Nordyne P3RA-030K, P3RA-060K, P3RA-048K, P3RA-042K, P3RC-030K Owner's Manual

...
10 and 12 SEER
Single Package Air Conditioner
Single Package Air Conditioner
Read this owner information to become familiar with the capabilities and use of
your appliance. Keep this with literature on other appliances where you have easy access to it in the future. If a problem occurs, check the instructions and follow
recommendations given. If these suggestions don't eliminate your problem, call
INTRODUCTION
Most any air conditioner will keep you cool. Our air conditioner was designed to do it efficiently. Efficiency means less cost to you while keeping you comfortable.
WHY YOUR AIR CONDITIONER WORKS SO WELL, SO QUIETLY
1. Air is cooled by a large evaporator coil. Moisture is also removed from the air by
this same coil.
2. Air is then delivered through the main duct, via registers, into your home.
3. Return air is drawn through the return register.
4. This air enters the unit, passes through the evaporator coil, is cooled and dehumidi-
fied. Then the cycle begins again.
SECTION t. OWNER INFORMATION
OPERATING INSTRUCTIONS
To Turn On Air Conditioner
If you have a heating/cooling thermostat:
1. Set the system switch to "Cool."
2. Set the thermostat at the temperature level you desire.
3. Turn the power on. Your air conditioner should start as soon as room temperature
rises above the setting on the thermostat.
If you have one thermostat for heating and another for cooling, they must be inter- locked to prevent simultaneous operation (See Figure 1):
1. Turn the heating thermostat to its lowest possible setting.
2. If the cooling thermostat has an "On/Off" switch, turn it "On."
3. Set the cooling thermostat to the desired temperature.
4. Turn the power on. Your air conditioner
should start when room temperature ex- ceeds the thermostat setting.
To Shut Off Air Conditioner
If you have a heating/cooling thermostat:
1. Turn the system switch to "Heat" or "Off."
2. Turn the thermostat to the desired heating temperature setting.
3. If you are turning yourairconditionerofffor the winter or an extended period, shut off
the power to the air conditioner.
If you have one thermostat for heating and another for cooling, they must be
interlocked to prevent simultaneous operation (See Figure I):
1. Turn your cooling thermostat "Off" or to its highest setting.
2. Turn the heating thermostat to the desired
temperature.
3. If you are turning your air conditioner off for the winter or aM extended period, shut off
the power to the air conditioner.
BEFORE YOU CALL A SERVICEMAN Let your serviceman check your system at the
start of each air conditioning season. He will make sure it'sworking right, clean or change filters and make any needed adjustments.
In addition, follow these simple rules:
1. Never runyour system without filter. Ifyou do, the coolingcoils will get dirty and may
become dogged.
2. Set your thermostat at the comfort level you wish -- and then leave it alone. Let it
control the operation of the air conditioning system. Ifyou get chilly, turn itup a degree
at a time until comfort is restored.
3. It takes longer for an air conditionerto cool your dwelling than it does for your furnace
to heat it. So... don't turnthe uniton and
expect a dramatic drop in temperature, at least notdght away. Ifyourhome ishotand
humid, the temperature will drop slowly.
4. Check your filters every ten days in sum-
mer to see if they are dirty. To keep them
clean, use a mild solutionofdetergent and water on washable types. Replace non
washable filters.
5. Keep your outdoor condenser coil clean. You can hose it down when it gets dirty.
If your air conditioner isn't working:
1. Make sure the fuses are not blown or that your circuit breakers are on.
2. See that your thermostat is set at the
desired temperature andthat your system's
switch is on "Cool."
3. For free air flow, make sure your return register is not covered and that the filter is clean.
4. Check the outdoor condenser coil and make sure it is clean and not clogged with
grass or leaves.
if your air conditioner still isn'tworking, call your
nearest distributor.
Cooling Furnace
Thermostat Thermos1
Double Throw
Double Po_ Switch
3"o Air Conditio TM To Furnace
Figure 1. Thermostat Interlock System
2
SECTION 2. INSTALLER INFORMATION
GENERAL
Read the following instructions completely before performing the installation,
These instructionsare for the use of qualified
personnel specially trained and experienced in the installation of this type of equipment and related system components. Some states re- quire installation and service personnel to be
licensed. Unqualified individuals should not attempt to interpret these instructions or install
this equipment.
The single packaged air conditioners are de- signed for outdoor installationonly and can be readily connected into the high static duct system of a home. The only connections needed for installation are the supply and return ducts, the line voltage, and thermostat wiring. A complete air conditioning system typically
consists of:
Single Package Air Conditioner
Home Fittings Kit
Unit Fittings Kit
Thermostat
The single package air conditioner is com-
pletely assembled, factory wired, and factory run tested. The units are ready for easy and
immediate installation.
PRE-INSTALLATION CHECK
Before any installationis attempted, the cooling
load of the area to be conditioned must be calculated and a system of the proper capacity
selected. Itis recommended that the area to be conditioned be completely insulated and vapor
sealed.
The installer should comply with all local codes and regulations which govern the installationof this type of equipment. Local codes and regulations take precedence over any recom-
mendations contained in these instructions. Consult local building codes and the National
Electrical Code (ANSI Cl) for special installa-
tion requirements.
Inspecting Equipment: All units are securely packed at the time of shipment and, upon
arrival, should be carefully inspected for dam- age. Claims for damage (apparent or con-
cealed) should be filed immediately with the carrier.
INSTALLATION
1. SELECT THE BEST LOCATION FOR
THE AIR CONDITIONING UNIT
IMPORTANT: DO NOT PLACE UNIT UNDER THE HOME.
Select a solid, level position, preferably on a
concrete slab, slightly above the grade level, and parallel to the home.
The hot condenser air must be discharged
up and away fi'om the home, and if possible, in a direction with the prevailing wind.
De not place the unit in a confined space.
If practical, place the air conditioner where it
and the ducts will be shaded from the after- noon sun when the heat load is greatest.
Try to select a site for the unitthat is as close
as possible to the proposed return grille location.
Keep inmind that the length ofthe supply and
return ducts should be kept to a minimum with no sharp radiused bends.
2. UNPACK THE UNIT
It is recommended that the unit be unpacked at
the installation site to minimize damage due to handling.
CAUTION:
Do not tip the unit on its side. Oil may
enter the compressor cylinders and
cause starting trouble. If unit has been
set on its side, restore to upright posi- tion and do not run for several hours.
Then run unit for a few seconds. Do this three or four times with five min-
utes between runs.
The electrical supply should be checked to determine if adequate power is available. If there is any question concerning the power supply, contact the local power company.
a. Remove the bands from around the unit. b. Unfold the top and bottom cap flanges.
c. Carefully remove the top cap and tube.
6ft.
Figure 2. Minimum Unit Clearances
3. INSTALL THE RETURN AND SUPPLY AIR FITTINGS ON THE UNIT
The supply and returnfittings are included with select models. If supplied, the duct fittings are shipped in the supply duct. They attach to the unitopenings with a flange and bead arrange-
ment, secured with two sheet metal screws. Note: For ease of access, install fitting before
positioningunitin final location.
SUPPLY DUCT Positionthe supplyduct collar,ifsupplied,sothe
edge ofthe unitopening fitsbetween the flange and the bead. Overlap the collar ends keeping the small screw holes underneath. Align the
holes inthe crimped area and installone screw.
Note: It may be necessary to loosen the four screws that hold the transition duct in order to
installthe supply fitting. Re-tighten when instal- lation is complete.
Tap collar as necessary to ensure engagement with unit opening and install second screw.
Tighten first screw. Rotate collar clockwise so
joint is near three o'clock position.
RETURN DUCT The 12" return duct is installed in the same
manner as the supply duct. Ifthe unit has a 14"
return, follow these instructions.
10 SEER Return
Model eia. (in)
2 Ton 12 2 1/2 Ton 12
3 Ton 12 3 1/2 Ton 12
4 Ton 14
5 Ton 14
12 SEER Return
Model Dia. (in)
2 Ton 12 2 1/2 Ton 12
3 Ton 12 3 1/2 Ton 14
4 Ton 14
Align the slots with the holes in the collar and
install two screws. Position the collar over the opening and align the four notches inthe collar
with the four dimples in the panel. Using self-
ddlling screws (10-16x.5) attach the collar to
the rear panel.
4. LOCATING AND INSTALLING THE RE-
TURN AIR ASSEMBLY
To avoid complications, locate and install the
return air assembly first. The return air box with grille and filter (Figure 4) should not be located
in heavy traffic areas like hallways or center of rooms. A good spot is in a corner or under a
table, if a minimum two inch clearance is avail- able. If desired, the return opening can be
located inside a closet with Iouvered doors that have an open area equal to or greater than the
12"x 20" grille furnished. The return airgrille can
be placed in the wall of acloset and the air ducted into the filter box through a boxed-in area at the
closet floor level. Make sure the filter is readily accessible.
After determining the location of the return air opening, start the installation from under the
home by cutting a small hole in the fiber underboard to determine hew the floor joist
:ILTER
CUT FLOOR
Supply Air Return Air
Figure 3. Return and Supply Air Fittings
4
Figure 4. Return Air Box
location will affect cutting the opening needed
for the box. Floor joists generally are located on
16" centers, leaving 14-3/8" between joists. After measuring the return air box (approxi- mately 12-1/4" x 14-1/4"), cut the hole through
the floor so that the box will fit between the floor
joists. Careshould betakenwhen cuttingthrough
carpeting to avoid snags. In most installations it will be necessary to cut a similar hole in the fiberboard directly under the hole in the floor.
However, if the floor is more than ten inches deep, it will only be necessary to cut a hole for
the collar on the return air box orforthe insulated duct.
Set the box into the opening and fasten with screws or nails. Put the filter and return air grille
in place.
5. LOCATING AND INSTALLING THE SUPPLY DAMPER(S)
CAUTION:
When a home is not equipped with a
make-ready kit means must be pro-
vided to prevent simultaneous opera- tion of the heating and cooling units. A
heat/cool thermostat is available for this purpose.
When installing this air conditioning system in conjunction with a furnace,
a damper must be installed in the fur- nace base assembly to prevent cold air being discharged around the heat exchanger. Damage to the heat ex- changer and asphyxiation may occur
ifa damper is not installed.
Figure 5. Supply Damper
nearest register. The round supply opening in
the slanted side of the damper should face the
side of the home where the air conditioner is located. To locate the center of the heat duct,
first cut a small hole in the fiberboard below the
duct at the desired location. After locating the duct center, cut a hole approximately 3/4" larger
than the damper opening in the fiberboard. Cut a 9-1/8" x 13-1/8" hole in the duct and bend over
all tabs flat on the inside of the heat duct. After inserting the damper into the duct, bend over all
tabs flat on the inside of the heat duct. Seal the opening between the fiberboard and damper or
flexible duct.
DUCTINGSYSTEM
DUCT REQUIREMENTS The supply duct system, including the number
and type of registers, will have much more
effect on the performance ofan air conditioning system than any other factor. The duct must
be sufficiently large to conduct an adequate amount of air to each register.
THE AIR CONDITIONING OUTPUT OF THE SYSTEM WILL NOT COOL THE HOME IF THE AiR IS LOST TO THE OUTSIDE THROUGH LEAKS IN THE DUCT SYSTEM. ALSO, DUCTS WHICH ARE COLLAPSED OR
RESTRICTED BY FOREIGN OBJECTS WILL PREVENT ADEQUATE AIR FLOW.
Check with the furnace manufacturer for damper requirements. Failure to
install the required furnace damper may invalidate code agency listing and
limited warranty on the furnace.
When locating the supply damper(s), carefully
check floor joists and frame members that could interferewith the installation ofthe damper
or flexible duct. Ideally, the damper should be located in the bottom of the main duct, forward
ofcenter ofthe home, at least three feet from the
Note: For highly resistive duct systems it may be necessary to add an additional return air duct
and or supply to achieve maximum perfor-
mance and prevent coil icing and refrigerant
flood back.
CONNECTING THE RETURN AND SUPPLY
AIR FLEXIBLE DUCTS
a.
The supply duct for all units istwelve inches in diameter. The return duct may be 12" or
14" diameter depending on unit size. (See
Table on page 4).
5
Loading...
+ 11 hidden pages