Noritz America PVC-2CT, PVC-3CT Installation Manual

Parts
Shape
PVC Concentric
Termination
Bird Screen
Installation Manual
Installation Guide
2” & 3” PVC Concentric Termination
Model: PVC-2CT & PVC-3CT
WARNING: If the Information in this manual is not followed exactly, a fire,
explosion or carbon monoxide poisoning may result causing property damage, personal injury or death.
1
Rev. 04/17
Item
Pipe & Fitting Material
United States
Canada
Exhaust
Vent/Air
Intake
Schedule 40 PVC
ANSI/ASTM D1785
CSA B137.3
PVC‐DWV
ANSI/ASTM D2665
CSA B181.2
Schedule 40 CPVC
ANSI/ASTM F441
CSA B137.3
Pipe
Cement/
Primer
PVC
ANSI/ASTM D2564
ULC S636 Certified
Materials Only
CPVC
ANSI/ASTM F493
Note: 1. Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenylsulfone) in non-metallic venting system is prohibited.
2. Canada exhaust vent with exception of fresh air intake must be
certified ULC S636 materials only.
This manual covers the installation of the Noritz 2” & 3” PVC Concentric Vent Termination Model name PVC-2CT & PVC-3CT for all Noritz condensing tankless water heaters that utilities schedule 40 PVC for venting. Read these instructions completely before attempting installation.
Parts/Tools Required:
2” or 3” PVC Pipe and Fittings – Schedule 40 PVC/CPVC
PVC/CPVC Primer
PVC/CPVC Solvent Cement
Stainless Steel Screw / Screwdriver (optional)
NOTE: All pipe, fittings, primer, and solvent cement MUST conform to ANSI and ASTM standards. Refer to table 1 below for approved piping materials.
TABLE 1: Pipe and Fitting Specifications
2
Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of CSA B149.1 code. Vent systems must be composed of pipe, fittings, cements, and primers listed to ULC S636. This concentric termination kit has been certified to ULC S636 for use with those IPEX PVC vent components which have been certified to this standard. In Canada, the primer and cement must be of the same manufacturer as the vent system; do not mix primers and cements from one manufacturer with a vent system from a different manufacturer. Follow the manufacturer’s instructions in the use of primer and cement and never use primer or cement beyond its expiration date.
The safe operation, as defined by ULC S636, of the vent system and this termination kit is based on following these installation instructions, the vent system manufacturer’s installation instructions, and proper use of primer and cement. Acceptability under Canadian standard CSA B149.1 is dependent upon full compliance with all installation instructions. Under this standard, it is recommended that the vent system be checked once a year by qualified service personnel. The authority having jurisdiction (gas inspection authority, municipal building department, fire department, etc.) Should be consulted before installation to determine the need to obtain a permit.
3
Loading...
+ 6 hidden pages