Nordyne O5LD-091A-12-R Maintenance Manual

Installation, Operation and
Maintenance Manual
Oil Fired Warm Air Furnaces
O5LD-091A-12-R (Lowboy Model)
FOR YOUR SAFETY:
Do not store or use gasoline or other flammable liquids or
ALL INSTALLATIONS MUST MEET ALL
LOCAL, PROVINCIAL/STATE, AND
FEDERAL CODES WHICH MAY
DIFFER FROM THIS MANUAL
Read this complete manual before beginning installation. These instructions must be kept with the furnace for future reference.
964D-0712
NORDYNE INC.
240009611 Rev A 05/2012
TABLE OF CONTENTS
1. INTRODUCTION............................................................................................................ 3
2. HEAT LOSS .................................................................................................................. 3
3. LOCATION OF UNIT....................................................................................................... 3
4. AIR CONDITIONING APPLICATIONS................................................................................. 3
5. COMBUSTION AIR......................................................................................................... 4
6. CHIMNEY VENTING ....................................................................................................... 4
7. BAROMETRIC DAMPER CONTROL..................................................................................... 4
8. FAN TIMER BOARD AND LIMIT CONTROL.......................................................................... 5
9. ELECTRICAL CONNECTIONS ........................................................................................... 5
10. HUMIDIFIER ............................................................................................................... 6
11. PIPING INSTALLATION................................................................................................. 6
12. OIL FILTER.................................................................................................................6
13. OIL BURNER NOZZLES................................................................................................. 6
14. OIL BURNER ADJUSTMENT ........................................................................................... 6
15. BURNER ELECTRODES ................................................................................................. 6
16. BURNER PRIMARY (SAFETY) CONTROL ........................................................................... 7
17. COMBUSTION CHAMBER .............................................................................................. 7
18. CIRCULATING AIR BLOWER .......................................................................................... 7
19. MAINTENANCE AND SERVICE........................................................................................ 8
20. OPERATING INSTRUCTIONS.......................................................................................... 9
A.1 OIL BURNER AIR ADJUSTMENT .....................................................................................10
A.2 BURNER ELECTRODES .................................................................................................10
A.3 START UP ..................................................................................................................10
OPERATION OF OIL BURNER ..............................................................................................15
FINAL CHECK OUT ............................................................................................................21
PARTS LISTING ................................................................................................................23
2
IMPORTANT: 3. LOCATION OF UNIT
SAVE THESE INSTRUCTIONS FOR FUTURE
REFERENCE
1. INTRODUCTION
Please read these instructions completely and carefully before installing and operating the furnace.
MODELS O5LD-091A-12-R
Model O5LD-091A-12-R is an oil fired forced air up­flow furnace with an output capacity range of 59,000 BTU/Hr. to 85,000 BTU/Hr.
DO NOT USE GASOLINE, CRANK CASE OIL, OR ANY OIL CONTAINING GASOLINE.
All models are CSA listed, (NRTL/C) for use with No. 1 (Stove) and No. 2 (Furnace) Oil. Please refer to the tables in Appendix A for performance and dimensional data.
In Canada, the installation of the furnace and related equipment shall be installed in accordance with the
regulations of CAN/CSA - B139, Installation Code For Oil-Burning Equipment, as well as in accordance with
local codes.
In the United States of America, the installation of the furnace and related equipment shall be installed in accordance with the regulations of NFPA No. 31,
Standard for the Installation of Oil-Burning Equipment
as well as in accordance with local codes.
Regulations prescribed in the National Codes and Local regulations take precedence over the general instructions provided on this installation manual. When in doubt, please consult your local authorities.
All models are furnace should be carefully inspected for damage when being unpacked.
shipped assembled and pre-wired. The
,
2. HEAT LOSS
The maximum hourly heat loss for each heated space shall be calculated in accordance with the procedures described in the manuals of the Heating, Refrigeration and Air Conditioning Institute of Canada (HRAI), or by other means prescribed, or approved by the local authority having jurisdiction.
In the United States, Manual Calculation" published by the Air Conditioning Contractors of America, describes a suitable procedure for calculating the maximum hourly heat loss.
J. titled,
"Load
The furnace should be located such that the flue connection to the chimney is short, direct and consists
as few elbows as possible. When possible, the unit
of should be centralized with respect to the supply return air ductwork. A central location minimizes the trunk duct sizing. All models may be installed on combustible floors.
The minimum installation clearances are listed in Table
1.
and
Table 1: Clearances – (Inches)
Location Clearance to Combustibles
Top
Bottom
S/A Plenum
Rear Sides Front
1
0
1
6*
1**
1*
4 in. measured horizontally or
Flue Pipe
below flue pipe. 8 in. measured vertically or above flue pipe
Enclosure
Closet
** 18 in. required on one side for service access to rear
* 24 in. required for service clearance
4. AIR CONDITIONING APPLICATIONS
If the furnace is used in conjunction with air conditioning, with
or upstream from the evaporator coil to avoid condensation in the heat exchanger. In a parallel installation, the dampers or air controlling means must prevent chilled air from entering the furnace. If the dampers are manually operated, there must be a means of control to prevent the operation of either system unless the dampers are in the full heat or full cool position. The air heated by the furnace shall not pass through a refrigeration unit unless the unit is specifically approved for such service.
The blower speed must be checked and adjusted compensate for evaporator coil. Refer to Appendix B for recommended wiring and electrical connections of the air conditioning controls.
the furnace shall be installed in parallel
to
the pressure drop caused by the
3
5. COMBUSTION AIR
If the furnace is installed in a closet or utility room, two openings must be provided connecting to a well­ventilated space (full basement, living room or other room opening thereto, but not a bedroom or bathroom). One opening shall be located above the level of the upper vent opening and one opening below the combustion air inlet opening in the front of the furnace. Each opening shall have a minimum free area of 1½ square inches per 1,000 Btu/h of total input rating of all appliances installed in the room.
For furnaces located in buildings of unusually tight construction, such as those with high quality weather stripping, caulking, windows and doors, or storm sashed windows, or where basement windows are well sealed, a permanent opening communicating with a well ventilated attic or with the outdoors shall be provided, using a duct if necessary. The duct opening shall have a free area of 1½ square inches per 1,000 Btu/h of total input rating of all appliances to be installed. When a furnace is installed in a full basement, infiltration is normally adequate to provide air for combustion and draft operation. Furnace rooms under 65m³ (700 ft³) should automatically be treated as confined space.
The flue pipe must not pass through any floor or ceiling, but may pass through a wall where suitable fire protection provisions have been installed. Refer to the latest edition of CAN/CSA B-139 for rules governing the installation of oil burning equipment. In the United States, refer to the latest edition of NFPA 31 for regulations governing the installation of oil burning equipment.
See appendix A for burner set-up.
Fig. 1: Checking Over-Fire Draft.
6. CHIMNEY VENTING
The flue pipe should be as short as possible with horizontal pipes sloping upward toward the chimney at a rate of one-quarter inch to the foot. The flue pipe should not be smaller in cross sectional area than the flue collar on the furnace. The flue pipe should connect to the chimney such that the flue pipe extends into, and terminates flush with the inside surface of the chimney liner. Seal the joint between the pipe and the lining. The chimney outlet should be at least two feet above the highest point of a peaked roof. All unused chimney openings should be closed. Chimneys must conform to local, provincial or state codes, or in the absence of local regulations, to the requirements of the National Building Code.
NOTE: THE FURNACE IS APPROVED FOR USE WITH TYPE L VENT OR EQUIVALENT.
CHIMNEY VENTED VERSIONS OF THE FURNACE MUST BE CONNECTED TO A FLUE HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF THE APPLIANCE.
7. BAROMETRIC DAMPER CONTROL.
The barometric damper control, also known as a draft regulator, is used on conventional chimney venting only. This control automatically maintains a constant negative pressure in the furnace to obtain maximum efficiency. It ensures that proper pressures are not exceeded. If the chimney does not develop sufficient draft, the draft control cannot function properly. The draft regulator, when installed should be in the same room or enclosure as the furnace and should not interfere with the combustion air supplied to the burner. The control should also be located near the furnace flue outlet and installed according to the instructions supplied with the regulator. The flue outlet pressure (measured between the furnace and draft regulator, or the oil burner mounting plate over-fired draft access port. Fig 1) should be set to -0.02 in. w.c.
NOTE: THE RECOMMENDED OVER-FIRE DRAFT PRESSURE IS -0.02 IN. W.C. (SEE FIG.
1).
4
8. FAN TIMER BOARD AND LIMIT CONTROL (FIG.2) (page 17)
The Electronic Fan Timer integrates control of all burner and circulator fan operations. This control is the central wiring point for most of the electrical
components in the furnace. The United Technologies 1158-120 has an adjustable fan on time
that is set by selecting the dipswitch combination displayed in Chart 1. This fan on delay can be set at 30, 60, 90 or 120 seconds. This provides a delay between the burner ignition and blower start-up to eliminate excessive flow of cold air when the blower
comes on. The United Technologies 1158-120 has
an adjustable fan off time of 2, 3, 4 or 6 minutes displayed in Chart 1. The fan off delay time starts when the burner motor is de-energized at the end of a call for heat. Blower shutdown is delayed to remove any residual heat from the heat exchanger and improve the annual efficiency of the furnace.
The electronic fan timer board works in conjunction with snap disc limit controls, which perform a safety function, and breaks power to the oil burner primary control, which shuts off the burner if the furnace over­heats. The limit control is thermally operated and automatically resets. The limit control is factory installed pre-set and is not adjustable.
If the limit control opens with the United Technologies 1158-120 electronic fan control, the circulating fan will
be energized as well. When the limit closes, the fan off timer will begin. At the end of the fan off time cycle the burner will be energized, initiating a normal burner
cycle.
CHART 1
United Technologies 1158-120 Dip Switch Position Blower Delay Times 1 2 3 4 On
Seconds
Off
Minutes
Off Off 30 On Off 60 Off On 90 On On 120
Off Off 2 On Off 3 Off On 4 On On 6
9. ELECTRICAL CONNECTIONS
The furnace is listed by the Canadian Standards Association under the NRTL (North American) Standard. It is factory wired and requires minimal field wiring. All field wiring should conform to CAN/CSA C22.1 Canadian Electrical Code, Part 1, and by local codes, where they prevail. In the United States, the wiring must be in accordance with the National Fire Protection Association NFPA-70, National Electrical Code, and with local codes and regulations.
The furnace should be wired to a separate and dedicated circuit in the main electrical panel; however, accessory equipment such as electronic air cleaners and humidifiers may be included on the furnace circuit. Although a suitably located circuit breaker can be used as a service switch, a separate service switch is advisable. The service switch is necessary if reaching the circuit breaker involves becoming close to the furnace, or if the furnace is located between the circuit breaker and the means of entry to the furnace room. The furnace switch (service switch) should be clearly marked, installed in an easily accessible area between the furnace and furnace room entry, and be located in such a manner to reduce the likelihood that it would be mistaken as a light switch or similar device.
The power requirement for the O5LD-091A-12-R model is: 120 VAC, 1 Ø, 60 Hz., 12A.
Accessories requiring 120 VAC power sources such as electronic air cleaners and humidifier transformers may
be powered from the electronic fan timer board where
provisions have been made for connections, but should have their own controls. Do not use the direct drive motor connections as a power source, since there is a high risk of damaging the accessories by exposure to high voltage from the auto-generating windings of the direct drive motor.
5
Thermostat wiring connections and air conditioning contactor low voltage connections are shown in the wiring diagrams in Appendix B. Some micro-electronic thermostats require additional controls and wiring. Refer to the thermostat manufacturer's instructions.
The thermostat should be located approximately 5 feet above the floor, on an inside wall where there is good natural air circulation, and where the thermostat will be exposed to average room temperatures. Avoid locations where the thermostat will be exposed to cold drafts, heat from nearby lamps and appliances, exposure to sunlight, heat from inside wall stacks, etc.
The thermostat heat anticipator should be adjusted to the amperage draw of the heating control circuit as measured at the "R" and "W" terminals of the thermostat. To reduce the risk of damaging the heat anticipator, do not measure this current with the thermostat connected to the circuit. Measure the amperage by connecting an ammeter between the two wires that will connect to the thermostat "R" and "W" terminals.
10. HUMIDIFIER
A humidifier is an optional accessory available through most heating supplies outlets. Installation should be carried out in accordance with the humidifier manufacturer's installation instructions. Water or water droplets from the humidifier should not be allowed to come into contact with the furnace heat exchanger. Do not use direct drive motor connections as a source of power for 120 VAC humidifiers and humidifier transformers.
11. PIPING INSTALLATION
The entire fuel system should be installed in accordance with the requirement of CAN/CSA B-139, and local regulations. Use only an approved fuel oil tanks piping, fittings and oil filter.
In the United States the installation must be in accordance with NFPA No. 31 and local codes and authorities.
Install the oil filter as close to the burner as possible. For further details of the oil supply tank and piping requirements, please refer to the instructions and illustrations in the oil burner and oil pump instructions shipped with the furnace.
12. OIL FILTER
All fuel systems should include an oil filter between the fuel oil storage tank and the oil burner. When using an oil burner nozzle smaller than 0.65 U.S. Gallons Per Hour, install an additional 7 to 10 micron filter as close as possible to the oil burner.
13. OIL BURNER NOZZLES
The O5LD-091A-12-R is certified for multiple firing rates, ranging from 70,000 to 105,000 Btu/h. By manipulating the oil burner nozzle, flame retention head, static plate and temperature rise; the furnace may be fired at an ideal rate for a wide range of structures. Refer to Table A-1, and the furnace rating plate to determine the proper combinations.
14. OIL BURNER ADJUSTMENT
The burner air supply is adjusted to maintain the fuel to air ratio to obtain ideal combustion conditions. A lack of
air causes "soft" and "sooty" flames, resulting in soot build-up throughout the heat exchanger passages. Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel efficiency. The O5LD-091A-12-R furnace operates most efficiently with a No. 1 smoke spot on the Bacharach Scale. This is not necessarily the optimum setting; however, because dust will inevitably build up on the air moving components of the oil burner assembly. This will result in decreased air supply with the potential result of soot building up in the flue gas passageways of the heat exchanger. Soot behaves as an insulator and impairs good heat transfer. Stack temperature will increase, and the overall efficiency will decrease. As a means of avoiding this problem, it is advisable to adjust the air supply to provide no more than a trace smoke spot on the Bacharach Scale.
BEFORE OPERATING THE FURNACE CHECK BURNER ALIGNMENT WITH COMBUSTION CHAMBER. THE END CONE OF THE AIR TUBE MUST BE CENTRED TO THE ACCOMODATING RING PROVIDED IN THE DESIGN OF THE COMBUSTION CHAMBER. ADJUST AS NECESSARY.
15. BURNER ELECTRODES
Correct positioning of the electrode tips with respect to each other, to the fuel oil nozzle, and to the rest of the burners is essential for smooth light ups and proper operation. Refer to the oil burner instructions shipped with the furnace for electrode specifications.
NOTE: Beckett AF Series Burner electrode specifications have been revised. They should be adjusted to be 5/16” above the nozzle centerline.
6
16. Burner Primary (Safety) Control
The furnace is equipped with a primary combustion control, sometimes referred to as the burner relay or burner protector relay, which uses a light sensing device (cad cell) located in the burner housing, to monitor and control combustion. Over time, dust or combustion residuals can build up on the lens of the cad cell impairing its response to the flame. The cad cell should be checked for cleanliness and proper alignment if the primary control frequently shuts down combustion.
ALL FURNACE CONTROLS ARE SENSITIVE AND SHOULD NOT BE SUBJECTED TO TAMPERING. IF PROBLEMS PERSIST, CALL YOUR SERVICE CONTRACTOR.
17. COMBUSTION CHAMBER
This furnace is equipped with a high quality cerafelt combustion chamber. It is held in place by a retaining bracket.
CHECK THE ALIGNMENT OF THE COMBUSTION CHAMBER AND OIL BURNER BEFORE FIRING. IT IS POSSIBLE FOR THE COMBUSTION CHAMBER TO SHIFT IF SUBJECTED TO ROUGH HANDLING DURING TRANSIT.
inspected for damage or carbon build up whenever the oil burner is removed for repairs or routine maintenance.
The combustion chamber should be
DO NOT START THE BURNER UNLESS THE BLOWER ACCESS DOOR IS SECURED IN PLACE.
18. CIRCULATING AIR BLOWER
The O5LD-091A-12-R furnace model is equipped with PSC motor Direct Drive blower systems. Direct drive blower speed adjustments are not normally required in properly sized extended plenum duct systems. The motor RPM and air CFM delivery will vary automatically to accommodate conditions within the usual range of external static pressures typical of residential duct systems. Under-sized duct systems may require a higher blower speed to obtain a reasonable system temperature rise. Some older duct systems were not designed to provide static pressure. They typically feature special reducing fittings at each branch run and lack block ends on the trunk ducts.
7
This system may require modification to provide some resistance to the airflow to prevent over-amping of the direct drive blower motor. Selecting a lower blower speed may correct this problem. Direct drive blower speeds are adjusted by changing the "hot" wires to the motor winding connections. Please refer to wiring diagrams in Appendix B or the wiring diagram label
affixed to the furnace. THE NEUTRAL WIRE
(normally the white wire) IS NEVER MOVED TO ADJUST THE BLOWER SPEED.
It is possible and acceptable to use a single blower speed for both heating and cooling modes. The simplest method to connect the wiring from both modes is to use a "piggy-back connector" accommodating both wires on a single motor tap. It is also acceptable to connect the selected motor speed with a pigtail joined to both heating and cooling speed wires with a wire nut. As a safety precaution against accidental disconnection of the wires by vibration, it is advisable to secure the wire nut and wires with a few wraps of electricians tape.
DO NOT CONNECT POWER LEADS BETWEEN MOTOR SPEEDS. THE NEUTRAL WIRE MUST ALWAYS BE CONNECTED TO THE MOTOR'S DESIGNATED NEUTRAL TERMINAL.
If the joining of the blower speed wiring is done in the furnace junction box, tape off both ends of the unused wire.
Do not use the blower speed wires as a source of power to accessories as electronic air cleaners and humidifier transformers. The unused motor
taps auto-generate sufficiently high voltages to damage accessory equipment.
DISCONNECT THE POWER SUPPLY TO THE FURNACE BEFORE OPENING THE BLOWER ACCESS DOOR TO SERVICE THE AIR FILTER, FAN AND MOTOR. FAILURE TO SHUT OFF POWER COULD ALLOW THE BLOWER TO START UNEXPECTEDLY, CREATING A RISK OF DEATH OR PERSONAL INJURY.
19. MAINTENANCE AND SERVICE
Annual Service By Contractor
A: Routine Maintenance By Home Owner
Other than remembering to arrange for the annual professional servicing of the furnace by the service or installation contractor, the most important routine service performed by the homeowner is to maintain the air filter or filters. A dirty filter can cause the furnace to over-heat, fail to maintain indoor temperature during cold weather, increase fuel consumption and cause component failure.
The furnace filter(s) should be inspected, cleaned or replaced monthly. The furnace is factory equipped with a semi-permanent type filter. If the filter is damaged, replace with filters of the same size and type. (See Appendix A, Table A-8).
During the routine service, inspect the general condition of the furnace watching for signs of oil leaks in the vicinity of the oil burner, soot forming on any external part of the furnace, soot forming around the joints in the vent pipe, etc. If any of these conditions are present, please advise your service or installation contractor.
THE COMBUSTION CHAMBER (FIREPOT) IS FRAGILE. USE CARE WHEN INSPECTING AND CLEANING THIS AREA.
The heat exchanger should be inspected periodically and cleaned if necessary. If cleaning is necessary,
SHUT OFF POWER TO THE FURNACE and remove
the burner. Using a stiff brush with a wire handle, brush off scale and soot from inside the drum and flue pipe. To clean the radiator, remove the clean-out caps screws, and remove the caps carefully to avoid tearing the gaskets. A wire brush can be used to loosen dirt and debris on the inside surfaces of the radiator. Clean out all accumulated dirt, soot and debris with a wire handled brush and an industrial vacuum cleaner. Before replacing the clean-out caps, inspect the gaskets. If the gaskets are broken, remove the remnants and replace with new gaskets.
The blower motor is factory oiled and permanently
sealed. DO NOT LUBRICATE. Excess oil causes
premature electric failure.
Inspect the blower fan. Clean if necessary.
Oil Burner Maintenance: Follow the instructions of the oil burner manufacturer. (See oil burner manufacturer's instructions supplied with furnace or burner). It is advisable to change the oil burner nozzle and oil filter on an annual basis.
The venting system should be cleaned and inspected for signs of deterioration. Replace pitted or perforated vent pipe and fittings. The barometric damper should open and close freely.
All electrical connections should be checked to ensure tight connections. Safety controls such as the high limit controls should be tested for functionality. The fan control should be checked to ensure that the fan on and off delay function continues to start and stop the blower fan at the optimal settings.
8
20. OPERATING INSTRUCTIONS
Before Lighting
Open all supply and return air registers and grilles.
Open all valves in oil pipes.
Turn on electric power supply.
To Light Unit
Set the thermostat above room temperature to call for heat. The burner should start. NOTE: It may be necessary to press the RESET button on the primary combustion control relay.
To Shut Down Unit
Set the thermostat to the lowest possible setting.
Set the manual
switch (if installed) in the Electrical
Power Supply Line to "OFF".
NOTE: IF THE FURNACE IS TO BE SHUT DOWN FOR AN EXTENDED PERIOD OF TIME, CLOSE THE OIL SUPPLY VALVE TO THE BURNER.
There will be a fan on time delay before the circulating
fan is energized. The United Technologies 1158-120
has an adjustable fan on time that is set by selecting the dipswitch combination displayed in Chart 1. This fan on delay can be set at 30, 60, 90 or 120.
Set the thermostat below room temperature. The oil burner should stop.
air circulation blower will continue to run until the
The time off setting selected on the electronic fan timer
control times out. The United Technologies 1158-120
have an adjustable fan off time of 2, 3, 4, & 6 minutes. The fan timer control adjustments may be altered if the air at the room registers is uncomfortably high upon blower start up or shutdown.
The necessary adjustments to the fan control settings should the
be determined by measuring the temperature of
air
in the supply air take-off, or within the first few inches of the supply air trunk. The side mid point of the transition is usually ideal, providing that the thermometer probe is beyond the "line of sight" wherein false readings from radiant heat could be
observed. The system temperature rise is the
difference in temperature between the supply air and return air.
To check the operation of the limit switch, shut off power to the furnace. Temporarily remove the neutral wire from the direct drive blower motor. Restore the electrical power to the furnace and set the thermostat above room temperature.
After three or four minutes of burner operation, the limit control should turn the burner off. When the limit function test is complete, shut off electrical power to the furnace, replace the neutral wire to the blower fan motor, and then restore power. The blower fan will start up immediately. Once the temperature has dropped and the limit control has reset, the fan will operate until the fan off time is achieved. The oil burner will then resume operation and continue until the thermostat is satisfied. Restore the thermostat setting to a comfortable temperature.
DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED, WHEN THE FURNACE IS FULL OF VAPOUR, OR WHEN THE COMBUSTION CHAMBER IS VERY HOT. NEVER BURN GARBAGE OR PAPER IN THE FURNACE, AND NEVER LEAVE PAPER OR RAGS AROUND THE UNIT.
9
Loading...
+ 19 hidden pages