5. Installing temperature sensor on recirculation system
The sensor should be installed as close to the return connection of the unit as possible in order
to measure the return temperature accurately.
1) Open the cover of temperature sensor package. See Figure 3.
6. Setting on the control panel
7. How to Use
1) Turn the power off on the remote.
2) Press and hold the 'Function Button' to enter
'Installer Mode', '[1:RC]' will be displayed.
3) Press the 'Dial Button' so 'oFF' is ashing. (Default
setting is 'oFF' and recirculation function is not
activated.)
4) Turn the 'Dial Button' clockwise so 'on' is ashing.
(This will active the recirculation function.)
5) Press the 'Dial Button' to store the current setting
mode and return back to ‘Installer Mode’.
6) Turn the 'Dial Button' to '[2:RM]' then press the 'Dial
Button' to save the setting.
7) Turn the 'Dial Button' to '[tt24]' (On Demand
Recirculation Mode) then press the 'Dial Button' to
save the setting.
Note> ① '[tt24]' (On Demand Recirculation Mode)
cannot be accepted if the Temperature
Sensor is not connected to the terminal
block.
②
You can nd ' ' icon on the display
panel properly setting and connection the
Temperature Sensor.
1) Before hot water is required, press any of the push button switches.
2) Pump will begin to circulate and prime the lines with hot water. The pump will continue to
run until water reaches the most remote xture.
Note> The pump run time and delivery time are determined by water pipe distance and
size. Longer runs will result in longer run times.
3) Pump will shut down automatically once hot water is available.
4) Do not repeatedly press the push button switch.
To activate the function, follow the procedure below.
Water
Heater
Return Line
Cold Water Line
Push
Button
Switch
#3
Push
Button
Switch
#1
Push
Button
Switch
#2
Hot Water Line
Figure 3
Figure 5
Figure 4
Figure 6
2) Connect cables to terminal block. See Figure 4.
3) Close the cover. See Figure 5.
4) Install the temperature sensor:
Normal recirculation control is overwritten by the following:
1. Set to External recirculation automatically.
2. Recirculation is initiated by pressing a Push Button Switch.
3. Disables automatic timer function.
4. When the temperature reaches 102°F at the Temperature Sensor, recirculation will stop.
5. Or when 5 minutes have passed after pressing the Push Button Switch, recirculation will stop.
Multiple switches connected to a common branch circuit.
Note> ① You can connect up to 10 push button switches to one terminal.
②
Use cables with a diameter of AWG24 or greater.
③
Make sure that the total cable length does not exceed 328 feet (100 meters).
① Fasten to the pipe using the included stainless steel tie bands.
②
Temperature sensor must be installed in the vertical position.
③
Sensor orientation must be installed as pictured. See Figure 6.