Norlake UF202 Installation Manual

UNDERCOUNTER FREEZERS
Installation, Operation and Maintenance Instructions
INSPECTION
When the equipment is received, all items should be carefully checked against the bill of lading to insure all crates and cartons have been received. All units should be inspected for concealed damage by uncrating the units immediately. If any damage is found, it should be reported to the carrier at once and a claim should be filed with the carrier. This equipment has been inspected and tested in the manufacturing facility and has been crated in accordance with transportation rules and guidelines. Manufacturer is not responsible for freight loss or damage.
INSTALLATION
GENERAL
After the unit crate and base have been removed, locate the legs or casters found in the interior of the cabinet. Attach the legs or casters to the unit base by screwing them into the same threaded fittings that were used to secure the crate base to the cabinet. Insure that they are screwed all the way into the base.
If for some reason the doors are not squared up on the cabinet, the doors can be adjusted. Opening the door(s) and loosening the screws that hold both the top and bottom hinges to the cabinet can accomplish this. After adjusting the door so that it is aligned correctly, tighten the screws to securely hold the hinges in place.
LOCATION
The refrigeration system located at the bottom of the cabinet requires free air access for proper operation. Important: The cabinet may be enclosed on two sides, however, there must be a minimum four inch clearance from the back of the cabinet to a wall, and from the bottom of the cabinet to the floor. This model cannot be operated without the legs or casters in place, and the bottom of the cabinet cannot be enclosed. The cabinet should be level when it is placed in its permanent location.
ELECTRICAL
Check the proposed outlet to be used to insure that the voltage, phase and current carrying capacity of the circuit from the electrical panel correspond to the requirements of the cabinet. Never use an extension cord. All inter wiring between the electrical panel and the unit must be done in accordance with the National Electric Code and all state and local codes. See the Serial Tag for all pertinent electrical information.
Observe all Warning Labels. Disconnect power supply when servicing equipment to eliminate injury from electrical shock or moving parts.
1 4/09 110072
OPERATION
FORCED AIR UNIT COOLER MODELS
The undercounter series of freezers employ a unit cooler evaporator located inside the cabinet as the heat-removing source. Through the refrigeration process, heat is captured in the evaporator, transferred to the condensing unit located at the bottom of the cabinet, and expelled to the surrounding outside air. It is extremely important to maintain the minimum four-inch clearance as described in this manual under “Location” for the refrigeration process to function properly. The cabinet cannot be operated without the legs or casters installed.
After shutting the door on these freezer models, a short amount of time must be allowed before the door can be reopened. This is due to the tight seal maintained between the door and the cabinet. Waiting a few moments for the pressure to equalize permits the door to be opened easily.
With this freezer unit, a positive defrost is required to remove frost from the coil. This is accomplished by energizing heaters positioned on the coil surface. The time clock, refer to Figure 1, is factory set to allow four defrosts per day. Note: Setting the correct time of day will be required
to maintain these defrost periods.
When the preset defrost time is reached, the time clock automatically terminates the refrigeration process by turning off the condensing unit and unit cooler fan motors, and energizes the defrost heaters. As the coil temperature increases, the frost begins to melt producing water that runs down the coil to the unit cooler drain pan and exits through the drain tube to the vaporizer. After all the frost has been removed and the coil temperature reaches approximately 50˚F, the defrost is terminated through the action of the defrost termination control located on the unit cooler, and the refrigeration process resumes. In order to insure that any excess water remaining on the coil is not sprayed into the cabinet interior, and all heat generated by the defrost is removed, the unit cooler
fans will not operate until the coil temperature reaches approximately 25˚F. ADJUSTMENTS
The timer switch is located behind the lower front panel. Remove the retainer screw and move the time forward to allow for adjustment.
1. Time clock adjustments: Setting the correct time of day – To set the correct time of day, simply rotate the small inner-dial counterclockwise until the correct time of day on the large dial is opposite the “time” indicator. In referring to the drawing of the time clock, the correct time of day shown is 8:00 a.m.
Number of defrosts per day – The time is factory set to defrost the evaporator at 2:00 a.m., 8:00 a.m., 2:00 p.m., and at 8:00 p.m. The four settings should provide adequate defrosting for even the most heavily used system. If more defrosts are required, remove a knurled slotted screw from the holder, insert the screw into the time slot on the large dial where a defrost is desired, and tighten. Insure that an equal time exists between each defrost pin. If experience shows that the four set defrost periods are more than necessary, one or more of the knurled setscrews may be removed. At least one of the knurled setscrews must be located on the large lower dial
at all times.
Fail Safe Feature – On the small, upper dial there is a pointer that is used to set a 100% fail­safe feature. The fail-safe of the timer is factory set at 30 minutes, indicating that the system will revert to cooling thirty minutes after a normal defrost cycle began should a malfunction occur.
2 4/09 110072
Loading...
+ 2 hidden pages