READ and UNDERSTAND this manual completely before using the generator! Failure to properly set up,
operate, and maintain this generator could result in serious injury or death from carbon monoxide poisoning,
electric shock, fire/explosion, or burns. In particular, be aware of the following hazards:
CO Poisoning
Generators give off carbon monoxide, a poisonous gas that can kill you. You CANNOT smell it, see it, or taste it.
ONLY run generator OUTDOORS and at least 20 feet from the home, away from windows, vents and air intakes, to allow
proper ventilation. If you start to feel sick, dizzy, or weak while using the generator, shut off the engine and get to fresh air
RIGHT AWAY. NEVER run generator inside any enclosed or semi-enclosed spaces, including homes, basements,
garages, sheds, boxes, RVs, boats or pick-up truck beds. These spaces can trap poisonous gases, EVEN if you run a fan or
open windows.
Install carbon monoxide alarms inside nearby structures/buildings (battery-operated, or plug-in with battery backup).
Electric shock / Electrocution
High voltage electricity from generator can kill. DO NOT operate in wet locations. Be sure generator is properly grounded.
Use only UL-listed, outdoor-rated grounded extension cords of proper size.
NEVER plug the generator directly into a wall outlet. ANY connection to a building’s electrical system MUST ISOLATE
THE GENERATOR FROM UTILITY POWER via a UL-approved transfer switch installed by a licensed electrician.
Otherwise, back feed from the generator into the power grid could kill utility workers.
Fire / Explosion
DO NOT overload generator (per rated capacity), and OPERATE ONLY in an area with adequate cooling ventilation so
engine does not overheat. Exhaust can be extremely hot. Keep muffler at least 7’ from all combustible objects.
All fuels are flammable. Never fuel a running or hot engine. Never pump fuel directly into generator at gas station – use
approved container to transfer fuel. Ensure there are no fuel leaks, and keep sources of sparks and flames away.
ALWAYS keep a fire extinguisher rated “ABC” nearby.
STOP!
CHOOSE THE RIGHT GENERATOR FOR YOUR NEEDS. See the “Power load Planning & Management” section of
this manual to determine your power load requirements and then compare to the generator’s rated capacity.
INSPECT COMPONENTS: Closely inspect to make sure no components are missing or damaged. See the “Unpacking &
Delivery Inspection” section for instructions on whom to contact to report missing or damaged parts.
ARRANGE FOR PROFESSIONAL INSTALLATION of a transfer switch if you will be connecting the generator to
your building’s electrical system. See the “Installation/Initial Set-Up” section for more information about this
requirement.
ITEM NUMBER: 165912
SERIAL NUMBER: _____________
M165912I.3
Owner’s Manual
Instructions for Installation/Set-up, Operation, Servicing, & Storage
Portable, Outdoor Use-Only, Gasoline Generator
2,400 Watt Continuous (2,700 Watt Surge) Capacity
Can be used to power individual appliances plugged directly into the generator’s outlets, or as a back-up
connection to a building’s power supply (via a professionally installed UL-approved transfer switch.
Any Questions, Comments, Problems, or Parts Orders
Call NorthStar Product Support 1-800-270-0810
Hazard Signal Word Definitions
2
Table of Contents
Hazard Signal Word Definitions ................................................................................................. 2
About Your Generator ................................................................................................................. 4
Improper use or maintenance of this generator can result in serious injury or death from
carbon monoxide poisoning, electric shock/electrocution, fire/explosion, or burns.
Read this manual completely before using the generator and follow all instructions and
safety rules.
Thank you for purchasing your NorthStar portable generator!
About Your Generator
This engine-driven, portable generator is designed to provide up to 2700 Watts of
electrical power (2400 watts continuous, 2700 watts surge).
It can supply power:
1. As a portable power source. You can plug appliances directly into the generator’s
electrical outlets.
2. As a back-up, standby power source for a building. A licensed electrician can connect
the generator to your building’s electrical system via the installation of an UL-approved transfer switch.(See the “Installation & Initial Set-up” section of this manual to learn
more about specific requirements and precautions relating to wiring the generator to your
building’s electrical system.)
You must select a generator adequately sized for your power needs. You need to
determine the power needs of all the appliances/tools you wish to power at the same time and
choose a generator rated to provide at least that power level. See the “Power Load Planning &
Management” section of this manual to determine your specific power load requirements and
then compare them to this generator’s rated capacity. You must not overload the generator.
Overloading will cause damage to the generator and attached electrical devices, and may also
result in fire.
Be sure to read about site selection and grounding requirements for running this
generator. More detailed information can be found in the “Installation & Initial Set-up, Steps
5 & 6 of this manual.
This generator is too heavy for one person to lift without mechanical assistance. An
optional wheel kit is available from NorthStar and is recommended if you will be moving the
generator unassisted. Other optional accessories available from NorthStar include a vinyl
cover for storage, UL-approved transfer switches, and extension cords.
Contact NorthStar Product Support at 1-800-270-0810 with questions about optional
accessories or to order.
Read this Manual
You must follow all instructions and safety precautions presented throughout this manual. A
summary of important safety information can be found at the end of the manual. Keep this
manual for reference and review.
4
About Your Generator (cont’d)
5
ATTENTION:
All Rental Companies and Private Owners who loan this
equipment to others!
All persons to whom you rent/loan this generator must have access to and read this manual.
Keep this owner’s manual with the generator at all times and advise all persons who will
operate the machine to read it. You must also provide personal instruction on how to safely
operate the generator and remain available to answer any questions a renter/borrower might
have.
Proper preparation, operation, and maintenance will result in operator safety, as well as best
performance and long life of the generator. For detailed engine operation and maintenance
information, always refer to the engine Owner’s Manual furnished with the generator.
NorthStar is constantly improving its products. The specifications outlined herein are subject
to change without prior notice or obligation. The purchaser and/or user shall assume liability
for any modification and/or alterations of this equipment from original design and
manufacture.
Before using, the user shall determine the suitability of this product for its intended use and
assumes liability therein.
Contact NorthStar Product Support at 1-800-270-0810 for any questions about the
appropriate use of this generator.
Warranty Registration
Please fill out and submit the warranty registration card so that we have your contact
information for any future product literature or replacement parts you may need.
Always make sure safety labels are in place and in good condition. If a safety label
is missing or not legible, order new labels or unsafe operation could result.
To order replacement safety labels, call NorthStar Product Support at 1-800-270-0810.
This portable single phase generator has 1, 20
amp (A) push to reset circuit breaker to protect
against electrical overloads.
Reference 2 – (2) 120V 20A
Duplex Receptacles
The generator has a control panel with two 120V
duplex (two receptacles in a common housing)
receptacles. The duplex is a 120 volt (V) 20 amp
(A) straight blade receptacle, National Electrical
Manufacturer’s Association (NEMA) number 520R. This receptacle accepts NEMA plug
numbers 5-15P and 5-20P. Each receptacle on
the duplex is capable of drawing 20A.
Reference 3 – Generator Head
The electricity producing part of the generator.
Reference 4 – Oil Drain Plug
Refer to your Honda engine manual for oil
change recommendations.
Reference 5 – Vibration
Isolation Mount
The engine and generator mounted on rubber
cylinders that absorb most of the engine
vibration. This feature eliminates the tendency
of the machine to “walk” which is common in
engine powered equipment.
Reference 6 – Muffler
Honda’s standard muffler with an installed spark
arrestor.
Reference 7 – Choke Lever
Used during cold starts. Refer to the Honda
engine manual for usage.
Reference 8 – Ignition Switch
Lever
The red engine stop lever is located on the
engine. Always locate this lever and be familiar
with its location before operating the generator.
Reference 9 – Recoil
Grasp firmly when pull starting the engine.
Reference 10 – Gas Tank
Always allow room for gasoline expansion by
not filling the gas tank completely full.
Reference 11 – Air Cleaner
Refer to your Honda engine manual for air
cleaner care.
Power Load Planning & Management
WARNING
NEVER exceed the rated wattage capacity of your generator.
OVERLOADING may cause SERIOUS DAMAGE to the generator and
attached electrical devices, and may result in fire.
Device
Running
Watts
Device
Running
Watts
Air conditioner (12.000 BTU)
1700 (a,b)
Jet pump
800 (a)
Battery charger (20 Amp)
500
Lawn mower
1200
Belt sander (3”)
1000
Light bulb (100 Watt)
100
Chain saw
1200
Microwave oven
700
Circular saw (6½”)
2000 (a,b)
Milk cooler
1100 (a)
Coffee maker
1800 (a,b)
Oil burner on furnace
300
Compressor (1 HP)
1400 (a,b)
Oil-fired space heater (140,000 Btu)
400
Compressor (3/4 HP)
1800 (a)
Oil-fired space heater (85,000 Btu)
225
Compressor (1/2 HP)
1400 (a)
Oil-fired space heater (30,000 Btu)
150
Curling iron
700
Oven
4500
Dishwasher
1200
Paint sprayer, Airless (1/3 HP)
600 (a)
Edge trimmer
500
Paint sprayer, Airless (handheld)
150
Electric nail gun
1200
Radio
200
Your generator MUST BE SIZED PROPERLY to provide both the running and starting (surge)
wattage of the devices you will be powering. Before using your generator, determine the running
and starting wattage requirements of all the electrical devices you will be poweringsimultaneously.
The sum of the running and starting wattages of the devices being powered must not exceed the
continuous output rating of your generator. (The continuous output rating of your generator is listed
in the “Specifications” section of this manual.) Note that:
Devices without electric motors such as light bulbs, radios, and televisions have the same
running and starting wattage.
Devices with electric motors such as refrigerators, compressors, and hand tools typically
require a starting wattage that is 3 to 5 times greater than the running wattage.
The running and starting wattage requirements are often listed on a device’s nameplate. If wattage
is not given on the device’s nameplate, the wattage may be calculated by multiplying the nameplate
voltage by nameplate amperage, Watts = Volts X Amps.
Example conversion to watts:
120 Volts X 5 Amps = 600 Watts
If only the running voltage is given on the nameplate for a device with an electric motor, the starting
wattage can be approximated to be three to five times the running wattage.
Estimates for the running wattage requirements for common devices are listed in Table 1 below.
Guidance for starting wattages is provided in the table’s footnotes.
Table 1
10
Power Load Planning & Management (cont’d)
11
Device
Running
Watts
Device
Running
Watts
Electric range (1 element)
1500
Refrigerator
600 (b)
Electric skillet
1250
Slow cooker
200
Furnace fan (1/3 HP)
1200 (a)
Submersible pump (1-1/2 HP)
2800 (a)
Freezer
800 (b)
Submersible pump (1 HP)
2000 (a)
Hair dryer
1200
Submersible pump (1/2 HP)
1500 (a)
Hand drill (1”)
1100
Sump pump
600 (a)
Hand drill (1/2”)
875
Table saw
2000 (a)
Hand drill (3/8”)
500
Television
500
Hand drill (1/4”)
250
Toaster
1000
Hedge trimmer
450
Vacuum cleaner
250
Home computer
150
VCR
70
Impact wrench
500
Water Heater
3000
Weed trimmer
500
Device to be Powered
Greater of Starting/Running
Wattage
Light Bulb
75 W
Refrigerator – 18 Cu. Ft.
1600 W
Microwave
700 W
Window AC
1800 W
Sump pump (1/3 hp)
2100 W
Total
6275W
STAGGERING LOADS
(a) Hard-starting motors require 3-5 times the rated running watts
(b) For extremely hard to start loads such as air conditioners and air compressors, consult the
equipment dealer to determine maximum wattage
To calculate the running and starting wattage requirements for the devices you will be
powering, follow these steps:
1. Make a list of all electrical devices you will be powering at the same time with the generator.
2. List the greater of the running or starting wattage next to each device as obtained from the
devices’ nameplate or Table 1. If only the running wattage for a device with an electric
motor is known, the starting wattage can be estimated to be at least 3 times the running
wattage.
3. Add the wattages for all devices on your list. This total must be lower than the continuous
output rating of your generator.
Example:
In this example, the generator must have a continuous output of at least 6275 W in order to
power all of the devices simultaneously.
You can increase the number of devices your generator can power by staggering the load on the
generator. For example, you could alternately power your refrigerator and air conditioner for
limited periods of time -- powering only one of the devices at a time and never powering both at the
same time.
Installation / Initial Set-Up
Steps for Installation / Initial Set-Up
1. Unpacking & delivery inspection.
2. Planning the power load to stay within the generator’s rated
capacity.
3. Setting up generator for the type of power generation you need:
a. portable power source, or
b. connected to a building as a back-up power source.
4. Selecting a site for using the generator.
5. Grounding.
1. Unpacking & Delivery Inspection
You should inspect the generator immediately after you receive delivery.
See the “Machine Component Identification” section of this manual for a
diagram of the generator and its components.
If you have missing or damaged components, contact Product Support at 1-800-270-0810.
2. Planning the Power Load
Plan your power load so that you do not exceed the generator’s rated capacity.
See the “Power Load Planning & Management” section of this manual to review how to plan and
manage power loads for the generator.
There are a number of important steps required to set up your generator for initial use. These
steps are:
Each of these steps is discussed in detail below:
12
Installation / Initial Set-Up (cont’d)
13
3. Set-up either as a BUILDING BACK-UP or PORTABLE Power Source
This generator is designed to provide up to 2700Wof electrical power. It can supply electricity in
two ways:
1. As a back-up, standby power source for a building. For this application, you must arrange
for a licensed electrician to connect the generator to your building’s electrical system via the
installation of an UL-approved transfer switch. The transfer switch must be installed in
accordance with building electrical code and guidelines supplied by your power company.
2. As a portable power source. You can plug appliances or tools directly into the generator’s
electrical outlets.
Specific requirements for each are given below.
Note: Regardless of whether you use your generator as a back-up power source connected to a
building or as a portable power source, you must not overload the generator. Overloading
may cause serious damage to the generator and attached electrical devices.
Using as a
Back-up Power
Source for a
Building
Contact a licensed electrician to install a UL-approved transfer switch if
you want to use your generator as a back-up power source for a building.
What does a transfer switch do? It:
a) Safely connects the generator to your building’s electrical system by
isolating your generator from your utility company’s power lines,
AND
b) Connects your generator to a critical subset of your building’s circuits
that are needed for emergency power needs.
If your generator will be connected to your building’s electrical system, it
MUST ALWAYS be isolated from the utility power grid with a UL-approved
transfer switch installed by a licensed electrician in compliance with all
applicable building and electrical codes, and in accordance with guidelines
supplied by your power company.
DANGER:
A transfer switch must be installed in order to isolate your
generator from the utility power grid. If your generator is NOT
properly isolated from the utility system, serious hazards will
arise:
When your generator is running, it’s output will back feed into
the utility power line and transformer that are normally used to
provide you with power. The transformer will step up the
current to the normal line voltage. An unsuspecting utility line
worker working on what he thinks is a deactivated line could
be electrocuted.
If your generator is connected (running or not) when utility
power is restored, your generator will be destroyed. It could
also explode or cause fire.
Loading...
+ 29 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.