminals TB10 NONRESET (+) and (–).

3.5.6 Accessories DC Power Output Connections

Terminal TB2 supplies one (1) non-resettable, power-limited 24 VDC circuit and one nonresettable, power-limited 5 VDC circuit available to power external devices. Applications that require a 5V connection to the Accessories Output, such as an UZC-256, must be within 10 feet (3.658 meters) of the power supply. The distance from the power supply to the accessory requiring power must not extend past the length of the supplied cable, P/N 75657 (supplied with UZC-256), which is 10 feet long. Do not splice or otherwise extend P/N 75657. Refer to section B.2, "Wire Requirements" of this manual for all applications requiring a 24V connection. Connect wiring with all power sources off.
• 24 VDC (nominal) @ 0.5 A max
• 5 VDC (nominal) @ 0.15 A max
Figure 3.7 Connecting to the Accessories Output TB2 on CPS-24/E
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 25
Page 26
Installation NAC Connections and Releasing Circuits
nfs640-nacout.cdr
Style Y (Class B)
Connection
Style Z (Class A)
Connection
Unused Circuits
UL-listed ELR-2.2K,
1/2 W (supplied)
Figure 3.8 Notification Appliance Circuit (NAC)
Connections
Figure 3.9 NAC Terminals and NAC LEDs
TB9 - NAC#1
TB8 - NAC#2
TB7 - NAC#3
TB6 - NAC#4
CPU-320-NACS.wmf
A–
A–
A–
A–
A+
A+
A+
A+
B–
B–
B–
B–
B+
B+
B+
B+

3.6 NAC Connections and Releasing Circuits

The control panel provides four NAC terminals as shown in Figure 3.9. Each can be configured as Style Y (Class B) or Style Z (Class A) as shown in Figure 3.8. Each circuit can provide 1.5 A of current, but the total current drawn from the main power supply cannot exceed 7.4 A in alarm condition (refer to Table A.2). Additionally, TB2 (on CPS-24), TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm. NAC circuits are supervised and power-limited. Use UL-listed 24 VDC notification appliances only (refer to the Device Compatibility Document).
NOTE: Any NAC can be programmed as a releasing circuit, and the releasing circuit must be supervised; For more information, refer to Section 4.7 “Releasing Applications” in this manual
and the NFS-320/E/C Programming Manual. Refer to the Device Compatibility Document for UL­listed compatible releasing devices. Sample connections for NAC terminals are shown in
26 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Figure 3.8. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is part of Step 4.
Page 27
Output Relay Connections Installation
Stat-X
Stat-X
Stat-X
REL-2.2K
Releasing Circuit
+
_
Ematch Protection Device P/N 3005014
Figure 3.10 Wiring Diagram for Stat-X Devices
Yellow
Green
Red
Black
StatXMultiEOL.wmf
CPU-320-relays.wmf
Figure 3.11 Form-C Relay
Connections

3.6.1 Stat-X Devices

Figure 3.10 shows typical wiring for STAT-X devices using the Ematch Protection Device (P/N
3005014). Note the following:
• Each Stat-X device requires an Ematch Protection Device to protect against high-voltage transient signals, such as lightning, that may cause the device to accidentally release.
• Multiple Stat-X devices can be connected in series (as shown).
• No more than ten (10) Stat-X devices can be connected on a single releasing circuit.
• A REL-2.2K can be installed on a single Stat-X device for short circuit detection. For multiple Stat­X devices installed in series, the REL-2.2K is installed on the last device on the releasing circuit (as shown). A REL-2.2K is required for ULC applications.
• Stat-X devices are not to be used with the FCM-1 or FCM-1-REL.

3.7 Output Relay Connections

The panel provides a set of Form-C relays. These are rated for 2.0 A at 30 VDC (resistive):
• Alarm - TB4
• Trouble - TB4
• Supervisory - TB5
• Security - TB5
These are power-limited only if connected to a power-limited source.
Using VeriFire Tools, the Supervisory and Security contacts can also be configured as Alarm contacts. Follow instructions in the VeriFire Tools online help.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 27
Page 28
Installation Backup-Alarm Switches
!
Figure 3.12 Backup Alarm
Switches
CPU-320-bckalm.wmf

3.8 Backup-Alarm Switches

WARNING:
Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if they are used for releasing functions!
Backup alarm switches are provided that enable NACs and the alarm relay to activate during a backup alarm condition. If the main board’s microcontroller fails and an alarm is reported by any detector or a monitor module that has backup reporting enabled, the NAC will turn on if the corresponding switch was enabled. The alarm will activate during microcontroller failure regardless of the settings of switches SW1-SW4.
• SW1 - NAC#1
• SW2 - NAC#2
• SW3 - NAC#3
• SW4 - NAC#4
So, for example, if SW1 and SW4 were enabled at the time of an alarm during microcontroller failure, NAC#1 and NAC#4 would activate. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1.
28 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 29
UL Power-limited Wiring Requirements Installation
640-2-PWRLMTWIR-ISO2.wmf
Figure 3.13 Typical Wiring for UL Power-limited Wiring Requirements
(Shown with relays as connected to power-limited modules)
NOTE: AC and battery wiring are not power-limited. Maintain at least 0.25 inches (6.35 mm)
between power-limited and non power-limited circuit wiring. Install tie wraps and adhesive squares to secure the wiring. Use a power-limited source for relay output on terminals TB5 and TB4. See Figure 2.2, “NFS-320 and Power-Supply: Wiring Connections” on page 13 to identify power­limited and non-powerlimited circuits.
NOTE: Drawing is not to scale; proportions and angles are exaggerated to show wire-placement more clearly.
NOTE: If additional knockouts are added to the backbox, proper separation of power-limited and nonpower-limited wiring should be maintained.
Power-limited Circuits*
Nonpower-
limited
circuits
To cabinet-mounted batteries
(nonpower-limited)
Power-
limited
circuits
NPL
NPL
Maintain vertical separation where circuits appear to
“cross”

3.9 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25 inches (6.35 mm) from any nonpower­limited circuit wiring. All power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockout and or conduits. To maintain separation, group non-power limited modules together, i.e., group modules on the same side of the enclosure or in separate rows.
Figure 3.13 shows one configuration that meets these UL requirements. Equipment is configured with at least a 0.25 inch (6.35 mm) separation between power-limited and nonpower-limited wiring; AC and battery wiring is routed away from power-limited wiring.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 29
Page 30
Installation Installing EIA-485 Devices
cpu2-640tb200.wmf
NOTE: In order to meet UL wiring requirements, please install grounding straps as shown below.

3.9.1 Labeling Modules and Circuits

At the time of installation, each nonpower-limited circuit connected to ACM-8R, and LDM-R32 modules must be identified in the space provided on the cabinet door label when connected to a non-power-limited source of power.
The label lists all compatible power-limited modules and circuits; also see Figure 2.2 on page 13.
The LDM-R32 is power-limited only when connected to power-limited sources. When connected to a non-power-limited source, the power-limited marking must be removed.

3.10 Installing EIA-485 Devices

Figure 3.14 provides a closer view of the EIA-485 connections provided on TB11. Because specific connections can vary by the type of device being connected, refer to the product installation manual for details.
Figure 3.14 EIA-485 Connections

3.11 Installing Remote Printers and/or CRT

3.11.1 Custom Cable Fabrication

A custom cable needs to be fabricated to connect the PRN Printer or the CRT-2 Monitor to the system. Length of the cable will vary with each installation, but should not exceed a maximum length of 20 feet (6.1 m). Printer must be installed in the same room as the panel, and the cable be installed in conduit. Construct cable as follows:
1. Using overall foil/braided-shield twisted-pair cable, properly connect one end to the DB-25 Connector using the wiring specifications shown in the table below. (Custom cable kit P/N 90106 is provided.)
30 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 31
Installing Remote Printers and/or CRT Installation
Note: Outputs are power-limited but are not supervised.
CPU-320-prn.wmf
DB-25 connector on PRN series printer (female socket shown)
Control Panel
Terminate one end of shield at backbox
Figure 3.15 Remote Printer Connections
2. Tighten clamp on connector to secure cable.
DB-25 Connector (Custom cable kit 90106)
Pin 3 TX
Pin 2 RX
Pin 7 REF
TB12 on Control Panel

3.11.2 Installing and Configuring the PRN Series Printer

When connected to the Control Panel via an EIA-232 interface, the PRN prints a copy of all status changes within the control panel and time-stamps the printout with the time of day and date the event occurred. It provides 80 columns of data on standard 9" by 11" tractor-feed paper.
NOTE: You can also use the EIA-232 printer interface with UL-listed information technology equipment, such as personal computers, to monitor the control panel for supplementary purposes.
This section contains information on connecting a printer to the control panel and for setting the printer options.
Connecting a Remote PRN Series Printer
Remote printers require a 120 VAC, 50/60 Hz primary power source. If required for the fire alarm system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power source (battery backup). Because a secondary power source is not provided, use a separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective Signaling. You may use your building emergency power supply, so long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB12 terminal block on the control
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the remote printer.
panel as shown in Figure 3.15.
Tighten securely.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 31
Page 32
Installation Installing Remote Printers and/or CRT
DB-25 connector
on CRT-2
(female socket shown)
Control Panel
nfs640-crt2conn.cdr
Terminate one end of shield at backbox
Figure 3.16 Connecting a CRT-2
Setting Printer Options
Refer to the documentation supplied with the PRN series printer for instructions on using the printer menu controls. Set the printer options (under the menu area) according to the settings listed in Table 3.3.
Option Setting Option Setting
Font LPI ESC Character Bidirectional Copy
CG-TAB Country Auto CR
Color Option Formlen
Lines Standard
HS Draft 6 LPI ESC ON
Graphic E-US ASCII OFF
Not Installed
6LPI=60 Exec 10.5
CPI Skip Emulate I/O
Buffer
Serial
Baud Format
Protocol Character Set Sl.Zero Auto LF PAPER
BIN 1
BIN 2
SINGLE
PUSH TRA
PULL TRA
PAP ROLL
10 CPI
0.5 Epson FX-850
40K
9600, 4800, or 2400 7 Bit, Even, 1 Stop XON/XOFF Standard On Off
12/72" 12/72" 12/72" 12/72" 12/72" 12/72"
Table 3.3 PRN Setup Options

3.11.3 Installing and Configuring a CRT-2

A CRT-2 can only be used in a non-networked application when used with the NFS-320/E/C. For further details on setting up the CRT-2, refer to the NFS-320/E/C Operations Manual.
Connect a CRT-2 to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB12 terminal block on the control panel as shown in Figure 3.16.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the CRT-2. Tighten securely.
3. Set parameters as discussed in Table 3.16.
32 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Setting CRT-2 Parameters
The CRT-2 communicates with the control panel through a protocol defined by thirteen groups of parameters. To access a parameter group, press the corresponding function key (F1-F12) as shown in Table 3.4 below. You can then program parameters in each group.
Page 33
Installing Remote Printers and/or CRT Installation
Enter the CRT-2 setup menu by pressing and holding the <Ctrl> key while pressing the <Scroll Lock> key. Use arrow keys to move through the selections in each setup group; press the space bar to view the options for each parameter. When finished programming all setup groups, press the <Pause> key. To save all changes, press <Y>.
Table 3.4 shows the standard settings for using the CRT-2 with the NFS-320/E/C; for one instance where these settings may change slightly see Section 3.11.4 “Connecting Multiple Printers, CRTs, or CRT/PRN Combination”. The basic settings for using the CRT-2 with NFS-320/E/C are:
• Baud Rate 9600 • Data format 8 1 N • Protocol xon/off.
NOTE: This section covers installation only; for information on how the CRT-2 functions as part of the fire alarm system, see the NFS-320/E/C Operations Manual.
NOTE: The CRT cannot be connected at the same time as the network.
Function Key CRT-2 Parameters
F1: Quick (“Read Status” key)
F2:Genrl (“Alter Status” key)
F3: Displ (“Prog” key)
F4: Kybd (“Spl Funct” key)
F5: Keys (“Prior” key)
F6: Ports (“Next” key)
F7: Host (“Auto Step” key)
F8: Print (“Activ Signal” key)
F9: Emul Attribute=Page
F10 Setup Group F10 does not affect communications with the control panel.
F11 Setup Group F11 does not affect communications with the control panel.
F12: Prog (“Ack Step” key)
Emulation=CRT-2 Comm Mode=Full Duplex Enhanced=On
Emulation=CRT-2 Auto Font Load=On Monitor Mode=Off Host/Printer=EIA/Aux
Page Length=24 Display Cursor=On Columns=80 Scroll=Jump
Language=U.S. Keyclick=Off Key Lock=Caps
Enter Key=<CR> Alt Key=Meta Pound Key=U.S.
EIA Baud Rate=9600 Aux Baud Rate=9600 EIA Xmt=Xon-Xoff Aux Xmt=Xon-Xoff EIA Break=Off Aux Break=Off
Comm Mode=Full Duplex Recv <DEL>=Ignore Send Block Term=<CR>
Prnt Line Term=<CR><LF> Prnt Block Term=<CR> Secondary Recv=Off
WPRT Intensity=Dim WPRT Blink=Off Status Line=Off
Program the function keys as follows: F1 ~A F2 ~B F3 ~C F4 ~D F5 ~E F6 ~F F7 ~G F8 ~H F9 ~I F10 ~J F11 ~K F12 ~L F13 ~M F14 ~N F15 ~O F16 ~P Shift F13 ~Q
EIA Baud Rate=9600 Aux Baud Rate=9600 Language=U.S.
Enhanced=On Auto Page=Off Bell Volume=09
Screen Length=26 Lines Cursor=Blink Line Width Change Clear=Off Refresh Rate=60 Hz
Char Set Mode=ASCII Key Repeat=Off Keyboard Present=Yes
Return Key=<CR> Disconnect=Pause
EIA Data Format=8/1/N Aux Data Format=8/1/N EIA Recv=Xon-Xoff(XPC) Aux Recv=Xon-Xoff(XPC) EIA Modem Control=Off Aux Modem Control=Off
Local=Off Send ACK=On Null Suppress=On
Bright Video=Off WPRT Reverse=Off Display NV Labels=Off Fkey Speed=Normal
EIA Data Format=8/1/N Aux Data Format=8/1/N Host/Printer=EIA/Aux
Auto Wrap=Off Auto Scroll=On Warning Bell=On
Screen Video=Normal Auto Adjust Cursor=On Speed=Normal Overscan Borders=Off
Key Mode=ASCII Margin Bell=Off
Backspace=<BS>/<DEL> Desk Acc=Disabled
EIA Parity Check=On Aux Parity Check=On EIA Xmt Pace=Baud Aux Xmt Pace=Baud EIA Disconnect=2 sec Aux Disconnect=2 sec
Recv <CR>=<CR> Send Line Term=<CR><LF>
Page Edit=Off WPRT Underline=Off Save Labels=On
Table 3.4 Standard CRT-2 Settings for Use with NFS-320/E/C

3.11.4 Connecting Multiple Printers, CRTs, or CRT/PRN Combination

Connecting multiple devices requires changing the CRT-2 setup using the F1(Quick) menu:
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 33
Page 34
Installation Wiring a Signaling Line Circuit (SLC)
To Control Panel TB12-PC/CRT REF TB12-PC/CRT TX TB12- PC/CRT RX
To EIA-232 port of CRT-2
(female socket shown)
To AUX Port of CRT-2 (female socket shown)
To EIA-232 port of next CRT-2 or PRN (female socket shown)
prncrt-conn.cdr
Note: For wire requirements, see Table B.1 in Appendix B “Electrical Specifications”.
Figure 3.17 Connecting Multiple Devices on the EIA-232 Circuit
• Set Host/Printer=EIA/AUX.
• Set EIA Data Format=8/1/N.
• If the AUX device is a printer, set the Printer and AUX Data Format=7/1/E.
• If the AUX device is a second CRT-2, set the AUX Data Format=8/1/N.
Connect multiple devices as shown in Figure 3.17.

3.12 Wiring a Signaling Line Circuit (SLC)

Overview
Communication between the control panel and intelligent and addressable initiating, monitor, and control devices takes place through a Signaling Line Circuit (SLC). You can wire an SLC to meet the requirements of NFPA Style 4, Style 6, or Style 7 circuits.
This manual provides requirements and performance details specific to this control panel; for installation information and general information, refer to the SLC Wiring Manual.
Wiring
Maximum wiring distance of an SLC using 12 AWG (3.31 mm total twisted-pair for Style 4, Style 6 and Style 7 circuits.
Capacity
The NFS-320/E/C provides one (1) SLC, with a total capacity of 318 intelligent/addressable devices:
• 01-159 intelligent detectors
• 01-159 monitor and control modules
Units employing multiple detector operation shall include a minimum of two detectors in each protected space and reduce the detector installation spacing to 0.7 times the linear spacing in accordance with National Fire Alarm Code, NFPA. For spacing requirements refer to the detector’s installation instructions.
2
) wire is 12,500 feet (3810 meters)
NOTE: To meet the ten-second response time required by UL 864, 9th edition, when SLC loops are configured to run in CLIP mode, all input modules must be mapped to address 19 and lower. There are no limits to detectors or output modules.
34 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 35
Connecting a PC for Off-Line Programming Installation
Note: T-Tapping is not allowed on a four-wire SLC.
SLC B (output loop)
SLC A (loop return)
SLC B SLC A
Style 4 SLC Loops Style 6 SLC Loops
SLC Loop Connections
on FACP’s main circuit board
TB13 on
NFS-320/E/C
nfs640-slcloops.cdr, CPU-320-SLC-TB.wmf
Figure 3.18 SLC Loop Connections and Wiring
Installation
This control panel supports one SLC loop, which connects to TB13 on the control panel. For details on designing, installing and configuring SLC loops, see the SLC Wiring Manual.

3.13 Connecting a PC for Off-Line Programming

A PC can be hooked up to the control panel to allow the VeriFire Tools programming utility to upload and download the operating program. Refer to the insert in the VeriFire Tools CD and to the program’s on-line help function for instructions. There are two options for connection:
Two options are available.
1. For PCs with USB Ports, connect the PC to USB B via a standard USB B cable.
2. For PCs without USB Ports, connect the PC’s serial port to the Control Panel’s Network/Service Connection (J1, NUP).
NOTE: Download operations that change the basic program of the control panel must be performed by responsible service personnel in attendance at the control panel. After downloading a program, test the control panel in accordance with NFPA 72.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 35
Page 36

4.1 Overview

• Control
•Strobe
• Horn
• (Blank)
• Release Ckt
• Rel Ckt Ulc
• Nonreset Ctl
• Alarms Pend
•Gen Alarm
•Gen Supervis
• Gen Trouble
• Gen Pend
• Trouble Pend
Chapter Covers the following topics

Section 4: Applications

Section 4.3 “NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit)”
Section 4.5 “NFPA 72 Proprietary Fire Alarm Systems”
Section 4.6 “Fire/Security Applications”
Section 4.7 “Releasing Applications”
How to install UDACT/UDACT-2 with the control panel for use as a NFPA Central or Remote Station Fire Alarm System (Protected Premises Unit)
How to set up a Protected Premises Unit to communicate with a listed compatible Protected Premises Receiving Unit.
How to use the control panel as a combination Fire/Security system, including the following:
• Installing a Security Tamper Switch into the cabinet
• Circuit Wiring
How to install the following releasing applications:
• Releasing Device to the Control Panel (NAC integral circuits)
• Releasing Device to the FCM-1 Module
• NBG-12LRA Agent Release-Abort Station
Municipal Box (Auxiliary)
Municipal Box applications require a TM-4 Transmitter module. Refer to the TM-4 Transmitter Module installation document for installation details.

4.2 Devices Requiring External Power Supervision

With version 12.0 and higher, certain type codes have external power supervision (FlashScan only) built into the software. An external power-supervision relay is required (see Figure 4.1) unless one of the following typecodes is selected for the device:
36 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 37
NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit) Applications
Device to be Supervised
Non-resettable 24 VDC Power from a listed source
– +
– +
SLC from FACP
FCM-1
N.C. Supervision Relay Contact Part of EOLR-1 (Not required for FlashScan type codes that provide built-in power supervision.)
Power Supervision Relay (EOLR-1) (Not required for FlashScan type codes that provide built-in power supervision.)
3030-external-power-suptpH.wmf
*If the SLC device does not match the one in this figure, refer to the SLC manual appendix, which contains wiring conversion charts for type V and type H modules.
Figure 4.1 Enabling External Power Supervision Using Relays

4.3 NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit)

Figure 4.2 shows typical wiring diagram for a NFPA 72 Central Station Fire Alarm System (Protected Premises Unit) or a Remote Station Fire Alarm System (Protected Premises Unit) using the Universal Digital Alarm Communicator/Transmitter (UDACT or UDACT-2) and control panel. This provides typical wiring only; connect and program the UDACT or UDACT-2 according to the directions given in the UDACT Instruction Manual or UDACT-2 Instruction Manual.
NOTE: An NFPA 72 Central Station or Remote Station requires 24 hours of standby power and 5 minutes in alarm.
NOTE: This application can also be done with the TM-4 Transmitter; refer to the TM-4 Transmitter Module installation document for more details.
NOTE: For additional setup information for the UDACT-2, refer to the UDACT-2 Instruction Manual.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 37
Page 38
Applications NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit)
UDACT in ABS-8RB
(shown with cover removed)
Solid earth ground
To supervised phone lines
Ferrite cores P/N 29090
FACP Cabinet
EIA-485 (ACS Mode)
24 VDC Nonresettable power
Supervised and power-limited EIA-485 and power wiring
CPU-320-udact.wmf
Figure 4.2 Typical Wiring Diagram for a Central Station Fire Alarm System
NOTE: Install a UL-listed 120 ohm End-of-Line resistor (P/N 71244) UDACT TB1 terminals 3
and 4 if this is the last or only device on EIA-485 line.
38 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 39
0
NO
ON
NC
C 18/24
115 230
1
1
S5W
LED3
LED4
LED1LED2
S1W
ELR
TXACS
RXACS
POWER
TROUBLE
SW4
REMOTE
STATION
ALARM
ACS
TB2 TB1
ACS REF
REMOTE
STATION
SUPERVISORY
MUNICIPAL
BOX
REMOTE STATION TROUBLE
T3B
S2W
S3W
SW6
NON-ISOLATED
DISABLE
ISOLATED
ENABLE
+24VDC
REF
+
-
LINE SEIZE
LED 3
LED 20
LED 8
LED 2
LED 1
LED 9
LED 14
LED 13
+ 24V
COMMON
INPUT 1
INPUT 2
INPUT 3INPUT 4INPUT 5
TRANS CLEAR
SW1
SW2
SW3
SW4
RESET
TEST
REPORT
REAL TIME
EIA-485 COMM LOSS
POWER
LED 5
LED 6
LED 7
LED 17
LED 18
LED 19
LED 4
LED 15 LED 16
LINE FAIL
NO TONE
KISS OFF
COMM FAIL
PRI
SEC
OPTION SELECT SWITCH
1 2 3 4
OFF
ON
ON
LED21
TONE DETECT
RECON
PULSE1
LED6 LED7
LED101
LED100
LED4 LED2
LED3 LED5
LED1 LED8
STATA
STATB
RCDA RCDB
A HI
B HI
EF B TERM B
SW101
SW102
SW103
ON OFF
EF A TERM A
SW100
ON OFF
NUP1
NUP2
J3 J2
LCMATERM
A
SW1
ON
SW2
OFF
LCM ALCM B
RESET
POWER
RECON
PULSE1
LED6 LED7
LED101
LED100
LED4 LED2
LED3 LED5
LED1 LED8
STATASTATB
RCDA RCDB
A HI
B HI
EF B TERM B
SW101
SW102
SW103
ON OFF
EF A TERM A
SW100
ON OFF
NUP1
NUP2
J3 J2
LCMATERM
A
SW1
ON
SW2
OFF
LCM ALCM B
RESETPO WER
EIA-485
24V
Relay Drive
24V
EIA-485
24V
+
_
+
+
+
+
+
NFS-320
NCM-W
To Previous
Node on
Network
To Next Node
on Network
NCA-2
NCM-W
_
_
_
_
_
TM-4
UDACT-2
MR-101/C
FMM-1
SLC
+
NOTES:
• Drawing is not to scale.
• The UDACT/UDACT-2 should be set for “Receive Only” for this configuration. For additional UDACT/UDACT-2 setup information, refer to the
UDACT Installation Manual. or UDACT-2 Instruction Manual.
• This illustration is show with the NCM-W. For other NCM or HS-NCM setup, refer to the
NCM Installation or HS-NCM Installation documents.
• For additional setup information on the TM-4, refer to the TM-4 Instruction Manual.
EIA-485
{ {
{ {
24V
EIA-485
_
Central Station Fire Alarm System Canadian Requirements Applications

4.4 Central Station Fire Alarm System Canadian Requirements

For Canadian applications requiring a second dial-out option, refer to the following illustration for UDACT/UDACT-2 and TM-4 setup:
Figure 4.3 Central Station Canadian Requirements for Second Dial-Out Connection
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 39
Page 40
Applications NFPA 72 Proprietary Fire Alarm Systems
NFS-320/E
Protected Premises Unit
Compatible Receiving Unit
(see UDACT Manual or UDACT-2
Manual)
Telephone line and backup
UDACT
or UDACT-2
NFS-320/E
Figure 4.4 Typical Proprietary Fire Alarm Systems Wiring Connections

4.5 NFPA 72 Proprietary Fire Alarm Systems

When connected and configured as a protected premises unit with UDACT or UDACT-2, the NFS­320/E will automatically transmit General Alarm, General Trouble, and General Supervisory signals to a listed compatible Protected Premises Receiving Unit. See the UDACT Manual or UDACT-2 Manual for compatible receiving units. A simplified drawing of connections between the receiving unit and the NFS-320/E protected premises unit is shown in Figure 4.4.
Connect the receiving unit to the protected premises unit as shown in Section 4.3 “NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit)”.
For information on installing and programming the Receiving unit, refer to the documentation for that control panel.

4.6 Fire/Security Applications

NOTE: NFS-320/E/C is not approved for use in security applications in Canada.

4.6.1 General Operation

The control panel can be used as a combination Fire/Security system when installed and operated according to the instructions in this section.
For security applications, program one or more monitor modules (listed for security applications) with the lights the The panel sounder will sound until the Security alarm is acknowledged. You can also program additional sounders or output devices to activate with the security alarm initiating device. The
SECURITY Type Code is designed to indicate an alarm as follows: (a) on an open or short circuit; or
(b) on a ±50% change in resistance value from the End-of-Line resistor value.
A tamper switch installed in the cabinet door will indicate a door tamper condition whenever the door is open. If the control panel indicates a Security alarm, you can acknowledge, silence, and reset the condition from the control panel.
When the system resets, a 30-second exit timer starts. During this time the tamper switch and all Security alarms are ignored. There is no entrance delay timer.
40 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
SECURITY Type Code, and wire as shown in Figure 4.6. Activating this type of module
SECURITY LED, and displays a security alarm condition on the control panel LCD display.
Page 41
Fire/Security Applications Applications
!
320_STS1.wmf
Connect to J5 “Security Tamper”
STS-200 mounting location
Figure 4.5 Installing the STS-200 Security Tamper Switch
For bypass of security zones, use the DISABLE routine (covered in the Status Change section of the NFS-320/E/C Operations Manual) for Security type devices.
WARNING:
Damage can result from incorrect wiring connections.

4.6.2 Installing a Security Tamper Switch

To wire the cabinet with a Security Tamper Switch kit model STS-200, refer to Figure 4.5:
1. Install the STS-200 Tamper Switch into the location shown in Figure 4.5. Push the switch through the opening until it snaps into place.
2. Connect the STS-200 connector to J5 (Security Tamper) on the Control Panel. (As shown in Figure 4.5, J5 is located on the circuit board, underneath the edge of KDM-R2.)

4.6.3 Receiving Unit

For applications requiring transmission of security alarm information to a central receiving unit, the control panel may be connected via the UDACT or UDACT-2 to a compatible receiving unit (see the UDACT Manual or UDACT-2 Manual). For information on configuring the Receiving unit for Combination Fire/Security applications, refer to the documentation for that control panel.

4.6.4 Programming

The control panel can communicate with any number of security devices. To do so, program the points as follows:
1. Select the address of the module(s) to be used for security.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 41
Page 42
Applications Fire/Security Applications
FlashScan Monitor Module
UL-listed, normally-closed security switch
UL-listed, normally-open security switch
SLC Channel A or B
NFS-320/E Protected Premises Unit
CPU2-640-burgtpH.wmf
UL-listed 47K End-of-Line Resistor (provided with module)
*If the SLC device does not match the one in this figure, refer to the SLC manual appendix, which contains wiring conversion charts for type V and type H modules.
2. Select the Type Code SECURITY.
NOTE: For detailed instruction on programming Type Codes, refer to the NFS-320/E/C Programming Manual.

4.6.5 Wiring for Proprietary Security Alarm Applications

Table 4.6 shows typical wiring for proprietary security alarm applications with modules. Note the following:
• The module is programmed with software
SECURITY Type Code.
• For use with UL listed systems only; application not for ULC security usage.
• NAC devices used for security cannot be shared with fire NAC devices.
• Refer to the Device Compatibility Document for compatible NAC devices.
• All monitor modules used for security application must be installed in the NFS-320/E cabinet with STS-1 Security Tamper Switch.
Figure 4.6 Wiring Diagram for Proprietary Security Alarm Applications
42 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 43
Releasing Applications Applications
!
!

4.7 Releasing Applications

WARNING:
When used for CO2 releasing applications, observe proper precautions as stated in NFPA 12. Do not enter the protected space unless physical lockout and other safety procedures are fully completed. Do not use software disable functions in the panel as lockout.
WARNING:
Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if they are used for releasing functions!

4.7.1 Overview

This control panel can be used for agent release or preaction/deluge control applications. In a properly configured system with compatible, listed actuating and initiating devices, this control panel complies with the following NFPA standards for installation in accordance with the acceptable standard:
Standard Covers
NFPA 12 CO
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam-Water Deluge and Foam-water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems
Extinguishing Systems
2
Table 4.1 NFPA Standards for Releasing Applications

4.7.2 Programming

The control panel supports up to ten releasing software zones. You can map these zones to activate Control Panel releasing outputs and FCM-1 modules. Program the FCM-1 module for the appropriate type code according to the chart below:
Type Code: RELEASE CKT
• For use in UL applications.
• Do not use REL device at the solenoid.
• Cannot use power-limited wiring.
• Supervised for open circuit only.
• Supervised for power loss with power­supervision relay.
For more information, refer to the NFS-320/E/C
Type Code: REL CKT ULC
• For use in UL or ULC applications.
• Requires REL device at solenoid.
• Power-limited wiring.
• Supervised for open circuit and shorts.
• Supervised for power loss with power­supervision relay.
Programming Manual.

4.7.3 Wiring

References to wiring diagrams for releasing applications:
To connect Refer to
A releasing device to the control panel. Section 4.7.4 “Connecting a Releasing Device to the Control Panel”.
A releasing device to the FCM-1 Module. Section 4.7.5 “Connecting a Releasing Device to the FCM-1 Module”.
An NBG-12LRA Agent Release-Abort Station. Section 4.7.7 “Connecting an NBG-12LRA Agent Release-Abort Station”.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 43
Page 44
Applications Releasing Applications
!
CPU-320-RELCONN1.wmf
REL-2.2K (Use with Type Code
Rel Ckt ULC, or see Circuit
Requirement 4.)
Compatible UL-listed 24 VDC releasing device
B+ NAC/Releasing output (source) B– NAC/Releasing output (source) A+ Class A (return for NAC only) A– Class A (return for NAC only)
Note: See text below for circuit requirements.
Figure 4.7 Typical Style 4 Connection of a Releasing Device to Control Panel
Control Panel

4.7.4 Connecting a Releasing Device to the Control Panel

Use TB6 (NAC#4), TB7 (NAC#3), TB8 (NAC#2), or TB9 (NAC#1) on the control panel for NAC⁄Releasing Circuits. The releasing circuit must be supervised and use listed, compatible releasing devices.
WARNING:
Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if they are used for releasing functions!
Circuit Requirements. When connecting a releasing device, note the following:
1. The control panel provides four NAC/Releasing Circuits (Style Y or Z). Each circuit can
2. Refer to the Releasing Applications appendix in the NFS-320/E/C Programming Manual for
3. For applications using power-limited circuits:
4. For applications not requiring power-limited circuits
provide 1.5 A. Total current drawn from the power supply cannot exceed 7.4 A in an alarm condition (refer to Table A.2, “System Draw Current Calculations,” on page 54). Use compatible UL-listed 24 VDC appliances only. For more information on compatible appliances, refer to the Device Compatibility Document.
configuration details (such as setting the Soak Timer).
a) Use an in-line supervisory device (P/N REL-2.2K) with control panel releasing circuits. Connect the End-of-Line device as shown in Figure 4.7. b) Program the releasing circuit for Type Code REL CKT ULC. c) Circuits are supervised against opens and shorts.
– a) If the application does not require supervising the releasing device against shorts, in-line supervisory devices (P/N REL-2.2K) are not required. b) In non-power-limited applications, program the releasing circuit for Type Code RELEASE CKT. c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit device wiring and any power-limited circuit wiring.)
44 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 45
Releasing Applications Applications
IQActuatorsa.wmf
IQActuatorsb.wmf
IQActuatorsb.wmf
5. The releasing circuit must be programmed with a releasing type code listed in the NFS­320/E/C Programming Manual.
NOTE: As per UL 864 9th Edition, a supervisory signal must be indicated at the panel whenever a releasing circuit is physically disconnected. Use a monitor module to monitor dry contacts off the switch. See 4.11.
Figure 4.8 Releasing Circuits (Option 1)
Figure 4.9 Releasing Circuits (Option 2)
Figure 4.10 Releasing Circuits (Option 3)
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 45
Page 46
Applications Releasing Applications
GasDisconnect.wmf
–
+
–
Compatible UL-listed 24 VDC releasing device
REL-47K
(Use with Type Code
Rel Ckt ULC, or see Circuit
Requirement 3.)
Brown Red
Non-resettable 24 VDC Power
Power Supervision Relay (EOLR-1)
Relconn-fcmtpH.wmf
+ –
FCM-1
– +
SLC from FACP
Note: See text for circuit requirements.
N.C. Supervision
Relay Contact
Part of EOLR-1
*If the SLC device does not match the one in this figure, refer to the SLC manual appendix, which contains wiring conversion charts for type V and type H modules.
Figure 4.12 Typical Connection of a 24 VDC Releasing Device to the FCM-1 Module
)
Figure 4.11 Release Circuits (Mechanical Disconnect Switch)

4.7.5 Connecting a Releasing Device to the FCM-1 Module

The module can control 1 A of current. Make sure to keep total system current within the limits of the power supply. You can power the module from the power supply of the Control Panel or any UL/ULC listed 24 VDC regulated power-limited power supply for Fire Protective Signaling. For more information, refer to the Device Compatibility Document.
46 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Circuit Requirements When connecting a releasing device to the FCM-1 module, note the following:
1. Refer to the Releasing Applications appendix in the NFS-320/E/C Programming Manual for configuration details (such as setting the Soak Timer).
2. For applications using power-limited circuits: a) Use an in-line supervisory device (P/N REL-47K) with the FCM-1 module. Connect the in­line supervisory device as shown in Figure 4.12. b) Program the releasing circuit for Type Code REL CKT ULC. c) Circuits are supervised against opens and shorts.
3. For applications not requiring power-limited circuits a) In-line supervisory devices (P/N REL-47K) are not required; however, the releasing device circuit is not supervised against shorts. b) In non-power-limited applications, program the releasing circuit for Type Code
:
RELEASE CKT.
Page 47
Releasing Applications Applications
!
SLC (-)
SLC (+)
Non-resettable
24 VDC power
(-)
(+)
Compatible UL-listed
24 VDC releasing device.
One (1) device maximum.
Module polarities are shown in alarm condition.
All wiring shown is supervised and power-limited.
Figure 4.13 NPFA Style Y (Class B) Wiring of the FCM-1-REL
Compatible UL-listed 24 VDC releasing device. One (1) device maximum.
Non-resettable
24 VDC power
SLC (-)
SLC (+)
(-)
(+)
Figure 4.13 NPFA Style Z (Class A) Wiring of the FCM-1-REL
Module polarities are shown in alarm condition.
All wiring shown is supervised and power-limited.
FCM-1-REL
FCM-1-REL
When using the FCM-1-REL for
Style Y (Class B) applications,
remove jumper J1.
fcm-1-rel-y.wmf
fcm-1-1rel-z.wmf
NOTE: With software version 12.0 or higher ALL new FlashScan Mode SLC releasing applications require the FCM-1-REL control module. The V-type FCM-1 control module may be used in SLC releasing applications with software version 12.0 or higher. H-type FCM-1 control modules do not support FlashScan Mode releasing applications with software version 12.0 or higher. Use H-type FCM-1 for CLIP mode releasing applications.
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit. d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit device wiring and any power-limited circuit wiring.
WARNING: The XP6-C is not listed for releasing applications and cannot be substituted for FCM-1.

4.7.6 Connecting a Releasing Device to the FCM-1-REL

Typical Connections Figure 4.13 shows typical connections for wiring a releasing device to the
FCM-1-REL. Refer to the Device Compatibility Document for compatible releasing devices.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 47
Page 48
Applications Releasing Applications
SLC loop to FACP
FCM-1
FRM-1
FMM-1
FMM-101
Black
Red
Yellow
Violet
Black
Red
Non-resettable +24 VDC from main power supply
Manual Abort
Manual Release
Normal
Release
NBG-12LRA See Document 51369 for installation details.
ELR mode R-47K supervised and power-limited
RedBrown
24 VDC UL-listed releasing device
C.
N.O.
REL-47K
(use with Type Code
Rel Ckt ULC)
NFS640-NBG12LRAtpH.wmf
System
Common (–)
24 VDC power
from FACP’s
main power supply
N.C.
Power Supervision
Relay (EOLR-1)
N.C. Supervision Relay Contact
Figure 4.14 Typical Connections for an NBG-12LRA Agent Release-Abort Station
Polarity shown in
an energized
state.
*If the SLC device does not match the one in this figure, refer to the SLC manual appendix, which contains wiring conver­sion charts for type V and type H modules.
Critical Requirements. When connecting a releasing device to the FCM-1-REL module, note the following:
1. See “Power Considerations” on page 52 for information on monitoring 24 VDC power.
2. Do not T-tap or branch a Style Y or Style Z circuit.
3. Only one (1) 24V solenoid or two (2) 12V solenoids in series can be connected to the FCM-1­REL.
4. Do not loop wiring under the screw terminals. Break the wire run to provide supervision of connections.
5. All applications using the FCM-1-REL are power-limited:
a. Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT.
b. Circuits are supervised against opens and shorts.
6. Refer to the NFS-320/E/C Programming Manual for instructions on setting the Soak Timer.
The FCM-1-REL module must be programmed with the correct releasing type code listed in the NFS-320/E/C Programming Manual.

4.7.7 Connecting an NBG-12LRA Agent Release-Abort Station

48 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 49
Releasing Applications Applications
NOTE: If using the on-board NACs, see Circuit Requirements for Section 4.7.4 “Connecting a Releasing Device to the Control Panel” on page 44. If using FCM-1, see Circuit Requirements for Section 4.7.5 “Connecting a Releasing Device to the FCM-1 Module” on page 46.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 49
Page 50

Section 5: Testing the System

Continued on next page...
!

5.1 Acceptance Test

When finished with the original installation and all modifications, conduct a complete operational test on the entire installation to verify compliance with applicable NFPA standards. Testing should be conducted by a factory-trained fire alarm technician in the presence of a representative of the Authority Having Jurisdiction and the owner’s representative. Follow procedures outlined in NFPA Standard 72’s section on Inspection, Testing and Maintenance.

5.2 Periodic Testing and Service

Periodic testing and servicing of the control panel, all initiating and notification devices, and any other associated equipment is essential to ensure proper and reliable operation. Test and service the control panel according to the schedules and procedures outlined in the following documents:
• NFPA Standard 72’s section on Inspection, Testing and Maintenance.
• Service manuals and instructions for the peripheral devices installed in the system. Correct any trouble condition or malfunction immediately.

5.3 Operational Checks

Between formal periodic testing and servicing intervals, the following operation checks should be performed monthly, or more frequently when required by the Authority Having Jurisdiction.
• Before proceeding: a) notify the fire department and the central alarm receiving station if transmitting alarm conditions; b) notify facility personnel of the test so that alarm sounding devices are disregarded during the test period; and c) when necessary, disable activation of alarm notification appliances and speakers to prevent their sounding.
• Disconnect all releasing devices to prevent accidental activation in accordance with NFPA 2001 and NFPA 12A releasing agents.
WARNING:
Do not rely on disable/enable software settings to lockout releasing devices.
• Check that the green POWER LED lights.
• Check that all status LEDs are off.
• Press and hold the LAMP TEST key. Verify that all LEDs and all LCD display segments work.
• Activate an Initiating Device Circuit using an alarm initiating device or an addressable initiating device on the SLC and check that all programmed active notification appliances function. Reset the alarm initiating device, the control panel, and any other associated equipment. Select the paging function and confirm that the message can be heard in the affected fire zones. Repeat the above step with each Initiating Device Circuit and each addressable device.
• Remove AC power, activate an Initiating Device Circuit through an alarm initiating device or an addressable initiating device on the SLC, and check that programmed active notification appliances sound, and alarm indicators illuminate. Measure the battery voltage with notification appliances active. Replace any battery with a terminal voltage less than 21.6 VDC and reapply AC Power
50 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 51
Battery Checks and Maintenance Testing the System
!
!
.
NOTE: The battery test requires fully charged batteries. If batteries are new or discharged due to a recent power outage, allow the batteries to charge for 48 hours before testing.
• Return all circuits to their pretest condition.
• Check that all status LEDs are off and the green POWER LED is on.
• Notify fire, central station and/or building personnel when you finish testing the system.

5.4 Battery Checks and Maintenance

Maintenance-free sealed lead-acid batteries used in the system do not require the addition of water or electrolyte. These batteries are charged and maintained in a fully charged state by the main power supply’s charger during normal system operation. A discharged battery typically reaches the voltage of 27.6 VDC within 48 hours; the charge rate depends on the battery size (2.0A for 18­26AH; 5.0A-5.7A for 26AH-200AH).
Immediately replace a leaking or damaged battery. Batteries should be replaced in accordance with the battery manufacturer’s recommendations.
WARNING:
Batteries contain Sulfuric Acid which can cause severe burns to the skin and eyes and damage to fabrics.
• If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or eyes with water for at least 15 minutes. Water and household baking soda provides a good neutralizing solution for Sulfuric Acid.
• If Sulfuric Acid gets into eyes, seek immediate medical attention.
• Ensure proper handling of the battery to prevent short circuits.
• Take care to avoid accidental shorting of the leads from uninsulated work benches, tools, bracelets, rings, and coins.
WARNING:
Shorting the battery leads can damage the battery, equipment, and could cause injury to personnel.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 51
Page 52

Appendix A: Power Supply Calculations

Calculations must be done to determine standby and alarm DC current loads. Ampere-hour requirements must be calculated as well to determine battery size.
The CPS-24/E power supply provides filtered 24VDC power that may be used for operating external devices. Use Table A.2 to determine if external loading is within the capabilities of the power supply.

A.1 Calculating AC Branch Circuit Current

Use Table A.1 below to determine the total amount of current, in AC amperes, that a 120 VAC, 50/60 Hz service must be able to supply to the fire alarm system. Devices rated for 220-240 VAC operation will draw approximately one-half the current listed in Table A.1.
Device Type No. of Devices Current (amps) Total Current
CPS-24 Power Supply [ 1 ] X 5.0 = 5.0
CPS-24/E Power Supply [ ] X 2.5 =
FCPS-24S6/S8 [ ] X 3.2 =
ACPS-2406 [ ] X 2.7
ACPS-610 [ ] X 5.0
ACPS-610/E [ ] X 2.5
APS-6R [ ] X 2.5 =
CHG-120 [ ] X 2.0 =
Sum column for AC Branch Current required=amps
*
*
*
=
=
=
Table A.1 120 VAC Fire Alarm Circuit
* Separate calculations are required for any devices powered by the ACPS-
610 or ACPS-2406. They have their own integral battery charger and batteries can be connected directly to them. Refer to the ACPS-2406 or ACPS-610 Installation Manuals for battery calculations.
AC Branch Circuit Installation
For guidelines on wiring the AC branch circuit current, see “Operating Power: AC Branch Circuit” on page 60 in Appendix B.1 “Electrical Specifications”.

A.2 Calculating the System Current Draws

The control panel’s main power supply must be able to power all internal system devices (and several types of external devices) continuously during non-fire alarm conditions. Use column 1 in Table A.2 to calculate the Non-Fire Alarm Load on the power supply regulator when applying primary power. The main power supply must also provide a finite amount of additional current during a fire alarm condition. Use column 2 in Table A.2 to calculate the additional current needed during fire alarms. The requirements for non-fire alarm and fire alarm current loads cannot exceed the capabilities of the power supply as listed below:
• 3.9 A at 24 VDC during Standby; and
• 7.4 A at 24 VDC during Alarm.
The current draw from all NACs plus DC output from TB10 and TB2 is 3.0 A during standby, and
6.0 A in alarm.
52 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 53
Calculating the System Current Draws Power Supply Calculations
How to Use the Calculating Tables
As used in this section, “Primary” refers to the control panel’s on-board power supply, its primary source of AC power. “Secondary” refers to the control panel’s backup batteries (or any other 24 VDC power supply listed for Fire Protective Signaling and connected in place of the batteries). The term “standby” refers to the output current required when no fire alarm is present. The term “alarm” refers to the output current required when a fire alarm is present.
The Primary Power Source Non-Alarm Current and Alarm Current columns are DC current calculations. These calculations confirm that the power supply can provide enough current to support the system during Primary Non-Fire Alarm and Fire Alarm conditions.
Quantities List the number of devices powered by the FACP and its power supply. Devices powered by the Accessories Output (TB10 and TB2) draw current directly from the panel. Devices powered by the Panel Output draw current through the fire panel’s connection to the power supply. Use these quantities to calculate total current draw of each set of devices in calculation columns 1, 2, and 3.
Calculation Column 1 (Primary, Non-Fire Alarm Current in amps) Add the contents of calculation column 1 to get the current drawn from the power supply during a non-alarm condition, with AC power applied. This current draw cannot exceed 3.9 A without an auxiliary power supply.
Calculation Column 2 (Primary, Fire Alarm Current in amps) Calculation column 2 lets the system designer determine the current load that the power supply must support during a fire alarm. The total current draw during a fire alarm cannot exceed 7.4 A without an auxiliary power supply.
Typically, a system should contain capacity to activate all output circuits and relays, and support fire alarms on no less than 10% of Initiating Device Circuits, subject to the requirements of the Authority Having Jurisdiction (AHJ).
The Control Panel provides power for Notification Appliance Circuits. Refer to the Device Compatibility Document for 24 VDC notification appliances that are UL- and ULC-listed for fire alarm systems.
Calculation Column 3 [Secondary (Battery) Non-Alarm Current] Column 3 lets the system designer calculate the non-fire alarm current drawn from the secondary source in a non-fire alarm condition during AC power loss.The non-fire alarm current is required to complete the standby battery calculations. After summing all current draws, insert the total in Table A.3.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 53
Page 54
Power Supply Calculations Calculating the System Current Draws
Category
Primary, Non-Fire Alarm Current (amps)
Calculation Column 1
NFS-320/E # NACs in use (0, 1, 2, 3 or 4) CPS-24/E KDM-R2 (Backlight on)
SLC loop†: 1 x [0.200]= 1 x [0.200]= 1 x [0.200]=
NCA, NCA-2 Back-light ON NCA, NCA-2 Back-light OFF NCM-W/F HS-NCM-W/MF/SF/WMF/WSF/MFSF TM-4 DPI-232 (Refer to manual**)
APS-6R ACPS-2406, ACPS-610
ACM-24AT ACM-48A AEM-24AT AEM-48A
Maximum number of LEDs illuminated on these annunciators during non-fire conditions:
AFM-16AT, AFM-32A ACM-16AT, ACM-3 2A AEM-16AT, AEM-3 2A
AFM-16A ACM-8R (refer to manual**) LDM (refer to manual**) FDU-80 LCD-80 LCD2-80
FZM-1, MMX-2 Auxiliary power [ ] x [0.0115]= [ ] x [0.090]= [ ] x [0.0115]=
RPT- W, R PT- WF, RP T-F RPT-485W, RPT-485WF
UDACT Communicator UDACT-2 Communicator NFV-25/50 (see manual**)
FWSG (only if powered by the FWSG 24V connections TB:A2 and TB:A3)
Four-Wire Smoke Detectors‡ [][]x [ ]=
Power Supervision Relay EOLR-1
Notification Appliance powered from Main Power Supply
DHX-501, FSD-751RPFSD-751RPL(Duct Detectors with internal relays) Refer to installation document
CHG-120 Battery Charger [ ] x [0.060]=
Local Energy Municipal Box [ ] x [ ]=
Compatible Devices not listed above†† [][]x [ ]=
Sum each column for totals Primary, non-alarm: Primary, alarm: Secondary, non-alarm:
**
*
Qty X [current draw]= Total Qty X [current draw]= Total Qty X [current draw]= Total
1
x [0.250] =
[]
x [0.035]
n/a
n/a
[]
x [0.100]=
[]
x [0.400]=
[]
x [0.200]=
[]
x [0.110]=
[]
x [0.400]=
[]
x [0.110]=
[]
x [ ]=
[]
x [0.016]=
[]
x [0.016]=
[]
x [0.002]=
[]
x [0.002]=
[ ] x [0.0054]= [ ] x [0.0054]=
[]
x [0.040]=
[]
x [0.040]=
[]
x [0.002]=
[]
x [0.025]=
[]
x [ ]=
[]
x [ ]=
[]
x [0.0643]=
[]
x [0.100]=
[ ] x [0.017]= [ ] x [0.017]= [ ] x [0.017]=
[]
x [0.040]=
[]
x [0.052]=
[]
x [ ]=
[ ] x [0.040]= [ ] x [0.040]= [ ] x [0.040]=
x [ ]=
[ ] x [0.020]= [ ] x [0.020]= [ ] x [0.020]=
[][]x [ ]=
x [ ]=
x [ ]=
Calculation Column 2 Primary, Fire Alarm Current (amps)
1
x [0.250] =
[]
x [0.035]
n/a
n/a
[]
x [0.100]=
[]
x [0.400]=
[]
x [0.200]=
[]
x [0.110]=
[]
x [0.400]=
[]
x [0.175]=
[]
x [ ]=
[]
x [0.070]=
[]
x [0.070]=
[]
x [0.056]=
[]
x [0.056]=
[]
x [0.056]=
[]
x [0.056]=
[]
x [0.018]=
[]
x [0.065]=
[]
x [ ]=
[]
x [ ]=
[]
x [0.0643]=
[]
x [0.100]=
[]
x [0.100]=
[]
x [0.087]=
[]
x [ ]=
[][]x [ ]=
x [ ]=
[][]x [ ]=
x [ ]=
[][]x [ ]=
x [ ]=
[][]x [ ]=
x [ ]=
Calculation Column 3 Secondary, Non-Fire Alarm Current (amps)
1
x [0.250] =
[]
x [0.035]
1
x [0.040]
[]
x [0.100]=
[]
x [0.400]=
[]
x [0.200]=
[]
x [0.110]=
[]
x [0.400]=
[]
x [0.110]=
[]
x [ ]=
[][]x [0.025]=
x [0.0013]=
[]
x [0.016]=
[]
x [0.016]=
[]
x [0.002]=
[]
x [0.002]=
[]
x [0.040]=
[]
x [0.040]=
[]
x [0.002]=
[]
x [0.025]=
[]
x [ ]=
[]
x [ ]=
[]
x [0.0643]=
[]
x [0.050]=
[]
x [0.040]=
[]
x [0.052]=
[]
x [ ]=
[][]x [ ]=
x [ ]=
[][]x [ ]=
x [ ]=
[][]x [ ]=
x [ ]=
Table A.2 System Draw Current Calculations
* Maximum current draw for all NACs plus DC output from TB10 and TB2 is 3.0 A during standby. † Value represents an SLC’s maximum current draw. Refer to device datasheets for individual current draws. ‡ The total regulated load current supplied to four-wire smoke detector and power supervision relays cannot exceed 1.25 A. ** Enter the total notification appliance draw from the Main Power Supply, excluding the current from APS-6R supplies. Refer to Device Compatibility Document. †† Refer to manual and/or Device Compatibility Document. See Table 1.1, “Reference Documentation,” on page 8 for specific documentation part numbers.
54 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 55
Calculating the System Current Draws Power Supply Calculations
A.2.1 Calculating the Maximum Secondary Power Fire Alarm
Current Draw
Use Table A.3 below to determine the maximum current requirements of secondary power source during fire alarm conditions. The result obtained is the amount of current that the batteries must be able to supply to the fire alarm system. Use the result in Table A.4 to determine the size of the batteries needed for the fire alarm system.
Results taken from Table A.3 below assume that, while in a fire alarm condition, batteries must feed the main power supply (and any additional supplies such as the APS2-6R) with the maximum rated power each supply can provide.
Device Quantity
Alarm Current, from Table A.2, col 2 =
APS2-6R
Sum Column for Secondary Fire Alarm Load =
*
[] X 6 =
Current (in amps)
Table A.3 Maximum Secondary Power Fire Alarm Current Draw
* Actual load current may be used in place of maximum rated supply
current. To calculate actual load current, sum the current draws for each appliance connected to APS-6R supplies.
Total Current/Type
NOTE: The Secondary Fire Alarm Load cannot exceed the following:
• 12 A with BAT-12260 batteries (12 V, 26 AH).
• 20 A with BAT-12550 batteries (12 V, 55 AH).
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 55
Page 56
Power Supply Calculations Calculating the Battery Requirements

A.3 Calculating the Battery Requirements

A.3.1 Calculating the Battery Capacity

Use this table to determine the battery capacity needed for the system:
Current (amps) X Time (hours) = AH
Secondary Non-Fire Alarm Current (from column 3 in Table A.2) (see Note 8)
________________
APS-6R Standby Load Current
Required Secondary Non-Fire Alarm Standby Time (24 or 60 hours)
X
________________ = _________AH
Required Secondary Non-Fire Alarm Standby Time (24 or 60 hours)
________________ X
Secondary Fire Alarm Load (from Table A.3) (see Note 8)
________________ X
Sum Column for Total Secondary Amp Hours calculated = _________AH
Multiply by the derating factor x 1.2 (see Note 7) = _________AH
Battery Size – Total Secondary Amp Hours Required = _________AH
1. NFPA 72 Local, Proprietary, and Central Station systems requires 24 hours of standby power followed by 5 minutes in alarm.
2. NFPA 72 Auxiliary and Remote Station Systems require 24 hours of standby power followed by 5 minutes in alarm.
3. Batteries installed in a system powered by an automatic starting engine generator need to provide at least 4 hours of standby power.
4. Factory Mutual requires 90 hours of standby for deluge-preaction systems.
5. Emergency voice/alarm communications systems require 2 hours of operation in the alarm condition. Due to the sporadic nature of voice operation, however, NFPA 72 permits 15 minutes of operation at a maximum connected load to equal 2 hours of normal use.
6. If the total exceeds 26 AH, the system requires a separate NFS-LBB, BB-100 or BB-200 battery enclosure for two larger capacity batteries.
7. The following battery derating factors must be used for Canadian installations using NFS-320C charger:
• For a 26 AH battery, use derating factor of 1.5
• For a 55 AH battery, use derating factor of 1.8
• For a 100 AH battery, use derating factor of 2.5
• For a 200 AH battery, use derating factor of 2.5
8. For 26 AH batteries: maximum standby current cannot exceed 0.65A; maximum alarm current cannot exceed 6.75A
________________ = _________AH
Required Fire Alarm Standby Time: (for 5 minutes, enter 0.084; for 15 minutes, enter 0.25)
________________ = _________AH
Table A.4 Secondary Power Standby and Fire Alarm Load
56 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 57
Calculating the Battery Requirements Power Supply Calculations

A.3.2 Calculating the Battery Size

Use this table to choose the battery size, in amp-hours, needed to support the fire alarm system. The CPS-24/E can charge batteries from 18 to 200 AH. Select batteries that meet or exceed the Total Amp-Hours calculated in Table A.4 and that are within the acceptable battery charger range. Write the amp-hours requirements on the Protected Premises label.
The maximum battery size that can be mounted inside the NFS-320’s cabinet is 26AH.
Battery Size
18 AH 12 volts two BAT-12180 NFS-320 enclosure, BB-25
26 AH 12 volts two BAT-12260 NFS-320 enclosure, BB-25
100 AH 12 volts four for 100 AH
*Manufactured to our specifications.
†
Red version available; add “R” to part number listed here
Voltage Rating
Number Required
two for 200 AH
Part Number*
BAT-121000 BB-100
Backbox Part Number
BB-200
Table A.5 Selecting Battery and Battery Backbox
†
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 57
Page 58

Appendix B: Electrical Specifications

B.1 Electrical Specifications

AC Power
Component Values
Main Power Supply 120 VAC, 50/60 Hz, 5.0 A; or
220-240 VAC, 50/60 Hz, 2.5 A
Wire size Maximum 12 AWG (3.31 mm
NOTE: If using an auxiliary power supply such as FCPS-24S6/S8 or APS-6R, refer to the documentation for that equipment.
Batteries
The control panel uses only sealed lead-acid batteries for secondary standby power. Maximum bat­tery capacity for the CPS-24/E main power supply is 200 AH. The NFS-320 enclosure provides space for up to two 26 AH batteries. Use external battery boxes if the installation requires larger capacity batteries; see Table A.5, “Selecting Battery and Battery Backbox,” on page 57.
When AC Power is lost, the deeply-discharged battery cutoff protection will be invoked at 17 volts. The power supply will be disconnected from the batteries. The power supply’s normal operation will be restored when AC power returns.
2
) with 600 VAC insulation
The table below contains battery charger specifications.
Charger Description Specifications
CPS-24/E Main Power Supply
CHG-120 Battery Charger
ACPS-2406 Auxiliary Charger/Power Supply
ACPS-610 Addressable Charger/Power Supply
An internal battery charger for 18 AH to 200 AH
An external battery charger designed to charge lead-acid batteries between 26 AH and 120 AH
An internal battery charger for 7 AH to 26 AH
An internal battery charger for 12 AH to 200 AH
Normal Charge: 27.6 VDC +/- 0.24 VDC Charging Current: 2.0 A or 5.7 A (Software selectable)
Dual Rate: High Charge: 28.1 VDC Normal Charge: 27.6 VDC Charging Current: 4.5 A
Normal Charge: 27.6 VDC Charging Current: 1.1 A max (0.750 A typical)
Normal Charge: 27.6 VDC +/- 0.24 VDC Charging Current: 2A, 5A, or OFF
(Software Selectable)
Signaling Line Circuit (SLC)
Item Value
Voltage 24 VDC nominal, 27.6 VDC maximum
Maximum length 12,500 ft. (3810 m) total loop length (NFPA Style 4, 6, and 7)
Note: Refer to Appendix B.2 “Wire Requirements” for limitations.
Maximum current 400 mA peak, (max short circuit; circuit will shut down until short is fixed). For
battery calculations use 200mA.
Maximum resistance 50 ohms (supervised and power-limited)
58 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 59
Electrical Specifications Electrical Specifications
Notification Appliance Circuits and Releasing Circuits
Item Value
Max. wiring voltage drop 2 VDC
NAC Nominal operating voltage
Special Applications for Releasing Circuits
Current for all external devices connected to the control panel’s power supply
Optional ACPS-2406 Total 6 A in alarm (5 A continuous)
Optional ACPS-610 Total 6 A in alarm (1.5 A single output)
Optional APS-6R Total 6 A in alarm (4 A continuous)
Maximum signaling current/circuit per NAC
End-of-Line Resistors (ELRs)
NOTE: For a list of compatible Notification Appliance Circuits and Releasing Circuits see Notifier Device Compatibility Document 15378.
(Retrofit note: SLCs with old CMX modules are restricted to 1.2 VDC.)
24 VDC regulated; 1.5 A max.
20.16 - 26.42 VDC
7.4 A in alarm (3.9 A continuous) TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
1.5 A Note: Some devices have maximum draws less than this; refer to the device’s documentation.
Control Panel NACs (TB6, TB7, TB8, TB9): 2.2K, 1/2 watt XP6-C, FCM-1 Modules: 47K, 1/2 watt
Output Relays (common)
Output relays for Alarm and Trouble are common on TB4; Supervisory, and Security are program­mable on TB5. See Figure 3.11, “Form-C Relay Connections” on page 27).
Contact ratings: 2.0 A @ 30 VDC (resistive)
Four-wire Smoke Detector Power
Control Panel terminals TB10 RESET (+) and (–) supply filtered, low-noise power for four-wire smoke detectors. Specifications are:
• Nominal voltage: 24 VDC special applications.
• Maximum rated current: 1.25 A DC
• Maximum ripple voltage: 176 mVrms
• TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
Refer to the Device Compatibility Document for compatible 24 VDC detectors.
Power Output
Control Panel terminals TB10 NONRESET (+) and (–) supply one (1) power-limited circuit avail­able to power external devices, such as notification appliances and annunciators.
• Nominal voltage: 24 VDC regulated, special applications, 1.5 A max.
• Maximum rated current: 1.25 A DC
• Maximum ripple voltage: 176 mVrms
• TB10, TB2, and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
Refer to the Device Compatibility Document for compatible devices and notification appliances.
NOTE: The Control Panel provides a total of 7.4 A of power in alarm (3.9 A in standby), shared by all internal circuitry and external provisions (24 V resettable and non-resettable). TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 in alarm. For power requirements, refer to the power supply calculation tables in Appendix A.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 59
Page 60
Electrical Specifications Wire Requirements
Operating Power: AC Branch Circuit
The control panel requires connection to a separate dedicated AC branch circuit. Follow these guidelines when connecting the AC branch circuit:
• Label the branch circuit “Fire Alarm”. This must be a separate dedicated AC fire alarm circuit.
• Connect the branch circuit to the line side of the main power feed of the protected premises.
• Do not power other equipment from the fire alarm branch circuit.
• Run the AC branch circuit wire continuously, without any disconnect devices except for overcurrent protection, from the power source to the fire alarm control panel.
• Overcurrent protection for the AC branch circuit must comply with Article 760 of the National Electrical Codes, as well as local codes.
• Use 12 AWG (3.31 mm
Connect the ground terminal (TB1-Earth) to a solid earth ground (a metallic, cold water pipe may be suitable in some installations). This connection is vital in reducing the panel’s susceptibility to transients generated by lightning and electrostatic discharge.
2
) wire with 600 VAC insulation for the AC branch circuit.
Operating Power: Secondary Power Source (Batteries)
The battery charger is current-limited and can recharge sealed lead-acid type batteries. The battery charger shuts off when the control panel is in alarm.

B.2 Wire Requirements

Each type of circuit within the Fire Alarm Control System requires use of a specific wire type to ensure proper circuit operation. The wire gauge of a particular circuit depends on the length of that circuit and the current traveling through it. Use Table B.1 below to determine the specific wiring requirements for each circuit.
Compliance with the Federal Communications Commission (FCC) and Canadian Department of Communication regulations on electrical energy radiation requires the following: Use twisted-pair shielded wire for any non-SLC-loop wiring entering or exiting the cabinet that is not enclosed in conduit. Use twisted-pair unshielded wiring for SLC-loop wiring.
NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce problems by exclusively using electronic sounders (such as the SpectrAlert, SpectrAlert Advanced or MA/SS-24 Series) instead of more electronically noisy notification appliances (such as electromechanical bells or horns).
60 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 61
Wire Requirements Electrical Specifications
Circuit Type
SLC (power limited)
Circuit
Function
Connects to intelligent and addressable modules.
Wire Requirements
Twisted-unshielded pair, 12 to 18 AWG (3.31 to 0.82 mm
2
). 50 ohms maximum per length of Style 6 and 7 loops. 50 ohms per branch maximum for Style 4 loop.
Twisted-shielded pair
NOTE:
• Shields must be isolated from ground.
Distance
(feet/meters)
12,500 ft. (3,810 m) 9,500 ft. (2,895.6 m) 6,000 ft. (1,828.8 m) 3,700 ft. (1,127.76 m)
5,000 ft. (1,524 m)
3,700 ft. (1,127.76 m)
Typ i cal Wi re Type
12 AWG (3.31 mm 14 AWG (2.08 mm 16 AWG (1.31 mm 18 AWG (0.82 mm
12 to 16 AWG (3.31 to
1.31 mm
2
)
18 AWG (0.82 mm
2
)
2
)
2
)
2
)
2)
• Shields should be broken at each
device.
Untwisted, unshielded wire, in conduit or outside of conduit.
5,000 ft. (1,524 m)
3,700 ft. (1,127.76 m)
12 to 16 AWG (3.31 to
1.31 mm 18 AWG (0.82 mm
2
)
2)
Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to ground) should not exceed 0.5 mircofarads.
EIA-485 (power limited)
Connects to FDU-80, ACS modules, LCD-
Twisted-shielded pair with a characteristic impedance of 120 ohms. 18 AWG (0.82
2
mm
) minimum.
6,000/1829 (max)
16 AWG (1.31 mm
2
)
80, or TM-4 Transmitter
EIA-232 (power limited)
Connects to Printers, CRT,
Twisted-shielded pair in conduit. 18 AWG (0.82 mm2) minimum.
20 feet (6.1 m) (without modem)
16 AWG (1.31 mm
2
)
or PC.
IDC Initiating Device Circuit
FMM-1, FMM-101, FDM-1, XP10-
12-18 AWG (3.31 to 0.82 mm Maximum circuit resistance is 20 ohms.
2
).
12 to 18 AWG (3.31 to
0.82 mm
2
)
M, XP6-MA (power limited)
NAC Notification Appliance Circuit
Releasing Module
FCM-1*, XP6-C (power limited)
12-18 AWG (3.31 to 0.82 mm At alarm current level, no more than a 1.2 V drop at the end of the circuit, or sized to provide the minimum rated operating voltage of the appliances used.
FCM-1-REL 12-18 AWG (3.31 to 0.82 mm
5 ohms maximum per circuit for class A or class B, or sized to provide the minimum rated operating voltage of the appliances used.
2
).
To meet 1.2 V drop, or sized to provide the minimum rated operating voltage of the appliances used.
2
).
To meet 5 ohms maximum current resistance, or sized to provide the minimum rated
12 to 18 AWG (3.31 to
0.82 mm
12 to 18 AWG (3.31 to
0.82 mm
2
)
2
)
operating voltage of the appliances used.
24 VDC Power Runs (power-limited)
To T M - 4 Transmitter, Annunciator and FCM-1 modules
CHG-120 External battery
12-18 AWG (3.31 to 0.82 mm Size wire so that no more than 1.2 V drop across wire run from supply source to end of any branch.
12 AWG (3.31 mm
2
) in conduit 20/6.1 (max) 12 AWG (3.31 mm2)
2
).
To meet 1.2 volt drop 12 to 18 AWG (3.31 to
0.82 mm
2
)
charger
*FCM-1 can not be used for synchronized strobe/sounder applications.
Table B.1 Wire Requirements
NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length
maximum to meet UL 60950.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 61
Page 62

Index

Numerics
24 VDC, see Power (DC)
A
A77-716B, see Power Supervision Relay
(Replaced by EOLR-1)
AC, see Power Acceptance Test ACM-8R
Labeling Requirements Agent Release-Abort Station Alarm Relays, see Form-C Relays
23, 24
50
30
48
27
B
Backup-Alarm Switches 28 Batteries, also see Power: DC
Battery Calculations
Battery Checks and Maintenance
Battery Specifications
Connections
24
24
52, 53, 54, 55, 56, 57
51
58
C
Cabinets
Dimensions
Mounting Central Receiving Unit, also see UDACT Manual
41
Circuit Board, see CPU Compatible Equipment Components Control Panel Circuit Board, see CPU CPS-24/E, see Power Supply CPU
Drawing
Overview CRTs
33
CRT/PRN Combination
CRT-2 Configuration
CRT-2 Function Keys and Parameters
Installation
15
20
16, 17
13, 14
11, 13, 14
11
33
32
33
30–34
D
DC, see Power 23, 24
E
Electrical connections 22 Electrical Specifications Ematch Protection Device EOLR-1, see Power Supervision Relay External Power Supervision
58
27
36
F
FCM-1, also see Releasing Applications
Circuit Requirements
FCM-1-REL, also see Releasing Applications
Connections Fire/Security Applications Form-C relays Four-wire Smoke Detector
Specifications
47
27, 59
46
47
40–42
59
I
Installation
Checklist
Preparation
19
18
J
Jumper Locations 13, 14
K
KDM-R2 11
Removal/Installation
21
L
LDM-R32
non-power-limited circuits lockout
50
30
M
Main Power Supply, see Power Supply Maintenance microcontroller failure Multiple Detector Operation
50
28
34
N
NACs (Notification Appliance Circuits)
Backup option
NAC Connections
Releasing applications
Specifications NBG-12LRA NCM, Also see Networking
Installation Networking NFPA Applications
NFPA 72 Central or Remote Station Fire
NFPA Applications (Overview) NFS-320 (120V Operation), see Basic Equipment Packages
11
28
59
48
20
22
Alarm System
26
26, 28, 43, 44
37
36
62 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Page 63
Index O–W
NFS-320 (120V operation), see Basic Equipment Packages NFS-320 (120Voperation), see Basic Equipment Packages NFS-320E (220-240V Operation) Nonpower-limited circuits
Notification Appliance Circuits, see NACs
13
14
UL wiring requirements
11
29, 30
O
Operating Power 60 Operational Checks Option boards
Installation steps
Output relays
Connections Specifications
50
20
27, 59
59
P
Periodic Testing 50 Power
AC Power Checklist AC Power Connections AC power connections AC specifications DC Power Connections DC power connections Installation steps Non-resettable Power specifications
Resettable Power Supervision Relay power supply Power Supply Calculations Power supply calculations Power-limited Wiring Requirements Printers
33
Installation
PRN series connections
PRN settings
PRN/CRT Combination
Remote PRN Proprietary Security Alarm Applications
Wiring Protected Premises Unit
24
12
30–34
32
31
42
23
23, 24
23
58
23, 24
24
22
25
22, 59
48
52, 54, 55, 56, 57
53
29
31
33
37
Connections FCM-1-REL Connections
44
47
S
Security Relays, see Form-C Relays 27 Security Tamper Switch Service
50
SLC
Device Capacity Installation Maximum Wiring Distance
specifications SLC See also SLC Wiring Manual Specifications Standard equipment Stat-X
Device Wiring STS-1, also see Security Tamper Switch Supervisory and Security contacts
configuring as Alarm contacts Supervisory Relays, see Form-C Relays Supplemental Documentation Switches
Backup-Alarm
Switch Locations System
Description of features
Limitations
Options System Current Draws System current draws
35
58, 59
11
41, 42
34
34
58
34
11
27
42
27
27
8
28
14
10
11
52, 54, 55, 56, 57
53
T
Terminal Block Locations 13, 14 Testing
50
TM-4
see TM-4 Transmitter Module Installation
Document
Trouble Relays, see Form-C Relays
21
27
U
UDACT also see Central Receiving Unit
and the UDACT Manual
UL nonpower-limited wiring requirements UL Requirements
29
37
29
R
Related Documentation 8 Relays, see Form-C Relays Releasing Circuits
Connections Releasing Applications Specifications
Releasing Device
Circuit Requirements
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 63
26
27
43–49
59
44
V
VeriFire 35
W
Wiring
Proprietary Security Alarm Applications
42
Wire Requirements
60
Page 64
World Headquarters 12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118
www.notifier.com
Loading...