Nordyne Q3RA-036K, Q3RC-036K, Q3RA-060K, Q3RA-048K, Q3RA-030K Installation Manual

...
Page 1
10 and 12 SEER Single Package Heat Pump
Single Package Heat Pump
IMPORTANT:
Read this owner information to become familiar with the capabilities and use of your appliance. Keep this with literature on other appliances where you have easy access to it
in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don't eliminate your problem, call your installing contractor or
distributor in your area.
INTRODUCTION
Your heat pump isaunique, all weather comfort-
control system appliance. The basic operation of the heating/cooling system is described and
illustrated on page 1 of this manual. The surprising fact that heat exists in air even at below-freezing temperatures isactually the basic law of physics which the heat pump uses to provide energy saving heating comfort. At
outdoor temperatures of 47° Fahrenheit or (or
8° Celsius), your heat pump can deliver approximately 2 to 3 units of heat energy per each unit ofelectrical energy used, as com pared
to a maximum of only 1 unit of heat energy
produced with conventional heating systems. During the cooling season, the heat pump reverses the flow of the heat-absorbing refrigerant to become an energy-efficient, central
air conditioner.
Page 2
2
Page 3
SECTION 1. OWNER INFORMATION
Your heat pump will heat and cool your home year round, saving your energy dollars. During the summer, a heat pump performs like any
normal air conditioner. That is, the excess heat energy inside the home is absorbed by the
refrigerant and exhausted outside the home. During the winter months, a heat pump performs
like an air conditioner run in reverse. That is, available heat energy outside the home is
absorbed by the refrigerant and exhausted inside the home. This is an efficient heating means because you only pay for "moving" the heat from the outdoors to the indoor area. You do not pay
to generate the heat, as is the case with more traditional furnace designs.
FAN SWITCH
SYSTEM SWITCH
TEMPERATURE SCALES
TEMPERATURE SELECTOR
Figure 1. Typical Thermostat
It is the sole responsibility of the homeowner to make certain that the heat pump has been correctly set upand adjusted to operate properly.
The manufacturer warrants the heat pump to be free from defects in workmanship or material for a period of one year. A warranty certificate with full details is included with the heat pump.
However, we will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation,
adjustments, improper operating procedure on the part of the user, etc.
Some specific examples of service calls which
are not included in the limited warranty are:
1. Correcting wiring problems in the electrical circuit supplying the heat pump.
2. Resetting circuit breakers or other switches.
3. Adjusting or calibrating of thermostat.
To avoid misunderstandings at a later date, carefully review these responsibilities with your
dealer or service company.
OPERATING INSTRUCTIONS
To Operate Your Heat Pump For Cooling --
1. Set the thermostat system switch to COOL
and the thermostat fan switch to AUTO. (See
Figure 1)
2. Set the thermostat temperature selector tothe desired cooling temperature. The outdoor unit
fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor
temperature at the desired cooling level.
NOTE: Ifthe thermostat temperature level is re- adjusted, or if the thermostat system switch is
re-positioned, the outdoor unit fan and the compressor may not start immediately. A
protective timer circuit holds the compressor and the outdoor fan off for approximately five
minutes following a previous operation or the interruption of the main electric power.
To Operate Your Heat Pump For Heating --
1. Set the thermostat system switch for HEAT and thethermostat fan switch toAUTO. (See
Figure 1)
2. Set the thermostat temperature selector to the desired heating temperature. The outdoor
unit fan, the indoor blower, and the
compressor will all cycle on and off to
maintain the indoor temperature atthe desired heating level.
NOTE: If the thermostat temperature level is re- adjusted, or if the thermostat system switch is
re-positioned, the outdoor unit fan and the compressor may not start immediately. A
protective timer circuit holds the compressor and the outdoor fan off for approximately five
minutes following a previous operation or the interruption of the main electrical power.
Emergency Heat -- Some thermostats will includea system switch position termed EM HT orAUX HT, etc. This isa back-upheating mode tobe used only if there is a suspected problem,
With the system switch set to EM HT, etc., the compressor and outdoor fan will be locked off
and supplemental heat (electric resistance
3
Page 4
heating)will be usedas a sourceof heat. Sustaineduseof electricresistanceheatin
placeoftheheatpumpwillresultinanincrease inelectricutilitycosts.
Defrost -- During cold weather heating
operation, the outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is
normal and the unit will periodically defrost itself. During the defrost cycle, the outdoor fan will stop, while the compressor continues to run and heat the outdoor coil, causing the snow and ice
to melt. During defrost, there may be some steam rise from the outdoor unit as the warm coil
causes some melted frost to evaporate.
6ft.
24"
12"
12"
SECTION 2. INSTALLER INFORMATION
GENERAL
Read the following instructions completely before performing the installation.
These instructions are for the use of qualified
personnel specially trained and experienced in
the installati0n of this type of equipment and
related system components. Some states require installation and service personnel to be licensed. Unqualified individuals should not attempt to interpret these instructions or install this
equipment. The single packaged air conditioners are
designed for outdoor installation only and can be readily connected into the high static duct system
of a home. The only connections needed for installationare the supply and return ducts, the
line voltage, and thermostat wiring. A complete air conditioning system typically consists of:
Single Package Heat Pump
Home Fittings Kit
Unit Fittings Kit
Thermostat The single package air conditioner iscompletely
assembled, factory wired, and factory runtested. The units are ready for easy and immediate
installation. Use of components other than those specified
may invalidate ARI Certification, Code Agency Listing, and limited warranty on the air
conditioner.
PRE-INSTALLATION CHECK Before any installationis attempted, the cooling
load of the area to be conditioned must be
Figure 2. Minimum Unit Clearances
calculated and a system of the proper capacity selected. It is recommended that the area to
be conditioned be completely insulated and vapor sealed.
The installer should comply withall local codes and regulations which govern the installation
of this type of equipment. Local codes and regulations take precedence over any
recommendations contained in these instructions. Consult local building codes and
the National Electrical Code (ANSI CI) for special installation requirements.
The electrical supply should be checked to determine if adequate power is available. If
there is any question concerning the power supply, contact the local power company.
Inspecting Equipment: All units are securely packed at the time of shipment and, upon
arrival, should be carefully inspected for damage. Claims for damage (apparent or
concealed) should be filed immediately with the carrier.
INSTALLATION
1. SELECT THE BEST LOCATION FOR
THE HEAT PUMP UNIT
IMPORTANT: DO NOT PLACE UNIT UNDER THE HOME.
Select a solid, level positionl preferably on
a concrete slab, slightly above the grade
level, and parallel to the home.
The hot condenser air must be discharged
up and away from the home, and if possible, in a direction with the prevailing wind.
Page 5
Donotplacetheunitinaconfinedspace. Ifpractical,placetheheatpumpwhereitand
theductswillbeshadedfromtheafternoon
sunwhentheheatloadisgreatest. Trytoselectasitefortheunitthatisasclose
as possibleto the proposedreturngrille location.
Keepinmindthatthelengthofthesupplyand returnductsshouldbekeptto aminimum
withnosharpradiusedbends.
2. UNPACK THE UNIT
It is recommended that the unit be unpacked at the installation site to minimize damage due to handling.
CAUTION:
Do not tip the unit on its side. Oil may enter the compressor cylinders and
cause starting trouble. If unit has
been set on its side, restore to upright
position and do not run for several
hours. Then run unit for a fewseconds.
Do this three or four times with five
minutes between runs.
The supply and return fittings are included with select models. If supplied, the duct fittings are shipped in the supply duct. They attach to the unit openings with a flange and bead arrangement, secured with two sheet metal screws. Note: For ease of access, install fitting before positioning unit in final location.
SUPPLY DUCT
Position the supply duct collar, if supplied, so the edge of the unit opening fits between the flange and the bead. Overlap the collar ends keeping the small screw holes underneath. Align the
holes in the crimped area and install one screw.
Note: It may be necessary to loosen the four
screws that hold the transition duct in order to
install the supply fitting. Re-tighten when
installation is complete.
Tap collar as necessary to ensure engagement with unit opening and install second screw.
Tighten first screw. Rotate collar clockwise so
joint is near three o'clock position.
RETURN DUCT
The 12" return duct is installed in the same
mannerasthesupplyduct. Iftheduct hasa 14" return, follow these instructions.
a. Remove the bands from around the unit. b. Unfold the top and bottom cap flanges.
c. Carefully remove the top cap and tube.
3. INSTALL THE RETURN AND SUPPLY AIR FITTINGS ON THE UNIT
Align the slots with the holes in the collar and
installtwo screws. Position the collar over the
opening and align the four notches in the collar with the four dimples in the panel. Using self-
drilling screws (10-16x.5) attach the collar to the rear panel. On some models a 14" duct collar is provided for the return duct.
ou'°°':i
SupplyAir ReturnAir
Figure 3. Return and Supply Air Fittings
4. LOCATING AND INSTALLING THE
RETURN AIR ASSEMBLY
To avoid complications, locate and install the return air assembly first. The return air box with grille and filter (Figure 4) should not be located
in heavy traffic areas like hallways or center of rooms. A good spot is in a corner or under a
table, if a minimum two inch clearance is available. If desired, the return opening can be
10 SEER Return
Model eia. (in)
2 Ton 12 2 1/2 Ton 12
3 Ton 12 3 1/2 Ton 12
4 Ton 14 5 Ton 14
12 SEER Return
Model Oia. (in)
2 Ton 12 2 1/2 Ton 12
3 Ton 12
3 1/2 Ton 14
4 Ton 14
5
Page 6
_RILLE
--ILTER
- RETURN AIR
CUT FLOOR
Figure 4. Return Air Box
located inside a closet with Iouvered doors that have an open area equal to or greater than the
12"x 20" grille furnished. The return air grille can be placed in the wall ofa closet and the air ducted into the filter box through a boxed-in area at the closet floor level. Make sure the filter is readily
accessible.
When locating the supply damper(s), carefully check floor joists and frame members that
could interfere with the installation ofthe damper or flexible duct. Ideally, the damper should be
located in the bottom of the main duct, forward of center of the home, at least three feet from the nearest register. The round supply opening in the slanted side of the damper should face the side of the home where the heat pump is
located. To locate the center of the heat duct, first cut a small hole in the fiberboard below the
duct at the desired location. After locating the duct center, cut a hole approximately 3/4" larger than the damper opening in the fiberboard. Cut
a 9-1/8" x 13-1/8" hole in the duct and bend over
all tabs flat on the inside of the heat duct. After inserting the damper into the duct, bend over all
tabs fiat on the inside of the heat duct. Seal the
opening between the fiberboard and damper or
flexible duct.
DUCTING SYSTEM
After determining the location of the return air
opening, start the installation from under the
home by cutting asmall hole inthe fiber underboard to determine how the floor joist location will affect
cutting the opening needed for the box. Floor joists generally are located on 16" centers, leaving
14-3/8" between joists. After measuring the
return air box (approximately 12-1/4" x 20-1/4"),
cut the hole through the floor so that the box will
fit between the floor joists. Care should be taken
when cutting through carpeting to avoid snags. In
most installations it will be necessary to cut a
similar hole in the fiberboard directly under the
hole in the floor. However, ifthe floor is more than
ten inches deep, it will only be necessary to cut a
hole for the collar on the return air box or for the
insulated duct.
Set the box into the opening and fasten with
screws or nails. Put the filter and return air grille
in place.
5. LOCATING AND INSTALLING THE
SUPPLY DAMPER(S)
DUCT REQUIREMENTS The supply duct system, including the number
and type of registers, will have much more effect on the performance the system than any other factor. The duct must be sufficiently large to conduct an adequate amount of air to each register.
THE HEAT PUMP SYSTEM WILL NOT COOL OR HEAT THE HOME IF THE AIR IS LOST TO THE OUTSIDE THROUGH LEAKS IN
THE DUCT SYSTEM. ALSO, DUCTS WHICH ARE COLLAPSED OR RESTRICTED BY
FOREIGN OBJECTS WILL PREVENT
ADEQUATE AIR FLOW.
Note: For highly resistiveductsystems itmay be
necessary to add an additional return air duct to achieve maximum performance.
CONNECTING THE RETURN AND SUPPLY
AIR FLEXIBLE DUCTS
The return duct may be 12" or 14" diameter depending on unit size. (See Table on page 4)
a. The supply duct for all units is twelve inches
in diameter.
b. The flexible ducts can be connected to the
corresponding fittings with the clamps provided with the ducts. Note: Allconnections should be leak tight or a loss in cooling capacity will result.
Figure 5. Supply Damper
6
Page 7
c. The flexible ducts may be cut to the required
length, see instructions packed with duct. Keep all ducts as short and straight as
possible. Avoid sharp bends.
d. Ducts may be spliced with sheet metal
sleeves and clamps. (See Ducting Installation Accessories below.)
e. Once the inner duct is connected to the
proper fitting, the insulation and plasticsleeve should be pulled over the connection and clamped.
f. For homes with multiple supply ducts or for
special applications, a Y fitting is available to divide the supply air so it can be ducted to different areas of the home for more efficient
cooling. Note: The Y fitting should be
insulated for maximum performance.
Blower Speed -- The blower speed is preset at
the factory for operation at the same speed for
heating and cooling. For optimum system
Elbow
P-Trap
Figure 6. Drain Trap
performance and comfort, it may be necessary
to change the factory set speed. To change the
blower speed:
1. Disconnect all electrical power to the unit and remove the service panel.
2. See figure 8 for wire color vs. motor speed guide.
TYPICAL APPLICATIONS
SINGLE DUCT APPLICATION MULTIPLE DUCT APPLICATION
Ref. No. Description
12" x 20" Return Air
(_ 16" x 20" Air Filter (_ 12" x 20" Grille
(_ Supply Damper (_ 12" or 14" Diameter Flex Return Duct
(_ 12" Diameter Flex Supply Duct (_ 12" x 12" x 12" "Y" Fitting
Figure 7. Typical Applications
7
Page 8
3,
Place the desired blower speed lead
on the "NO" terminal of the blower relay. Use another wire tie (field
supplied) to bundle the remaining motor lead up and out of the way.
CAUTION:
To avoid personal injury or property
damage, make certain that the motor leads cannot come into contact with
any uninsulated metal components of
the unit.
Check all factory wiring per the unit wiring diagram and inspect the factory wiring connec- tions to be sure none loosened during shipping
or installation.
Wire Color Motor Speed
Black High Red Low
Figure 8. Motor Lead Connection
CONDENSATE DRAIN
A 3/4" condensate fitting extends out of the side
of the unit. The drain trap, shipped in the electrical compartment, must be installed to
prevent water from collecting inside the unit. Thread the elbow provided with the unit into the
drain connection until hand tight. Install the trap into the fitting making sure it is level. Route the condensate from the trap to a suitable drain. Any tubing or hose connected must have the outlet below trap level for proper drainage.
WARNING:
Turn off electrical power before servicing controls. Severe electrical shock may result unless power is turned
off. Unit must be installed in compliance with the National Electrical Code (NEC)
and local codes.
ELECTRICAL CONNECTIONS
1. ELECTRICAL SERVICE
High Voltage
a. Install a branch circuit disconnect of adequate
size per NEC. Locate the disconnect within sight of the unit.
b. Extend leads through power wiring hole
provided. Connect L1 and L2 directly to the contactor. (See Figure 9.)
c. Ground the heat pump unit using the green
grounding screw provided inthe control panel.
Low Voltage
a. Route 24v control wires through the sealing
grommet near the power entrance. (Sea Figure 9.)
b. Connect the control wires to the defrost
board and blower relay wire. (See Figure 10.)
2. OVERCURRENT PROTECTION
Ingeneral, the best fuse or breaker for any heat
High Voltage ._r
Low Voltage _
Figure 9. Power Entry
8
Page 9
FROM BLOWER RELAY
_l!_Green
m
C
I
W2
t
Yl
L ............
R
i
G _
'
i l I
0 I _ I
b
E
,
-- i
INDOOR
THERMOSTAT
SUB-BASE
o(_
-- 0(_
-- 31 _
BOARD
_ Brown
Orange
Accessory Heat Plug
Typical Wiring (Field Supplied) for 1-Stage Cool, 1 Stage Electric Heat
FROM BLOWER RELAY
-I/_/_ Green
m
C
W2 ........ =.....
Yt
©
R
G
'
I i
O = I
@_ ' ,
--i- 7 I i
E
INDOOR
THERMOSTAT
SUB-BASE
i I
L .........
_L
I-T- -t"
' J i
J J J t J i_
i i
J _ ......
-_'_ o<_Z_
o_
-- O
DEFROST
BOARD
Optional Outdoor
Thermostat (Field Supplied)
Brown
i Orange
Accessory Heat Plug
Typical Wiring (Field Supplied) for 1-Stage Cool, 2-Stage Electric Heat
with an Optional Outdoor Thermostat
Figure 10, Typical Heat Pump Thermostat Connections
9
Page 10
40 45
o
lo
Figure 11, Outdoor Thermostat
pump is the smallest size that will permit the equipment to run under normal use and service without nuisance trips. Such a device, sized
properly,gives maximum equipment protection.
The principalreason for specifying a time delay type is to prevent nuisance trips when the unit
starts.
In the event that a fuse does blow or a breaker
trips, always determine the reason. Do not
arbitrarily put in a larger fuse or breaker and do not, in any case, exceed the maximum size listed
on the data label of the unit.
3. LOCATING THE THERMOSTAT
Locate the thermostat away from drafts and slamming doors and place itwhere there isa free flowof air. Mount on an inside wall approximately
five feet from the floor.
Do not locate near a lamp, kitchen range, direct
sunlight, or in line with air flow from supply
registers.
Connect the Heat.Cool Thermostat: The heat- coolthermostat is equipped witha system HEAT-
COOL switch, which provides a positive means of preventing simultaneous operation of the heating and cooling units. Thethermostatisalso equipped
with an ON-AUTO fan switch which allows the
home owner to operate the indoor blower when air circulation is desired.
Connect the low voltage wires to the respective
terminals on the thermostat base. See thermo-
stat instruction sheet for more detailed informa-
tion. (See Figure 10).
If two stage heating is desired, an optional outdoor thermostat may be installed:
Connect the thermostat to the orange tow volt- age wire and the W terminal on the indoor thermostat base (See Figure 10). See the ther-
mostat instructions for details on setting the outdoor thermostat.
4. DEFROST CYCLE CONTROL
The defrost cycle is initiatedvia a signal from the
defrost sensor on the outdoor coil tothe defrost control board inside the controlpanel indicating
the coil temperature is low enough to start accumulating frost. The board has interval
settings of 30 minutes, 60 minutes, and 90 minutes.These time intervalsrepresent thetime elapsed before defrosting cycle starts and they are dependent on the climate conditions of the installation. A 30 minute setting would be
recommended ina moist climate such asSeattle, Washington. A 90 minute setting would be
adequate in a dry climate such as southern Arizona. The factory time interval setting is 30
minutes.
5. OUTDOOR THERMOSTAT (if supplied)
The outdoor thermostat prevents the electrical auxiliary heat (if used) from operating above a desired set point. Selection of the set point is determined from the building design heat load.
The thermostat is adjustable from 45°F to 0°F.
The factory temperature setting is at 40°F.
6. ELECTRIC HEAT PACKAGE (OPTIONAL)
The heat pumps are shipped withoutan auxiliary
electric heat kit installed. If electric heat is desired, an accessory Heater Kit must be field
installed. See Specifications Sheet for available kits and their application.
Select the correct size heat package for the installation.
Follow installation instructions provided with each heater kit.
Installation is most easily accomplished
before making duct or electrical connections.
Blower speed must be set to high speed for
electric heat operation.
SYSTEM OPERATION
1. PRE-START CHECK LIST
The following check list should be observed prior
to starting the unit.
10
Page 11
[] Istheunitlevel?Itshouldbelevelorslightly
slantedtoward the drain for proper condensatedrainage.
[] Istheunitinstalledwiththeproperclearances
(SeeFigure2)?
[] isthewiringcorrectaccordingtothewiring
diagramandelectricalcodes?
[] Areallthewiringconnectionstight?Check
thecondenserfanto makesureit turns freely.
[] Istheovercurrentprotectionpropedysized? [] Is thethermostatwiredcorrectly?Is it
installedinaproperlocation?
2. START-UP PROCEDURE
The control circuit consists of an anti-short cycle timer that will not let compressor re-start before five (5) minutes have elapsed.
Set the thermostat system switch to OFF, and the thermostat fan switch to AUTO. Apply power
at the disconnect switch and check the system operations:
a. Air Circulation -- Leave the thermostat
system switch at OFF, and set thethermostat fan switch to ON. Blower should run
continuously. Check the air delivery at the supply registers and adjust register openings
for balanced air distribution. Examine ductwork for leaks orobstruction ifinsufficient air is detected.
Set the thermostat fan switch to AUTO; the
blower should stop running,
b. System Heating -- Set the thermostat
system switch to HEAT and set the thermostat
fan switch to AUTO. Position the thermostat temperatu re selector above the existing room
temperature and check for the discharge of warm air at the supply registers.
c. System Cooling -- Set the thermostat
system switch to COOL and set the thermostat fan switch to AUTO. Position the thermostat
temperature selector below the existing room temperature. Allow the cooling system to
operate for several minutes and check for the discharge of cool air at the supply registers,
d. Short cycle protection-- The control circuit
is equipped with a time-delay feature for protection against short cycling. With the
system operating in the cooling mode, gradually raise the thermostat temperature setting untilthe whole system de-energizes.
immediately lower the thermostat
temperature to the originalsetting and veri_ that the indoor blower is energized. After approximately 5 minutes the compressor and the outdoor fan will energize.
Emergency Heat -- (Available only when Electric heat is supplied) Set the thermostat
system switch to EM HT and set the
thermostat fan switch to either AUTO
(intermittent air) or to ON (continuous air). Position the thermostat temperature selector above the existing room temperature and check the following:
1. The thermostat auxiliary heat light (RED) should be on.
2. The heat pump compressor and the fan should not run; low voltage circuit remains energized.
3. The blower will run according to the thermostat fan switch setting.
10 SEER - Refrigerant Charging Tables for Heating Mode of Operation
2 Ton
0 10
Disch. SuC. Disch.
....... >r_ Press
25 132
27 _t_ _
:_ 28
3o
20
Suc
=ress
32 33 34
35 36
37 38
OUTDOOR TEMPERATURE
30 40
Suc
_ress
56 57 58
59
6O 61
62
11
Page 12
10 SEER - Refrigerant Charging Tables for Heating Mode of Operation - Continued
2-1/2 Ton
OUTDOOR TEMPERATURE
0 10 20 30
3 Ton
4O 5O 6O
_r_s_ m
61 62
63
64 65
66 67
3-1/2 Ton
I0 20
OUTDOOR TEMPERATURE
30 40 5O 6O
4 Ton
5 Ton
lo
Disch. Suc Temp. >tea=
144 27
32 33
OUTDOOR TEMPERATURE
20 30
4O 5O
2O 4O 5O
6O
60
Press
2L
21
2a 2__4
2._s
2O
OUTDOOR TEMPERATURE
Suc
Presa
27 28
29 3O
3t 32 33
4O
Suc
_eSS
50
51 52
53 54
55 56
5O
60
* Note: All pressures am listed in psig. and all temperatures in degrees F.
- Shaded Boxes indicate flooded conditions
I- Rated Design Values. Suction Pressure v_ll be lower than design
value if indoor air flow, entedng dry bulb, or entebng wet bulb
temperatures are lower than design.
- Discharge temperatures greater than charted values indicates a refdgerant undercharge.
12
Page 13
12 SEER - Refrigerant Charging Tables for Heating Mode of Operation
2 Ton
2-1/2 Ton
lO
Dlsch. Temp.
119
OUTDOOR TEMPERATURE
20 30 40 5O 6O
3 Ton
0
3-1/2 Ton
0
4 Ton
0
10
10
lo
m
s4JC.
press,
2_
3_2.o
31
3!_3
3.._!_s
OUTDOOR TEMPERATURE =
20 30
Pres_
32 33 34
35 36
37 38
4O
>r_s
56 57
58
59
6O
61 62
5O
10
SUC
=ress
24
25 26
27 28
29 3C_
Disch
Temp+
126
OUTDOOR TEMPERATURE
20 30
Suc. Olsch.
_res_ press
3.__.s
36
3._.Z_7
38 39 i
40 I 181 41 J 185
5O
6O
m
pressi
z_
2_
2___8
2g
3o
3_Z..2
OUTDOOR TEMPERATURE
20 30
29 30
31 32
33
6O
Dise.h
T_mp.
140
40
Suc
=res_
58 59
60
61 62 63
64
50
6O
* Note: All pressures are listed in psig. and all temperatures in deg. F.
- Shaded Boxes indicate flooded conditions
r-_-[--_. F_,ted Design Values. Suction Pressure will be lower than design
value if indoor air flow, entedng dry bulb, or entering w_t bulb temberatums are _ower than de.sign.
60
Suc
)r_ss
78 79
80 81
82
83 84
- Discharge temperatures greater than charted values indicates a
refdgerant undercharge.
13
Page 14
2 Ton
OUTDOOR TEMPERATURE (°F 1
70 75 80 85 90 95 100
:Suct. Press. Dis Press. Dis. Temp Dis. Press. Dm. Temp. DIS. Press. DIS. Temp. Dis. Press DIS, Tem£ is. Press Dis. Temp =is. Press. Dis Tem_ Dis. Press. Dis. Temp.
70 177 162 72 176 162 189 166 74 175 162 189 167 202 171
76 173 162 189 !68 203 173 216 177 78 179 168 190 170 204 174 217 179 230 183 80 195 175 206 177 219 181 232 185
82 211 182 222 184 234 188 24z 192 ....._;_ __i_ii_ii_!;
84 227 188 238 191 249 195 _...._,_,_ _%
86 232 192 242 194 253 197 265 202 88 246 198 257 200 269 204 90 261 203 272 206 92 276 208 94 96
2-1/2 Ton
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100
Suct. Press. DIS. Press 3is. Temp Dis. Press. DR. Temp, DIS. Press. DIS. Temp. D_. Press DIS Temp. )is. Press )_ Temp DIS. Press. Dis. Temp DIS. Press. DIS. Temp.
72 205 163 74 204 163 216 163 76 203 163 216 164 229 164 78 195 158 216 165 229 166 242 167 80 201 163 212 163 230 167 243 169 256 169 82 218 168 23D 168 245 171 258 172 84 235 173 247 173 260 174 273 175 86 252 177 284 177 276 178 88 256 181 268 181 280 181 292 182 90 272 184 284 184 296 184 92 288 187 299 186 94 303 188 96 98
105
)is. Press. Dis. Temp.
I
=o
284 210 _=_ 287 211 t,,_ 290 212
=
105
DIS. Press Dis. Temp O_
"I
311 187 _,) 314 188
317 190 "_
Page 15
3 Ton 0 "_
..0o
OUTDOOR TEMPERATURE(°F) _ _,_
70 75 80 85 90 98 loo lo5 _ Ill
Suct. Press. Dis. Press. Dis. Temp Dis. Press Dis. Temp Dis. Press. Dis. Temp )is. Press. Dis. Temp. Dis. Press Dis. Temp Dis. Pr_s. DisTemp _is. Press. Dis. Temp. Dis. Press. Dis. Temp. _"_1
78 213 168 "1 i
_=# ft,w
72 212 168 225 169 i 74 211 16B 225 !70 239 172 _"_ O 76 205 157 225 171 239 173 253 174 O
78 214 173 225 172 240 175 254 176 268 178 _'_"Q"
--'_
8O
231 177 242 177 256 178 270 180 82 247 182 259 181 271 182 285 184 (D "! 84 264 185 275 186 288 187 _'
86 268 189 280 189 292 189 304 191 _1=
88 284 192 295 192 308 193 _1 90 299 195 311 195 323 196
m.
92 314 197 326 198 '_1 94 329 199
-I
96 _I1
3-1/2 Ton
OUTDOOR TEMPERATURE (°F) _=_
70 75 80 85 90 95 I 100 185
Suct. Press. Dis,Press ]ls. Temp. )is. Press Dis,Temp ]is. Press Dis. Temp. Dis. Press. Dis. Temp. Dis. Press DIs. Temp Dis. Press Dis. Temp. iDis. Press, Dis,Temp. ]is. Press. Dis. Temp. O
70 208 170 O 72 207 171 219 171 _1
74 206 171 219 171 23! 172 76 198 166 219 172 232 173 244 174
O
78 204 171 215 171 232 175 246 176 258 176 _,.
80 221 176 232 176 247 178 260 179
238 180 249 180 262 181 276 182 O82
B4 254 184 266 184 278 185 i_2_'_;;_ 86 259 188 270 188 282 188 294 189 88 275 191 286 190 298 191 90 290 193 301 193 313 193
92 305 195 316 194 94 319 196 96
Page 16
4Ton .O_
OUTDOOR TEMPERArURE(°F)
T0 75 80 85 90 95 100 105
Suct. Press DIS Press Dis. Temp. Dis. Press DisTemp.i DIS. Press. Dis. Temp Dis. Press. Dis. Tamp Dis. Press Dis. Temp. Dis. Press Dis. Temp., Dis. Press. Dis. Temp Dis. Press. Dis. Temp.
65 187 154 67 186 154 199 156
69 185 154 199 157 212 159 71 176 149 198 158 213 161 226 163
73 182 154 195 156 213 162 228 165 24! 168 75 200 161 213 163 229 167 243 170
77 218 168 231 170 245 173 259 176 _ _;;_!_
79 236 174 249 176 262 178 _,_t_i
81 241 178 253 17g 266 181 27g 184 ii_!i_ _ 83 257 182 270 184 283 186 85 274 187 286 188 299 191 87 290 190 302 192
89 305 193 91
5 Ton
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
Suct. Press. Dk. Press Dis. Tamp, DIS. Press. Dis. Temp Dis. Press. Dis. Tamp _is, Press. Dis. Temp. Dis. Press Dis. Temp. DIS. Press. Dis. Temp DIS. Press. Dis, Tamp _)is. Press. Dis, Temp.
62 198 166 64 197 166 211 167
66 196 166 211 16E 226 170 68 187 160 211 169 226 171 241 t73
70 193 166 207 167 227 173 242 175 257 177 72 212 172 226 174 244 177 259 179 74 232 178 248 179 261 182 277 184 76 250 183 265 185 279 187 78 255 187 269 188 283 190 298 193 80 273 192 287 193 301 194 _BI_
82 291 195 305 196 319 198 84 308 198 322 199
86 325 201 B8
O "_
-N
o-
m,
;3
LQ
O
Q.
O
Page 17
2 Ton
OUTDOOR TEMPERATURE (°F) _j_
70 75 80 85 90 95 100 105 Ill
D_. Temp. D_. Press D_. Temp,! )is Press. Dis. Temp. D_, Press. Dis, Temp. Dis, Press. D_. Temp. 3is. Press. Dis. Temp. Dis, Press. D_. Temp. rrl
Suct. Press, Press. Dis.
Temp.
Press.
73 161 132 i _1_
I
75 160 132 171 132 _1_ 77 159 132 171 133 182 134 (_
79 150 126 171 134 183 135 195 136 ___,,
e=
81 156 132 167 132 184 137 196 138 208 138
83 172 137 183 137 197 140 210 141 "=
_t
85 188 142 199 142 212 143 224 145 =l
e-l=
87 204 146 215 146 227 147 89 209 150 220 150 231 150 242 152 :_- 91 224 153 235 153 246 153 _c%_= _ r,_
93 239 156 249 155 260 156 rJ___.
95 253 158 263 157 -I 97 266 159 fJ_
-.I
99 _,1
o-
u)
2-1/2 Ton
_--h
OUTDOOR TEMPERATURE I"F)
70 75 80 85 90 95 100 105
_uct. Press. D_. Press. Dis. Temp, D_. Press. D_. Temp. D_. Press 3is. Temp Dis. Press. D_. Temp. D_. Press. Dis. Temp. D_. Press Dis. Temp Dk. Press. Dis. Temp. D_, Press. Db. Temp,
72 172 143 74 171 !43 184 144 _"
76 170 143 184 145 197 146 #J_ 78 163 139 184 146 197 148 210 149
80 169 145 181 145 198 149 212 151 225 153 O 82 186 150 198 151 213 153 227 155 Q. 84 203 155 215 156 229 158 242 159
86 220 160 232 161 245 162 iii_i_i!i;!_i _;_ ;;_
88 225 164 236 164 249 165 261 167 i;i;_ _ .................
90 241 167 252 168 265 169 _!_7_ _ii;! ,_;_;;_!;;_! "_
256 170 268 171 280 172 __.
92 94 271 173 283 173 _,1 96 2_6 175
O
98
Page 18
O
_o 3 Ton _ M
Orj
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
Suct. Press. 3_.Press D$ Temp _.Press. Dis. Temp D_,Press D_.Temp. D_.Press D_.Temp, Dis,Press 3_.Temp. DB.Press. D_.Temp D_.Press. D_.Temp. D_.Press. D_.Temp
69 164 145 71 163 145 176 145
73 162 145 176 146 189 146 75 155 141 176 147 190 147 203 148 77 161 147 173 146 190 149 204 150 217 150 79 179 _51 191 150 205 152 219 152
81 196 155 208 154 221 155 235 155
83 213 156 22s ls8 23s 158 _i!_i_
85 218 162 229 161 241 161 254 162 87 234 165 245 164 258 164 i_ili_ i_i_i_i
89 249 167 261 166 274 166 91 265 168 276 167 93 279 169
95
3-1/2 Ton
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
Suct. Press. Dis. Press, D_ Temp. DE. Press. Dis Temp D_.Press. DB. Temp. D_.Press !D_.Temp. D_.Press D_.Temp. D_.Press. D_.Tamp. D_.Press. D_.Temp._D_.Press. D_,Temp
69 178 148
71 176 148 189 149 73 175 148 188 150 201 151
75 163 140 188 151 202 153 215 154 77 169 146 182 !47 203 154 216 156 230 158
79 188 153 201 154 218 158 232 161
81 2o6 159 219 160 234 163 248 165
83 224 164 237 166 250 168 _;;!!_ii!i 85 229 168 24! 169 254 171 267 174
87 246 173 258 174 271 175 i_2'8_i _'_O_:_i i 89 262 177 274 177 287 179
91 278 180 290 180
93 293 182 95
c
m.
..,=
--I
E
0'2
o
m,
0
O
Page 19
4 Ton
OUTDOOR TEMPERATURE (°F)
70 75 B0 85 90 95 100
Suct, Press. I_.Prees Dis. Temp. )_.Press. D_.Temp. 3_.Press. D_.Temp IDa. Press. Dis. Temp. D_.Press Dis Temp. D_.Press D_.Temp D_.Press. D_.Temp
66 180 154 68 179 154 193 155 70 178 154 193 156 207 15B 72 171 150 193 157 208 159 222 161 74 17B 156 190 156 208 161 223 163 23B 165 76 196 162 209 162 225 165 240 167 78 214 167 227 168 242 169 257 171
80 232 172 245 173 259 174 82 84 86 88 90 92
O..Pre.O,.Temp.0
o_
237 176 250 176 263 177 277 179
2,_ 179 26T 180 280 1B_ _:_i!_;
271 183 284 183 297 185
287 185 300 186
303 1B8 (,_
* Note: All pressures are listed in psig. and all temperatures in °F.
o
I I o
........... Shaded Boxes indicate flooded conditions
I - Rated Design Values. Suction Pressure will be lower than design
value if indoor air flow, entering dry bulb, or entering wet bulb ,",
temperatures are lower than design, o
- Discharge temperatures greater than charted values indicate an undercharged system.
Page 20
INSTALLER
PLEASE LEAVE THESE
INSTALLATION INSTRUCTIONS
WITH THE HOMEOWNER.
IIIIIIIIIIIIIIIIIIIII
708299A
708299A (Replaces 7082990)
Specificationsand illustrationssubjectto change without
noticeand withoutincurringobligations.(11/03)
Loading...