Nordyne MS3BA030KA, MS3BA042KA, MS3BA036KA, MS3BA024KA, MS3BA048KA Installation Instructions Manual

...
Outdoor Air Conditioner
10 SEER Standard Efficiency Split System
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes require licensed
installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation.
These units have been designed and tested for capacity and efficiency in accordance with ARI
Standards. Split System Air Conditioning units are designed for use with awide variety of fossil
fuel furnaces, electric furnaces, air handlers,
and evaporator coil combinations.
USER'S iNFORMATiON
.
Set the thermostat temperature to the desired temperature level by using the temperature selector. Please refer to the
separate detailed user's manual for complete thermostat programming
instructions. The furnace and indoor blower will cycle on and off to maintain the indoor
temperature at the desired heating level.
Read this owner information to become familiar
with the capabilities and use of your appliance.
Keep this with literature on other appliances
where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don't eliminate your problem, call
your servicing contractor.
OPERATING iNSTRUCTiONS
To Operate Your Air Conditioner for Cooling m
I. Set the thermostat system switch to COOL
or AUTO and the thermostat fan switch to AUTO. (See Figure I)
2. Set the thermostat temperature to the desired temperature level by using the temperature selector. Please refer to the
separate detailed thermostat user's manual for complete instructions regarding
thermostat programming. The outdoor unit and indoor blower will both cycle on and off to maintain the indoor temperature
at the desired cooling level.
To Operate Your Furnace
for Heating
1. Set the thermostat system switch to HEAT
or AUTO and the thermostat fan switch to AUTO. (See Figure I)
To Shut OffYour Air Conditioner
Set the thermostat system switch to OFF and the thermostat fan switch to AUTO. (See Figure I)
The system will not operate, regardless of the thermostat temperature setting.
To Operate the Indoor Blower Continuously
Set the thermostat fan switch to ON (See Figure I ) The indoor blower will start immediately, and will
run continually until the fan switch is reset to
AUTO.
The continuous indoor blower operation can be obtained with the thermostat system switch
set in any position, including OFF.
SYSTEMSWITCH
FAN SWITCH
Figure 1. Typical Thermostat
The continuousindoorbloweroperationis typicallyusedtocirculatetheindoorairtoequalize
a temperatureunbalancedueto a sun load, cooking,orfireplaceoperation.
To Maintain Your Air Conditioner--
Read Your Warranty
Please read the separate warranty document completely. It contains valuable information
about your system.
1. GENERAL iNFORMATiON
Read the following instructions completely before performing the installation.
Condensing Unit Section -- Each condensing unit is shipped with a refrigerant charge adequate
to operate the outdoor section with an indoor
matching coil or air handler and 15 feet of refrigeration line.
NOTE: DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.
Liquid and Suction Lines-- Refrigerant grade copper tubing should be used when installing
the system. Refrigerant suction line tubing should be fully insulated to prevent condensate
damage.
Field Connections for Electdca_ Power Supply
-- All wiring must comply with the current provisionsofthe"National Electrical Code" (ANSI
CI.) and with applicable local codes having
jurisdiction. Size of electrical conductors and
circuit protection must be in compliance with the information listed on the outdoor unit data label.
2. SAFETY CONSiDERATiONS
Pressures Within the System -- Split System
Air Conditioning equipment contains liquid and gaseous refrigerant under pressure. Installation
and servicing of this equipment should be accomplished by qualified, trained personnel
thoroughly familiar with this type of equipment.
Under no circumstances should the homeowner attempt to install and/or service the equipment
without proper supervision from trained and qualified service personnel.
WARNmNG'.
Ensure aH emectricam power to the unit is off prior to installing or servicing the
equipment. Failure to do so may cause
personal injury or death.
Be certain the emectricam power to the outdoor u nit and the furnace/air handier
is disconnected before doing the following recommended maintenance.
1. Regulady:
a. Clean or replace the indoor air filter at the
start of each heating and cooling season, and when an accumulation of dust and dirt
is visible on the air filter.
b. Remove any leaves and grass clippings
from the coil in the outdoor unit, being careful not to damage the aluminum fins.
c. Check for any obstruction, such as twigs,
sticks, etc.
Do not over-oil, or oil motors not factory- equipped with oil tubes. The compressor is hermetically "sealed" and does not require lubrication.
2. Before Each Cooling Season:
If the furnace/air handler blower motor and the outdoor unit fan motor(s) have oil tubes
at the motor bearings, apply 10 drops of SAE No. 20 motor oil to each oil tube.
3. Before Calling a Service Technician, Be Certain:
a. The unit thermostat is properly set -- see
"To Operate Your Air Conditioner for Cooling" and "To Operate Your Furnace
for Heating."
b. The unit disconnect fuses are in good
condition, and the electrical power to the unit is turned on.
Labels,Tags,Precautions-- Whenworking withthis equipment,followall precautionsin literature,ontags,andon labelsprovidedwith
theequipment.ReadandthorougNyunderstand the instructionsprovidedwith the equipment
priortoperformingtheinstallationandoperational checkoutoftheequipment.
CantileverMount -- The cantilevermount shouldbedesignedwithadequatesafetyfactor
tosupporttheweightoftheequipment,andfor loadsthemountissubjectedtoduringoperation.
installed equipmentshould be adequately securedto the cantilevermountand levelled
priortooperationof theequipment.
3. SiTE PREPARATION
Unpacking Equipment- Remove the cardboard carton and Literature Package from the equipment.
inspect for Damage -- inspect the equipment for damage prior to installing the equipment at
the job site. Ensure coil fins are straight and, if necessary, comb fins to remove flattened and
bent fins.
Preferred Location of the Outdoor Unit at the Job Site -- Conduct a survey of the job
site to determine the optimum location for mounting the outdoor unit. Overhead
obstructions, poorly ventilated areas, and areas subject to accumulation of debris should
be avoided. The outdoor unit must be installed in such a manner that airflow through the coil is
not obstructed and that the unit can be serviced.
Facility Prerequisites -- Electrical power supplied must be adequate for proper operation
of the equipment. The system must be wired and provided with circuit protection in accordance
with local building codes and the National Electrical Code.
Minimum Circuit Ampacity-- Electrical wiring to the equipment must be compatible and in
compliance with the minimum circuit ampacity listed on the outdoor unit data label.
Maximum Fuse/Circuit Breaker Size-- Circuit protection for the outdoor unit must be compatible
with the maximum fuse/circuit breaker size listed on the outdoor unit data label.
4. _NSTALLING THE OUTDOOR UNiT
Slab Mount -- The site selected for a slab mount installation requires a stable foundation
and one not subject to erosion. The slab should be level and anchored (if necessary) prior to
placing the equipment on the slab.
Roof Mount --The method of mounting should be designed so as not to overload roof structures
nor transmit noise to the interior of the structure. Refrigerant and electrical lines should be routed
through suitably waterproofed openings to prevent water leaking into the structure.
5. NSTALMNG THE NDOOR UNIT
The indoor section of the unit should be installed before proceeding with the routing of refrigerant
piping. Consult the Installation instructions of the indoor unit (i.e., air handier, fan coil unit,
etc.) for details regarding installation.
6. CONNECTING REFRIGERANT TUBING BETWEEN THE _NDOOR
AND OUTDOOR UNiT
Generam information -- Once the outdoor and indoor unit placement has been determined, route the refrigerant tubing between the
equipment in accordance with sound installation practices. Refrigerant tubing should be routed
in a manner that minimizes the length of tubing and the number of bends in the tubing.
Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation. Tubing should be kept
clean of foreign debris during installation and installation of a liquid line filter drier is
recommended if cleanliness or adequacy of system evacuation isunknown or compromised. Every effort should be made by the installer to
ensure that the field installed refrigerant containing components of the system have been
installed in accordance with these instructions and sound installation practices so as to insure
reliable system operation and longevity. The maximum recommended interconnecting
refrigerant line length is 75 feet, and the vertical elevation difference between the indoor and
outdoor sections should not exceed 20 feet.
Optiona! Equipment -- Optional equipment (i.e.: filter/driers, liquid line solenoid valves, etc.)
should be installed in strict accordance with the manufacturer's Installation Instructions.
Loading...
+ 5 hidden pages