Nortec LINKS XPS MH User Manual

Important: Read and save these instructions. This guide to be left with equipment.
2559106-D | 10 OCT 2014
LINKS XPS
MH
Installation and Operation Manual
Includes installation, operation maintenance and troubleshooting information for your MHTC Evaporative Media humidifier
INSTALLATION DATE (MM/DD/YYYY)
MODEL #
SERIAL #
CYLINDER #
Thank you for choosing NORTEC.
Proprietary Notice
This document and the information disclosed herein are proprietary data of NORTEC HUMIDITY LTD. Neither this document nor the information contained herein shall be reproduced used, or disclosed to others without the written authorization of NORTEC HUMIDITY LTD., except to the extent required for installation or maintenance of recipient’s equipment. All references to the NORTEC name should be taken as referring to NORTEC HUMIDITY LTD.
Liability Notice
NORTEC does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by NORTEC.
Copyright Notice
Copyright 2012, NORTEC HUMIDITY LTD. All rights reserved.
Contents
3 Multi Unit Systems
4 Installing Links XPS into the Control Cabinet
4 Mounting the Links XPS Assembly
7 Internal Wiring Connections
15 Configuring the Humidifiers
17 Wiring
19 Gateway Configuration
21 Changing Baud Rate (BACnet MSTP, Johnson N2, LonWorks)
23 Changing the IP Address (BACnet IP)
27 Network Integration
30 BACnet Pics and Bibs
30 Variable Definition
43 Start-up Checklist
44 Troubleshooting
44 Indicator Lights
50 Wiring Diagrams
Protocol
BACnet MS/TP
BACnet / IP
Johnson N2
LonWorks
The MHTC Nortec Links XPS Option allows for the integration of a MHTC Series humidifier within a BACnet, Johnson N2 or LonWorks network. This option features a gateway that has the capability of converting information from the host Modbus protocol to a specified secondary protocol.
The following protocol options are available, and must be specified at time of order:
Table 1: Protocol Options
Multi-Unit Systems (“Master/Slave”)
Up to 8 humidifiers can be chained and monitored through a single Links XPS package. In this configuration, the unit with the Links XPS package is designated the “Master Unit”, while the remaining 7 humidifiers are configured as “Slaves”. The master unit is connected to the Building Management Systems (BMS). Each unit is separately addressed, it is possible to monitor and control each unit individually.
Different networking configurations may be achieved depending on the type of network being used. One networking example could have a Gateway installed inside the lead unit, which could then be daisy-chained to successive units. In turn, the lead unit would connect to a Building Management System (BMS) network via a shielded, twisted-pair connection. Please see wiring section for additional detail. A second example could have a series of units directly connected to an Ethernet network. This is only possible for BACnet communication and is essentially referred to as a BACnet/IP configuration.
Links XPS for MHTC | 2
Installing Links XPS into the Control Cabinet
If the Links XPS package was included with the original unit order, the necessary hardware will have been factory mounted and wired into the MHTC control cabinet. In this case, please skip ahead to the Wiring section for information on how to complete connections to the building automation system.
If Links XPS is being retrofit, or added to an existing MHTC unit in the field, follow the steps below prior to connecting wiring to the building automation system.
Mounting the Links XPS Assembly
Caution: Disconnect electrical power from humidifier before performing work inside control cabinet.
Locate the MHTC control panel and turn the power switch to the off position. Ensure that the power is also turned off at the breaker panel to prevent electrical shock. Open the control cabinet by loosening the screws on the on right side of the cabinet and sliding the brass lock clip out of the way.
MHTC ReFlow Models
1 Using the 4 plastic standoffs and plastic screws provided, attach the Links XPS module to
the steel back plate in the location shown in Figures 1and 2.
2 Secure the XPS transformer into the location shown in Figures 1 and 2. Use the two #6-32
thread cutting screws provided to secure the transformer in place.
3 Install the XPS Terminal strip onto the DIN rail at the bottom of the control cabinet as shown
in Figure 1. It may be necessary to remove one or both of the rail locks and shift the entire control terminal strip over to accommodate the XPS terminal strip.
Note: The exact location the XPS transformer may vary depending on the revision of back plate. Also, units produced before August 2011 may not have the holes for the XPS module and transformer. These models will require new holes to be drilled during installation.
3 | Links XPS for MHTC
Figure 1: Component Identification
Figure 2: Component Hole Location
Links XPS for MHTC | 4
MHTC Flow Models:
1 On MHTC Flow models, Links XPS replaces the remote fault relay board. Remove the
remote fault relay board indicated in Figure 3 and disconnect the cable.
Underneath the remote fault relay board, the 4 holes for the XPS module and two holes for the XPS transformer should be visible. Depending on the revision of the backplate these holes may be in different configurations or may not be present at all. In the case of the
latter, drill 4x ¼” holes to accommodate the XPS module. Subsequently drill 2x 9/64” holes
to accommodate the XPS transformer.
2 Using the 4 plastic standoffs and plastic screws provided, attach the Links XPS module to
the steel back plate.
3 Secure the XPS transformer using the two #6-32 thread cutting screws. 4 Install the XPS Terminal strip onto the DIN rail at the bottom of the control cabinet as shown
in Figure 1. It may be necessary to remove one or both of the rail locks and shift the entire control terminal strip over to accommodate the XPS terminal strip.
5 | Links XPS for MHTC
Figure 3: MHTC Flow Control Cabinet
Links XPS for MHTC | 6
Internal Wiring Connections
1 Connect the two black wires from the Links XPS transformer to the terminal 21 and 22 on
the MHTC control panel as shown in Figure 4. These wires are not polarity sensitive.
7 | Links XPS for MHTC
Figure 4: Transformer Power Connections
2 Identify the Modbus and Building Automation System ends on the XPS module.
Figure 5: Communication Ports XPS Module
3 Connect the two white wires from the transformer to the power terminals on the Modbus end of XPS module as shown in Figure 5. Also, connect one of the two short grey 3-wire cables into the +, -, and GND terminals on the XPS module as shown in Figure 5.
Links XPS for MHTC | 8
Figure 6: Links XPS Lonworks Module Terminals
4 Connect the other end of the short grey 3-wire cable from step 3 into the Net+, Net-, and GND terminals on the DIN rail. The red cable should be connected to the Net + terminal, the black to the Net - terminal, and grey/bare to the GND terminal. Refer to Figure 6.
9 | Links XPS for MHTC
Figure 7: Communication Connections
5 Locate the long grey 3-wire cable with the RJ-45 plug on one end. Connect the wire end of this cable into the Net+, Net -, and GND terminals used in step 4. The red cable should be connected to the Net + terminal, the black to the Net - terminal, and grey/bare to the GND
terminal. These wires can either be “doubled up” with the cable from step 4 or installed on the opposing side of the DIN rail. The cable, shown “doubled up”, is depicted in Figure 6.
Links XPS for MHTC | 10
6 Connect RJ-45 end of the cable in step 6 into the port on the lower end of the processor board. The processor board is mounted on the door of the control cabinet.
11 | Links XPS for MHTC
Figure 8: RJ45 Connection to Processor Board
7 Locate the remaining short 3-wire cable. Connect this cable to the Building Automation System end of the XPS module as shown in Figure 8 (N2, BACnet MSTP) or Figure 9 (LonWorks). Lonworks is not polarity sensitive.
Note: BACnet IP packages do not require this step since they use the ethernet port on the XPS module for communications.
Figure 9: Building Automation Connections (Johnson N2/ BACnet MS/TP)
Figure 10: Building Automation Connections (Lonworks)
Links XPS for MHTC | 12
Wiring diagrams are provided below for reference.
13 | Links XPS for MHTC
Figure 11: Links XPS for MHTC with BACnet MSTP or N2
Figure 12: Links XPS for MHTC with BACnet IP only
Links XPS for MHTC | 14
15 | Links XPS for MHTC
Figure 13: Links XPS for MHTC with LonWorks
Configuring the Humidifiers
The PCB processor board will need to be configured to work with the Links XPS modules. Additionally, Nortec Links XPS can connect to a maximum of 8 units from a single Links XPS gateway. If slave units are being used it is necessary to set the address of each slave module. The address should be the number the nit will have on the networked chain.
Links XPS can be used for control, monitoring, or both. To set the control mode on the humidifier, on the humidifier refer to the procedure on page 52 of the MH2 Installation and Operation Manual to enter the controls menu.
If you would like to control the humidifier directly by signal writing values over the Links XPS package set the Signal Source to Modbus. The humidifier will now look for values to be written to the humidifier.
If you would like to use an analog control signal (from a wall stat or building automation system) leave Signal Source setting to Analog and then set Hum. Control and Controlsign. to match the type of controls being used. Ensure that controls are physically wired to terminals 3 and 4 on the DIN rail terminal strip.
To set the humidifier to recognize the Links XPS package:
1 On the humidifier keypad, Press the menu button on the keypad and scroll to the User menu
using the arrow keys. Press Set to enter the User menu.
2 When prompted for a password, use the arrow keys to enter 8808 and press Set to confirm. 3 Scroll to the Modbus menu and press Set to enter the menu. 4 Set the Parity to None1. 5 Set the Modbus address of the lead unit to 1. Repeat this step for any slave humidifiers,
taking care to assign each slave unit a unique and sequential number. For example if the lead is 1, subsequent units should be 2, 3, 4, etc. Note: Ensure that no units share the same Modbus address.
6 Place the appropriate Unit Identifier label on each humidifier. These laps should match the
Modbus address for that humidifier and should be placed in a visible location.
7 Connect the slave humidifiers (if applicable) to the Nortec Links Module. A twisted pair cable
should be used so that the Net (+) terminal on the Links module should connect to the Net (+) terminal on the slave unit (NHTC). The Net (–) terminal on the module should be connected to the Net (–) terminal on the slave unit. Refer to the Links XPS wiring diagram for more information.
Links XPS for MHTC | 16
8 Ensure shield wiring matches the following pattern if distances between humidifiers is
significant (2200 ft):
Figure 14: Multiple Slave Humidifiers
17 | Links XPS for MHTC
Protocol
Signal
Type Polarity
Recommended
Cable
Maximum
Recommended Distance
from Nortec Module
A
B
BACnet MS/TP
EIA-485,
2-wire
Net +
Net -
18-24 AWG
Shielded, Twisted
Pair
120  Impedance
2300 ft at 9.6 kbps
2000 ft at 38.4 kbps
Johnson N2
LonWorks
FTT-10, 2-
wire
Tx Rx
18-24 AWG
Twisted Pair
120  Impedance
Should not exceed 50 ft.
BACnet/IP
LAN
standard
N/A
N/A
CAT.5E cable with
RJ-45 termination
Depends on cable
manufacturer
Wiring
BACnet MS/TP, Johnson N2, and LonWorks
Links XPS is pre-installed and factory wired. Connections must be made between the master humidifier and the BMS, and the master humidifier and any slaves that may be present.
Up to 8 units (1 master, 7 slaves) may be connected to a BMS through a single gateway in the master unit. The units are daisy chained via the Links XPS terminal strip. The wire shield should only be connected at one end per pair of units when “daisy chaining”.
Table 2 refers to the recommended wire types and maximum recommended lengths from the Nortec Links XPS module to the Building Management system. Communication between the humidifiers and Nortec Links XPS will occur via a EIA-485 signal type. Nortec recommends using a 18-24 AWG shielded, 120 twisted pair wire between the lead humidifier and each of the slave humidifiers. Total cable length runs between the Nortec Links XPS module and the furthest slave humidifier should not exceed 2,000 feet. Signal boosters or repeaters may be necessary for longer wire runs or where electrical noise interference is prevalent.
Table 2: Recommended Wire Types and Lengths
Links XPS for MHTC | 18
Loading...
+ 47 hidden pages