Nordyne Q3B, Q3C, Q3A, Q3B A, Q3B C Owner's Manual

USER'S MANUAL AND INSTALLATION INSTRUCTIONS
Q3B (A,C) Series 10 and 12 SEER Single Package Heat Pump
Single Package Heat Pump
IMPORTANT
Read this owner information to become familiar with the capabilities and use of your appliance. Keep this with literature of other appliances where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your installing contractor or distributor in your area.
INTRODUCTION
Your heat pump is a unique, all weather com­fort-control system appliance. The basic op­eration of the heating/cooling system is de­scribed on page 2 of this manual. The surpris­ing fact that heat exists in air even at below­freezing temperatures is actually the basic law of physics which the heat pump uses to provide energy saving heating comfort. At outdoor temperatures of 47° Fahrenheit (or 8°
Celsius), your heat pump can deliver approxi­mately 2 to 3 units of heat energy per each unit of electrical energy used, as compared to a maximum of only 1 unit of heat energy pro­duced with conventional heating systems. During the cooling season, the heat pump reverses the flow of the heat-absorbing refrig­erant to become an energy-efficient, central air conditioner.
SECTION 1. OWNER INFORMATION
To Operate Your Heat Pump For Heating —
Your heat pump will heat and cool your home year round, saving your energy dollars. During the summer, a heat pump performs like any normal air conditioner. That is, the excess heat energy inside the home is absorbed by the refrigerant and exhausted outside the home. During the winter months, a heat pump performs like an air conditioner running in reverse. That is, available heat energy outside the home is absorbed by the refrigerant and exhausted inside the home. This is an efficient heating means because you only pay for “moving” the heat from the outdoors to the indoor area. You do not pay to generate the heat, as is the case with more traditional furnace designs.
OPERATING INSTRUCTIONS
To Operate Your Heat Pump in Cooling —
1. Set the thermostat system switch to COOL and the thermostat fan switch to AUTO. (See Figure 1)
2. Set the thermostat temperature selector to the desired cooling temperature. The outdoor unit fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
To Shut Off Air Conditioner
1. Turn the system switch to "Heat" or "Off."
2. Turn the thermostat to the desired heating
temperature setting.
FAN SWITCH
1. Set the thermostat system switch to HEAT and the thermostat fan switch to AUTO. (See Figure 1)
2. Set the thermostat temperature selector to the desired heating temperature. The outdoor unit fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor temperature at the desired heating level.
Defrost — During cold weather heating operation, the outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is normal and the unit will periodically defrost itself. During the defrost cycle, the outdoor fan will stop, while the compressor continues to run and heat the outdoor coil, causing the snow and ice to melt. During defrost, there may be some steam rising from the outdoor unit as the warm coil causes some melted frost to evaporate.
BEFORE YOU CALL A SERVICEMAN
Check your system at the start of each air conditioning season. Make sure it's working correctly, clean or change filters and make any needed adjustments.
In addition, follow these simple rules:
1. Never run your system without a filter. If
you do, the cooling coils will collect dirt and may become clogged.
2. Leave thermostat set at the comfort level
you wish. Let it control the operation of the air conditioning system. If room temp is unsatisfactory, gradually raise the setting until comfort is restored.
3. It takes longer for an air conditioner to cool
your dwelling than it does for your furnace to heat it. So . . . don't turn the unit on and expect an immediate drop in temperature. If your home is hot and humid, the tempera­ture will drop slowly.
4. Check your filters every 30 days to see if
they are dirty. To keep them clean, use a mild solution of detergent and water on washable types. Replace non washable filters.
5. Keep your outdoor condenser coil clean.
(You can hose it down when it gets dirty.)
TEMPERATURE SELECTOR
Figure 1. Typical Heat/Cool Thermostat
2
If your air conditioner isn't working:
1. Make sure the fuses are not blown or that
your circuit breakers are on.
2. See that your thermostat is set at the desired temperature and that your system's switch is on "Cool."
3. For best air flow, make sure your return grille is not covered and that the filter is clean.
4. Check the outdoor condenser coil and make sure it is clean and not clogged with grass or leaves.
If your air conditioner still isn't working, call your nearest distributor.
SECTION 2. INSTALLER INFORMATION
GENERAL
Read the following instructions completely before performing the installation.
These instructions are for the use of qualified personnel specially trained and experienced in the installation of this type of equipment and related system components. Some states re­quire installation and service personnel to be licensed. Unqualified individuals should not attempt to interpret these instructions or install this equipment.
The single packaged heat pumps are designed for outdoor installation only and can be readily connected into the high static duct system of a home. The only connections needed for installation are the supply and return ducts, the line voltage, and thermostat wiring.
The single package heat pump is completely assembled, factory wired, and factory run tested. The units are ready for easy and immediate installation.
this type of equipment. Local codes and regu­lations take precedence over any recommen­dations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation require­ments.
The electrical supply should be checked to determine if adequate power is available. If there is any question concerning the power supply, contact the local power company.
Inspecting Equipment: All units are securely packed at the time of shipment and, upon arrival, should be carefully inspected for dam­age. Claims for damage (apparent or con­cealed) should be filed immediately with the carrier.
INSTALLATION (For Platinum Series ready homes)
1. LOCATE THE 40 AMP BRANCH CIR­CUIT DISCONNECT RECEPTACLE AND DISCONNECT COVER LOCATED OUT­SIDE ON ONE OF THE OUTER WALLS OF THE HOME.
Locate the unit within the reach of the Power Cord assembly and branch circuit receptacle.
• Create a solid, level position, preferably on a
concrete slab or plastic pad (use NORDYNE P/N-903897 or equivalent) and slightly above grade level, located where the skirting chan­nel across top of unit is directly under bottom edge of wall. (See Fig. 2)
• Minimum clearances to obstructions. (See
Fig. 2)
Use of components other than those specified may invalidate ARI Certification, Code Agency Listing, and limited warranty on the heat pump.
PRE-INSTALLATION CHECK
Before any installation is attempted, the cooling load of the area to be conditioned must be calculated and a system of the proper capacity selected. It is recommended that the area to be conditioned be completely insulated and vapor sealed.
The installer should comply with all local codes and regulations which govern the installation of
6 ft.
24"
Skirting Channel
36"
Figure 2. Minimum Unit Clearances
12"
12"
3
2. UNPACK THE UNIT
It is recommended that the unit be unpacked at the installation site to minimize damage due to handling.
a. Remove the bands from around the unit. b. Unfold the top and bottom cap flanges. c . Carefully remove the top cap and tube.
!
CAUTION:
Do not tip the unit on its side. Oil may enter the compressor cylinders and cause starting trouble. If unit has been set on its side, restore to upright posi­tion and do not run for several hours. Then run unit for a few seconds. Do this three or four times with five min­utes between runs.
3. INSTALL THE RETURN AND SUPPLY AIR FITTINGS ON THE UNIT
The supply and return fittings are shipped in the supply duct. They attach to the unit openings with a flange and bead arrangement, secured with two sheet metal screws. Note: For ease of access, install fitting before positioning unit in final location.
CONNECTING THE RETURN AND SUPPLY AIR FLEXIBLE DUCTS
a. Use 12” duct to connect unit to the home
duct system. (See Fig. 3 and 4)
b. Use 14” duct to connect unit to furnace.
(See Fig. 3 and 4)
c. The flexible ducts can be connected to the
corresponding fittings with clamps (field supplied). Note: All connections should be leak tight or a loss in cooling capacity will result.
d. The flexible ducts may be cut to the re-
quired length, see instructions packed with duct. Keep all ducts as short and straight as possible. Avoid sharp bends.
e. Ducts may be spliced with sheet metal
sleeves and clamps.
f. Once the inner duct is connected to the
proper fitting, the insulation and plastic sleeve should be pulled over the connec­tion and clamped.
g. For homes with multiple supply ducts or for
special applications, a Y fitting is available to divide the supply air so it can be ducted to different areas of the home for more efficient cooling/heating. Note: The Y fitting should be insulated for maximum perfor­mance.
CONDENSATE DRAIN
SUPPLY DUCT
Position the supply duct collar so the edge of the unit openings fit between the flange and the bead. Overlap the collar ends keeping the small screw holes underneath. Align the holes in the crimped area and install one screw.
Tap collar as necessary to ensure engagement with unit opening and install second screw. Tighten first screw.
DUCTING SYSTEM
DUCT REQUIREMENTS
THE AIR OUTPUT OF THE SYSTEM WILL NOT CONDITION THE HOME IF THE AIR IS LOST TO THE OUTSIDE THROUGH LEAKS IN THE DUCT SYSTEM. ALSO, DUCTS WHICH ARE COLLAPSED OR RESTRICTED BY FOREIGN OBJECTS WILL PREVENT ADEQUATE AIR FLOW.
A 3/4” condensate drain connection is located on the side of the unit below the electrical compartment. (See Figure 5). A field supplied condensate drain should be installed. Route the condensate to a suitable drainage area. Any connecting tube or hose must have the outlet below the fitting on the unit for proper drainage.
12" Dia.
Supply Air To Main Ducts (2)
Figure 3. Supply Air Fittings
12"
Dia.
Supply Air
From Furnace
14" Dia.
4
Q3B WITH M1 OR E2 FURNACE INSTALLATION
12" Flex Duct
SINGLE DUCT APPLICATION
14" Flex Duct
12" Flex Duct
14" Flex Duct
MULTIPLE DUCT APPLICATION
Figure 4. Typical Applications
5
!
WARNING:
Turn off electrical power before ser­vicing controls. Severe electrical shock may result unless power is turned off. Unit must be installed in compliance with the National Electri­cal Code (NEC) and local codes.
Contactor Lugs
L2 (White) L1 (Black)
Ground (Green)
Low Voltage Connections
Low Voltage Entry
Condensate Drain
Figure 5. Power Entry and Hook Up
High Voltage Entry
ELECTRICAL CONNECTIONS
1. ELECTRICAL SERVICE
HIGH VOLTAGE
a. An approved branch circuit disconnect
receptacle of adequate size and discon­nect cover per NEC has already been installed at the intended location of the unit on one of the four exterior walls of the home.
b. Attach the approved Power Cord/Discon-
nect Plug (NORDYNE P/N-903899) to the unit using a strain relief connector (Romex type or equivalent) through the high voltage knockout provided.
c . Extend the power cord leads up into the
control panel and connect L1 (Black) and L2 (White) directly to the contactor lugs provided. (See Fig. 5)
d. Ground the heat pump unit by attaching the
power cord ground wire (Green-w/ eyelet) to the unit using the green grounding screw provided in the control panel. (See Fig. 5)
LOW VOLTAGE
a. Low voltage wiring from the indoor furnace
and thermostat will be located under the home near the branch circuit receptacle and cover. Route the 24V control wires through the low voltage sealing grommet. (See Figure 5)
b. Connect the low voltage control wires to the
leads in the low voltage compartment as shown in Figure 5 and 6.
6
Figure 6. Low Voltage Connections
Loading...
+ 14 hidden pages