Nortec Steam Humidifiers User Manual

RESDELUX Steam Humidifiers
Installation, Operation,
Maintenance and
Troubleshooting Guide
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. This
guide to be left with equipment owner.
Form 03-58 1505691 REV. A
INSTALLATION 1
RECEIVING & UNPACKING EQUIPMENT ................................1
PRE-INSTALLATION CHECKPOINT ...................................1
HUMIDIFIER CONFIGURATION......................................1
LOCATION & MOUNTING .........................................1
HUMIDIFIERS .............................................1
STEAM DISTRIBUTOR NOZZLE (in duct location) ..........................2
STEAM HOSE INSTALLATION.....................................3
CONDENSATE HOSE (supplied)....................................3
BLOWER PACK CONNECTION ....................................3
CABINET MOUNTING THEBLOWER PACK ............................3
REMOTE MOUNTING THEBLOWER PACK ............................4
PLUMBING .................................................5
WATER SUPPLY LINE .........................................5
DRAIN LINE...............................................5
ELECTRICAL................................................6
ELECTRICAL REQUIREMENTS FOR PERMANENTLY CONNECTED RESDELUX .........6
ELECTRICAL REQUIREMENTS FOR THE CORD CONNECTED MODEL RESDELUX/C ......6
LOW VOLTAGE CONTROL WIRING AND INSTALLATION ......................6
CONTROL WIRING ........................................6
CONTROL INSTALLATION ....................................7
OPERATION 7
INTRODUCTION ..............................................7
RESDELUX OPERATION .........................................7
MANUAL CAPACITY ADJUSTMENT .................................8
OTHER POTENTIOMETERS .....................................8
MAINTENANCE 8
STEAM CYLINDER ............................................8
WHEN TO REPLACE THE STEAM CYLINDER ............................8
HOW TO REMOVE THE STEAM CYLINDER .............................9
HOW TO INSTALL THE REPLACEMENT CYLINDER ........................9
MANDATORY CLEANING OF THE DRAIN VALVE ...........................10
EXTENDED SHUTDOWN ........................................10
TROUBLESHOOTING 11
DIAGNOSTIC PROCEDURES - TROUBLESHOOTING .........................11
PROCEDURES AND TERMS USED IN DIAGNOSING .........................11
PRINCIPLE OF OPERATION .....................................12
FILL RATE ...............................................12
DRAIN TIME ..............................................12
RATED AMPERS ...........................................12
SHORT CYCLING ...........................................12
FOAMING ...............................................12
BACKPRESSURE ...........................................12
MONITORED LEG...........................................12
RESDELUX WIRING DIAGRAM .....................................13
SUGGESTED WIRING INTERFACE FOR FAN CONTROL .......................14
SPARE PARTS LIST AND EXPLODED VIEW ............................15-16
PERIODIC MAINTENANCE CHECKLIST ................................17
INSTALLATION
Wall
HUMIDIFIER CONFIGURATION
RECEIVING & UNPACKING EQUIPMENT
1. Check packing slip to ensure ALL material has been delivered.
2. All material shortages are to be reported to NORTEC within 48 hours from receipt of goods. NORTEC assumes no responsibility for any material shortages beyond this period.
3. Inspect shipping boxes for damage and note on shipping waybill accordingly.
4. After unpacking, inspect equipment for damage and if damage is found, notify the shipper promptly.
5. All NORTEC products are shipped on an F.O.B. factory basis. Any and all damage, breakage or loss claims are to be made directly to the shipping company.
PRE-INSTALLATION CHECKPOINT
1. Ensure that available voltage and phase corresponds with humidifier voltage and phase as indicated on humidifier’s nameplate label.
2. Ensure that the dedicated external disconnect switch is of sufficient size to handle the rated amps as indicated on the nameplate label. Refer to local codes.
To avoid any danger, never operate the
humidifier with a door off.
To open the door, use the key to unlock, lift door
up slightly and pull door forward.
LOCATION & MOUNTING
HUMIDIFIERS
RESDELUX Series humidifiers are designed to mount on a suitable wall or vertical surface. Do not sit on the floor due to additional clearances required for plumbing, electrical, and control access holes. The clearance dimensions shown in this manual are for reference only and are the minimum required for maintenance of the humidifier. Local and National Codes should be consulted prior to final location and installation of the humidifier. NORTEC does not accept responsibility for installation code violations.
1. Location of the humidifier should be below and
as close as possible to the steam distributor location or blower pack. Net output will be reduced as a result of heat loss through long steam hose.
2. See Figure #2 for front clearance requirements
for access during installation, maintenance and troubleshooting.
Figure #2
Clearance Requirements
3. Report any discrepancy immediately.
Figure #1
RESDELUX Series Humidifier
Condensate
Return
Steam Outlet
Nameplate
Label
Drain
Water
Supply
PowerAnd
Control
Wiring
NOTE: Localand national codes may deviate. Please consult applicable codes for clearance requirements
3. Where possible, mount humidifier at a height
convenient for servicing.
4. To mount the humidifier use two #8 screws, 2”
long, and secure into a standard 2”X4” wood stud or equivalent structure.
5. Make sure humidifier is level.
-1-
Min. 36"
Frontal
Clearance
Figure #3
Wall Mounting Detail
the duct. Remove internal insulation material if necessary. (See Figure #5).
Fasten HumidifierTo
WallUsing Screws2” long
(2) suppliedby other
Wall
0.6”
(1.6 cm)
12.1” (30.7cm)
A
6. DO NOT mount humidifier on hot surfaces.
7. DO NOT mount humidifiers in an area where freezing may occur.
8. DO NOT mount humidifiers on a vibrating surface.
10. DO NOT mount the humidifier to a duct or plenum.
STEAM DISTRIBUTOR NOZZLE (in duct location)
1. When installing the steam distribution nozzle of the RESDELUX humidifier it must be located in the supply duct at least 4 feet from any obstructions such as bends, fans, filters, etc. to prevent wetting (see figure #4).
Figure #4
Steam Distributor Nozzle in Duct Location
Figure #5
Steam Distribution Nozzle Mounting Arrangement
3. When the steam distribution nozzle is located above the top surface of the humidifier: The
nozzle must be at least 1 ft (305 mm) above the top surface of the humidifier. Locate the steam hose so that it slopes at an angle of at least 20° (Figure #6).
Figure #6
Steam Plumbing Arrangement Above Humidifier
min. 2º min. 10º
min. 10º
12” min. (300 mm)
Rmin.
12” (300 mm)
12” (300 mm)
Min. 12”
2. The steam distribution nozzle can be mounted in the bottom wall or on the vertical walls of the duct. If the duct wall is more than 3/4" (20 mm) thick, the nozzle will have to be mounted from the inside of
6” min (150 mm)
To be 2” (50mm) longer then duct static pressure or minimum.
NHB, NHP, NHMC, RESDELUX ONLY
4. Steam distribution nozzle below top surface of humidifier: The steam hose must first rise to the
minimum height of 1 ft (305 mm) above the top surface of the humidifier and thereafter slope a
minimum 5° in a uniform manner toward the nozzle. A separate drain line must be provided for condensate that collects at the steam distribution nozzle (Figure #7).
-2-
Nortec Humidifier
Figure #7
Avoid W
Steam Plumbing Arrangement Below Humidifier
min. 2º
min. 10º
3. Avoid condensate traps in the hose, see Figure #8.
4. Use wall clips (p/n 158-5001) to support the steam and condensate hoses and maintain 1” clearance from the wall. The connection can also be made with ¾” copper pipe with 1” thermal
insulation rated for 215°F (101°C).
To be 2” (50mm) longer then duct static pressure or minimum.
min. 20 %
m
6
12” (300 mm)
min. 10º
12” min. (300 mm)
)
m
m
0
(15
in
m
6
min. 2º
min. 20 %
12” min. (300 mm)
)
m
m
0
5
(1
in
Nortec Humidifiers
All Models
12” (300 mm)
Rmin.
Nortec Humidifiers
0
5
(1
in
m
6
min. 10º
All Models
)
m
m
12” (300 mm)
12” (300 mm)
STEAM HOSE INSTALLATION
1. The length of the steam hose must not exceed 4’ (1.2m).
CONDENSATE HOSE (supplied)
Under normal circumstances, when the steam distribution nozzle is above the top surface of the humidifier, the condensate hose is routed back to the top of the humidifier and fed through the opening provided to the fill cup. Cut the ends diagonally and simply insert ½" in the appropriate hole in the top of the humidifier. Install a 3/8” copper tubing trap at the lowest point in the condensate system. Connect to the hose with a clamp Figure #6.
BLOWER PACK CONNECTION
The RESDELUX humidifier can be purchased with an optional blower pack for direct room humidification. The blower pack is field installed on the RESDELUX humidifier cabinet or located remote from the RESDELUX humidifier.
The blower pack is powered directly from the RESDELUX control board. It cannot be powered separately.
On a call for humidity, blower fans are powered and remain powered for about two minutes after steam production is interrupted.
Cabinet Mounting of the Blower Pack
2. It must not be restricted in any way (i.e. - a kink resulting from a short radius bend).
Figure #8
Steam Hose Routing
Avoid kinks
aterTraps
Gentle Sweeping Turns
Proper Slope
The RESDELUX blower pack comes with a basic hardware kit. The kit contains all the hardware required to cabinet mount the blower pack.
NOTE: Mounting of the blower pack must be performed before the RESDELUX humidifier is installed and wired.
1. Remove the RESDELUX humidifier and blower
pack from their shipping boxes.
2. Place the RESDELUX humidifier upright on a flat
surface.
3. Remove the 7/8” knockout on the top of the
RESDELUX humidifier. There are two knockouts, select the one closest to the large opening.
-3-
4. Put the power leads from the blower pack through
S
this opening as you position the blower pack on top of the RESDELUX humidifier
5. Push the blower pack forward until the locating tabs on the bottom of the blower pack with slots in the top of the RESDELUX push forward to engage.
6. Use two Phillips screws with star washers in the Blower Pack screw support tabs to secure to the RESDELUX unit.
7. Remove the front door and service cover from the RESDELUX humidifier.
8. Connect the power leads for the blower pack to terminal P7 on the RESDELUX control board located next to the capacity adjustment potentiometer.
9. Use the short piece of steam hose and hose clamps supplied with the basic hardware kit to connect the steam cylinder to the blower pack steam distributor.
Installation of the blower pack is now complete. For instructions on mounting the RESDELUX humidifier please see the location and mounting section.
Figure #9
Blower Pack Cabinet Assembly
switched off at the electrical panel, or that it is unplugged (RESDELUX/C).
3. Find a suitable location for mounting the remote blower pack. The surface should be flat with adequate clearances for the top, side, and front:
Table #1
Clearances of Remote Mounted Blower Pack
Minimum Ceiling
Clearance
inches (cm)
Minimum Side
Clearance
inches (cm)
Minimum frontal
Clearance
inches (cm)
18” (45) 18” (45) 60” (150)
4. Minimum slope of steam hose is 20°. Steam lines longer than 5 ft require condensate trap installation (see Figure #6).
5. RESDELUX blower pack has two teardrop (or keyhole) openings on the back of the cabinet for mounting purposes. They are located 8 ¼” apart, and 1” from the top of the blower pack cabinet.
6. Measure the screw locations and use two #8 screws, 2” long. The screws should be anchored in a standard 2” x 4” wood stud or equivalent to ensure adequate support of the blower pack and connecting steam hose.
7. Remove the 7/8” knockout on the top of the RESDELUX humidifier and insert the closed finger grommet into the opening.
Remote Mounting of the Blower Pack
1. The remote mounted blower pack should be located at least 7’ off the floor to prevent the discharged steam from coming in contact with pedestrian traffic or any obstruction.
2. When installing the remote blower pack, ensure the primary voltage to the RESDELUX has been
8. Put the power leads from the blower pack through this opening. If the wire leads are not long enough field splice the additional requirement, or get a wire extension kit (P/N 1502326) available from NORTEC.
Figure #10
Steam Absorption Distances
team absorption space size in inchesfor ambient humidity 30% RH, room temperature and selected steam outputs of RESDELUX humidifier.
H
W
F
0”
Steam Output F W H
4 lbs/hr 36" 12" 12"
6 lbs/hr 42" 16" 18"
8 lbs/hr 48" 18" 18"
-4-