Nordyne Q3RD, Q3RD-030K, Q3RD-036K, Q3RD-048K, Q3RD-024K Installation Manual

...
Page 1
13 SEER
Single Package Heat Pump
Single Package Heat Pump
iMPORTANT:
Read this owner information to become familiar with the capabilities and use of your
appliance. Keep this with literature on other appliances where you have easy access to it in the future, if a problem occurs, check the instructions and follow recommendations
given, if these suggestions don't eliminate your problem, call your installing contractor
iNTRODUCTiON
Your heat pump isa unique, all weather comfort- control system appliance. The basic operation
of the heating/cooling system is described and
illustrated on page 1of this man ual.The surprising fact that heat exists inair even at below-freezing temperatures is actually the basic law of physics
which the heat pump uses to provide energy saving heating comfort. At outdoor temperatures
of 47 ° Fahrenheit (or 8° Celsius), your heat
pump can deliver approximately 2 to 3 units of heat energy per each unit of electrical energy
used, as compared to a maximum of only 1 unit of heat energy produced with conventional
heating systems. During the cooling season, the heat pump reverses the flow of the heat- absorbing refrigerant to become an energy- efficient, central air conditioner.
Page 2
SECTION 1. OWNER INFORMATION
SYSTEM SWITCH
Your heat pump will heat and cool your home year round, saving your energy dollars. During
the summer, a heat pump performs like any normal air conditioner. That is, the excess heat
energy inside the home is absorbed by the
refrigerant and exhausted outside the home.
During the winter months, a heat pump performs like an air conditioner run in reverse. That is, available heat energy outside the home is
absorbed by the refrigerant and exhausted inside the home. This is an efficient heating means because you only pay for "moving" the heat from
the outdoors to the indoor area. You do not pay to generate the heat, as is the case with more
traditional furnace designs.
It is the sole responsibility of the homeowner to make certain that the heat pump has been
correctly set up and adjusted to operate properly.
The manufacturer warrants the heat pump to be free from defects in workmanship or material for
a period of one year. A warranty certificate with full details is included with the heat pump.
However, we will not be responsible for any costs found necessary to correct problems due
to improper setup, improper installation, adjustments, improper operating procedure on
the part of the user, etc.
Some specific examples of service calls which are not included in the limited warranty are:
1. Correcting wiring problems in the electrical circuit supplying the heat pump.
2. Resetting circuit breakers or other switches.
3. Adjusting or calibrating of thermostat.
FAN SWITCH
TEMPERATURE SCALES
TEMPERATURE SELECTOR
Figure 1. Typical Thermostat
NOTE: If the thermostat temperature level is re-
adjusted, or if the thermostat system switch is
re-positioned, the outdoor unit fan and the
compressor may not start immediately. A
protective timer circuit holds the compressor
and the outdoor fan off for approximately five
minutes following a previous operation or the interruption of the main electric power.
To Operate Your Heat Pump For Heating --
1. Set the thermostat system switch for HEAT and the thermostat fan switch to AUTO. (See
Figure 1)
2. Set the thermostat temperature selector to the desi red heating tem peratu re. The outdoor
unit fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor temperature at the desi red
heating level.
To avoid misunderstandings at a later date, carefully review these responsibilities with your dealer or service company.
OPERATING INSTRUCTIONS
To Operate Your Heat Pump For Cooling --
1. Set the thermostat system switch to COOL and the thermostat fan switch to AUTO. (See
Figure 1)
2. Set the thermostat temperature selector to the desired cooling temperature. The outdoor unit
fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor
temperature at the desired cooling level.
NOTE: If the thermostat temperature level is re-
adjusted, or if the thermostat system switch is
re-positioned, the outdoor unit fan and the
compressor may not start immediately. A
protective timer circuit holds the compressor
and the outdoor fan off for approximately five
minutes following a previous operation or the interruption of the main electrical power.
Emergency Heat -- Some thermostats will
include a system switch position termed EM HT orAUX HT, etc. This is a back-up heating mode to be used only if there is a suspected problem.
With the system switch set to EM HT, etc., the compressor and outdoor fan will be locked off and supplemental heat (electric resistance
Page 3
heating)will be usedas a sourceof heat. Sustaineduse of electricresistanceheat in
placeoftheheatpumpwillresultinanincrease in electricutilitycosts.
Defrost -- During cold weather heating
operation,theoutdoorunitwilldevelopacoating ofsnowandiceontheheattransfercoil.Thisis
normalandtheunitwillperiodicallydefrostitself.
Duringthedefrostcycle,theoutdoorfanwill
stop,whilethecompressorcontinuestorunand heattheoutdoorcoil,causingthesnowandice
to melt. Duringdefrost,theremaybe some steamrisefromtheoutdoorunitasthewarmcoil
causessomemeltedfrosttoevaporate.
SECTION 2. INSTALLER INFORMATION
6ft.
12"
Figure 2. Minimum Unit Clearances
GENERAL
Read the following instructions completely
before performing the installation.
These instructions are for the use of qualified personnel specially trained and experienced in
the installation of this type of equipment and
related system components. Some states require
installation and service personnel to be licensed.
Unqualified individuals should not attempt to
interpret these instructions or install this equipment.
The single packaged air conditioners are designed for outdoor installation only and can be
readily connected into the high static duct system of a home. The only connections needed for installation are the supply and return ducts, the
line voltage, and thermostat wiring. A complete air conditioning system typically consists of:
Single Package Heat Pump
Home Fittings Kit o Unit Fittings Kit
Thermostat The single package air conditioner is completely
assembled, factory wired, and factory run tested. The units are ready for easy and immediate
installation.
calculated and a system of the proper capacity selected. It is recommended that the area to
be conditioned be completely insulated and
vapor sealed. The installer should comply with all local codes
and regulations which govern the installation of this type of equipment. Local codes and
regulations take precedence over any recommendations contained in these
instructions. Consult local building codes and the National Electrical Code (ANSi CI) for
special installation requirements.
The electrical supply should be checked to
determine if adequate power is available. If there is any question concerning the power supply, contact the local power company.
inspecting Equipment: All units are securely packed at the time of shipment and, upon
arrival, should be carefully inspected for damage. Claims for damage (apparent or
concealed) should be filed immediately with the carrier.
INSTALLATION
1. SELECT THE BEST LOCATION FOR THE HEAT PUMP UNIT
Use of components other than those specified
may invalidate ARI Certification, Code Agency
Listing, and limited warranty on the air
conditioner.
PRE-INSTALLATION CHECK
Before any installation is attempted, the cooling
load of the area to be conditioned must be
IMPORTANT: DO NOT PLACE UNIT UNDER THE HOME.
- Select a solid, level position, preferably on a concrete slab, slightly above the grade level, and parallel to the home.
. The hot condenser air must be discharged
up and away from the home, and if possible,
in a direction with the prevailing wind.
Page 4
, Donotplacetheunitinaconfinedspace. , Ifpractical,placetheheatpumpwhereitand
theductswillbeshadedfromtheafternoon sunwhentheheatloadisgreatest.
, Trytoselectasitefortheunitthatisasclose
as possibleto the proposedreturngrille location.
Keepinmindthatthelengthofthesupplyand returnductsshouldbekepttoa minimum
withnosharpradiusedbends.
2. UNPACK THE UNIT
It is recommended that the unit be unpacked at
the installation site to minimize damage due to handling.
shipped in the supply duct. They attach to the
unit openings with a flange and bead arrangement, secured with two sheet metal screws. Note: For ease of access, install fitting
before positioning unit infinal location.
SUPPLY DUCT
Position the supply duct collar, if supplied, so the
edge of the unit opening fits between the flange and the bead. Overlap the collar ends keeping
the small screw holes underneath. Align the
holes in the crimped area and install one screw.
Note: It may be necessary to loosen the four screws that hold the transition duct in order to
install the supply fitting. Re-tighten when
installation is complete.
CAUTION:
Do not tip the unit on its side. Oil may
enter the compressor cylinders and
cause starting trouble, if unit has been
set on its side, restore to upright position and do not run for several
hours. Then run unit for a fewseconds.
Do this three or four times with five
minutes between runs.
a. Remove the bands from around the unit. b. Unfold the top and bottom cap flanges.
c. Carefully remove the top cap and tube.
3. INSTALL THE RETURN AND SUPPLY AiR FiTTiNGS ON THE UNIT
The supply and return fittings are included with select models. If supplied, the duct fittings are
Tap collar as necessary to ensure engagement with unit opening and install second screw.
Tighten first screw. Rotate collar clockwise so joint is near three o'clock position.
RETURN DUCT
The 12" return duct is installed in the same
manner as the supply duct. If the duct has a 14" return, follow these instructions.
Align the slots with the holes in the collar and
install two screws. Position the collar over the opening and align the four notches inthe collar with the four dimples in the panel. Using self-
drilling screws (10-16x.5) attach the collar to the
rear panel. On some models a 14" duct collar is
provided for the return duct.
4. LOCATING AND INSTALLING THE
RETURN AiR ASSEMBLY
To avoid complications, locate and install the
return air assembly first. The return air box with
grille and filter (Figure 4) should not be located
in heavy traffic areas like hallways or center of
rooms. A good spot is in a corner or under a table, if a minimum two inch clearance is available. If desired, the return opening can be
SupplyAir
Figure 3.
4
Return and Supply Air Fittings
Return Air
13 SEER Return Dia. (in)
2 Ton 12
2 1/2 Ton 14
3 Ton 14
3 1/2 Ton 14
4 Ton 14
Page 5
:ILTER
RETURN AIR
CUT FLOOR
ISTS
Figure 4. Return Air Box located inside a closet with Iouvered doors that have an open area equal to or greater than the
12"x 20" grille furnished. The return air grille can
be placed inthe wall of a closet and the air ducted into the filter box through a boxed-in area at the
closet floor level. Make sure the filter is readily accessible.
When locating the supply damper(s), carefully check floor joists and frame members that
could interfere with the installation of the damper or flexible duct. Ideally, the damper should be
located in the bottom of the main duct, forward
of center of the home, at least three feet from the nearest register. The round supply opening
in the slanted side of the damper should face
the side of the home where the heat pump is
located. To locate the center of the heat duct,
first cut a small hole in the fiberboard below the duct at the desired location. After locating the duct center, cut a hole approximately 3/4" larger than the damper opening inthe fiberboard. Cut
a 9-1/8" x 13-1/8" hole inthe duct and bend over all tabs flat on the inside of the heat duct. After
inserting the damper into the duct, bend over all
tabs flat on the inside of the heat duct. Seal the opening between the fiberboard and damper or
flexible duct.
DUCTING SYSTEM
After determining the location of the return air opening, start the installation from under the home bycutting asmall hole inthe fiber underboard
to determine how the floor joist location will affect cutting the opening needed for the box. Floor
joists gene rally are located on 16"centers, leaving
14-3/8" between joists. After measuring the return air box (approximately 12-1/4" x 20-1/4"),
cut the hole through the floor so that the box will fit between the floor joists. Care should be taken when cutting through carpeting to avoid snags. In
most installations it will be necessary to cut a similar hole in the fiberboard directly under the hole in the floor. However, if the floor is more than
ten inches deep, it will only be necessary to cut a hole for the collar on the return air box or for the
insulated duct.
Set the box into the opening and fasten with screws or nails. Put the filter and return air grille
in place.
5. LOCATING AND INSTALLING THE
SUPPLY DAMPER(S)
REGISTER
/
/
CLOSED
PUMPISOFF
DUCT REQUIREMENTS
The supply duct system, including the number and type of registers, will have much more
effect on the performance the system than
any other factor. The duct must be sufficiently
large to conduct an adequate amount of air to each register.
THE HEAT PUMP SYSTEM WiLL NOT COOL
OR HEAT THE HOME IF THE AiR IS LOST
TO THE OUTSIDE THROUGH LEAKS IN THE DUCT SYSTEM. ALSO, DUCTS WHICH
ARE COLLAPSED OR RESTRICTED BY
FOREIGN OBJECTS WILL PREVENT
ADEQUATE AIR FLOW.
Note: For highly resistive duct systems it may be necessary to add an additional return air duct to
achieve maximum performance.
CONNECTING THE RETURN AND SUPPLY
AiR FLEXIBLE DUCTS
The return duct may be 12" or 14" diameter depending on unit size. (See Table on page 4)
a. The supply duct for all units is twelve inches
in diameter.
b. The flexible ducts can be connected to the
corresponding fittings with the clamps provided with the ducts. Note: All connections
should be leak tight or a loss in cooling capadty will result.
Figure 5. Supply Damper
5
Page 6
c. Theflexibleductsmaybecuttotherequired
length,seeinstructionspackedwith duct. Keepall ductsas shortand straightas
possible.Avoidsharpbends.
d. Ducts may be splicedwith sheet metal
sleevesandclamps.(SeeDuctingInstallation
Accessoriesbelow.)
e. Oncethe innerduct is connectedto the
properfitting,theinsulationandplasticsleeve shouldbepulledovertheconnectionand
clamped.
f. Forhomeswithmultiplesupplyductsorfor
specialapplications,aYfittingisavailableto dividethesupplyairso it canbeductedto
differentareasofthehomeformoreefficient cooling. Note: The Y fittingshouldbe
insulatedfor maximumperformance.
BlowerSpeedTheblowerspeedis presetat
thefactoryforoperationatthesamespeedfor heatingandcooling. For optimumsystem
W
\
Figure 6. Drain Trap
performance and comfort, it may be necessary
to change the factory set speed. To change the
blower speed:
1. Disconnect all electrical power to the unit and remove the service panel.
2. See figure 8 for wire color vs. motor speed guide.
TYPICAL APPLICATIONS
SINGLE DUCT APPLICATION MULTIPLE DUCT APPLICATION
Ref. No. Description
12" x 20" Return Air
(_) 16" x 20" Air Filter (_ 12" x 20" Grille
(_) 12" Diameter Flex Supply Duct (_) 12" x 12" x 12" "Y" Fitting
6
Supply Damper
12" or 14" Diameter Flex Return Duct
Figure 7. Typical Applications
Page 7
Place the desired blower speed lead
3. CONDENSATE DRAIN
on the "NO" terminal of the blower
relay. Use another wire tie (field
supplied) to bundle the remaining motor
lead up and out of the way.
A 3/4" condensate fitting extends out of the side
of the unit. The drain trap, shipped in the electrical compartment, must be installed to
prevent water from collecting inside the unit.
Thread the elbow provided with the unit into the
CAUTION'.
drain connection until hand tight. Install the trap
into the fitting making sure it is level. Route the
To avoid personal injury or property
damage, make certain that the motor
leads cannot come into contact with
condensate from the trap to a suitable drain.
Any tubing or hose connected must have the
outlet below trap level for proper drainage.
any uninsulated metal components of the unit.
WARNING'.
Check all factory wiring per the unit wiring diagram and inspect the factory wiring connec- tions to be sure none loosened during shipping
or installation.
Model Wire Color / Motor Air Flow Q3RD Speed Tap Speed /O.3 In. WC)
2 Ton T3 Medium 1,140
2.5 Ton
3 Ton Red / T3 Medium 1,140
3.5 Ton T3 Medium 1,650
4 Ton T3 Medium 1,650
Red / T1 Low 750
Orange / T2 Med/Low 1,000
T4 Med/High 1,300 T5 High 1,350
Red Low 760
Black High 1000
T1 Low 750 T2 Med/Low 1,O00
T4 Med/High 1,300
Orange / T5 High 1,350
Red / T1 Low 1,340
Orange / T2 Med/Low 1,450
T4 Med/High 1,750 T5 High 1,965
T1 Low 1,340
Red / T2 Med/Low 1,450
Orange / T4 Med/High 1,750
T5 High 1,965
Figure 8. Motor Lead Connection
Turn off electrical power before
servicing controls. Severe electrical shock may result unless power isturned off. Unit must be installed in compliance with the National Electrical Code (NEC)
and local codes.
ELECTRICAL CONNECTIONS
1. ELECTRICAL SERVICE
High Voltage a. Install a branch circuitdisconnectof adequate
size per NEC. Locate the disconnect within sight of the unit.
b. Extend leads through power wiring hole
provided. Connect L1 and L2 directly to the contactor. (See Figure 9.)
c. Ground the heat pump unit using the green
grounding screw provided inthe control panel.
High Voltag
Low Voltag
\
Figure 9. Power Entry
7
Page 8
m
C
Q
W2
©-
Y1
@
R
Q
G
@
0
Q
E
iNDOOR
THERMOSTAT
SUB-BASE
FROMSLOWERRELAY
__/_ Green
o ?_-.)
--I------7
o_
i t
t
i t
_/
DEFROST
BOARD
o_
3- Orange
T
__. Srown
E
Accessory Heat Plug
Typical Wiring (Field Supplied) for 1=Stage Cool, 1 Stage Electric Heat
FROM SLOWER RELAY
m
C
@
W2
Y1
@
R
Q
G
Q
0
t
-Jr
t
-t- -$
t t t
-_- -t ....
t
I- i I I i-
_1- I I
i t I I
i 1 I-± ......
i t I
-1- .... t-- I-
I
i i i
I
_(_.)
o_
Q
E
t
Q
iNDOOR
THERMOSTAT
SUB-BASE
DEFROST
BOARD
_- Orange
Accessory Heat Plug
Optional Outdoor
Thermostat (Field Supplied)
Brown
Typical Wiring (Field Supplied) for 1=Stage Cool, 2=Stage Electric Heat
Figure 10. Typical Heat Pump Thermostat Connections
with an Optional Outdoor Thermostat
Page 9
40 45
with an ON-AUTO fan switch which allows the
home owner to operate the indoor blower when
air circulation is desired.
@
0
lo
Figure 11. Outdoor Thermostat
Low Voltage
a. Route 24v control wires through the sealing
grommet near the power entrance. (See Figure 9.)
b. Connect the control wires to the defrost
board and blower relay wire. (See Figure 10.)
2. OVERCURRENT PROTECTION
In general, the best fuse or breaker for any heat pump is the smallest size that will permit the equipment to run under normal use and service
without nuisance trips. Such a device, sized properly, gives maximum equipment protection.
The principal reason for specifying a time delay type is to prevent nuisance trips when the unit
starts.
In the event that a fuse does blow or a breaker trips, always determine the reason. Do not
arbitrarily put in a larger fuse or breaker and do not, in any case, exceed the maximum size listed
on the data label of the unit.
Connect the low voltage wires to the respective
terminals on the thermostat base. See thermo- stat instruction sheet for more detailed informa-
tion. (See Figure 10).
if two stage heating is desired, an optional
outdoor thermostat may be installed:
Connect the thermostat to the orange low volt- age wire and the W terminal on the indoor thermostat base (See Figure 10). See the ther-
mostat instructions for details on setting the outdoor thermostat.
4. DEFROST CYCLE CONTROL
The defrost cycle is initiated via a signal from the defrost sensor on the outdoor coil to the defrost
control board inside the control panel indicating the coil temperature is low enough to start
accumulating frost. The board has interval settings of 30 minutes, 60 minutes, and 90
minutes. These time intervals represent the time
elapsed before defrosting cycle starts and they are dependent on the climate conditions of the
installation. A 30 minute setting would be
recommended in amoist climate such as Seattle, Washington. A 90 minute setting would be
adequate in a dry climate such as southern Arizona. The factory time interval setting is 30
minutes.
5. OUTDOOR THERMOSTAT
3. LOCATING THE THERMOSTAT
Locate the thermostat away from drafts and slamming doors and place it where there is a free flow of air. Mount on an inside wall approximately
five feet from the floor.
Do not locate near a lamp, kitchen range, direct sunlight, or in line with air flow from supply
registers.
Connect the Heat=Cool Thermostat: The heat- cool thermostat is equipped with a system HEAT- COOL switch, which provides a positive means of
preventing simultaneous operation of the heating and cooling units. The thermostat is also eq uipped
The outdoor thermostat prevents the electrical auxiliary heat (if used) from operating above a
desired set point. Selection of the set point is determined from the building design heat load.
The thermostat is adjustable from 45°F to 0°F. The factory temperature setting is at 40°F.
6. ELECTRIC HEAT PACKAGE (OPTIONAL)
The heat pumps are shipped without an auxiliary
electric heat kit installed. If electric heat is
desired, an accessory Heater Kit must be field
installed. See Specifications Sheet for available kits and their application.
Page 10
Selectthecorrectsizeheatpackageforthe installation.
Followinstallationinstructionsprovidedwith eachheaterkit.
Installationis most easily accomplished
beforemakingductorelectricalconnections. Blowerspeedmustbesettohighspeedfor
electricheatoperation.
SYSTEM OPERATION
1. PRE-START CHECK LIST
The following check list should be observed prior to starting the unit.
[] Istheunitlevel? Itshouldbelevelorslightly
slanted toward the drain for proper condensate drainage.
Isthe unit installedwith the proper clearances
[]
(See Figure 2)? Is the wiring correct according to the wiring
[]
diagram and electrical codes? Are all the wiring connections tight? Check
[]
the condenser fan to make sure it turns freely.
Is the overcu rrent protection properlysized?
[]
Is the thermostat wired correctly? Is it
[]
installed in a proper location?
2. START=UPPROCEDURE
The control circuit consists of an anti-short cycle timer that will not let compressor re-start before
five (5) minutes have elapsed.
Set the thermostat system switch to OFF, and the thermostat fan switch toAUTO. Apply power
at the disconnect switch and check the system operations:
a. Air Circulation -- Leave the thermostat
system switch at OFF, and set the thermostat fan switch to ON. Blower should run
continuously. Check the air delivery at the supply registers and adjust register openings
for balanced air distribution. Examine ductwork for leaks or obstruction ifinsufficient
air is detected.
Set the thermostat fan switch to AUTO; the blower should stop running.
b. System Heating -- Set the thermostat
system switch to HEAT and set the the rmostat fan switch to AUTO. Position the thermostat
temperature selector above the existing room temperature and check for the discharge of
warm air at the supply registers.
c. System Cooling -- Set the thermostat
system switch to COOL and set the thermostat fan switch to AUTO. Position the thermostat
temperature selector below the existing room temperature. Allow the cooling system to
operate for several minutes and check for the discharge of cool air at the supply registers.
d. Short cycle protection-- The control circuit
is equipped with a time-delay feature for protection against short cycling. With the
system operating in the cooling mode, gradually raise the thermostat temperature
setting until the whole system de-energizes.
Immediately lower the thermostat
temperature to the original setting and verify that the indoor blower is energized. After
approximately 5 minutes the compressor and the outdoor fan will energize.
e=
Emergency Heat -- (Available only when Electric heat is supplied) Set the thermostat
system switch to EM HT and set the thermostat fan switch to either AUTO
(intermittent air) or to ON (continuous air). Position the thermostat temperature selector
above the existing room temperature and check the following:
1. The thermostat auxiliary heat light (RED) should be on.
2. The heat pump compressor and the fan should not run; low voltage
circuit remains energized.
3. The blower will run according to the thermostat fan switch setting.
10
Page 11
13 SEER - Refrigerant Charging Tables for Cooling Mode of Operation
2 OUTDOOR TEMPERATURE (°F)
TON 70 75 80 85 90 95 100 105
Suct. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis.
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.
72 150 121 74 152 127 166 128 76 154 132 168 133 182 134 78 157 136 170 138 184 138 197 140 80 161 139 173 141 186 143 199 144 213 145
82 177 144 189 147 202 149 215 150 _22_ 1_5! 84 192 150 205 153 217 154 231 156 _ , _:57 86 208 156 221 158 233 160
88 212 160 224 162 236 164 249 165 62 . _;67 90 228 166 240 168 252 169
92 243 172 256 174 268 175 94 259 178 271 180
96 275 184 98
2-1/2 TON 70 75 80 85 90 95 100 105
Suct. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis.
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.
75 147 122 77 149 127 163 128
79 152 132 165 133 179 135 81 154 137 168 138 181 139 195 141 83 158 139 170 142 183 144 197 145 211 147
85 174 145 186 148 199 150 213 151 227 _3 87 190 152 202 154 215 156 229 157 24 , :1_5_
89 206 158 218 160 231 162 91 209 161 222 164 235 166 247 167 !2_ . _i69
93 225 168 238 170 251 172 26 . _J3 95 241 174 254 176 267 178
97 257 180 270 182 99 273 186
101
Refrigerant Charging Chart Legend for Cooling Mode of Operation
* Note: All pressures are listed in psig. and all temperatures in °F.
- Shaded Boxes indicate flooded conditions
- Rated Design Values. Suction Pressure will be lower than design
- Discharge temperatures greater than charted values indicate an
value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design.
undercharged system.
11
Page 12
13 SEER =Refrigerant Charging Tables for Cooling Mode of Operation
Continued
3
]'ON 70 75 80 85 90 95 100 105
Suct. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis.
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.
72 156 121 74 158 126 172 128 76 160 131 174 133 188 134 78 163 136 176 138 190 139 204 141 80 167 138 179 142 192 144 206 146 220 148
82 t83 14s tgs 148 208 is0 222 t52
84 199 151 211 154 224 157 238 159 252:: , _6 86 215 158 227 160 240 163
88 218 161 231 164 243 167 256 169 _70. _ 90 234 168 247 171 259 173 71.75
92 250 175 263 177 275 180 94 266 182 279 184
96 282 188 98
3-1/2 TON 70 75 80 85 90 95 100 105
Suct. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis.
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.
69 156 127 71 158 133 171 135
73 160 138 173 140 187 142 75 163 141 176 145 189 147 202 150 77 167 144 179 148 191 152 204 154 218 157
79 182 151 194 156 207 159 220 162 ;2 : _ 81 198 159 210 163 222 166 236 169
83 213 166 225 170 238 173 25:1 . 76 _65 , 7_ 85 217 170 229 174 241 177 253 180 ;2B . 8_
87 232 178 244 181 257 184 _9. _ 89 248 185 260 189 272 192
91 263 193 276 196 93 279 200
95
Refriqerant Charqing Chart Leqend for Coolinq Mode of Operation
* Note: All pressures are listed in psig. and all temperatures in °F.
- Shaded Boxes indicate flooded conditions
- Rated Design Values. Suction Pressure will be lower than design
- Discharge temperatures greater than charted values indicate an
12
value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design.
undercharged system.
Page 13
13 SEER =Refrigerant Charging Tables for Cooling Mode of Operation
Continued
4
TON 70 75 80 85 90 95 100 105
Suct. Dis. Dis. Dis. Dis. Dis. Dis, Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis. Dis.
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.
67 157 131 69 159 136 174 139
71 161 142 176 144 191 147 73 162 150 178 149 193 151 209 154
75 166 152 180 155 196 156 211 159 226 161 77 183 158 197 161 213 163 228 166 iiiiiiiiii_i!iiii,iiiiiil_69iiii_ii
79 201 165 215 168 230 170 245 173 iiiili_oiXiXii.iiiilii_ii:751iiiii 81 219 171 233 174 247 177 iHiiii262;:iii_!i.iHiiiii_iX791ili!ii!iiiii!i!i_7i!!iiii,iiiii!i!_((_!iiill
83 222 175 236 178 251 181 264 183 iiiiili_'_91iii:!ii.iiiiilii_8_ii!ii!i!i}i 85 240 182 254 185 268 188 iiiitii_ii[iiiiiii,iiiitli;i_i_ii,!,ili
87 257 189 272 192 286 195 89 275 196 289 199
91 293 204 93
Refriqerant Charging Chart Legend for Coolinq Mode of Operation
* Note: All pressures are listed in psig. and all temperatures in °F.
- Shaded Boxes indicate flooded conditions
_,_,_ - Rated Design Values. Suction Pressure will be lower than design
- Discharge temperatures greater than charted values indicate an
value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design.
undercharged system.
13
Page 14
Z
Page 15
Small Packaged Heat Pump - Single Phase
NOTES: 1. Disconnect all power before servicing,
2. For supply connections use copper conductors only. 3, Not suitable on systems that exceed 150V to ground, 4, For replacement wires use conductors suitable for 105 ° C, 5, On models w/no pressure switch 15-YE(28) connects "Y" & "TI" on Defrost Board,
OUTDOOR FAN
MOTOR
BLACK
GREEN
TRANSFORMER
TO .... ON
_STAT
8LOWER
RELAY
BLACK
E R W2 0 Y C
DEFROST
CONTROL
BOARD
E DFT R W2 0
BLACK- BLACK-
BLACK_
OUTDOORTHERMOSAT
-GRE_ DUAL
CAPACITOR
COMPRESSOR C YELLOW-
,RED
F BLACK
1, Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre 3, Ne convient pas aux installations de plus de 150V a la terre.
BLOWER
MOTOR GREEN-YELLOW
COMPRESSOR
CONTACTOR
(SELECT MODELS ONLY
SEE NOTE 5)
LOW
PRESSURE
SWITCH
RED_BLACK-_
DEFROST REVERSING
SENSOR VALVE
COIL
WHITE WHITE
GREY_=_
YELLOW
BLUE RED
m RED
" WHITI!E _
--ORANGE
--BROW
Legend
FactoryWiring:
LowVoltage High Voltage
7105550
J
Page 16
4_ m O m
0_
-o cb o
o5"
Q-
Q-. _,
o_
(.Q Cb
o_
----:0 _D
m
r-
_m
m
-t
r-
_m
z_
=_ _
zm m
5"
-t
r-
_Z
Small Packaged Heat Pump - Single Phase
NOTES: 1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed150 V to ground.
4. Forreplacementwiresuseoonduotorssuitsbleforl05°C.
5. Onmodelsw/nopressureswitohl5-YE(28)connects"Y"&"Tl"o_DefrostBoard.
OUTDOOR FAN
MOTOR
-- GREEN BLA
I i_ BLAC K
TRANSFORMER WHITE
1240V COM RED
240V COM
TO"G"O. _ _-- _',
(SELECT MODELS ONLY
SEE NOTE 5)
T2 T LOW
BLACK PRESSURE
RED SWITCH
BLACK@
RED _
l GREY DUAL DEFROST REVERSING
CAPACITOR SENSOR VALVE
COIL
COMPRESSOR C YELLOW=
r BLACK _YELLOW _
1, Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre
3. Ne convient pas aux installations de plus de 150V a la terre.
WHITE WHITE
GREY__
, BLUE RED
- RED
WHIT!E_
--ORANGE
-- BROW
Legend
Factory Wiring: Low Voltage High Voltage
7105740
Loading...