Nortec M3RL, M7RL Installation Instructions Manual

Field Replacement Furnace Vent Transition Kit
INSTALLATION INSTRUCTIONS
For M3RL / M7RL Series Furnaces
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes. Safety markings designate a degree or level of seriousness and should not be ignored. A WARNING Indicates a potentially hazardous situation that if not avoided, could result in personal injury or death.
WARNING:
This kit must be installed by a qualified service technician in accordance with these instructions and all codes having jurisdiction. Failure to follow these instructions could result in serious injury, property damage, or death.
These instructions are primarily intended to assist qualified individuals experienced in the proper vent and combustion intake pipe installations of this appliance. Some local codes require licensed installation/service personnel for the installation of this type of equipment. The qualified service technician performing this work assumes responsibility for this furnace installation.
ABOUT THE VENT TRANSITION KIT
This kit is to be used for field replacement of a non-condensing M3RL / M7RL series furnace in manufactured housing. It may be used at elevations up to 8,000 feet above sea level. M3RL / M7RL series furnaces are condensing gas furnaces and must be vented with PVC or equivalent pipe to prevent vent corrosion. Using the replacement chase assembly and vent caps in this kit, you may easily install the vent and combustion air intake pipes for the new furnace. Before you begin the installation process, make sure your kit contains all the items listed in Table 1.
Removing Unnecessary Parts from the Old Roof Jack
NOTE: Disassembly instructions may vary depending upon
the age and design of the roof jack. See Figure 1.
1. Disassemble the top roof jack by removing the screws connecting it to the upper combustion air intake pipe.
2. Remove brackets from the combustion air intake upper pipe. NOTE: The brackets are fastened with 1/8” pop rivets and can be removed by drilling the rivets with a 1/8” drill bit.
3. Remove the inner and outer flue pipes (6” diameter) from the roof jack.
Installing the Vent & Combustion Air Intake Pipe
(After the M3RL / M7RL furnace is set in place)
1. Refer to Table 2 and choose proper vent pipe material.
2. Install 2” rubber couplings on the furnace pipes and assemble 90º SPIG x HUB elbow (large radius). See Figure 2.
3. Place bottom and top replacement caps on the roof jack. DO NOT screw the caps down at this time.
4. Cut 2” plastic pipes to length and route the vent and combustion air intake pipes through the replacement caps. NOTE: The maximum height from the top of the furnace to the top of the flue pipe must be no longer than 15 feet. See Figure 2.
IMPORTANT INFORMATION:
• Ventandcombustionairpipeandttingsmustbeone
of the materials listed below and must conform to the indicated ANSI/ASTM standards.
• CementandprimermustconformtoATSMStandard
D2564 for PVC and Standard D2235 for ABS. When joining PVC piping to ABS, use PVC solvent cement. In Canada, cements, cleaners, or primers must be certified as a system to ULC S636.
• Before permanentlyinstallingPVC components,itis
recommended you dry-fit them first to ensure proper fit and alignment with other vent pipes.
INSTALLING THE KIT
2. Replace the existing furnace with the new M3RL / M7RL furnace. Refer to the the installation instructions supplied with the furnace for additional information.
KIT CONTENTS
Replacement Vent Caps ...................................... Qty: 2
2" Rubber Couplings ............................................Qty: 2
2” Diameter Clamps ............................................. Qty: 4
90° Street Elbows ................................................ Qty: 2
#10 Sheet Metal Screws ......................................Qty: 6
Instruction sheet .................................................. Qty: 1
Table 1. Kit Contents
Materials Standards
Schedule 40PVC ........................................ D1785
PVC-DWV ................................................... D2665
SDR-21* & SDR-26* ................................... D2241
ABS-DWV ................................................... D2661
Schedule 40 ABS ....................................... F628
Foam/Cellular Core PVC ............................ F891
5. Permanently bond all PVC components together using appropriate primer and cement.
6. Screw the top & the bottom replacement caps to the outer pipes. NOTE: Two or more screws must be used on each cap.
7. Tighten the upper hose clamps on the 2” rubber couplings.
8. Secure the combustion air intake pipe to the lower combustion air intake pipe at the bottom of the upper pipe using at least two screws.
9. Seal around the two pipes on the top and bottom replacement caps with silicone sealant.
Top Roof Jack Assy
Screws
Roof Flashing
Bracket
Lower Combustion Air Intake Pipe
Figure 1. Typical Existing Roof Jack
Seal With
Silicone Sealant
Replacement Cap
Lower Vent Chase Pipe
2" X 90o Elbow - Large
Radius Hub X Hub
(Both Sides)
2" X 90o Elbow - Large
Radius Spig X Hub
(Both Sides)
Screw
Roof
Flashing
Screw
Bracket Rivets
Outer Flue Pipe Assy
Upper Combustion Air Intake Pipe
Bracket
5" to 13"
10" Min.
1" Min.
Upper Vent Chase Pipe
(8" Dia.)
Add 2 or More Screws Thru
Upper & Lower Pipes to
Prevent Telescoping
above roof
or expected
snow level
Roof
Replacement Cap
Seal With Silicone Sealant
8" Max.
2" X 90o Elbow
Large Radius
Hub x Hub 2 Req.
12” Min.
15' Max.
2" Dia. Rubber
(Both Sides)
Figure 2. Vent & Combustion Air Intake Pipe Installation
Specifications & illustrations subject to change without notice or incurring obligations (05/15). O’Fallon, MO, © Nortek Global HVAC LLC 2015. All Rights Reserved.
Furnace
Coupling
7093520 (Replaces 708300B)
Loading...