Nordyne Q4 User Manual

Single Package Heat Pump
Installation Instructions
460 Volt Q4 Series
IMPORTANT
Read these instructions thoroughly before starting the installation. Follow all precautions and warnings contained within these instructions and on the unit.
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes require licensed installation/service per­sonnel for this type equipment. All installations must be in accordance with these instructions and with all applicable national and local codes and standards.
TABLE OF CONTENTS
OWNER INFORMATION .......................................................................................................... 3
SPECIFICATIONS..................................................................................................................... 4
SAFETY CONSIDERATIONS................................................................................................... 5
• Labels, Tags................................................................................................................ 5
• Pressures Within The System..................................................................................... 5
INSTALLATION REQUIREMENTS .......................................................................................... 5
• Equipment Check........................................................................................................ 5
• Requirements and Codes ........................................................................................... 5
• Unit Location ............................................................................................................... 5
• Air Filters ..................................................................................................................... 5
• Condensate Drain ....................................................................................................... 5
UNIT INSTALLATION............................................................................................................... 7
• Ground Level............................................................................................................... 7
• Rigging and Hoisting................................................................................................... 7
• Rooftop........................................................................................................................ 7
AIR DUCTS ............................................................................................................................... 7
• Unconditioned Spaces. ............................................................................................... 7
• Acoustical Duct Work .................................................................................................. 8
• Horizontal to Down flow Conversion........................................................................... 8
• Clearance .................................................................................................................... 8
ELECTRICAL WIRING ............................................................................................................. 8
• Line Voltage ................................................................................................................ 8
• Blower Speed.............................................................................................................. 9
• Low Voltage Connections ........................................................................................... 9
• Room Thermostat ....................................................................................................... 9
• Defrost Cycle Timer .................................................................................................... 9
START-UP AND SYSTEM CHECK ........................................................................................ 10
• Air Circulation ............................................................................................................ 10
• System Cooling ......................................................................................................... 10
• System Heating......................................................................................................... 10
UNIT MAINTENANCE............................................................................................................. 11
• Refrigerant Charging................................................................................................. 11
• Routine Maintenance ................................................................................................ 11
BLOWER TABLE .................................................................................................................... 12
CHARGING CHARTS ........................................................................................................ 13-16
ACCESSORY KIT TABLE ...................................................................................................... 17
WIRING DIAGRAM ................................................................................................................. 18
2
SECTION 1. OWNER INFORMATION
5
4
2
3
6
1
WINTER HEATING
1. Outdoor air enters the heat pump.
2. The cold, heat-transfer section (outdoor coil) extracts the heat from the air as the refrigerant evaporates from a liquid to a cold gas.
3. The refrigerant, compressed to a hot gas by the heat pump, carries the heat to the heat­transfer section (indoor coil).
4. The hot, heat-transfer section (indoor coil) releases the heat as the refrigerant condenses from a gas to a liquid.
5. The blower circulates the heat throughout the home via the supply duct.
6. The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat.
It is the sole responsibility of the homeowner to make certain that heat pump has been correctly set up and adjusted to operate properly.
5
4
3
6
2
1
SUMMER COOLING
1. Indoor air enters the return air duct.
2. The cold, heat-transfer section (indoor coil) extracts the heat from the air as the refrigerant evaporates from a liquid to a cold gas.
3. The refrigerant, drawn to the heat pump and compressed to a hot gas, carries the heat outdoors.
4. The hot, heat-transfer section (outdoor coil) releases the heat as the refrigerant condenses from a gas to a liquid.
5. The heat pump (outdoor fan) discharges the heat to the outside air.
6. The refrigerant returns to the indoor coil and evaporates once again to absorb more heat.
2. Resetting circuit breakers or other switches.
3. Adjusting or calibrating of thermostat.
NORDYNE warrants the heat pump to be free from defects in material or workmanship for a period of one year. A warranty certificate with full details is included with the heat pump. How­ever, NORDYNE will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, adjust­ments, improper operating procedure on the part of the user, etc.
Some specific examples of service calls which are not included in the limited warranty are:
1. Correcting wiring problems in the electrical circuit supplying the heat pump.
To avoid misunderstandings at a later date, carefully review these responsibilities with your dealer or service company.
The heat pump system will heat and cool your home and save your energy dollars.
During the summer, a heat pump cools a house by absorbing heat from within the house and exhausting it outdoors. During the winter, a heat pump heats a house by absorbing heat outdoors and exhausting it indoors. This is an efficient heating means because you pay for “moving” heat from outdoors to indoors, but do not pay to generate the heat.
3
OPERATING INSTRUCTIONS
To Operate Your Heat Pump For Cooling —
1. Set the thermostat system switch to COOL and the thermostat fan switch to AUTO. (See Figure 1)
2. Set the thermostat temperature selector to the desired cooling temperature. The outdoor unit fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
NOTE: If the thermostat temperature level is re­adjusted, or if the thermostat system switch is re­positioned, the outdoor unit fan and the compressor may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately six minutes following a previous operation or the interruption of the main electric power
To Operate Your Heat Pump For Heating —
1. Set the thermostat system switch for HEAT and the thermostat fan switch to AUTO. (See Figure 1)
2. Set the thermostat temperature selector to the desired heating temperature. The outdoor unit fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor temperature at the desired heating level.
FAN SWITCH
TEMPERATURE SELECTOR
Figure 1. Typical Thermostat
Defrost — During cold weather heating
operation, the outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is normal and the unit will periodically defrost itself. During the defrost cycle, the outdoor fan will stop, while the compressor continues to run and heat the outdoor coil, causing the snow and ice to melt. During defrost, there may be some steam rise from the outdoor unit as the warm coil causes some melted frost to evaporate.
SPECIFICATIONS
Model Series Q4 Single Package Heat Pumps are designed for outdoor rooftop or ground level slab installations. The units are shipped ready for horizontal duct connections and are easily converted for down flow applications.
NOTE: If the thermostat temperature level is re­adjusted, or if the thermostat system switch is re­positioned, the outdoor unit fan and the compressor may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approx-imately six minutes following a previous operation or the interruption of the main electrical power.
Emergency Heat — Some thermostats will include a system switch position termed EM HT or AUX HT, etc. This is a back-up heating mode to be used only if there is a suspected problem. With the system switch set to EM HT, etc., the compressor and outdoor fan will be locked off and supplemental heat (electric resistance heating) will be used as a source of heat. Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs.
4
Cooling
Thermostat
R
Double Throw
Double Pole Switch
To Heat Pump
Furance
Thermostat
R
To Furance
Figure 2. Thermostat Interlock System
All models are shipped from the factory with the following:
1. Zero clearance to combustibles
2. Multi-speed direct-drive blower.
3. Blower Speed Relay.
4. Horizontal or Down flow duct connections.
for the job. The unit model number is printed on the data label. All units have been securely packaged at the point of shipment. After unpacking the unit, carefully inspect it for apparent and concealed damage. Claims for damage should be filed with the carrier by the consignee.
The unit dimensions are shown in Figure 3. Optional field-installed electric heater kits are
available in 9 kw and 15 kw heating capacities. A separate installation instruction document for the electric heaters and their application accompanies this one. A two stage heat 24VAC thermostat should be used with electric heater kits installed.
SAFETY CONSIDERATIONS
It is the responsibility of the installer to ensure that the installation is made in accordance with all applicable local and national codes.
!
WARNING:
Improper installation, service, adjustment, or maintenance may cause explosion, fire, electrical shock or other hazardous conditions which may result in personal injury or property damage. Unless otherwise noted in these instructions, only factory authorized kits or accessories may be used with this product. Noncompliance may void
the units warranty.
Labels, Tags When working with this
equipment, follow all precautions in the literature, on tags, and on labels provided with the unit and/or approved field installed kits. The type of hazard and severity are described on each label or tag.
Pressures Within The System This equipment contains liquid and gaseous refrigerant under high pressure. Installation or servicing should only be performed by qualified trained personnel thoroughly familiar with this type equipment.
INSTALLATION REQUIREMENTS
Equipment Check Before beginning the
installation, verify that the unit model is correct
Requirements and Codes The installer must comply with all local codes and regulations which govern this type equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. All electrical wiring must be made in accordance with local codes and regulations and with the National Electric Code (ANSI/NFPA
70) or in Canada the Canadian Electric Code Part 1 CSA C.22.1. Air Ducts must be installed in accordance with the standards of the National Fire Protection Association “Standards for Installation of Air Conditioning and Ventilation Systems” (NFPA 90A), “Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems” (NFPA 90B), these instructions and all applicable local codes.
NFPA publications are available by writing:
National Fire Protection Association Batterymarch Park Quincy, Maine 02269
Unit Location The Q4 series heat pump is designed only for outdoor installations. Choosing the location of the unit should be based on minimizing the length of the supply and return ducts. Consideration should also be given to availability of electric power, service access, noise, and shade. Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 4 for minimum clearances to obstructions.
Air Filters A suitable air filter must be installed in the return air system. Air filter pressure drop must not exceed 0.08 inches w.c. at 300 fpm.
Condensate Drain — Condensate is removed from the unit through the 3/4" female pipe fitting located on the front side of the unit. (See Figure
5.) Install a 2 inch condensate trap in the drain line of the same size and prime with water. When connecting rigid drain line, hold the female fitting with a wrench to prevent twisting. Do not over tighten! Refer to local codes and restrictions for proper condensate disposal requirements.
5
SUPPLY
24.9 3/4" NPT Female
Drain Connector
28.7
26.0
22.4
B
1.8
1.75 Ø Power Entry (Capped)
1.25 Ø Power Entry
13.3
0.88 Ø Control Wiring Entry
13.5
A
16.0
23.512.0
Top View
CG
13.5
47.5
16.0
12.0
RETURN
C
11.2
SUPPLY RETURN
16.0
13.5
11.2
16.0
13.5
10.0 24.9
55.8
Side View Back View
Model No.
Unit
Weight
Q4SA-036 340 28.0 26.0 33.7 31.3 Q4SA-048 345 28.0 26.0 33.7 31.3 Q4SA-060 400 29.5 26.5 37.7 35.3
6
Center of Gravity Height (in inches)
AB
with base rails without base rails
C
Figure 3. Dimensions
36"
36"
72"
36"
6"
Figure 4. Minimum Clearances
UNIT INSTALLATION
Ground Level When installing the unit at
ground level, provide a concrete mounting pad separate from the building foundation. The pad must be level to insure proper condensate disposal and strong enough to support the unit’s weight. Refer to Figure 3. Make sure the slab is a minimum of 2" above the grade and in an area that drains well (See Figure 6).
Rigging and Hoisting The unit should be lifted using slings and spreader bars. The spreader bars are necessary to prevent damaging the top of the unit’s cabinet. Make sure that the lifting equipment is adequate for the load. Refer to Figure 3 for unit weights. Keep the unit in an upright position at all times.
!
WARNING:
To avoid the risk of property damage or personal injury; it is the rigger’s responsibility to insure that whatever means are used to hoist the unit are safe and adequate.
Condensate Drain
Figure 5. Condensate Drain
Rooftop For rooftop installations use the
appropriate accessory roof curb and follow all instructions included with it. Locate the unit according to local building codes and ordinances. The curb must be level to insure proper condensate drainage (See Figure 7).
The roof must be capable of handling the weight of the unit. (See Figure 3) for unit weights. Reinforce the roof if required.
AIR DUCTS
This unit is designed only for use with a supply and return duct. Air ducts should be installed in accordance with the standards of the National Fire Protection Association “Standard for Installation of Air Conditioning Systems” (NFPA 90A), “Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems” (NFPA 90B), and all applicable local codes.
Design the duct work according to methods described by the National Warm Air Heating and Air Conditioning Association (ACCA). The ducts must be properly sized not to exceed .2" w.c. pressure drop at 400 scfm per nominal ton of cooling capacity.
!
CAUTION:
All panels must be securely in place when rigging and hoisting.
The rigging must be located outside the unit’s center of gravity. Refer to Figure 3 for center of gravity locations.
Duct work should be attached directly to the unit flanges for horizontal applications. On roof curb installations the ducts must be attached to the curb hangers, not the unit.
Unconditioned Spaces All duct work passing through unconditioned space must be properly insulated to minimize duct losses and prevent condensation. Use insulation with an outer vapor barrier. Refer to local codes for insulation material requirements.
7
Acoustical Duct Work Certain installations may require the use of acoustical lining inside the supply duct work. Acoustical insulation must be in accordance with the current revision of the Sheet Metal and Air Conditioning Contractors National Association (SMACNA) application standard for duct liners. Duct lining must be UL classified batts or blankets with a fire hazard classification of FHC-25/50 or less. Fiber duct work may be used in place of internal duct liners if the fiber duct work is in accordance with the current revision of the SMACNA construction standard on fibrous glass ducts. Fibrous duct work and internal acoustical lining must be NFPA Class 1 air ducts when tested per UL Standard 181 for Class 1 ducts.
Horizontal to Down flow Conversion The unit is shipped ready for horizontal duct connections. If down flow ducts are required, the unit must be converted following the steps below for both the supply and return ducts.
1) Locate the duct cap inside the duct openings and remove the screw holding it in place.
2) Lift the cap out of the unit. (The cap can be pushed up from the bottom by reaching through the fork slot).
3) Cover the horizontal duct opening with the cap. The insulation will be on the indoor side.
4) Fasten the cover with screws and seal to prevent air leakage.
Clearance — The Q4 Series is approved for 0 inch clearance.
ELECTRICAL WIRING
General Electrical power wiring must be
made in accordance with all applicable local codes and ordinances, and with the current revision of the National Electric Code NFPA 70 or in Canada CSA C.22.1 - Canadian Electrical Code Part 1. If any of the original wire as supplied with the unit must be replaced, it must be replaced with material of the same gage and temperature rating.
Line Voltage Before proceeding with the electrical connections, make certain that the voltage, frequency, and phase of the supply source are the same as those specified on the unit rating plate. Also verify that the service provided by the utility is sufficient to handle the additional load imposed by this equipment.
!
WARNING:
To avoid the risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical power supply.
See Figure 8 or the unit wiring label for proper
high and low voltage wiring. Make all electrical connections in accordance with all applicable codes and ordinances.
Figure 6. Ground Level Installation
8
2"
Figure 7. Roof Top Installation
Use a separate branch electrical circuit for this unit. A means of electrical disconnect must be located within sight of and readily accessibility to the unit. Internally mounted circuit breakers are available as field installed options. These circuit breakers can be used as an electrical disconnect.
Provide power supply (or supplies) for the unit in accordance with the unit wiring diagram, and the unit rating plate. Connect the line-voltage leads to the corresponding terminals on the contactor (or the circuit breaker when the field installed circuit breaker kits are used) inside the control compartment. Use only copper wire for the line voltage power supply to this unit. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit and for obtaining proper grounding. Grounding may also be accomplished by using the grounding lug provided in the control box.
!
WARNING:
The unit cabinet must have and uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. This ground may consist of electrical wire or approved conduit when installed in accordance with existing national or local codes.
Blower Speed The blower speed is preset at
the factory for operation at the same speed for heating and cooling. For optimum system performance and comfort, it may be necessary to change the factory set speed. To change the blower speed:
1. Disconnect all electrical power to the unit and remove the service panel.
2. Cut the wire tie holding the motor lead bundle. See Figure 9 for detailed information on the appropriate model and speed desired.
3. If the desired heating blower speed is different than the cooling speed, remove and discard the jumper wire between terminals #6 and #4. on the blower relay. Place the desired heating blower speed lead on terminal #6 and the desired cooling blower speed lead on terminal #4 of the blower relay. Use another wire tie (field supplied) to bundle the remaining motor leads.
!
CAUTION:
To avoid personal injury or property damage, make certain that the motor leads cannot come into contact with any uninsulated metal components of the unit.
Check all factory wiring per the unit wiring diagram and inspect the factory wiring connections to be sure none loosened during shipping or installation.
Low Voltage Connections Room Thermostat Several options are avail-
able for a room thermostat depending on the accessories installed with the unit. The avail­able thermostats recommended for use with the Q4 units are listed with the accessories in Table
5. Select a thermostat which operates in con­junction with the installed accessories. The thermostat should be mounted about five feet above the ground on an inside wall. The ther­mostat should be kept away from drafts, slam­ming doors, lamps, direct sunlight, or in line with the supply air flow.
To install the thermostat:
1. Position the sub base on an inside wall and mark the mounting holes and thermostat cable openings.
2. Cut out the cable opening and route the thermostat cable from the units low voltage compartment to the thermostat location. The thermostat cable is supplied by the installer.
3. Connect the cable leads to the sub base or thermostat terminals and to the units low voltage pigtails as shown in Figure 10. A system wiring diagram is also provided on the inside of the control panel cover and in Figure 8 of these installation instructions.
4. Secure sub base or thermostat to the wall using screws provided with the thermostat.
5. If sub base is used, install the correct thermostat housing to sub base.
6. Refer to thermostat instruction sheet for complete detailed mounting information.
Defrost Cycle Timer The defrost cycle timer controls the time interval of the hot gas defrost after the defrost sensor closes. It is located in the lower left corner of the defrost control board on the low voltage side of the control box. Three
9
interval settings are available: 30 minutes, 60 minutes, and 90 minutes. Time setting selection is dependent on the climate where the unit is being installed.
Example 1. Dry climate of Southern Arizona. A 90 minute setting is recommended.
Example 2. Moist climate of Seattle, Washington. A 30 minute setting is recommended.
To set the cycle timer, place the timing pin on the defrost control board to the desired time interval post.
Verify that all exterior panels are replaced and securely fastened.
Verify that the outdoor fan turns freely.
Verify that the power supply branch circuit
overcurrent protection is sized properly.
Verify that the thermostat is wired correctly. The thermostat function switch should be set to Off and the thermostat fan switch should be set to Auto.
Start-Up Procedure
Close all electrical disconnects to energize the system.
!
WARNING:
Note: All units are shipped from the factory with
the default time setting of 30 minutes.
START UP AND SYSTEM CHECK
Pre-Start Check List
Verify that the unit is level to allow proper condensate drainage.
Verify that there is free airflow to and from the outdoor coil and that all clearance requirements are met.
Verify that the duct work is sealed to prevent air leakage.
Verify that the line voltage power leads are securely connected and the unit is properly grounded.
Verify that the low voltage wires are securely connected to the correct leads on the low voltage terminal strip.
Q4SA-048D & Q4SA-060D Blower Wiring
Blower Speed
Blower Leads Low Medium High
Red BR T3 TB T1 TB T2
Black BR T6 BR T6 BR T3
Gray BR T4 BR T4 BR T6 Blue TB T1 BR T3 BR T5
Violet TB T1 TB T2 TB T1 BR T ( ) - Blo wer Re l a y T ermin al (number) TB T( ) - T e rm inal Block T ermin al (nu m b er)
Q4SA-036D Blower Wiring
Blo w er Spe ed
Blower Leads Low Medium High
Red BR T3 TB T1 TB T2
Black BR T6 BR T6 BR T3
Gray BR T4 BR T4 BR T4
Blue TB T1 BR T3 TB T1
Violet BR T5 BR T5 BR T5
Figure 9. Motor Lead Connection
10
If the unit is equipped with a crankcase heater, allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system. This warning should be followed at initial start up and any time the power has been removed for 12 hours or longer.
Air Circulation Leave the thermostat system
switch set to Off and set the thermostat fan switch to On. The blower motor should run continuously. Check for air delivery at the register(s). Ensure that there are no obstructions at the registers or in the duct work. Set thermostat fan switch to Auto.
System Cooling
1. Set the thermostat system switch to “Cool” and the thermostat fan switch to Auto”. Gradually lower the thermostat temperature switch below room temperature and observe that the blower, compressor, and fan energize. Check that air cooler than room temperature is being discharged at the register. Listen for any unusual noises.
2. After allowing the unit to run for several minutes, set the temperature selector above room temperature. The fan and compressor cycles off with the thermostat. The blower should also stop unless fan switch is set to ON position.
System Heating Set the system thermostat switch to HEAT and set the thermostat fan switch to AUTO. Verify that the compressor, outdoor fan, and blower are energized. Check for warm air at the supply registers.
UNIT MAINTENANCE
!
CAUTION:
!
WARNING:
To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.
Refrigerant Charging The Q4 packaged heat pumps are fully charged at the factory . The system refrigerant charge can be checked and adjusted through the service ports provided in the front panel. Use only gauge lines which have a Schrader depression device present to actuate the valve. Refrigerant charging must be done by qualified personnel familiar with safe and environmentally responsible refrigerant handling procedures.
!
WARNING:
The Q4 Single Packaged Heat Pumps are shipped fully charged and ready for installation. When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be done by qualified, trained personnel thoroughly familiar with this equipment. Some local codes require licensed installation/service personnel to service this type of equipment. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.
Use care when removing parts from this unit. Personal injury can result from sharp metal edges present in all equipment of sheet metal construction.
Routine Maintenance Proper maintenance
is important to achieve optimum performance from the heat pump. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these skills, contact your dealer for maintenance. Consult your local dealer about the availability of maintenance contracts. At a minimum, routine maintenance should include the following:
1. Inspect and clean or replace air filters at the beginning of each heating and cooling season, or more frequently if required.
2. Inspect the condensate drain and outdoor coil at the beginning of each cooling season. Remove any debris. Clean the outdoor coil and louvers as necessary using a mild detergent and water. Rinse thoroughly with water.
3. Inspect the electrical connections for tightness at the beginning of each heating and cooling season. Service as necessary.
!
CAUTION:
The unit should never be operated without a filter in the return air system. Replace disposable filters with the same type and size.
11
ECONOMIZER
PLUG
1 2
3 4
Blue
5 6 7 8 9
X
(Optional,Check
W3
W2
Y2
Y1
R
G
O
E
INDOOR
THERMOSTAT
SUB-BASE
Thermostat
Instructions)
FROM
BLOWER
RELAY
C
Y
O
W2
R
E
DEFROST
BOARD
Green
ECONOMIZER
PLUG
1 2
3 4
Blue
5 6 7 8 9
THERMOSTAT
X
W3
W2
Y2
Y1
R
G
O
E
INDOOR
SUB-BASE
(Optional,Check
Thermostat
Instructions)
FROM
BLOWER
RELAY
C
Y
O
W2
R
E
DEFROST
BOARD
Green
Typical Wiring (Field Supplied)
for 1-Stage Cool, 1-Stage Heat
Typical Wiring (Field Supplied)
for 2-Stage Cool, 1-Stage Heat
Figure 10. Typical Thermostat Connection
External Static Pressure Drop - inches water column
Model Speed 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Q4SA-036 High 1600 1510 1410 1310 1200 1070 930 760
Medium 141 0 1330 1250 1150 1050 940 820 670
Low 1130 1070 1000 930 850 760 650 530
Q4SA-048 High 2200 2140 2070 2000 1930 1850 1770 1690
Medium 194 0 1890 1830 1760 1700 1630 1560 1490
Low 1560 1510 1460 1410 1360 1310 1250 1200
Q4SA-060 High 2200 2140 2070 2000 1930 1850 1770 1690
Medium 194 0 1890 1830 1760 1700 1630 1560 1490
Low 1560 1510 1460 1410 1360 1310 1250 1200
- Speed set at factory
12
Table 1. Q4 Blower Curves
Q4SA-036
Disch.
Disch.
Disch.
Heat Pump in Heating
OUTDOOR TEMPERATURE (° F)
0 102030405060
Suc.
Disch.
Disch.
Press.
Press.
Temp.
123 138
17
130 136
18
137 134
19
Table 2. Q4SA Heating Charging Charts
20 21 22 23
144 132 151 130 158 128 165 126
Suc.
Press.
Q4SA-048
0 102030405060
Suc.
Disch.
Disch.
Press.
Press.
Temp.
Press.
129 134
14
136 132
15
143 130
16
150 128
17
157 126
18
164 124
19
171 122
20
22 23 24 25 26 27 28
Suc.
20 21 22 23 24 25 26
Disch. Press.
135 138 141 136 147 134 152 132 158 130 164 128 170 126
Disch. Press.
143 135 149 133 155 131 161 129 167 127 173 125 179 123
Disch. Temp.
Disch. Temp.
Suc.
Press.
27 28 29 30 31 32 33
Suc.
Press.
25 26 27 28 29 30 31
Disch. Press.
146 138 151 136 156 134 161 132 165 130 170 128 175 126
Disch. Press.
158 135 162 133 167 131 172 129 177 127 181 125 186 123
Press.
158 137 161 135 165 133 169 131 172 129 176 127 180 125
Press.
172 136 175 134 179 132 183 130 186 128 190 126 194 124
Disch. Temp.
Disch. Temp.
Disch. Temp.
Suc.
Press.
32 33 34 35 36 37 38
OUTDOOR TEMPERATURE (° F)
Disch. Temp.
Suc.
Press.
31 32 33 34 35 36 37
Suc.
Press.
41 42 43 44 185 140 57 211 158 70 236 175 45 46 47
Suc.
Press.
39 40 41 42 199 133 54 221 138 65 243 144 43 44 45
Press.
164 149 171 146 178 143
192 137 199 134 206 132
Disch. Press.
178 141 185 138 192 136
206 130 213 127 220 124
Disch. Temp.
Disch. Temp.
Suc.
Disch.
Disch.
Press.
Press.
Temp.
190 171
54
197 167
55 56 204 162 69 229 181
58 218 153 71 243 169
225 149
59
232 144
60
Suc.
Disch.
Press.
Press.
200 152
51
207 147
52 53 214 143 64 236 150
55 228 134 66 250 137
235 129
56
242 125
57
Disch. Temp.
Suc.
Disch.
Press.
Press.
67 215 194 68 222 187
72 250 163 73 257 157
Suc.
Disch.
Press.
Press.
62 222 162 63 229 156
67 257 131 68 264 125
Disch. Temp.
Disch. Temp.
13
* Note: All pressures are listed in
psig. and all temperatures in deg. F.
Shaded Boxes indicate flooded conditionsRated Design Values. Suction Pressure will be lower than design value if indoor air
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.
Discharge temperatures greater than charted values indicates a refrigerant
undercharge.
14
Disch.
Q4SA-060
Suc.
Disch.
Press.
Press.
OUTDOOR TEMPERATURE (° F)
0 102030405060
Disch. Temp.
Suc.
Press.
Disch. Press.
Disch. Temp.
Suc.
Press.
Disch. Press.
Disch.
Temp.
Suc.
Press.
Press.
Disch. Temp.
Suc.
Press.
Disch. Press.
Disch. Temp.
Suc.
Press.
Disch. Press.
Disch. Temp.
Suc.
Press.
Disch. Press.
Disch. Temp.
Heat Pump in Heating
122 126
Table 2a. Q4SA Heating Charging Charts
12
129 124
13
136 122
14
143 120
15
150 118
16
157 116
17
164 114
18
* Note: All pressures are listed in
psig. and all temperatures in deg. F.
19 20 21 22 23 24 25
139 127 145 125 151 123 156 121 162 119 168 117 174 115
26 27 28 29 30 31
32
156 127 160 125 165 123 170 121 175 119 179 117 184 115
Shaded Boxes indicate flooded conditionsRated Design Values. Suction Pressure will be lower than design value if indoor air
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.
Discharge temperatures greater than charted values indicates a refrigerant
undercharge.
33 34 35 36 37 38 39
172 128 176 126 180 124 183 122 187 120 191 118 194 116
179 135
41
186 132
42
193 129
43 44 200 126 54 220 134 64 241 143
207 123
45
214 120
46
221 118
47
199 148
51
206 143
52 53 213 139 63 234 149
55 227 130 65 248 136
234 125
56
241 121
57
61 220 161 62 227 155
66 255 130 67 262 124
Q4SA-036
70 75 80 85 90 95 100 105 Suct. Pres.
Table 3. Q4SA Cooling Charging Charts
Q4SA-048
Suct. Pres.
Disch.
72 189 153 74 190 167 204 158 76 190 184 205 170 219 158 230 155 242 156 78 191 201 206 184 221 172 234 160 245 164 256 160 80 192 218 208 198 222 185 236 172 249 170 260 166 271 163 82 209 213 224 198 238 187 252 178 265 171 275 169 286 167 84 226 210 240 198 254 189 267 181 280 175 291 173 86 256 200 269 191 282 184 295 178 88 285 194 298 187
90 287 203 300 196 92 303 205
Disch.
68 188 122 70 191 123 204 135 72 192 140 207 139 222 137 234 146 248 152 74 192 157 208 154 224 151 239 147 252 160 266 160 76 193 174 210 168 226 164 241 160 257 164 270 166 284 167 78 211 182 227 177 243 174 259 172 274 171 288 173 302 174 80 229 190 245 185 261 183 276 181 292 180 307 180 82 263 193 279 191 294 189 310 188 84 297 199 312 197
86 299 208 315 206 88 317 215
Disch.
Pres.
Temp.
70 75 80 85 90 95 100 105
Disch.
Pres.
Temp.
Disch.
Pres.
Disch.
Pres.
Disch. Temp.
Disch. Temp.
Disch.
Pres.
Disch.
Pres.
OUTDOOR T EMPERATURE ( °F )
Disch. Temp.
Disch. Temp.
Disch.
Pres.
OUTDOOR T EMPERATURE ( °F )
Disch.
Pres.
Disch. Temp.
Disch. Temp.
Disch.
Pres.
Disch.
Pres.
Disch. Temp.
Disch. Temp.
Disch.
Pres.
Disch.
Pres.
Disch. Temp.
Disch. Temp.
Disch.
Pres.
Disch.
Pres.
Disch. Temp.
Disch. Temp.
Disch.
Pres.
Disch.
Pres.
Heat Pump in Cooling
Disch. Temp.
Disch. Temp.
15
* Note: All pressures are listed in
psig. and all temperatures in deg. F.
Shaded Boxes indicate flooded conditionsRated Design Values. Suction Pressure will be lower than design value if indoor air
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.
Discharge temperatures greater than charted values indicates a refrigerant
undercharge.
16
Q4SA-060
70 75 80 85 90 95 100 105
Suct.
Disch.
Pres.
Table 3a. Q4SA Cooling Charging Charts
Pres.
68 192 157 70 193 165 208 164 72 194 182 210 172 226 164 239 165 252 167 74 195 199 211 187 227 178 243 168 256 175 269 171 76 195 216 213 201 229 191 245 181 260 180 273 178 287 175 78 214 215 231 204 247 195 262 188 278 183 291 181 304 179 80 232 216 249 207 265 199 280 193 295 188 309 185 82 267 210 282 203 298 197 313 192 84 300 206 315 201
86 303 216 318 210 88 320 219
Disch. Temp.
Disch.
Pres.
Disch. Temp.
Disch.
Pres.
OUTDOOR T EMPERATURE ( °F )
Disch. Temp.
Disch.
Pres.
Disch. Temp.
Disch.
Pres.
Disch. Temp.
Disch.
Pres.
Disch. Temp.
Disch.
Pres.
Disch. Temp.
Disch.
Pres.
Heat Pump in Cooling
Disch. Temp.
* Note: All pressures are listed in
psig. and all temperatures in deg. F.
Shaded Boxes indicate flooded conditionsRated Design Values. Suction Pressure will be lower than design value if indoor air
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.
Discharge temperatures greater than charted values indicates a refrigerant
undercharge.
Q4 ACCESSORIES
Descripti on Part Numb er
Roof Curb (8") 547830 Roof Curb (14") 547831 Manual F resh A ir Damper 547832 Economi zer, downflow 547833 Suppl y/ret urn trans i t ion, 16" 547834 Suppl y/ret urn trans i t ion, 18" 547835 Concent ric di ffuser, flush, 16" 547836 Concent ric di ffuser, flush, 18" 547837 Concent ric di ffuser, step down 16" 547838 Concent ric di ffuser, step down 18" 547839 Mot oriz ed Fresh Ai r Damper 547840 Economi zer, horizont al (s pecial order) 547841 Power E xhaus t, downflow economi zer (s pecial order) 547842 Power E xhaus t horizontal ec onom i zer (special order) 547843 Hail guard 30x76 (s pec ial order, s ee Note 1) 547845 Hail guard 34x76 (s pec ial order, s ee Note 2) 547846 Fil ter K i t, Downflow (See N ote 1) 547887 Fil ter K i t, Downflow (See N ote 2) 547888 Fil t er Rack , Downfl ow 547885 T-s tat , HP, 2 st age htg/ 1 st age cool, auto, (" M " brand) 912931 T-s tat, HP, 2 st age ht g/ 1 s t age c ool, aut o, (" I " brand) 912929 T-s tat, HP, 2 st age ht g/ 1 s t age c ool, m anual, (" M" brand) 912932 T-s tat, HP, 2 st age ht g/ 1 s t age c ool, m anual, (" I " brand) 912930 T-s tat, A C, 2 st age ht g/ 1 stage c ool, (" T , P , F" brand) 917004 T-s tat, HP, 2 st age ht g/ 1 s t age c ool, (" T , P , F" brand) 917005 12" Fl ex duc t adapt er ki t 913811 14" Fl ex duc t adapt er ki t 913812 12" Fl ex duc t adapt er ki t & P -T rap 913813 14" Fl ex duc t adapt er ki t & P -T rap 913814 Univ ersal Hard St art K i t 912933 Low Press ure S wit c h K i t 913551 High Pressure Switch Kit 913550 Low Ambi ent K i t 913770 P-Trap Kit 913810 Outdoor Therm ostat K it 913852 Circui t B reak er Ki t -S ingle P has e 913554 Circui t B reak er Ki t -Three Phas e 913740 4-pole s ingle circ ui t adapter kit (S ingle Phase Units Only) 913350 6-pole s ingle circ ui t adapter kit (S ingle Phase Units Only) 913556
Note 1: Q4SA-036( ) Note 2: Q4SA-048( ), Q4SA-060( ), Q4SC-036( ) Note 3: Q4SC-048K, Q4SC-060K
Table 4. Field Installed Accessory Kits
17
18
Convertible Packaged Heat Pump 460 Volt Three Phase 60Hz
NNOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C.
4. For supply wire ampacities and overcurrent protection, see unit rating plate.
Figure 8. Single Phase Wiring Diagram
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
INSTALLER:
PLEASE LEAVE THESE
INSTALLATION INSTRUCTIONS
WITH THE HOMEOWNER.
F
I
I
T
E
R
D
E
A
C
S
N
E
E
B
S
A
H
T
I
O
N
C
-
U
R
I
S
I
A
H
T
A
R
R
C
O
A
G
I
R
N
M
I
-
C
N
P
O
O
N
I
T
I
D
N
A
I
R
I
S
T
L
D
Y
I
I
T
N
I
O
G
N
I
W
N
G
I
T
H
®
G
N
I
-
N
C
O
O
I
N
T
I
D
0
1
2
D
A
R
N
A
D
R
¢707885W¤
707885ASt. Louis, MO
707885A (Replaces 7078850)
Specifications and illustrations
subject to change without notice and
without incurring obligations. (6/00)
Loading...