NorthStar 165165 Product Manual

WARNING
READ and UNDERSTAND this manual completely before using the generator! Failure to properly set up,
operate, and maintain this generator could result in serious injury or death from carbon monoxide poisoning, electric shock, fire/explosion, or burns. In particular, be aware of the following hazards:
CO Poisoning
Generators give off carbon monoxide, a poisonous gas that can kill you. You CANNOT smell it, see it, or taste it. ONLY run generator OUTDOORS and AWAY from building air intakes. NEVER run generator inside any enclosed
or semi-enclosed spaces, including homes, basements, garages, sheds, boxes, RVs, boats or pick-up truck beds. These spaces can trap poisonous gases, EVEN if you run a fan or open windows.
Install carbon monoxide alarms inside nearby structures/buildings (battery-operated, or plug-in with battery backup).
Electric shock / Electrocution
High voltage electricity from generator can kill. DO NOT operate in wet locations. Be sure generator is properly
grounded. Use only UL-listed, outdoor-rated grounded extension cords of proper size.
NEVER plug the generator directly into a wall outlet. ANY connection to a building’s electrical system MUST
ISOLATE THE GENERATOR FROM UTILITY POWER via a UL-listed transfer switch installed by a licensed electrician. Otherwise, back feed from the generator into the power grid could kill utility workers.
Fire / Explosion
DO NOT overload generator (per rated capacity), and OPERATE ONLY in an area with adequate cooling ventilation
so engine does not overheat. Exhaust can be extremely hot. Keep muffler at least 7 feet from all combustible objects.
All fuels are flammable. Never fuel a running or hot engine. Never pump fuel directly into generator at gas station –
use approved container to transfer fuel. Ensure there are no fuel leaks, and keep sources of sparks and flames away.
ALWAYS keep a fire extinguisher rated “ABC” nearby.
STOP!
CHOOSE THE RIGHT GENERATOR FOR YOUR NEEDS. See the “Power load Planning and Management”
section of this manual to determine your power load requirements and then compare to the generator’s rated ca pacity.
INSPECT COMPONENTS: Closely inspect to make sure no components are missing or damaged. See the “Unpacking
and Delivery Inspection” section for instructions on whom to contact to report missing or damaged parts.
ARRANGE FOR PROFESSIONAL INSTALLATION of a transfer switch if you will be connecting the generator
to your building’s electrical system. See the “Installation/Initial Set-Up” section for more information about this requirement.
ITEM NUMBER: 165165 SERIAL NUMBER: _____________
M165165A.2
Owner’s Manual
Instructions for Installation/Set-up, Operation, Servicing, and Storage
Portable, Outdoor Use-Only, Industrial Diesel Generator
6,120 Watt Continuous (6,500 Watt Surge) Capacity
Any Questions, Comments, Problems, or Parts Orders
Call NorthStar Product Support 1-800-270-0810
Hazard Signal Word Definitions
2
Table of Contents
Hazard Signal Word Definitions ................................................................................................. 2
About Your Generator ................................................................................................................. 4
Specifications ................................................................................................................................. 6
Safety Label Locations .................................................................................................................. 7
Machine Component Identification ............................................................................................. 8
Power Load Planning and Management ..................................................................................... 10
Installation / Initial Set-Up:
1. Unpacking and Delivery Inspection ....................................................................................... 12
2. Planning the Power Load ........................................................................................................ 12
3. Set-up as either a BUILDING BACK-UP or PORTABLE Power Source ............................ 13
4. Selecting a Suitable Site ......................................................................................................... 16
5. Grounding the Generator ........................................................................................................ 18
6. Battery Installation ................................................................................................................ 19
Operation:
1. General Safety Rules for Operation ....................................................................................... 20
2. Preparing for Operation .......................................................................................................... 23
3. Starting the Engine ................................................................................................................. 26
4. Checking Generator Output .................................................................................................... 27
5. Connecting Loads ................................................................................................................... 28
6. Stopping the Engine ............................................................................................................... 29
7. Storage and Exercise .............................................................................................................. 29
Maintenance and Repair .............................................................................................................. 31
Troubleshooting ............................................................................................................................. 33
Summary of Important Safety Information for Operation ....................................................... 34
Generator Exploded View ............................................................................................................ 38
Wiring Diagram ............................................................................................................................. 40
Generator Head Exploded View .................................................................................................. 41
Limited Warranty ......................................................................................................................... 43
3
About Your Generator
WARNING
Improper use or maintenance of this generator can result in serious injury or death from carbon monoxide poisoning, electric shock/electrocution, fire/explosion, or burns.
Read this manual completely before using the generator and follow all instructions and safety rules.
Thank you for purchasing your NorthStar portable generator!
About Your Generator
This engine-driven, portable generator is designed to provide up to 6500 Watts of electrical power (6120 watts continuous, 6500 watts surge).
It can supply power:
1. As a portable power source. You can plug appliances directly into the generator’s
electrical outlets.
2. As a back-up, standby power source for a building. A licensed electrician can connect
the generator to your building’s electrical system via the installation of an UL-listed transfer switch. (See the “Installation and Initial Set-up” section of this manual to learn
more about specific requirements and precautions relating to wiring the generator to your building’s electrical system.)
You must select a generator adequately sized for your power needs. You need to determine the power needs of all the appliances/tools you wish to power at the same time and
choose a generator rated to provide at least that power level. See the “Power Load Planning
and Management” section of this manual to determine your specific power load requirements
and then compare them to this generator’s rated capacity. You must not overload the
generator. Overloading will cause damage to the generator and attached electrical devices, and may also result in fire.
Be sure to read about site selection and grounding requirements for running this generator. More detailed information can be found in the “Installation and Initial Set-up,
Steps 5 and 6” of this manual. This generator is too heavy for one person to lift without mechanical assistance. An
optional wheel kit is available from NorthStar and is recommended if you will be moving the generator unassisted. Other optional accessories available from NorthStar include a vinyl cover for storage, UL-listed transfer switches, and extension cords.
Contact NorthStar Product Support at 1-800-270-0810 with questions about optional
accessories or to order.
Read this Manual
You must follow all instructions and safety precautions presented throughout this manual. A summary of important safety information can be found at the end of the manual. Keep this manual for reference and review.
4
About Your Generator (cont’d)
5
ATTENTION:
All Rental Companies and Private Owners who loan this
equipment to others!
All persons to whom you rent/loan this generator must have access to and read this manual.
Keep this owner’s manual with the generator at all times and advise all persons who will
operate the machine to read it. You must also provide personal instruction on how to safely operate the generator and remain available to answer any questions a renter/borrower might have.
Proper preparation, operation, and maintenance will result in operator safety, as well as best performance and long life of the generator. For detailed engine operation and maintenance information, always refer to the engine Owner’s Manual furnished with the generator.
NorthStar is constantly improving its products. The specifications outlined herein are subject to change without prior notice or obligation. The purchaser and/or user shall assume liability for any modification and/or alterations of this equipment from original design and manufacture.
Before using, the user shall determine the suitability of this product for its intended use and assumes liability therein.
Contact NorthStar Product Support at 1-800-270-0810 for any questions about the appropriate use of this generator.
Warranty Registration
Please fill out and submit the warranty registration card so that we have your contact information for any future product literature or replacement parts you may need.
Specifications – Item #165165A
SPECIFICATIONS
Item Number
165165
Maximum Output
6500 Watts (W)
Continuous Output
6120 Watts (W)
Voltage
120 / 240 Volt (V)
Phase
Single phase (4-wire)
Frequency
56.5 - 63.3 Hertz (Hz)
Power Factor
1.0 p.f.
Engine
9.4 HP Kubota OC95
Engine Speed
3600 RPM
Fuel Type
Diesel
Fuel Capacity
6.5 gallons (24.6 L)
Oil Capacity
1.76 US quarts (1.65 L)
Starting Method
Electric
120V Receptacle
20 Amp (A) Duplex GFCI (NEMA 5-20R)
30 Amp (A) Locking device
(NEMA L5-30R)
120/240V Receptacle
30 Amp (A) Locking device
(NEMA L14-30R)
Circuit Breakers
30 Amp (A) Magnetic, Qty. 1
20 Amp (A), Thermal type, Qty. 2
Grounding Screw
Receives 10 Ga. Fork Terminal
Battery (not included)
12 Volt, 36 Amp-Hour minimum,
Group size U1
Dimensions
Length
34.00" (86.4 cm)
Width
23.25" (59.1 cm)
Height
22.25" (56.5 cm)
Dry Weight
315 lb. (143 kg)
Gross Weight
330 lb. (150 kg)
6
Safety Label Locations – Item #165165A
On-Product Warning Labels
Part numbers
Description
779396
Battery Warning
791697
NorthStar
791724
Warning
793520
Fuel Warning
786635
Burn Hazard
793562
Fire Hazard
fig05699
Always make sure safety labels are in place and in good condition. If a safety label is missing or not legible, order new labels or unsafe operation could result.
To order replacement safety labels, call NorthStar Product Support at 1-800-270-0810.
7
Machine Component Identification - Item #165165A
Ref.
Description
Ref.
Description
1
Main Line Breaker
11
Oil Fill and Dip Stick
2
Thermal Circuit Breakers
12
Air Cleaner Housing
3
Voltmeter
13
Decompression Lever
4
120 Volt-20 Amp GFCI Duplex Receptacles
14
Muffler
5
Hour Meter
15
Ignition Fuse
6
Engine Stop Lever
16
Isolation Mounts
7
120 Volt-30 Amp Locking Receptacle
17
Battery Box
8
Engine Starting Key
18
Generator Head
9
120/240 Volt-30 Amp Locking Receptacle
19
6.5 Gallon Fuel Tank
10
Oil Drain Plug
20
Fuel Cap with Gauge
Figure 1 (Ref. 1-13)
Figure 2 (Ref. 14-20)
8
Machine Component Identification - Item #165165A
9
REFERENCE GUIDE
Reference 1 – Main Line Breaker
The main line breaker is a two-pole thermo-magnetic circuit breaker. The circuit breaker will protect the generator from overload and short circuit conditions. To reset the circuit breaker move the toggle to the OFF position, then back to the ON position. When this circuit breaker is in the OFF position, all receptacles will be off.
Reference 2 – Thermal Circuit Breakers
The control panel has two thermal circuit breakers. If the circuit breaker trips, a black post will extend from the circuit breaker, push the black post to reset the circuit breaker. If the circuit breaker will not reset, wait two minutes and try again.
Reference 3 – Voltmeter
The voltmeter allows for monitoring of the generator. The needle should be in the green area for all load conditions.
Reference 4 – 120 Volt-20 Amp GFCI Duplex Receptacles
The control panel is equipped with four 120 Volt-20 Amp ground fault circuit interrupt (GFCI) receptacles (NEMA 5-20R). The receptacles will accept either NEMA 5-15P or NEMA 5-20P plugs. In the center of each duplex receptacle there is both a test/reset button and indicator lamp. If there is a fault condition with a load connected to a duplex receptacle, the indicator lamp will glow and the reset button will extend. To test the GFCI press the test button and the reset button should extend. The reset button must be pushed to reset the receptacle.
Reference 5 – Hour Meter
The hour meter allows for monitoring of engine maintenance schedules.
Reference 6 - Engine Stop Lever
The engine is stopped by pushing and holding the engine stop lever. Turning the engine key to the OFF position will not stop the engine.
Reference 7 – 120 Volt-30 Amp Locking Receptacle
The control panel is equipped with one NEMA L5-30R receptacle. This receptacle accepts only NEMA L5-30P plugs.
Reference 8 – Engine Starting Key
To start the engine, turn the key to the START position.
Reference 9 – 120/240 Volt-30 Amp Locking Receptacle
The control panel is equipped with one NEMA L14-30R receptacle. This receptacle accepts only NEMA L14-30P plugs. This receptacle is popular for connection to a transfer switch for home standby power.
Reference 10 – Oil Drain Plug
Removal of plug allows drainage of oil from the engine. Consult your Kubota engine manual for further details.
Reference 11 – Oil Fill and Dip Stick
Consult your Kubota engine owner’s manual for details concerning oil change intervals.
Reference 12 – Air Cleaner Housing
Refer to the Kubota engine manual for air cleaner care.
Reference 13 – Decompression Lever
Reduces the load on the engine during starting for a smoother start.
Reference 14 – Muffler
Muffler can be very hot during operation and will burn you.
Reference 15 – Ignition Fuse
Your engine is equipped with a 30 Amp fuse located on the wire harness below the generator head.
Reference 16 – Isolation Mounts
The engine and generator are mounted on rubber mounts that absorb most of the engine vibration. This feature eliminates the tendency of
the machine to “walk” which is common with engine powered
equipment.
Reference 17 – Battery Box
The battery box provides protection for the battery and will accept a standard lawn tractor size battery (Group U1-7). The engine requires a 12 volt battery, with a minimum rating of 36 Ah (Amp-hour). See battery section for sizing.
Reference 18 – Generator Head
Your NorthStar product is equipped with a high quality brushless generator. The generator is maintenance free and will provide years of dependable service.
Reference 19 – 6.5 Gallon Fuel Tank
Large tank allows for extended run capabilities. Always allow room for fuel expansion by not filling the tank completely full.
Reference 20 – Fuel Cap with Gauge
The fuel cap is extra large, creating a large hole for refilling and a comfortable grip. You can always monitor the fuel level without removing the cap by using the fuel level indicator built into the fuel cap.
Power Load Planning and Management
WARNING
NEVER exceed the rated wattage capacity of your generator. OVERLOADING may cause SERIOUS DAMAGE to the generator and attached electrical devices, and may result in fire.
Device
Running
Watts
Device
Running
Watts
Air conditioner (12.000 BTU)
1700 (a,b)
Jet pump
800 (a)
Battery charger (20 Amp)
500
Lawn mower
1200
Belt sander (3")
1000
Light bulb (100 Watt)
100
Chain saw
1200
Microwave oven
700
Circular saw (6½")
2000 (a,b)
Milk cooler
1100 (a)
Coffee maker
1800 (a,b)
Oil burner on furnace
300
Compressor (1 HP)
1400 (a,b)
Oil-fired space heater (140,000 Btu)
400
Compressor (3/4 HP)
1800 (a)
Oil-fired space heater (85,000 Btu)
225
Compressor (1/2 HP)
1400 (a)
Oil-fired space heater (30,000 Btu)
150
Curling iron
700
Oven
4500
Dishwasher
1200
Paint sprayer, Airless (1/3 HP)
600 (a)
Edge trimmer
500
Paint sprayer, Airless (handheld)
150
Electric nail gun
1200
Radio
200
Electric range (1 element)
1500
Refrigerator
600 (b)
Electric skillet
1250
Slow cooker
200
Your generator MUST BE SIZED PROPERLY to provide both the running and starting (surge) wattage of the devices you will be powering. Before using your generator, determine the running and starting wattage requirements of all the electrical devices you will be powering simultaneously. The sum of the running and starting wattages of the devices being powered must not exceed the continuous output rating of your generator. (The continuous output rating of your generator is listed in the “Specifications” section of this manual.) Note that:
Devices without electric motors such as light bulbs, radios, and televisions have the same
running and starting wattage.
Devices with electric motors such as refrigerators, compressors, and hand tools typically
require a starting wattage that is 3 to 5 times greater than the running wattage.
The running and starting wattage requirements are often listed on a device’s nameplate. If wattage
is not given on the device’s nameplate, the wattage may be calculated by multiplying the nameplate
voltage by nameplate amperage, Watts = Volts X Amps.
Example conversion to watts:
If only the running voltage is given on the nameplate for a device with an electric motor, the starting wattage can be approximated to be three to five times the running wattage.
Estimates for the running wattage requirements for common devices are listed in Table 1 below. Guidance for starting wattages is provided in the table’s footnotes.
Table 1
120 Volts X 5 Amps = 600 Watts
10
Power Load Planning and Management (cont’d)
11
Device
Running
Watts
Device
Running
Watts
Furnace fan (1/3 HP)
1200 (a)
Submersible pump (1-1/2 HP)
2800 (a)
Freezer
800 (b)
Submersible pump (1 HP)
2000 (a)
Hair dryer
1200
Submersible pump (1/2 HP)
1500 (a)
Hand drill (1")
1100
Sump pump
600 (a)
Hand drill (1/2")
875
Table saw
2000 (a)
Hand drill (3/8")
500
Television
500
Hand drill (1/4")
250
Toaster
1000
Hedge trimmer
450
Vacuum cleaner
250
Home computer
150
VCR
70
Impact wrench
500
Water Heater
3000
Weed trimmer
500
Device to be Powered
Greater of
Starting/Running Wattage
Light Bulb
75 W
Refrigerator – 18 Cu. Ft.
1600 W
Microwave
700 W
Window AC
1800 W
Sump pump (1/3 hp)
2100 W
Total
6275W
STAGGERING LOADS
(a) Hard-starting motors require 3-5 times the rated running watts (b) For extremely hard to start loads such as air conditioners and air compressors, consult the equipment dealer to
determine maximum wattage
To calculate the running and starting wattage requirements for the devices you will be powering, follow these steps:
1. Make a list of all electrical devices you will be powering at the same time with the generator.
2. List the greater of the running or starting wattage next to each device as obtained from the
devices’ nameplate or Table 1. If only the running wattage for a device with an electric motor is known, the starting wattage can be estimated to be at least 3 times the running wattage.
3. Add the wattages for all devices on your list. This total must be lower than the continuous
output rating of your generator.
Example:
In this example, the generator must have a continuous output of at least 6275 W in order to power all of the devices simultaneously.
You can increase the number of devices your generator can power by staggering the load on the generator. For example, you could alternately power your refrigerator and air conditioner for limited periods of timepowering only one of the devices at a time and never powering both at the same time.
Installation / Initial Set-Up
Steps for Installation / Initial Set-Up
1. Unpacking and delivery inspection.
2. Planning the power load to stay within the generator’s rated
capacity.
3. Setting up generator for the type of power generation you need: a. portable power source, or
b. connected to a building as a back-up power source.
4. Selecting a site for using the generator.
5. Grounding.
6. Battery installation (electric start models only).
1. Unpacking and Delivery Inspection
You should inspect the generator immediately after you receive delivery.
See the “Machine Component Identification” section of this manual for a
diagram of the generator and its components.
If you have missing or damaged components, contact Product Support at 1-800-270-0810.
2. Planning the Power Load
Plan your power load so that you do not exceed the generator’s rated capacity. See the “Power Load Planning and Management” section of this manual to review how to plan and
manage power loads for the generator.
There are a number of important steps required to set up your generator for initial use. These steps are:
Each of these steps is discussed in detail below:
12
Installation / Initial Set-Up
13
3. Set-up as either a BUILDING BACK-UP or PORTABLE Power Source
This generator is designed to provide up to 6500W of electrical power. It can supply electricity in two ways:
1. As a back up, standby power source for a building. For this application, you must arrange
for a licensed electrician to connect the generator to your building’s electrical system via the
installation of an UL-listed transfer switch. The transfer switch must be installed in accordance with building electrical code and guidelines supplied by your power company.
2. As a portable power source. You can plug appliances or tools directly into the generator’s
electrical outlets.
Specific requirements for each are given below.
Note: Regardless of whether you use your generator as a back-up power source connected to a
building or as a portable power source, you must not overload the generator. Overloading may cause serious damage to the generator and attached electrical devices.
Using as a Back-up Power Source for a Building
Contact a licensed electrician to install a UL-listed transfer switch if you
want to use your generator as a back-up power source for a building. What does a transfer switch do? It:
a) Safely connects the generator to your building’s electrical system by
isolating your generator from your utility company’s power lines,
AND
b) Connects your generator to a critical subset of your building’s circuits
that are needed for emergency power needs.
If your generator will be connected to your building’s electrical system, it MUST ALWAYS be isolated from the utility power grid with a UL-listed transfer switch installed by a licensed electrician in compliance with all applicable building and electrical codes, and in accordance with guidelines supplied by your power company.
DANGER:
A transfer switch must be installed in order to isolate your generator from the utility power grid. If your generator is NOT properly isolated from the utility system, serious hazards will arise: When your generator is running, its output will back feed into
the utility power line and transformer that are normally used to provide you with power. The transformer will step up the current to the normal line voltage. An unsuspecting utility line worker working on what he thinks is a deactivated line could be electrocuted.
If your generator is connected (running or not) when utility
power is restored, your generator will be destroyed. It could also explode or cause fire.
In addition to isolating your generator from the utility system, the transfer switch connects your generator to a limited set of circuits in your building that have been chosen as critical to operate during a power outage.
Installation / Initial Set-Up
14
The generator cannot power your entire home -- you must work with the installing electrician to determine which devices/appliances you wish to power during an outage. The electrician can help you determine which circuits and devices can be powered simultaneously without overloading the generator.
(See the previous section of this manual entitled “Power Load Planning and
Management” for more information on load application and selection.)
Using as a Portable Power Source
When using the generator as a portable power source, you can plug electric devices and appliances directly into the generator’s electrical outlets.
There are three different kinds of electrical outlets on the generator:
1. One 120/240 Volt, 30 Amp locking receptacle (NEMA L14-30R
locking receptacle compatible with L14-30P mating plug)
2. One 120 Volt, 30 Amp locking receptacle (NEMA L5-30R receptacle
compatible with NEMA L5-30P mating plug)
3. Two 120 Volt, 20 Amp duplex GFCI straight-blade receptacles
(NEMA 5-20R duplex receptacles compatible with NEMA 5-20P or 5-15P mating plugs).
(See more technical detail about these receptacles and their associated
circuit breakers in the “Machine Component Identification” section of this
manual.)
Make sure you plug each electrical device/appliance into the correct
generator outlet based on the device’s plug configuration and voltage/amperage rating. Never exceed the amperage rating of an outlet.
NEMA
5-20R
duplex
NEMA L5-30R
NEMA L14-30R
Loading...
+ 30 hidden pages