Norlake OMC-082 Installation Manual

MILK COOLERS
Installation, Operation and
Maintenance Instructions
INSPECTION
When the equipment is received, all items should be carefully checked against the bill of lading to insure all crates and cartons have been received. All units should be inspected for concealed damage by uncrating the units immediately. If any damage is found, it should be reported to the carrier at once, and a claim should be filed with the carrier. This equipment has been inspected, tested and has been crated in accordance with transportation rules and guidelines. Manufacturer is not responsible for freight loss or damage.
INSTALLATION
GENERAL
After the unit crate and base have been removed, locate the casters found in the interior of the cabinet. Attach the casters to the unit base by screwing them into the same threaded fittings that were used to secure the crate base to the cabinet. Insure that the casters are screwed all the way into the base.
LOCATION
The self contained refrigeration system located at the bottom of the cabinet requires free air access for proper operation. The back of the cabinet may be positioned against a wall, however, there must be a minimum four inch clearance between the sides and a wall. These guidelines must be followed for cabinets with or without casters. A cabinet that will sit directly on the floor without casters should be leveled when it is placed in its permanent location. If casters are not used, it is required by NSF that the cabinet be sealed to the floor with an approved sealant such as Dow Corning #732 silicone.
8/04 127575
Table 1 - Physical Specifications
Unit Exterior Dimensions Refrigerant
OMC-082 35" x 34" x 44" See Serial Tag DOMC-084 35" x 35" x 44" See Serial Tag OMC-122 49" x 34" x 44" See Serial Tag DOMC-124 49" x 35" x 44" See Serial Tag OMC-162 63" x 34" x 44" See Serial Tag DOMC-164 63" x 35" x 44" See Serial Tag SMC-122 48" x 33-1/2" x 43" See Serial Tag SMC-162 63" x 33-1/2" x 43" See Serial Tag
* Note: Height dimension includes standard casters.
Model Width x Depth x Height* Type/Amt. (Oz)
ELECTRICAL
Check the proposed outlet to be used to insure that the voltage, phase, and current carrying capacity of the circuit from the electrical panel correspond to the requirements of the cabinet. NEVER use an extension cord to power any unit. All inter wiring between the electrical panel and the unit must be done in accordance with the National Electric Code and all state and local codes. Refer to Table 2 and the Serial Tag for all pertinent electrical information.
Observe all Warning Labels. Disconnect power supply to eliminate injury from electrical shock or moving parts when servicing equipment.
Table 2 - Electrical Data
Unit Type of
All Models Cord 115/60/1
Model Connection Volt/Hz/Ph
GENERAL OPERATION
The milk coolers are cooled entirely by convection as a result of copper coils completely encircling the perimeter of the storage compartment. During the refrigeration process, heat is removed through the evaporator tubing and expelled through the condensing unit. It is important that the flow of air through the side louvers is not restricted in order to ensure the condensing unit operates properly. Under normal operating conditions, any frost that might accumulate on the walls during the "on" cycle of the condensing unit may melt during the "off" cycle. Drains are installed in all milk coolers to accommodate melting frost.
The refrigeration system on this cabinet uses a temperature thermostat that senses the cut­in and cut-out temperatures of the cold wall evaporator coil. The temperature can be adjusted by turning the thermostat control knob which is located behind the louvered side panel.
2
Loading...
+ 2 hidden pages