A.3 START UP ..................................................................................................................10
OPERATION OF OIL BURNER ..............................................................................................15
FINAL CHECK OUT ............................................................................................................21
PARTS LISTING ................................................................................................................23
2
Page 3
IMPORTANT: 3. LOCATION OF UNIT
SAVE THESE INSTRUCTIONS FOR FUTURE
REFERENCE
1. INTRODUCTION
Please read these instructions completely and
carefully before installing and operating the furnace.
MODELS O5LD-091A-12-R
Model O5LD-091A-12-R is an oil fired forced air upflow furnace with an output capacity range of 59,000
BTU/Hr. to 85,000 BTU/Hr.
DO NOT USE GASOLINE, CRANK CASE OIL,
OR ANY OIL CONTAINING GASOLINE.
All models are CSA listed, (NRTL/C) for use with No. 1
(Stove) and No. 2 (Furnace) Oil. Please refer to the
tables in Appendix A for performance and dimensional
data.
In Canada, the installation of the furnace and related
equipment shall be installed in accordance with the
regulations of CAN/CSA - B139, Installation Code For Oil-Burning Equipment, as well as in accordance with
local codes.
In the United States of America, the installation of the
furnace and related equipment shall be installed in
accordance with the regulations of NFPA No. 31,
Standard for the Installation of Oil-Burning Equipment
as well as in accordance with local codes.
Regulations prescribed in the National Codes and
Local regulations take precedence over the general
instructions provided on this installation manual. When
in doubt, please consult your local authorities.
All models are
furnace should be carefully inspected for damage
when being unpacked.
shipped assembled and pre-wired. The
,
2. HEAT LOSS
The maximum hourly heat loss for each heated space
shall be calculated in accordance with the procedures
described in the manuals of the Heating, Refrigeration
and Air Conditioning Institute of Canada (HRAI), or by
other means prescribed, or approved by the local
authority having jurisdiction.
In the United States, Manual
Calculation" published by the Air Conditioning
Contractors of America, describes a suitable
procedure for calculating the maximum hourly heat
loss.
J. titled,
"Load
The furnace should be located such that the flue
connection to the chimney is short, direct and consists
as few elbows as possible. When possible, the unit
of
should be centralized with respect to the supply
return air ductwork. A central location minimizes the
trunk duct sizing. All models may be installed on
combustible floors.
The minimum installation clearances are listed in Table
1.
and
Table 1: Clearances – (Inches)
Location Clearance to Combustibles
Top
Bottom
S/A Plenum
Rear
Sides
Front
1
0
1
6*
1**
1*
4 in. measured horizontally or
Flue Pipe
below flue pipe.
8 in. measured vertically or
above flue pipe
Enclosure
Closet
** 18 in. required on one side for service
access to rear
* 24 in. required for service clearance
4. AIR CONDITIONING APPLICATIONS
If the furnace is used in conjunction with air
conditioning,
with
or upstream from the evaporator coil to avoid
condensation in the heat exchanger. In a parallel
installation, the dampers or air controlling means must
prevent chilled air from entering the furnace. If the
dampers are manually operated, there must be a
means of control to prevent the operation of either
system unless the dampers are in the full heat or full
cool position. The air heated by the furnace shall not
pass through a refrigeration unit unless the unit is
specifically approved for such service.
The blower speed must be checked and adjusted
compensate for
evaporator coil. Refer to Appendix B for recommended
wiring and electrical connections of the air conditioning
controls.
the furnace shall be installed in parallel
to
the pressure drop caused by the
3
Page 4
5. COMBUSTION AIR
If the furnace is installed in a closet or utility room, two
openings must be provided connecting to a wellventilated space (full basement, living room or other
room opening thereto, but not a bedroom or
bathroom). One opening shall be located above the
level of the upper vent opening and one opening below
the combustion air inlet opening in the front of the
furnace. Each opening shall have a minimum free area
of 1½ square inches per 1,000 Btu/h of total input
rating of all appliances installed in the room.
For furnaces located in buildings of unusually tight
construction, such as those with high quality weather
stripping, caulking, windows and doors, or storm
sashed windows, or where basement windows are well
sealed, a permanent opening communicating with a
well ventilated attic or with the outdoors shall be
provided, using a duct if necessary. The duct opening
shall have a free area of 1½ square inches per 1,000
Btu/h of total input rating of all appliances to be
installed. When a furnace is installed in a full
basement, infiltration is normally adequate to provide
air for combustion and draft operation. Furnace rooms
under 65m³ (700 ft³) should automatically be treated as
confined space.
The flue pipe must not pass through any floor or
ceiling, but may pass through a wall where suitable fire
protection provisions have been installed. Refer to the
latest edition of CAN/CSA B-139 for rules governing
the installation of oil burning equipment. In the United
States, refer to the latest edition of NFPA 31 for
regulations governing the installation of oil burning
equipment.
See appendix A for burner set-up.
Fig. 1: Checking Over-Fire Draft.
6. CHIMNEY VENTING
The flue pipe should be as short as possible with
horizontal pipes sloping upward toward the chimney at
a rate of one-quarter inch to the foot. The flue pipe
should not be smaller in cross sectional area than the
flue collar on the furnace. The flue pipe should connect
to the chimney such that the flue pipe extends into,
and terminates flush with the inside surface of the
chimney liner. Seal the joint between the pipe and the
lining. The chimney outlet should be at least two feet
above the highest point of a peaked roof. All unused
chimney openings should be closed. Chimneys must
conform to local, provincial or state codes, or in the
absence of local regulations, to the requirements of the
National Building Code.
NOTE: THE FURNACE IS APPROVED FOR
USE WITH TYPE L VENT OR EQUIVALENT.
CHIMNEY VENTED VERSIONS OF THE
FURNACE MUST BE CONNECTED TO A
FLUE HAVING SUFFICIENT DRAFT AT ALL
TIMES TO ENSURE SAFE AND PROPER
OPERATION OF THE APPLIANCE.
7. BAROMETRIC DAMPER CONTROL.
The barometric damper control, also known as a draft
regulator, is used on conventional chimney venting
only. This control automatically maintains a constant
negative pressure in the furnace to obtain maximum
efficiency. It ensures that proper pressures are not
exceeded. If the chimney does not develop sufficient
draft, the draft control cannot function properly. The
draft regulator, when installed should be in the same
room or enclosure as the furnace and should not
interfere with the combustion air supplied to the
burner. The control should also be located near the
furnace flue outlet and installed according to the
instructions supplied with the regulator. The flue outlet
pressure (measured between the furnace and draft
regulator, or the oil burner mounting plate over-fired
draft access port. Fig 1) should be set to -0.02 in. w.c.
NOTE: THE RECOMMENDED OVER-FIRE
DRAFT PRESSURE IS -0.02 IN. W.C. (SEE FIG.
1).
4
Page 5
8. FAN TIMER BOARD AND LIMIT CONTROL
(FIG.2) (page 17)
The Electronic Fan Timer integrates control of all
burner and circulator fan operations. This control is the
central wiring point for most of the electrical
components in the furnace. The United Technologies 1158-120 has an adjustable fan on time
that is set by selecting the dipswitch combination
displayed in Chart 1. This fan on delay can be set at
30, 60, 90 or 120 seconds. This provides a delay
between the burner ignition and blower start-up to
eliminate excessive flow of cold air when the blower
comes on. The United Technologies 1158-120 has
an adjustable fan off time of 2, 3, 4 or 6 minutes
displayed in Chart 1. The fan off delay time starts when
the burner motor is de-energized at the end of a call
for heat. Blower shutdown is delayed to remove any
residual heat from the heat exchanger and improve the
annual efficiency of the furnace.
The electronic fan timer board works in conjunction
with snap disc limit controls, which perform a safety
function, and breaks power to the oil burner primary
control, which shuts off the burner if the furnace overheats. The limit control is thermally operated and
automatically resets. The limit control is factory
installed pre-set and is not adjustable.
If the limit control opens with the United Technologies 1158-120 electronic fan control, the circulating fan will
be energized as well. When the limit closes, the fan off
timer will begin. At the end of the fan off time cycle the
burner will be energized, initiating a normal burner
cycle.
CHART 1
United Technologies 1158-120
Dip Switch Position Blower Delay Times
1 2 3 4 On
Seconds
Off
Minutes
Off Off 30
On Off 60
Off On 90
On On 120
Off Off 2
On Off 3
Off On 4
On On 6
9. ELECTRICAL CONNECTIONS
The furnace is listed by the Canadian Standards
Association under the NRTL (North American)
Standard. It is factory wired and requires minimal field
wiring. All field wiring should conform to CAN/CSA
C22.1 Canadian Electrical Code, Part 1, and by local
codes, where they prevail. In the United States, the
wiring must be in accordance with the National Fire
Protection Association NFPA-70, National Electrical
Code, and with local codes and regulations.
The furnace should be wired to a separate and
dedicated circuit in the main electrical panel; however,
accessory equipment such as electronic air cleaners
and humidifiers may be included on the furnace circuit.
Although a suitably located circuit breaker can be used
as a service switch, a separate service switch is
advisable. The service switch is necessary if reaching
the circuit breaker involves becoming close to the
furnace, or if the furnace is located between the circuit
breaker and the means of entry to the furnace room.
The furnace switch (service switch) should be clearly
marked, installed in an easily accessible area between
the furnace and furnace room entry, and be located in
such a manner to reduce the likelihood that it would be
mistaken as a light switch or similar device.
The power requirement for the O5LD-091A-12-R
model is: 120 VAC, 1 Ø, 60 Hz., 12A.
Accessories requiring 120 VAC power sources such as
electronic air cleaners and humidifier transformers may
be powered from the electronic fan timer board where
provisions have been made for connections, but
should have their own controls. Do not use the direct
drive motor connections as a power source, since
there is a high risk of damaging the accessories by
exposure to high voltage from the auto-generating
windings of the direct drive motor.
5
Page 6
Thermostat wiring connections and air conditioning
contactor low voltage connections are shown in the
wiring diagrams in Appendix B. Some micro-electronic
thermostats require additional controls and wiring.
Refer to the thermostat manufacturer's instructions.
The thermostat should be located approximately 5 feet
above the floor, on an inside wall where there is good
natural air circulation, and where the thermostat will be
exposed to average room temperatures. Avoid
locations where the thermostat will be exposed to cold
drafts, heat from nearby lamps and appliances,
exposure to sunlight, heat from inside wall stacks, etc.
The thermostat heat anticipator should be adjusted to
the amperage draw of the heating control circuit as
measured at the "R" and "W" terminals of the
thermostat. To reduce the risk of damaging the heat
anticipator, do not measure this current with the
thermostat connected to the circuit. Measure the
amperage by connecting an ammeter between the two
wires that will connect to the thermostat "R" and "W"
terminals.
10. HUMIDIFIER
A humidifier is an optional accessory available through
most heating supplies outlets. Installation should be
carried out in accordance with the humidifier
manufacturer's installation instructions. Water or water
droplets from the humidifier should not be allowed to
come into contact with the furnace heat exchanger. Do
not use direct drive motor connections as a source of
power for 120 VAC humidifiers and humidifier
transformers.
11. PIPING INSTALLATION
The entire fuel system should be installed in
accordance with the requirement of CAN/CSA B-139,
and local regulations. Use only an approved fuel oil
tanks piping, fittings and oil filter.
In the United States the installation must be in
accordance with NFPA No. 31 and local codes and
authorities.
Install the oil filter as close to the burner as possible.
For further details of the oil supply tank and piping
requirements, please refer to the instructions and
illustrations in the oil burner and oil pump instructions
shipped with the furnace.
12. OIL FILTER
All fuel systems should include an oil filter
between the fuel oil storage tank and the oil
burner. When using an oil burner nozzle smaller
than 0.65 U.S. Gallons Per Hour, install an
additional 7 to 10 micron filter as close as
possible to the oil burner.
13. OIL BURNER NOZZLES
The O5LD-091A-12-R is certified for multiple firing
rates, ranging from 70,000 to 105,000 Btu/h. By
manipulating the oil burner nozzle, flame retention
head, static plate and temperature rise; the furnace
may be fired at an ideal rate for a wide range of
structures. Refer to Table A-1, and the furnace rating
plate to determine the proper combinations.
14. OIL BURNER ADJUSTMENT
The burner air supply is adjusted to maintain the fuel to
air ratio to obtain ideal combustion conditions. A lack of
air causes "soft" and "sooty" flames, resulting in soot
build-up throughout the heat exchanger passages.
Excess combustion air causes a bright roaring fire and
high stack temperatures resulting in poor fuel
efficiency. The O5LD-091A-12-R furnace operates
most efficiently with a No. 1 smoke spot on the
Bacharach Scale. This is not necessarily the optimum
setting; however, because dust will inevitably build up
on the air moving components of the oil burner
assembly. This will result in decreased air supply with
the potential result of soot building up in the flue gas
passageways of the heat exchanger. Soot behaves as
an insulator and impairs good heat transfer. Stack
temperature will increase, and the overall efficiency will
decrease. As a means of avoiding this problem, it is
advisable to adjust the air supply to provide no more
than a trace smoke spot on the Bacharach Scale.
BEFORE OPERATING THE FURNACE
CHECK BURNER ALIGNMENT WITH
COMBUSTION CHAMBER. THE END
CONE OF THE AIR TUBE MUST BE
CENTRED TO THE ACCOMODATING
RING PROVIDED IN THE DESIGN OF
THE COMBUSTION CHAMBER. ADJUST
AS NECESSARY.
15. BURNER ELECTRODES
Correct positioning of the electrode tips with respect to
each other, to the fuel oil nozzle, and to the rest of the
burners is essential for smooth light ups and proper
operation. Refer to the oil burner instructions shipped
with the furnace for electrode specifications.
NOTE: Beckett AF Series Burner electrode
specifications have been revised. They should be
adjusted to be 5/16” above the nozzle centerline.
6
Page 7
16. Burner Primary (Safety) Control
The furnace is equipped with a primary combustion
control, sometimes referred to as the burner relay or
burner protector relay, which uses a light sensing
device (cad cell) located in the burner housing, to
monitor and control combustion. Over time, dust or
combustion residuals can build up on the lens of the
cad cell impairing its response to the flame. The cad
cell should be checked for cleanliness and proper
alignment if the primary control frequently shuts down
combustion.
ALL FURNACE CONTROLS ARE SENSITIVE
AND SHOULD NOT BE SUBJECTED TO
TAMPERING. IF PROBLEMS PERSIST, CALL
YOUR SERVICE CONTRACTOR.
17. COMBUSTION CHAMBER
This furnace is equipped with a high quality cerafelt
combustion chamber. It is held in place by a retaining
bracket.
CHECK THE ALIGNMENT OF THE
COMBUSTION CHAMBER AND OIL BURNER
BEFORE FIRING. IT IS POSSIBLE FOR THE
COMBUSTION CHAMBER TO SHIFT IF
SUBJECTED TO ROUGH HANDLING DURING
TRANSIT.
inspected for damage or carbon build up whenever the
oil burner is removed for repairs or routine
maintenance.
The combustion chamber should be
DO NOT START THE BURNER UNLESS THE
BLOWER ACCESS DOOR IS SECURED IN
PLACE.
18. CIRCULATING AIR BLOWER
The O5LD-091A-12-R furnace model is equipped with
PSC motor Direct Drive blower systems. Direct drive
blower speed adjustments are not normally required in
properly sized extended plenum duct systems. The
motor RPM and air CFM delivery will vary
automatically to accommodate conditions within the
usual range of external static pressures typical of
residential duct systems. Under-sized duct systems
may require a higher blower speed to obtain a
reasonable system temperature rise. Some older duct
systems were not designed to provide static pressure.
They typically feature special reducing fittings at each
branch run and lack block ends on the trunk ducts.
7
This system may require modification to provide some
resistance to the airflow to prevent over-amping of the
direct drive blower motor. Selecting a lower blower
speed may correct this problem. Direct drive blower
speeds are adjusted by changing the "hot" wires to the
motor winding connections. Please refer to wiring
diagrams in Appendix B or the wiring diagram label
affixed to the furnace. THE NEUTRAL WIRE
(normally the white wire) IS NEVER MOVED TO
ADJUST THE BLOWER SPEED.
It is possible and acceptable to use a single blower
speed for both heating and cooling modes. The
simplest method to connect the wiring from both
modes is to use a "piggy-back connector"
accommodating both wires on a single motor tap. It is
also acceptable to connect the selected motor speed
with a pigtail joined to both heating and cooling speed
wires with a wire nut. As a safety precaution against
accidental disconnection of the wires by vibration, it is
advisable to secure the wire nut and wires with a few
wraps of electricians tape.
DO NOT CONNECT POWER LEADS
BETWEEN MOTOR SPEEDS. THE NEUTRAL
WIRE MUST ALWAYS BE CONNECTED TO
THE MOTOR'S DESIGNATED NEUTRAL
TERMINAL.
If the joining of the blower speed wiring is done in the
furnace junction box, tape off both ends of the unused
wire.
Do not use the blower speed wires as a source of
power to accessories as electronic air cleaners
and humidifier transformers. The unused motor
taps auto-generate sufficiently high voltages to
damage accessory equipment.
DISCONNECT THE POWER SUPPLY TO THE
FURNACE BEFORE OPENING THE BLOWER
ACCESS DOOR TO SERVICE THE AIR
FILTER, FAN AND MOTOR. FAILURE TO
SHUT OFF POWER COULD ALLOW THE
BLOWER TO START UNEXPECTEDLY,
CREATING A RISK OF DEATH OR
PERSONAL INJURY.
Page 8
19. MAINTENANCE AND SERVICE
Annual Service By Contractor
A: Routine Maintenance By Home Owner
Other than remembering to arrange for the annual
professional servicing of the furnace by the service or
installation contractor, the most important routine
service performed by the homeowner is to maintain the
air filter or filters. A dirty filter can cause the furnace to
over-heat, fail to maintain indoor temperature during
cold weather, increase fuel consumption and cause
component failure.
The furnace filter(s) should be inspected, cleaned or
replaced monthly. The furnace is factory equipped with
a semi-permanent type filter. If the filter is damaged,
replace with filters of the same size and type. (See
Appendix A, Table A-8).
During the routine service, inspect the general
condition of the furnace watching for signs of oil leaks
in the vicinity of the oil burner, soot forming on any
external part of the furnace, soot forming around the
joints in the vent pipe, etc. If any of these conditions
are present, please advise your service or installation
contractor.
THE COMBUSTION CHAMBER (FIREPOT) IS
FRAGILE. USE CARE WHEN INSPECTING
AND CLEANING THIS AREA.
The heat exchanger should be inspected periodically
and cleaned if necessary. If cleaning is necessary,
SHUT OFF POWER TO THE FURNACE and remove
the burner. Using a stiff brush with a wire handle,
brush off scale and soot from inside the drum and flue
pipe. To clean the radiator, remove the clean-out caps
screws, and remove the caps carefully to avoid tearing
the gaskets. A wire brush can be used to loosen dirt
and debris on the inside surfaces of the radiator. Clean
out all accumulated dirt, soot and debris with a wire
handled brush and an industrial vacuum cleaner.
Before replacing the clean-out caps, inspect the
gaskets. If the gaskets are broken, remove the
remnants and replace with new gaskets.
The blower motor is factory oiled and permanently
sealed. DO NOT LUBRICATE. Excess oil causes
premature electric failure.
Inspect the blower fan. Clean if necessary.
Oil Burner Maintenance: Follow the instructions of the
oil burner manufacturer. (See oil burner manufacturer's
instructions supplied with furnace or burner). It is
advisable to change the oil burner nozzle and oil filter
on an annual basis.
The venting system should be cleaned and inspected
for signs of deterioration. Replace pitted or perforated
vent pipe and fittings. The barometric damper should
open and close freely.
All electrical connections should be checked to ensure
tight connections. Safety controls such as the high limit
controls should be tested for functionality. The fan
control should be checked to ensure that the fan on
and off delay function continues to start and stop the
blower fan at the optimal settings.
8
Page 9
20. OPERATING INSTRUCTIONS
Before Lighting
Open all supply and return air registers and grilles.
Open all valves in oil pipes.
Turn on electric power supply.
To Light Unit
Set the thermostat above room temperature to call for
heat. The burner should start. NOTE: It may be
necessary to press the RESET button on the primary
combustion control relay.
To Shut Down Unit
Set the thermostat to the lowest possible setting.
Set the manual
switch (if installed) in the Electrical
Power Supply Line to "OFF".
NOTE: IF THE FURNACE IS TO BE SHUT DOWN
FOR AN EXTENDED PERIOD OF TIME, CLOSE THE
OIL SUPPLY VALVE TO THE BURNER.
There will be a fan on time delay before the circulating
fan is energized. The United Technologies 1158-120
has an adjustable fan on time that is set by selecting
the dipswitch combination displayed in Chart 1. This
fan on delay can be set at 30, 60, 90 or 120.
Set the thermostat below room temperature. The oil
burner should stop.
air circulation blower will continue to run until the
The
time off setting selected on the electronic fan timer
control times out. The United Technologies 1158-120
have an adjustable fan off time of 2, 3, 4, & 6 minutes.
The fan timer control adjustments may be altered if the
air at the room registers is uncomfortably high upon
blower start up or shutdown.
The necessary adjustments to the fan control settings
should
the
be determined by measuring the temperature of
air
in the supply air take-off, or within the first few
inches of the supply air trunk. The side mid point of the
transition is usually ideal, providing that the
thermometer probe is beyond the "line of sight"
wherein false readings from radiant heat could be
observed. The system temperature rise is the
difference in temperature between the supply air and
return air.
To check the operation of the limit switch, shut off
power to the furnace. Temporarily remove the neutral
wire from the direct drive blower motor. Restore the
electrical power to the furnace and set the thermostat
above room temperature.
After three or four minutes of burner operation, the limit
control should turn the burner off. When the limit
function test is complete, shut off electrical power to
the furnace, replace the neutral wire to the blower fan
motor, and then restore power. The blower fan will
start up immediately. Once the temperature has
dropped and the limit control has reset, the fan will
operate until the fan off time is achieved. The oil burner
will then resume operation and continue until the
thermostat is satisfied. Restore the thermostat setting
to a comfortable temperature.
DO NOT ATTEMPT TO START THE BURNER
WHEN EXCESS OIL HAS ACCUMULATED,
WHEN THE FURNACE IS FULL OF VAPOUR, OR
WHEN THE COMBUSTION CHAMBER IS VERY
HOT. NEVER BURN GARBAGE OR PAPER IN
THE FURNACE, AND NEVER LEAVE PAPER OR
RAGS AROUND THE UNIT.
9
Page 10
APPENDIX A – O5LD-091A-12-R
O5LD-091A-12-R furnace may be used with the following oil burners.
Please note: The Beckett AF oil burner is for applications using indoor air for combustion only.
Table A-1 Beckett AF Oil Burner Set-Up
Beckett AF Series Oil Burners
(For use with chimney vented units only)
Furnace Model
Output
BTU/Hr
Burner
Model
Nozzle
Pump
Pressure
Flow
Rate
Head 1
Static
Plate
O5LD-070A-12-R2 59,000 AF76BNHS
O5LD-091A-12-R
76,000 AF76BNHS
O5LD-105A-12-R 85,000 AF76BNHS
1
Head is shielded by ceramic insulator. 2 Low Firing Rate Baffle required when using a 0.50-gallon
0.50 /
80°A
0.65 /
80°A
0.75 /
80°A
100 psig
100 psig
100 psig
0.50
usgph
0.65
usgph
0.75
usgph
F3 3- in.
F3 3- in.
F3 3- in.
nozzle. Bold models indicate the factory equipped firing rate.
A.1 OIL BURNER AIR ADJUSTMENT
For complete details, consult the oil burner instruction
manual provided in the furnace documents envelope.
Beckett AF Burner
Adjust the air shutter by loosening the locking screws
and moving the air shutter, and if necessary, the bulk
air band.
A.2 BURNER ELECTRODES
Adjustment of the electrode tips with respect to each
other, the nozzle, and to the rest of the burner is very
important to ensure smooth start-ups and to permit
efficient combustion.
Beckett AF Burner
Electrode gap: 5/32 inch.
Distance above horizontal centerline: 5/16 inch. Older
instruction sheets specify 7/16 inch. The current
specification is 5/16 inch.
Distance ahead of nozzle: 1/16 inch.
“Z” dimension, the distance from the front of the end
cone (head) to the face of the nozzle should be 1-1/8
inches. If a ceramic head is used, the distance from
the end cone to the nozzle face is increased to 1-3/8
inches.
A.3 START UP
The furnace should be operated for a minimum of 10
minutes to reach steady state conditions before fine
tuning combustion. The warm up time is ideal for
testing the oil pump pressure.
Drill a 1/4-inch test port in the venting between the
furnace flue outlet and draft regulator (barometric
damper). Insert a stack thermometer and note the flue
gas temperature. The flue gases should be within a
range of 350°F to 450°F. If the flue gases are below
the range, it may be necessary to slow down the
blower fan. If the flue gases are above the range, the
blower fan may require speeding up. Stack
temperature varies directly with the system
temperature rise. System temperature rise is the
difference between the furnace outlet temperature and
furnace inlet temperature as measured in the vicinity of
the connection between the plenum take-offs and the
trunk ducts. Temperature rise value is listed on the
system rating plate.
Perform a smoke spot test. The smoke spot should not
exceed No. 1 on the Bacharach Scale.
10
Page 11
After the air adjustments have been completed,
re-check the draft pressure at the test port on the
burner mounting plate as shown in Figure 2. The draft
should be adjusted to -0.02 inches w.c.
In the United States, the Beckett AF Burner may be
equipped with Beckett's "Inlet Air Shut-Off" to increase
efficiency. (Beckett Part No. AF/A 5861).
NOTE: USE OF THE INLET AIR SHUT-OFF COULD
CAUSE POST COMBUSTION NOZZLE DRIP.
11
Page 12
Table A-5 Direct Drive Blower Set-Up
Blower Set-Up Cooling Capacity
0.20 in. w.c. 0.50 in. w.c.
Furnace Model Blower
Speed Motor Speed Motor
Tons Power
CFM
Range
O5LD-070A-12-R
10-10T
DD Low 1/2 HP Med-Low1/2 HP 3 1/2 HP 700 – 1600
O5LD-091A-12-R
10-10T
DD Med-Low1/2 HP Med-Low1/2 HP 3 1/2 HP 700 – 1600
O5LD-105A-12-R
10-10T
DD Med-Low1/2 HP
Med-
High 1/2 HP 3 1/2 HP 700 – 1600
Table A-6 Direct Drive Blower Characteristics
CFM
External Static Pressure – Inches w.c.
Furnace Model Blower
Motor
HP
Motor
FLA
T
Speed
0.2 0.3 0.4 0.5 0.6
High
1722 1645 1516 1462 1375
O5LD-A-12-R
Med-
High
1604 1545 1473 1383 1302
Med-
Low
1147 1133 1106 1063 1013
070 - 105
10-10T
DD
1/2 HP 7.1 70°F
Low
747 738 720 702 669
12
Page 13
13
CABINET PLENUM OPENINGS FLUE
WIDTH
A
LENGTH
B
HEIGHT
C
SUPPLY
D X E
RETURN
F X G
DIAM.
HEIGHT
H
FILTER
(PERM)
SHIP
WEIGHT
(LBS.)
O5LD-091A-12-R
22 51½ 32 20½ x 19 20½ x 18½ 5 26.25 20 x 20 x 1240
Table A-9: General Dimensions (Inches)
Page 14
Chimney Vent Burner Wiring Diagram
O5LD-091A-12-R
APPENDIX B: WIRING DIAGRAMS
14
Page 15
OPERATION OF OIL BURNER
Once the furnace flue pipe, electrical and oil line
connections have been made, use the following
instructions to set the burner:
Shut off the electrical power to the furnace.
Install an oil pressure gauge to the pressure port on
the oil pump. (Refer to the oil pump specification sheet
included with the burner instructions).
Restore electrical power to the furnace.
Start the furnace and bleed all air from the fuel oil
lines.
Close the purge valve and fire the unit.
Allow the furnace to warm up to normal operating
temperatures. During this time, set the pump pressure
in accordance with the data provided in Appendix A,
Table A-2, and A-5.
When the furnace has reached "steady state" (after
approximately 10 minutes). Set combustion air damper
to get a TRACE of smoke.
Check the system temperature rise. The temperature
rise is the difference between the return air temperature
measured at a point near the return air inlet, and the
supply air temperature measured near the furnace
outlet. The system temperature rise is listed on the
furnace rating plate. If the temperature rise is too high,
the airflow must be increased. If the temperature rise is
too low, the fan should be slowed down.
Set the heat anticipator adjustment in the
thermostat (if so equipped), by removing the "R"
or "W" wire to the thermostat, then reading the
amperage draw between the two wires. Failure to
remove one of the wires from the thermostat while
performing this test could burn out the heat
anticipator. Set the heat anticipator to the
amperage measured.
NOTE: THE FURNACE SHOULD BE RUN
THROUGH AT LEAST THREE FULL CYCLES
BEFORE LEAVING THE INSTALLATION, TO
ENSURE THAT ALL CONTROLS ARE OPERATING
PROPERLY AND AS EXPECTED.
NOTE: ALL JOINTS IN ANY POSITIVE
PRESSURE VENTING SYSTEM MUST BE
CHECKED FOR LEAKS BEFORE LEAVING
THE INSTALLATION SITE
Turn off the burner. Observing the duct thermometer in
the supply air stream, note the temperature at which
the blower fan stops. The fan adjustments can be
made by moving the dipswitch settings on the timer
control board for fan off delay.
To check the operation of the limit switch, shut off
power to the furnace. Temporarily remove the
neutral wire from the direct drive blower motor.
Restore the electrical power to the furnace and
set the thermostat above room temperature. After
three or four minutes of burner operation, the limit
control should turn the burner off. When the limit
function test is complete, shut off electrical power
to the furnace, replace the neutral wire to the
blower fan motor, and then restore power. The
blower fan will start up immediately. Once the
temperature has dropped and the limit control has
reset, the fan will operate until the fan off time is
achieved. The oil burner will then resume
operation and continue until the thermostat is
satisfied. Restore the thermostat setting to a
comfortable temperature.
15
Page 16
Table C-1: 1158-120 ELECTRONIC FAN TIMER (EFT) DETAILED SEQUENCE OF OPERATION
Mode Action System Response
EFT closes the oil primary control T - T connections).
Thermostat calls for heat. ("W"
terminal is energized).
Thermostat ends call for heat.
HEAT
COOL
FAN
LIMIT
FAN
EAC
HUM Humidity control is connected. Humidifier connections are energized when the oil burner motor is energized.
("W" terminal is de-energized).
Burner fails to light.
Established flame fails.
Thermostat begins call for cool.
(G and Y terminals are
energized).
Thermostat ends call for cool. (G
and Y terminals are deenergized).
Thermostat begins call for fan.
(G terminal is energized).
Thermostat ends call for fan. (G
terminal is de-energized).
Limit switch string opens.
Limit switch string closes (with
existing call for heat).
Limit switch string closes
(without existing call for heat).
Continuous circulating fan is
connected.
Electronic Air Cleaner is
connected.
Ignition system and the oil primary control start the furnace. Oil flows as long as the oil
primary control senses flame.
Burner motor is energized and heat "fan on" delay timing begins. When timing is
complete, the circulator fan is energized at heat speed.
The oil primary control is de-energized, terminating the burner cycle.
Heat "fan off" delay timing begins. Length of delay depends on EFT dipswitch settings.
When timing is complete, the circulator fan is de-energized.
EFT returns to standby mode, (Oil primary control and circulator fan are off, unless
continuous fan operation is selected at the thermostat).
Oil primary control locks out within lockout timing, (30 seconds).
Burner motor is de-energized. (Even though thermostat is still calling for heat).
If circulator fan has started, it continues through the selected heat “fan off” delay
period.
Burner motor is de-energized and oil primary control goes into recycle mode.
If the selected heat “fan off” delay timing is longer than the recycle delay timing, the
circulator fan continues to run through the next trial for ignition.
Cooling contactor is energized immediately.
Circulator fan is energized at cool speed.
Cooling contactor is de-energized immediately.
Circulator fan turns off immediately.
Circulator fan is energized immediately at cooling speed.
Circulator fan is de-energized immediately.
Oil primary control shuts off burner.
Circulator fan is energized immediately at heat speed.
EFT opens the oil primary control T - T connections. Circulating fan runs as long as
limit string stays open.
If there is a call for cooling or fan, the circulating fan switches from heating to cooling
speed.
EFT begins heat “fan off” delay sequence.
Circulating fan turns off after the selected heat “fan off” timing.
EFT re-closes the oil primary control T - T connections.
Oil primary control is energized, initiating burner light off.
Circulator fan turns off when heat “fan off” delay time is complete.
Normal operation resumes; EFT control is in standby mode awaiting next thermostat
command.
Circulating fan is energized when there is no call for heat, cool, or fan.
If fan operation is required by a call for heat, cool, or fan, the EFT switches off the
continuous fan speed tap before energizing the other fan speed.
Electronic air cleaner (EAC) connections are energized when the heat or cool speed of
the circulator fan is energized. EAC connections are not energized when the optional
continuous fan terminal is energized.
16
Page 17
FIGURE 2: UNITED TECHNOLOGIES 1158-120 FAN TIMER BOARD (O5LD-019A-12-R)
17
Page 18
Troubleshooting
IMPORTANT: Due to the potential hazard
of line voltage, only a trained, experienced
service technician should perform the
troubleshooting procedure.
PRELIMINARY STEPS:
Check the diagnostic light for indications of burner
condition. Refer to the oil primary control LED
DIAGNOSTIC LIGHT section for details.
WHEN SIMULATING A CALL FOR HEAT
AT THE OIL PRIMARY CONTROL,
DISCONNECT AT LEAST ONE
THERMOSTAT LEAD WIRE FROM THE T1 T2 TERMINALS TO PREVENT DAMAGE TO
THE THERMOSTAT. NEGLECTING THIS
PROCEDURE MAY BURN OUT THE HEAT
ANTICIPATOR OF A STANDARD 24 VAC
THERMOSTAT, OR CAUSE HARM TO
COMPONENTS WITHIN A MICROELECTRONIC THERMOSTAT.
Check Oil Primary Control and Igniter
If the trouble does not appear to be in the burner or
ignition hardware, check the oil primary control and the
igniter by using the following equipment:
Screwdriver, Voltmeter (0 - 150 V
Insulated jumper wires with both ends stripped.
AC)
ELECTRICAL SHOCK HAZARD.
TROUBLESHOOTING IS DONE WITH THE
SYSTEM POWERED. BE CAREFUL TO OBSERVE
ALL NECESSARY PRECAUTIONS TO PREVENT
ELECTRICAL SHOCK OR EQUIPMENT DAMAGE.
Preliminary Checks:
Make sure that limit switches are closed and contacts are
clean.
Check for line voltage power on the oil primary control
black and white lead wires.
Before checking the oil primary control, perform
these preliminary checks, (repair or replace
controls as necessary):
Check the power supply; fuse box or
breaker, any service switches, all wiring
connections, and burner motor reset
button (if equipped).
Check the limit switches to ensure that the
switch contacts are closed.
Check the electrode gap and position.
Check the contacts between the oil
primary control and the electrodes.
Check oil supply (tank gauge).
Check the oil nozzle, oil filter, and oil
valves.
Check the piping or tubing to the oil tank.
Check the oil pump pressure.
Refer to Table C-4 or C-5 for further troubleshooting
information.
18
Page 19
Table C4: System and General Troubleshooting
Problem Possible Cause Remedy
Check thermostat and adjust. Also, check thermostat for accuracy; if it is
a mercury switch type, it might be off level.
Check furnace switch, main electrical panel furnace fuse or circuit
breaker. Also look for any other hand operated switch, such as an old
poorly located furnace switch, which was not removed during furnace
replacement.
Remove thermostat wires from oil primary control terminals T-T. Place a
jumper across T-T. If furnace starts, replace thermostat, thermostat subbase (if equipped), or both.
Check reset button on oil primary control. Remove thermostat wires
from oil primary control terminals T1 - T2. Check for 24V across T -T. If
no voltage is present, check for 115V to oil primary control. If 115V is
present, go to Table C-3.
Check photo cell (cad cell) wiring for short circuits. Also, check for room
light leaking into cad cell compartment. Repair light leak if necessary.
See Table C-3.
Check for open limit or auxiliary limit. Also, check internal wiring
connections; loose connectors, etc.
Check fuel oil supply. Check that all hand operated fuel oil valves are in
the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate or Tables
in Appendix A as a guide.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace
oil pump if necessary. Ensure that erratic pressure readings are not
caused by defective fuel oil line.
Check fuel oil lines. Replace any compression fittings found with high
quality flared fittings. Check for any signs of oil leaks. Any oil leak is a
potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load,
determine why. Replace if necessary.
If cad cell is dirty, clean it. (Determine why cad cell is getting dirty). If
cad cell is poorly aimed, realign it. NOTE: The photocell should have a
resistance of 100K in absence of light; a maximum of 1500 in the
presence of light. Ensure that room light is not leaking into the cad cell
compartment. (See diagnostic light section).
Check fuel oil supply. Check that all hand operated fuel oil valves are in
the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate or Tables
in Appendix A as a guide.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace
oil pump if necessary. Ensure that erratic pressure readings are not
caused by defective fuel oil line.
Check fuel oil lines. Replace any compression fittings found with high
quality flared fittings. Check for any signs of oil leaks. Any oil leak is a
potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load,
determine why. Replace if necessary.
Furnace will not warm home
to desired temperature.
Electrodes out of adjustment or
defective.
Poor transformer high voltage
connections or defective
transformer.
Fuel oil filter clogged. Replace fuel oil storage tank filter and / or fuel oil in-line filter.
Defective oil pump.
Fuel oil line partially clogged or
contains air.
System temperature rise too high.
Poor “fan off” delay timing
selection, (fan stops too soon).
Fuel oil leak. Check fuel oil line for leaks. Repair or replace if necessary.
Stack temperature too high.
Thermostat improperly adjusted or
in poor location.
Insufficient combustion air
adjustment at oil burner, or
improper draft pressure.
Heat exchanger partially clogged.
Poor alignment between oil burner
blast tube and fire pot.
Flame impingement caused by
Incorrect nozzle angle.
Defective fire-pot Check fire-pot. Repair or replace.
Airflow blocked or dirty air filter. Clean or replace air filter.
Thermostat adjustments or
location.
Insufficient airflow.
Defective high limit control.
Under-sized nozzle.
Blower fan motor stopping
intermittently on overload.
Burner motor stopping
intermittently on overload.
Check electrode settings. Check electrodes for dirt build-up or cracks in
por
celain.
Check contacts between the igniter and electrodes. If OK, replace the
igniter
Check burner motor / fuel oil pump coupling. Check oil pump pressure.
Replace fuel oil pump if necessary.
Bleed air from oil line. If problem persists, replace oil line.
System temperature rise ideally should not exceed 85°F. Check for
clogged air filters. Check blower fan for excess dirt build-up or debris.
Speed up blower fan if necessary.
Check “fan off” delay timing setting. Use a duct thermometer in the
supply air plenum take-off or first few inches of the supply air trunk duct.
Ideally, the fan will shut off at a temperature of 90° - 100°F. Manipulate
the dip switch settings to come as close as possible to this “fan off”
temperature.
Check stack temperature. Stack temperatures will normally range from
350° to 450°F. Check draft regulator. Draft should be set to -0.02 in. w.c.
Check thermostat heat anticipator setting against measured amperage
draw. Increase heat anticipator setting if necessary. If the thermostat is
being influenced by drafts, sunlight, duct work, etc., relocate to more
suitable location.
Adjust the oil burner combustion air band and draft regulator to gain the
highest practical CO
See Burner Set Up.
Check for soot build-up in heat exchanger flue passages, especially in
the outer radiator.
Check alignment. Blast tube should be centered with fire pot burner
opening. Oil burner head should be ¼ inch back from the inside surface
of the fire pot.
Check nozzle size and angle. (See Appendix A). Check distance from
head to inside surface of the fire pot.
Check thermostat heat anticipator setting against measured amperage
draw. Increase heat anticipator setting if necessary. If the thermostat is
being influenced by drafts, sunlight, duct work, etc., relocate to more
suitable location.
Check all dampers. Open closed dampers including registers in unused
rooms. Check system temperature rise. If temperature rise is too high,
speed up blower fan.
Test high limit function of all limit switches. Use a duct thermometer to
assess accuracy of limit control. Check for obstructions to airflow around
limit switch bi-metal elements. Replace control if necessary.
Check nozzle. If problem is not caused by air flow problems, use larger
nozzle, if permitted by rating plate.
Check blower fan motor amperage draw. Check motor ventilation ports,
clean if necessary. Replace motor if necessary.
Check burner motor. Replace if necessary.
or lowest practical O2 content in the flue gases.
2
Home does not heat evenly Improper distribution of heat. This is not likely to be a furnace problem. Balance duct system.
20
Page 21
Table C-4: System and General Troubleshooting continued
Problem Possible Cause Remedy
Airflow blocked or dirty air filter. Clean or replace air filter.
Supply air temperature too
hot.
Supply air temperature too
cool.
Supply air temperature too
cool during first moments of
furnace cycle.
Insufficient airflow.
Excess airflow. Check system temperature rise. Slow down blower fan if necessary.
Excessive duct losses.
Fan control "fan on" setting too
low.
Excessive duct losses.
Check all dampers. Open closed dampers including registers in unused
rooms. Check system temperature rise. If temperature rise is too high,
speed up blower fan.
Check supply air ductwork. Seal leaky joints and seams. Insulate
ductwork if necessary.
Increase differential between fan control "fan off" and "fan on" settings.
(L4064B, L6064A fan / limit controls only, no adjustments available for
L4064W fan / limit control). Register air deflectors may help.
Check supply air ductwork. Seal leaky joints and seams. Insulate
ductwork if necessary.
FINAL CHECK OUT 3. Where the oil shut-off valve from the oil storage
ENSURE THAT ALL SAFETY DEVICES AND
ELECTRICAL COMPONENTS HAVE BEEN
SET FOR NORMAL OPERATION. ENSURE
THAT ALL ELECTRICAL CONNECTIONS
ARE TIGHT AND THAT THE WIRING IS
SECURE.
tank is located.
How to operate the thermostat, and other
4.
related accessories.
5. How to operate the manual reset button on the
primary control, and especially when not to push the
reset button.
IMPORTANT:
Please ensure that the homeowner is informed and
understands:
1. Where the circuit breaker or fuse is located in
the main electrical panel.
2. Where the furnace switch is located, and the
switch "on" and "off" positions if not obvious.
6. How and where to visually inspect the venting
system for leaks or other problems.
7. How to inspect, clean and replace the air filter,
and other homeowner maintenance procedures.
8. Who to call for emergency service and routine
annual service.
9. The terms and conditions of the manufacturer's
warranty and the contractor's warranty
.
21
Page 22
HOMEOWNER’S REFERENCE TABLE
Model No.
Serial No.
Date Installed
Contractor
Contact
Address
Postal Code
Telephone No.
After Hours No.
If different from Installation Contractor:
Service Tech.
Telephone No.
After Hours No.
Fuel Oil Supplier
Contact
Telephone No.
Fuel Supplier
After Hours No.
22
Page 23
PARTS LISTING: LOWBOY MODEL: O5LD-091A-12-R
Ref. No. Description Part No.
1 Left Side Panel Assembly 29631AD
2 Right Side Panel Assembly 29630AD
3 Upper Rear Panel 29638AD
4 Blower Division Panel Assembly 29676
5 Base Panel Assembly 28459
6 Inner Front Panel 30154
7 Blower Access Door 27367AD
8 Front Door Panel 30157AD
Logo Bezel 28479
Logo Label 28563
9 Top Front Panel 26017AD
10 Heat Exchanger Assembly Kit 550001635
12 Replacement Combustion Chamber 27000WP
13 Baffle 30152
14 Clean-out Gasket Retainer (2 per unit) 29161
Clean-out Gasket (2 per unit) 29163
15 Oil Burner Mounting Plate Assembly 109007674
Inspection Door Gasket 29871
16 Pouch Gasket 2080175
17 Flue Pipe Collar 27476
18 Air Filter – 20 x 20 x 1 (Permanent) 2180032
19 Control Panel 29653
20 Control Panel Cover 29654
21 Wire Harness Blower Motor Direct Drive 29690
22 Wire Harness Fan Timer Board 29364
23 Wire Harness Transformer and Supply 29751
24 Fan Timer Control 1158-120 UTEC 29388