Nordyne G6RL 90+, G6RC 90+, G6RD 93+ User Manual

Page 1
Residential Gas Furnaces
Installation Instructions
G6RC Series 90+ Upflow Condensing Furnace G6RD Series 93+ Upflow Condensing Furnace G6RL Series 90+ Downflow Condensing Furnace
G6RC 90+, G6RD 93+ Upflow G6RL 90+ Downflow
!
WARNING:
Improper installation, adjustment, al­teration, service, or maintenance can cause injury or property damage. Re­fer to this manual for assistance. For additional information consult a quali­fied installer, service agency, or the gas supplier.
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance. Some local codes require licensed installa­tion/service personnel for this type of equip­ment. Read all instructions carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CARE­FULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
!
FOR YOUR SAFETY:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
!
FOR YOUR SAFETY:
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
• Extinguish any open flame.
Page 2
Page 3
Table of Contents
Furnace Specifications ......................................................................................................... ... 4-5
Furnace Airflow Data.......................................................................................................... 6-7
Installation Requirements ...................................................................................................... .... 8
Supply Air Plenum Installation ..................................................................................................9
Installation on a Concrete Slab ............................................................................................. 9
Installation on a Combustible Floor....................................................................................... 9
Circulating Air Supply............................................................................................................... 10
Return Air ............................................................................................................................ 11
Venting and Combustion Air Requirements .......................................................................... 11
Air Requirements for One-Pipe Installation ........................................................................ 13
Installation in An Unconfined Space ................................................................................... 13
Installation in A Confined Space ......................................................................................... 13
• Air From Inside .................................................................................................................. 1 3
• Air Directly Through An Exterior Wall ............................................................................... 14
• Outdoor Air Through Vertical Openings or Ducts ............................................................. 14
• Outdoor Air Through Horizontal Openings or Ducts......................................................... 14
Venting Requirements .............................................................................................................. 1 4
Vent Pipe Material ............................................................................................................... 14
Vent Pipe Length and Diameter .......................................................................................... 14
Vent Pipe Installation ..........................................................................................................15
Pipe Routing & Support....................................................................................................... 15
Location of Outdoor Terminations....................................................................................... 18
Horizontal Venting ............................................................................................................... 19
Vertical Venting ................................................................................................................... 20
Vent Freezing Protection..................................................................................................... 20
Concentric Vent Termination............................................................................................... 20
Drainage of Condensate From Furnace................................................................................. 21
Gas Supply and Piping........................................................................................................ 22
Leak Check.......................................................................................................................... 22
Conversion..................................................................................................................... ...... 23
High Altitude Application ..................................................................................................... 23
Natural Gas High Altitude Conversion ................................................................................ 23
LP/Propane Gas Sea Level and High Altitude Conversion ................................................ 23
Electrical Wiring ........................................................................................................................ 24
Line Voltage Wiring .............................................................................................................24
Low Voltage Wiring ............................................................................................................. 25
Start-up and Adjustments......................................................................................................... 25
Start-Up Procedure..............................................................................................................26
Verifying and Adjusting Firing Rate..................................................................................... 26
Verifying and Adjusting Temperature Rise ......................................................................... 27
Verifying Burner Operation.................................................................................................. 27
Verifying Operation of the Supply Air Limit Switch ............................................................. 29
Description of Components ..................................................................................................... 29
Maintenance ............................................................................................................................... 31
Combustion Air and Vent System ....................................................................................... 31
Air Filter(s) .................................................................................................................. ......... 31
Lubrication ........................................................................................................................... 31
Condensate Drain Assembly............................................................................................... 31
Blower Compartment........................................................................................................... 31
Heat Exchanger and Burner Maintenance.......................................................................... 31
Location of Major Components ........................................................................................... 32
System Operation Information ................................................................................................. 31
Sequence of Operation ....................................................................................................... 33
Furnace Fails to Operate .................................................................................................... 34
Twinning of Two Furnaces .................................................................................................. 34
Installation/Performance Checklist ......................................................................................... 35
Page 4
4
FURNACE SPECIFICATIONS
Upflow G6RC & G6RD Furnaces
Combustion Air
Inlet
23 1/4"
A
Exhaust Vent
3/4"
3/4"
Figure 1. G6RC, G6RD Unit Dimensions
1 1/2" x 3 1/2" Dia.
43"
15"
1"
22 1/2"
19 3/4"
25 1/8"
Opening for
Gas Connection
7/8" Dia. Electric
Connection
25 1/4"
8"
Return Air Opening
(Side)
Combustion Air Vent (See Fig. 15 for sizes)
+
20 1/2"
33"
3/4"
B
C
Return Air Opening
(Bottom)
D
2 1/4"
3/4"
2" PVC Exhaust Vent (See Fig. 15 for sizes)
30 1/4"
25 1/4"
27 5/8"
1 1/2" x 3 1/2" Dia. Opening for Gas Connection
7/8" Dia. Electric Connection
+
8"
25 5/8"
1 1/4"
23"
28"
Condensate Drain Outlets
23"
Bottom Return Opening
Page 5
Downflow G6RL Furnace
Combustion Air Inlet
24 1/2"
Exhaust Vent
3/4"
22 1/2"
Exhaust
Vent
2"
3/4"
A
B
3/4"
27 7/8"
3/4"
Figure 2. G6RL Unit Dimensions
24 7/8"
7/8" Dia. Electric
43"
1 1/2" x 3 1/2" Dia.
Gas Connection
1"
Connection
21 7/8"
Opening for
21 1/4"
8"
21 1/2"
15 1/2"
Condensate Drain Outlet
C
C
L
Bottom Supply Air Opening
(Side)
D
2 1/2"
Combusting
Vent
(3" for 80/100
2" for 40/60)
21 1/2"
Condensate
Drain
Outlet
24 7/8"
7/8" Dia. Electric
Connection
1 1/2" x 2 1/2"
Knockout
For Gas
Connection
21 7/8"
10 1/4"
19 3/4"
Bottom Opening
5
Page 6
6
1170
1060
1160
1050
1310
1080
1630
1400
1250
1700
1480
1320
1140
1650
1480
1320
1140
2070
1760
1470
1280
1030
gh*G6RC040C-08
g
G6RC040C-12
gh*G6RC060C-12
gh*G6RC080C-12
gh*G6RC080C-16
Med-High
g
G6RC100C-16
gh*G6RC120C-16
g
G6RC120C-20
Med-High
gh*G6RD040C-10
gh*G6RD060C-10
Model Input Motor Motor
Number (Btuh) Speed HP
Table 1. Furnace Airflow Data
Heating
40,000 Medium 1/5
40,000 Medium 1/3
60,000 Medium 1/3
80,000 Medium 1/3
80,000
100,000 Med-High** 1/2
120,000 Med-High** 1/2
120,000
40,000 Medium 1/3
60,000 Medium** 1/3
Hi
Low**
Hi
h*
Low**
Hi
Low**
Hi
Low**
Hi
Med-Low**
Low
h*
Hi
Med-Low
Low
Hi
Med-Low
Low
h*
Hi
Med-Low**
Low
Hi
Low**
Hi
Low
Ex ternal Static Pressure (Inches W ater Column)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
950 36 920 38 890 39 850 41 800 43 750 46 690 50 630 55 740 47 710 49 680 51 650 53 600 58 550 63 490 - 430 -
620 56 590 59 560 62 520 - 470 - 410 - 350 - 290 ­1330 - 1280 - 1230 ­1190 - 1160 - 1110 -
830 42 810 43 780 44 760 46 720 48 670 52 610 57 550 63 1310 - 1260 - 1210 ­1160 45 1120 46 1080 48
800 65 780 67 760 68 740 70 710 73 680 - 650 - 620 ­1490 46 1450 48 1390 50 1230 56 1200 58 1150 60
780 - 750 - 720 - 680 - 630 - 570 - 510 - 440 ­1840 - 1780 - 1700 41 1600 43 1560 44 1470 47
1/2
1380 50 1350 51 1300 53 1100 - 1050 - 1000 - 950 - 900 - 850 - 800 - 750 ­1910 45 1860 47 1780 49 1640 53 1620 53 1540 56 1440 60 1410 61 1370 63 1230 - 1210 - 1180 ­1860 56 1800 58 1730 60 1650 63 1610 65 1550 67 1440 72 1410 74 1380 75 1230 - 1210 - 1180 ­2260 - 2200 - 2140 -
3/4
1870 56 1840 56 1790 58 1540 67 1530 68 1510 69 1360 - 1330 - 1310 ­1050 - 1005 - 960 - 915 - 855 - 800 - 730 48 670 53
990 - 950 - 905 - 860 - 810 - 760 46 700 50 650 54
770 46 740 48 700 50 660 53 625 56 580 61 540 65 500 70 1175 45 1125 47 1075 49 1075 49 1040 51 995 53 950 56 900 59 840 63 790 67 720 73
800 66 770 69 745 71 710 74 670 - 630 - 580 - 530 -
- 1120 - 1030 - 940 37 850 41
- 1010 - 910 38 820 42 720 48
45 1100 47 1040 50 980 53 920 56 49 990 52 940 55 890 58 830 63
53 1210 57 1100 63 980 - 830 ­64 1010 69 910 - 810 - 680 -
42 1550 45 1470 47 1380 50 1290 54 49 1350 51 1280 54 1210 57 1150 60 55 1190 58 1120 62 1040 67 960 -
51 1620 53 1520 57 1420 61 1310 66 58 1420 61 1340 65 1250 69 1150 75 66 1270 68 1210 72 1140 - 1060 -
- 1090 - 1030 - 960 - 880 ­63 1570 66 1480 70 1380 75 1270 82 70 1410 74 1320 79 1230 84 1120 ­79 1280 81 1220 85 1150 - 1080 -
- 1090 - 1030 - 960 - 880 -
- 1990 - 1910 - 1810 57 1710 61 59 1710 61 1660 63 1610 65 1560 67 71 1430 73 1370 76 1300 80 1220 85
- 1250 - 1220 - 1190 - 1150 -
51 970 54 920 57 860 61 800 66
CAPACITIES —Furnace Airflow Data
Page 7
Heating
g
Med-High
g
g
g
g
g
Med-High
1430
1295
1145
1000
1425
1265
1130
1500
1350
1195
1040
1945
1800
1540
1360
Model Input Motor Motor
Number (Btuh) Speed HP
G6RD080C-14 80,000
G6RD100C-14 100,000 Med-Hi
Table 2. Furnace Airflow Data
G6RD120C-14 120,000 Med-Hi
G6RD120C-19 120,000
G6RL040C-12 40,000 Medium 1/3
G6RL060C-12 60,000 Medium 1/3
G6RL080C-16 80,000 Med-High 1/2
G6RL100C-16 100,000 Med-High** 1/2
Hi
Med-Low**
Hi
Med-Low
Hi
Med-Low
Hi
Med-Low**
High*
Low**
High*
Low**
High*
Med-Low**
High*
Med-Low
h*
Low
h*
Low
h*
Low
h*
Low
Low
Low
1/2
h** 1/2
h** 1/2
3/4
Ex ternal Static Pressure (Inches W ater Column)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
1620 - 1560 45 1490 47 1450 49 1400 50 1350 52 1255 56 1225 57 1180 60 1080 65 1055 67 1030 68 1620 54 1555 57 1485 59 1430 62 1375 64 1330 66 1260 70 1220 72 1170 75 1085 - 1050 - 1015 - 970 - 935 - 890 - 850 - 800 ­1700 62 1635 65 1565 67 1510 70 1455 73 1405 75 1330 79 1280 - 1240 ­1140 - 1110 - 1075 ­2140 - 2070 - 2010 ­1955 - 1900 56 1850 57 1660 64 1620 65 1575 67 1450 73 1430 74 1400 75
1280 - 1210 - 1180 - 1140 - 1090 - 1070 - 1030 - 990 ­1140 - 1090 - 1060 - 1030 - 980 35 950 36 910 37 870 39
875 39 835 41 820 41 805 42 780 43 770 44 760 45 750 45 1260 40 1190 43 1155 44 1120 45 1075 47 1030 49 980 52 940 54 1120 45 1070 48 1040 49 1010 50 960 53 930 55 890 57 850 60
855 59 815 62 800 64 780 65 760 67 730 70 710 - 690 ­1635 - 1585 - 1525 - 1460 46 1400 48 1330 51 1260 54 1180 57 1435 47 1395 49 1350 50 1300 52 1255 54 1200 56 1150 59 1090 62 1230 55 1200 56 1165 58 1130 60 1090 62 1050 65 1000 68 960 71 1050 - 1035 - 1010 - 980 - 950 - 910 - 870 - 820 ­1600 53 1555 54 1500 56 1445 59 1380 61 1310 65 1240 68 1160 73 1475 57 1435 59 1385 61 1335 63 1290 66 1240 68 1190 71 1130 75 1320 - 1290 - 1250 - 1215 - 1170 - 1120 - 1070 - 1020 ­1150 - 1130 - 1110 - 1075 - 1040 - 1000 - 950 - 890 -
49 1365 52 1300 54 1240 57 1170 60 54 1240 57 1180 60 1120 63 1060 66 61 1105 64 1060 66 1020 69 980 72 70 960 73 920 - 870 - 820 ­62 1355 65 1290 68 1220 72 1160 ­70 1210 73 1150 - 1080 - 1010 -
- 1070 - 1010 - 950 - 890 -
70 1435 74 1370 77 1310 - 1240 ­78 1290 - 1230 - 1170 - 1100 -
- 1145 - 1100 - 1050 - 1000 -
- 1010 - 980 - 940 - 910 -
- 1870 56 1800 59 1730 61 1650 64 59 1740 61 1690 62 1630 65 1570 67 69 1495 71 1460 72 1410 75 1370 77 78 1340 79 1300 81 1270 83 1230 -
** Factory Set Cooling Speed ** Factory Set Heating Speed
- Not Recommended
NOTES: 1. Airflow rates of 1800 CFM or more require two return air connections. Data is for operation with filter(s).
2. Temperature rises in the table are approximate. Actual temperature rises may vary.
3. Temperature rises and airflows for external static pressures greater than 0.5 are for reference only. These conditions are not recommended.
7
Page 8
INSTALLATION REQUIREMENTS
(
)
Requirements and Codes
This furnace must be installed in accordance with these instructions, all applicable local build­ing codes, and the current revision of the Na­tional Fuel Gas Code (ANSI-Z223.1, NFPA-54). The current revision of the National Fuel Gas Code is available from:
American National Standards Institute, Inc. 1430 Broadway
New York, New York 10018 Canada installations shall comply with CAN/ CGA-B149 installation codes, local plumbing or waste water codes and other applicable codes. Additional helpful publications are:
• NFPA-90A - Installation of Air Conditioning and Ventilating Systems.
• NFPA-90B - Warm Air Heating and Air Conditioning Systems.
These publications are available from:
National Fire Protection Association, Inc. Batterymarch Park Quincy, Massachusetts 02269
!
WARNING:
This furnace is not approved for in­stallation in mobile homes. Installa­tion in a mobile home could cause fire, property damage, and/or personal injury.
Model
Number
G6R(C,D)040C 40,000 14 1/4 12 3 /4 5 1/8 11 3/ 4 133 G6R(C,D)060C 60,000 14 1/4 12 3 /4 5 1/8 11 3/ 4 140 G6R(C,D)080C 80,000 19 3/4 18 1 /4 7 7/8 17 1/ 4 172 G6R(C,D)100C 100,0 00 19 3/4 1 8 1/ 4 7 7/8 17 1/ 4 180 G6R(C, D)12 0C 120,000 22 1/2 21 9 1/4 20 204
G6RL040C 40,000 14 1/ 4 1 2 3 /4 4 5/8 12 3/ 4 135 G6RL060C 60,000 14 1/ 4 1 2 3 /4 4 5/8 12 3/ 4 135 G6RL080C 80,000 19 3/ 4 1 8 1 /4 10 18 1/4 174 G6RL100C 100,000 19 3/4 1 8 1 /4 10 18 1/4 185
Furnace
Btuh
Table 3. Furnace Dimensions and Shipping Weights
AB
Dimensions (inches)
CD
Shipping
Weight
lbs
CLEARANCES TO COMBUSTIBLE MATERIALS
This furnace is Designed Certified by AGA/CGA Laboratories for the minimum clearances to combustible material listed in Table 4. See the furnace name plate, located inside the furnace cabinet, for specific model number and clearance information.
MINIM UM CL EARANCES TO COMBUS TI BLE MATERI AL
Furn ace Cabi net Mi n imu m Cl earan ces (In ch es)
Input Width
(Btuh) (Inches) Side Vent Back Top Front
40, 000 14 1/ 4 0 0 0 1 1* 60, 000 14 1/ 4 0 0 0 1 1*
80, 000 14 1/ 4 0 0 0 1 1* 100,000 19 3/ 4 0 0 0 1 1* 120,000 22 1/ 2 0 0 0 1 1*
* 24 inches is the minimum clearance for servicing. 36 inches is the recommended clearance for service.
Table 4. Minimum Clearances to Combustible Materials
8
Page 9
Location
The furnace must be installed on a level surface, and as close to the center of the air distribution system as possible. See Table 3 for overall dimensions to determine the required clear­ances in hallways, doorways, stairs, etc. to allow the furnace to be moved to the installation point. The furnace must be installed so that all electri­cal components are protected from water. Minimum clearances to combustible materials are listed in Table 4. Access for positioning and servicing must be considered when locating the unit. 24 inches is the minimum required clear­ance for servicing the unit. 30 inches is the minimum required clearance for positioning the unit. 36 inches is the recommended clearance from the front of the unit. Please note that a panel or door can be located such that the minimum clearance on the rating plate is satis­fied, but that panel or door must be removable and allow the appropriate clearance for your installation.
This furnace is certified for use on wood flooring. The furnace must be installed on a solid surface and must be level front to back and side to side. This furnace must not be installed directly on carpeting, tile, or any combustible material other than wood flooring.
DOWNFLOW WARNING (G6RL Models):
The design of the downflow furnace is certified for natural or propane gas and for installation on non-combustible flooring. A special combus­tible floor sub-base is required when installing on a combustible floor. Failure to install the sub­base may result in fire, property damage and personal injury. The special downflow sub-bases are factory supplied accessories, part numbers 902677 and 902974. When the furnace is in­stalled on a factory or site-built cased air condi­tioning coil, the sub-base is not necessary. However, the plenum attached to the coil casing must be installed such that its surfaces are at least 1" from combustible construction. A gas-fired furnace installed in a residential garage must be installed so that the bottom of the furnace is located a minimum of 15" from the floor. The furnace must be located or protected to avoid physical damage by vehicles.
HORIZONTAL INSTALLATIONS
The G6RC model furnaces are approved for horizontal installation. Installation Kit #903568 is required for horizontal applications. Follow the installation instructions in the kit for proper conversion. NOTE: The G6RD and G6RL mod­els are NOT approved for horizontal installation.
SUPPLY AIR PLENUM INSTALLATION
A. Installation on a concrete slab - G6RL
1. Construct a hole in the floor per the dimensions in Figure 3.
2. Place the plenum and the furnace as shown in Figure 4.
B. Installation on a combustible floor - G6RL
1. Cut and frame the hole in the floor per the dimensions in Figure 5.
2. Place the sub-base for combustible floors over the hole with its duct collar extended downward. Attach the supply air plenum to the base in a manner which will ensure 1" clearance to the flooring or other combustible material. Place furnace on the combustible base as shown in Figure 6.
3. When the furnace is installed on a factory or site-built cased air conditioning coil, the sub-base is not necessary. However, the plenum attached to the coil casing must be installed such that its surfaces are at least 1" from combustible material.
18.75"
19.25"
Hole in
Floor
G6RL 080/100 G6RL 040/060
Figure 3. Opening for Concrete Slab
13.25"
19.25"
Hole in
Floor
9
Page 10
Concrete
Furnace
Floor
Sheet
Metal
Plenum
Figure 4. Furnace on a Concrete Slab
18.75"
or 13.25"*
16.75"
or 11.25"*
* Smaller dimensions for G6RL 040/060
9.25"
2.0"
28.38"
18.75"
19.63"
Hole in
Floor
G6RL 080/100 G6RL 040/060
Figure 5. Opening in Wood Floor
Downflow
Sub-base
Furnace
13.25"
19.63"
Hole in
Floor
Wood
Floor
Sheet
Metal
Plenum
Figure 6. Furnace on a Wood Floor
CIRCULATING AIR SUPPLY
Plenums and air ducts must be installed in accordance with the Standard for the Installa­tion of Air Conditioning and Ventilating Systems (NFPA No. 90A) or the Standard for the Installa­tion of Warm Air Heating and Air Conditioning Systems (NFPA No. 90B).
1.50"
1.58"
1 inch thick fiberglass 3 lb density
19.75"
or 14.25"*
Figure 7. Downflow Sub-Base Dimensions
If outside air is utilized as return air to the furnace for ventilation or to improve indoor air quality, the system must be designed so that the return air to the furnace is not less than 50°F (10°C) during heating operation. If a combination of indoor and outdoor air is used, the ducts and damper system must be designed so that the return air supply to the furnace is equal to the return air supply under normal, indoor return air applications.
When a cooling system is installed which uses the furnace blower to provide airflow over the indoor coil, the coil must be installed down­stream (on the outlet side) or in parallel with the furnace.
If a cooling system is installed in parallel with the furnace, a damper must be installed to prevent chilled air from entering the furnace and con­densing on the heat exchanger. If a manually operated damper is installed, it must be de­signed so that operation of the furnace is pre­vented when the damper is in the cooling posi­tion and operation of the cooling system is prevented when the damper is in the heating position.
19.63"
3"
10
Page 11
!
WARNING:
Products of combustion must not be allowed to enter the return air ductwork or the circulating air supply. Failure to prevent products of combustion from being circulated into the living space can create potentially hazardous con­ditions including carbon monoxide poisoning that could result in per­sonal injury or death.
All return ductwork must be ad­equately sealed, all joints must be taped, and the ductwork must be secured to the furnace with sheet metal screws. When return air is provided through the bottom of the furnace, the joint between the furnace and the re­turn air plenum must be sealed.
The floor or platform on which the furnace is mounted must provide sound physical support of the furnace with no gaps, cracks, or sagging be­tween the furnace and the floor or platform.
Return air and circulating air ductwork must not be connected to any other heat producing device such as a fire­place insert, stove, etc.
An important consideration in selecting one or two pipe installation is the quality of the combus­tion air. Indoor air is sometimes contaminated with various household chemicals which can cause severe corrosion in the furnace combus­tion system. Some common sources of these chemicals are detergents, bleaches, aerosol sprays, and cleaning solvents. Unless indoor air is known to be free of these materials, two pipe installation is recommended.
Provisions must be made for adequate supply of air for combustion and ventilation. For United States installations, the adequacy of air provi­sions can be determined by consulting the cur­rent version of the National Fuel Gas Code (ANSI Z223.1/NPFA-54). For Canadian installa­tions, requirements are specified in the National Standard of Canada (CAN/CGA B149.1 & .2). Consult local codes for special requirements.
NOTE: If the furnace is operated without ad­equate air for combustion and ventilation, it may not perform properly. Furnace components may be strained by high temperature and could fail prematurely.
!
WARNING:
Furnace installation using methods other than those described in the fol­lowing sections must comply with the National Fuel Gas Code and all appli­cable local codes to provide sufficient combustion air for the furnace.
Return Air
The return air ductwork may be connected to any or all of the following: left side return, right side return, or bottom return. Tables 1 and 2 show the airflow data for each furnace model.
Where maximum airflow is 1800 CFM or more two openings must be used.
VENTING AND COMBUSTION AIR REQUIREMENTS
NORDYNE condensing furnaces may be in­stalled with outdoor combustion air piped di­rectly to the furnace, or without such special piping. Codes refer to the former as "direct vent" or "two pipe" installation. Installation with air taken from around the furnace is sometimes referred to as "one pipe" installation - i.e. only the vent (exhaust) pipe is provided.
G6RC/G6RD
Protective Screen
G6RL
Figure 8. Protective Screen for One Pipe
Installations
11
Page 12
80,000
Vent or Chimney
Each opening must
be at least 100 sq. in.
or 1 sq. in. per 1000
Btuh of total input
rating, whichever is
greater. See minimum
area per table.
12" Max.
Each opening to outside must be at least 1 sq. in. per 4000 Btuh of total input rating.
-
-
-
-
-
-
12"
-
-
-
Max
Vent or Chimney
Furnace
Furnace
12" Max.
Water Heater
Minimum
Total Input
Rating (Btuh)
40,000 60,000
Free Area
(Each Opening)
100 sq. in. 100 sq. in. 100 sq. in.
Round Duct
Diameter
12" 12" 12"
Figure 9. Equipment in a Confined Space
with all Combustion Air drawn from Inside
Ventilation Louvers at each end of attic
Vent or Chimney
Attic Insulation
Water Heater
Total Input
Rating (Btuh)
40,000 60,000 80,000 100,000 120,000 140,000 160,000
Furnace
Minimum Free Area
(Each Opening)
10 sq. in. 15 sq. in. 20 sq. in. 25 sq. in. 30 sq. in. 35 sq. in. 40 sq. in.
Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Ducts must extend above attic insulation.
Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
12" Max
Round Duct
Diameter
4" 5" 5" 6" 6" 7" 8"
-
-
-
-
-
-
-
-
-
12" Max
Water Heater
Minimum
Total Input
Rating (Btuh)
40,000 60,000 80,000 100,000 120,000 140,000 160,000
Free Area
(Each Opening)
10 sq. in. 15 sq. in. 20 sq. in. 25 sq. in. 30 sq. in. 35 sq. in. 40 sq. in.
Round Duct
Diameter
4" 5" 5" 6" 6" 7" 8"
Figure 10. Equipment in a Confined Space
with all Combustion Air drawn from
Outdoors through Exterior Wall
Vent or Chimney
Ventilation Louvers (each end of attic)
---------
Furnace
Alternate
Air Inlet
Outlet Air
Water Heater
Inlet Air
---------
---------
Ventilation Louvers For Unheated Crawl Space
NOTE: Air open­ings shall each have a free area of not less than one square inch per 4,000 Btuh of the total input rat­ing of all equipment in the enclosure.
---------
Figure 11. Equipment in a Confined Space
with all Combustion Air drawn from
Outdoors through Vertical Ducts – from
Ventilated Attic
12
Figure 12. Equipment in a Confined Space
with all Combustion Air drawn from
Outdoors through Ventilated Crawl Space
and Ventilated Attic
Page 13
Vent or
Chimney
Air Duct must be at least 1 sq. in. per 2000 Btuh of total input rating.
Round Duct
Diameter
5" 6" 7" 8" 9" 10" 10"
Total Input
Rating (Btuh)
40,000 60,000 80,000 100,000 120,000 140,000 160,000
Air Duct
Furnace
Air Duct
Water Heater
Minimum
Free Area
(Each Opening)
20 sq. in. 30 sq. in. 40 sq. in. 50 sq. in. 60 sq. in. 70 sq. in. 80 sq. in.
Figure 13. Equipment in a Confined Space
with all Combustion Air Drawn from the
Outside through Horizontal Ducts
Air Requirements For One-Pipe Installation
When air for combustion is to be taken from around the furnace, a protective screen must be installed over the combustion air intake open­ing. This screen is provided with the furnace installation instructions and functions to prevent debris from entering the combustion system. It should be installed on the combustion air intake collar or inlet PVC. If furnace location is such that this opening might be unintentionally ob­structed, a 3" PVC elbow should be installed on the collar, and the screen placed inside the inlet of the elbow. See Figure 8.
Installation In An Unconfined Space
!
CAUTION:
"Tight" buildings (with weather strip­ping and caulk to reduce infiltration), may require special provisions for in­troduction of outside air to ensure satisfactory combustion and venting, even though the furnace is located in an unconfined space.
An unconfined space is an area including all rooms not separated by doors with a volume greater than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances which draw combustion air from that space. For example, a space including a water heater rated at 45,000 Btuh and a furnace rated at 75,000 Btuh requires a volume of 6,000 cubic feet [50 x (45 + 75) = 6,000] to be considered unconfined. If the space has an 8 foot ceiling, the floor area of the space must be 750 square feet (6,000 / 8 = 750). In general, a furnace installed in an unconfined space will not require outside air for combustion.
!
WARNING:
Furnaces installed with combustion air drawn from a heated space which includes exhaust fans, fireplaces, or other devices that may produce a negative pressure should be consid­ered confined space installations.
Installation In A Confined Space
A confined space is one which does not meet the unconfined space volume requirements, and typically involves installation in a small room. All such installations must have specific provisions for introduction of combustion and ventilation air.
Codes require that two openings be pro­vided for this - one with bottom edge within 12" of the floor and one with top edge within 12" of the ceiling.
openings must be per the following sections. Combustion air openings must not be restricted
in any manner. Furnaces installed in a confined space which
supply circulating air to areas outside of the space must draw return air from outside the space and must have return air ducts tightly sealed to the furnace.
Air From Inside
Air for combustion and ventilation may be taken from inside the building through an interior wall
if the building is not "tight" and if the total volume of the furnace space and the space from which air is drawn meets the volume requirements for an unconfined space.
openings in the wall must each have free area of at least one square inch per 1000 Btuh of appliance input, but not less than 100 square
The size and other criteria for these
In such cases, the two
total
13
Page 14
inches of free area. See Figure 9. For example, if the combined input rate of all appliances is less than or equal to 100,000 Btuh, must have a free area of at least 100 square inches. If the combined input rate of all appli­ances is 120,000 Btuh, a free area of at least 120 square inches.
Air Directly Through An Exterior Wall
If combustion air is provided directly through an exterior wall, the two openings must free area of at least one square inch per 4000
total
Btuh of
appliance input. (See Figure 10.)
each
each
opening
opening must have
each
have
NORDYNE condensing furnaces are classified as "Category IV" appliances, which require spe­cial venting materials and installation proce­dures. Category IV appliances operate with positive vent pressure and therefore require vent systems which are thoroughly sealed. They also produce combustion condensate, which is slightly acidic and can cause severe corrosion of ordinary venting materials. Furnace operation can be adversely affected by restrictive vent and combustion air piping. Therefore,
bustion air piping lengths must conform com­pletely to the requirements of Table 5.
vent and com-
Outdoor Air Through Vertical Openings or Ducts
If combustion air is provided through vertical ducts or openings to attics or crawl spaces, the two openings must each have free area of at least one square inch per 4000 Btuh of total appliance input. Ducts must have cross-sec­tional areas at least as large as the free area of their respective openings to the furnace space. Attics or crawl spaces must communicate freely with the outdoors if they are the source of air for combustion and ventilation. (See Figures 11 and 12.)
Outdoor Air Through Horizontal Openings or Ducts
If combustion air is taken from outdoors through horizontal ducts, the openings must free area of at least one square inch per 2000 Btuh of total appliance input. Ducts must have cross-sectional area at least as large as the free area of their respective openings to the furnace space. (See Figure 13.)
!
CAUTION:
each
have
Do not supply combustion air from an attic space that is equipped with power ventilation or any other device that may produce a negative pressure.
VENTING REQUIREMENTS
This section specifies installation requirements for vent and "2-pipe" combustion air piping. For "one pipe" installations, install vent piping per this section and provide air for combustion and ventilation per the previous section. The capac­ity table provided in this section applies to the total of vent and combustion air piping for either type of installation.
The furnace must be vented to the outdoors. It must not be vented in common with any other appliance, even if that appliance is of the con­densing type. Common venting can result in severe corrosion of other appliances or their venting and can allow combustion gases to escape through such appliances or vents. Do not vent the furnace to a fireplace chimney or building chase.
!
WARNING:
FURNACE MUST NOT BE COMMON VENTED WITH OTHER APPLIANCES.
Vent Pipe Material
Vent and combustion air pipe and fittings must be one of the following materials and must conform to the indicated ANSI/ASTM standards:
Material Standard Schedule 40 PVC D1785 PVC-DWV D2665 SDR-21* D2241 & SDR-26* ABS-DWV D2661 Schedule 40 ABS F628
Cement and primer must conform to ATSM Standard D2564 for PVC and Standard D2235 for ABS. When joining PVC piping to ABS, use PVC solvent cement. (See procedure specified in ASTM Standard D3138.)
Vent Pipe Length and Diameter
In order for the furnace to operate properly, the combustion air and vent piping must not be exces­sively restrictive. To ensure this use Table 5, which indicates the maximum allowable piping length for a furnace of specified input rate, when installed
14
Page 15
with piping of selected diameter and number of elbows. This table applies to the length and num­ber of elbows for each pipe. To use the table, the furnace input rate, the centerline length and the number of elbows on each pipe must be known. Choose the diameter for which the tabulated length is equal to or greater than required.
Proper use of the table is illustrated by the following example:
Example:
An 80,000 Btuh furnace is to be installed in a "one-pipe" system with 40 feet of vent piping. There are four elbows, including those exterior to the building.
Solution:
Consulting Table 5, in the single pipe length column for an 80,000 Btuh furnace, the maxi­mum allowable length of 2" is 60 feet with one elbow. Select 2-1/2 or 3" pipe. For three addi­tional elbows, deduct 2.5 ft. for each elbow, or
7.5 ft. for a maximum installed vent length of
52.5 ft.
NOTE: Always use the same or larger size piping for combustion air as is used for the exhaust vent.
Vent Pipe Installation
Pipe Routing and Support
Route piping as directly as possible between the furnace and the outdoors and remember that routing affects pipe size requirements per the preceding section. If a two pipe system is used, locate the combustion air intake and the vent exhaust in the same atmospheric pressure zone
- i.e. both must exit the building though the same portion of exterior wall or roof. Vent piping must be sloped upwards not less than 1/4" per foot in the direction from the furnace to the terminal. This is to ensure that any condensate flows back to the furnace (where it can be disposed of through the condensate disposal system).
The quality of outdoor air must also be consid­ered. Be sure that the combustion air intake is not located near a source of solvent fumes or other chemicals which can cause corrosion of the furnace combustion system.
Condensing furnace combustion products have very little buoyancy, so Table 5 is to be used without consideration of any vertical rise in the piping.
Combustion air must not be drawn
!
CAUTION:
from a corrosive atmosphere.
APPLICATION SINGLE PIPE L ENGTH (f t .) DIRECT VENT, DUAL PIPE LENGTH (ft.)
with 1 long radius el bows* . with 1 l ong radi us el bow s on each pi pe.*
PVC,CPVC or ABS Outlet Outlet Inlet/Outlet Inlet/Outlet Inlet/Outlet
SCH. 40 Pipe Size 2" 3" 2" 2" 3" 2" 3" 3"
Models
G6RC,D,L 80 150 40 40 50 50 90 90
040
Models G6RC,D,L 60 150 30 30 35 35 90 90 060 & 080
Models G6RC,D,L 30 150 15 15 25 25 90 90 100 & 120
*NOTES
1. Subtract 2.5 ft. for each additional 2" elbow and 3.5 ft. for each additional 3" elbow.
2. Two 45 degree elbows are equivalent to one 90 degree elbow.
3. One short radius elbow is equivalent to two long radius elbows
4. Do not include termination elbows in calculation of vent length
5. This table is applicable for elevations from sea level to 2000 ft. For higher elevations decrease vent pipe lengths by 8% per 1000 ft. of altitude.
6. Only the above pipe materials are approved for use with G6 Condensing Furnaces.
Table 5. Vent Table
15
Page 16
G6RC & G6RD Upflow Furnaces
Exhaust
Inlet
5/8"
Supports at Minimum of 5 ft. Intervals
Combustion Offset with
Exhaust Pipe for Adequate Dimensional Clearance
PVC or ABS Pipe
Straight Neoprene Coupling with 2 Hose Clamps* (Optional - Not Shown)
G6RL Downflow Furnaces
See Vent T able 4
Straps or Other Suitable
Coupling
Upward Pitch - 1/4" per Foot
Outlet Exhaust Vent
First Support Placed as Close to Furnace Connection as Possible
Exhaust Vent
Seal/Caulk around Pipe at Building
90˚ Elbow
12" Min.
7"
Wall
Normal Snow Level
Seal/Caulk around Pipe at Building
90˚ Elbow
12" Min.
Normal Snow Level
See Vent T able 4
Straps or Other Suitable
Supports at Minimum of 5 ft. Intervals
Coupling
Upward Pitch - 1/4" per Foot
Outlet Exhaust Vent
First Support Placed
Wall
as Close to Furnace
Connection as Possible
Exhaust Vent
Exhaust
Inlet
5/8"
Combustion Air Inlet
Offset with Exhaust Pipe for Adequate Dimensional Clearance
PVC or ABS Pipe
Straight Neoprene Coupling with 2 Hose Clamps
Figure 14. Horizontal Venting
* These couplings are field-supplied and can be used if the installation requires breakable
connections in the piping. Note that a maximum of two couplings per pipe are allowed.
16
Page 17
G6RC & G6RD Upflow Furnaces
Support System on
Vertical Rise Below Joints
Support System with
first support as close
to furnace as Possible
5'
Combustion
Air Pipe
Furnace Front
Exhaust
Vent
Straight Neoprene Couplings with 2 Hose Clamps* (Optional - Not Shown)
G6RL Downflow Furnaces
Exhaust
Vent
Combustion
Air Pipe
Cabinet
Support System on
Vertical Rise Below Joints
Support System with
first support as close
to furnace as Possible
Upward Pitch 1/4" per Foot
5'
Straight Neoprene Rubber Couplings with 2 Hose Clamps
Cabinet
Furnace Front
Upward Pitch 1/4" per Foot
Figure 15. Vertical Venting
* These couplings are field-supplied and can be used if the installation requires breakable
connections in the piping. Note that a maximum of two couplings per pipe are allowed.
G6RC & G6RD Upflow Furnaces
Combustion Air Inlet Pipe Collar Diameter 3" for coupling or reducer
Furnace Top
2" PVC
Exhaust Vent
All Models
G6RL Downflow Furnaces
Combustion Air Inlet 2" PVC on G6RL 040/060 models, 3" PVC on G6RL 080/100 models
Furnace Top
2" PVC Exhaust Vent All Models
Figure 16. Furnace Pipe Adaptions
17
Page 18
Piping must be mechanically supported so that its weight does not bear on the furnace. Sup­ports must be at intervals no greater than five feet, and at smaller intervals if necessary to ensure that there are no sagging sections to trap water. (See Figures 14 and 15.)
Figure 16 illustrates vent and combustion air pipe sizes exiting the furnace. Transition to the correct pipe size must be done close to the furnace so that the full length of pipe is of proper size.
Straight neoprene couplings are supplied with the downflow furnaces only. These couplings are to be installed in the combustion air inlet (if present) and exhaust vent piping at the furnace as shown in Figures 13 and 14. For an upflow furnace installation, if breakable connections are required in the combustion air inlet (if present) and exhaust vent piping, then straight neoprene couplings for 2” or 3” piping with hose clamps can be used. These couplings can be ordered through your local furnace distributor.
To install a coupling, slide the rubber coupling over the end of the pipe that is attached to the furnace and secure it with one of the hose clamps. Then slide the other end of the rubber coupling onto the other pipe from the vent and secure the coupling with the second hose clamp. Ensure that the connection is tight and leak free.
NORDYNE condensing furnaces have been certified for installation with zero clearance be-
tween vent piping and combustible surfaces. However, it is good practice to allow space for convenience in installation and service.
Location of Outdoor Terminations
Vent and combustion air intake terminations must be located to ensure proper furnace opera­tion and to conform to applicable codes. Figure 16 illustrates necessary distances from the vent termination to windows and building air intakes.
In Canada, the Canadian Fuel Gas Code takes precedence over these instructions. Specifically, all minimum distance require­ments with respect to termination of the vent piping listed below (items 1 through 8).
The following list is a summary of vent terminal location requirements:
1. The termination must be 12 inches above snow level or grade level whichever is higher. See Figure 18 for alternate method to achieve 12" above snow level.
2. The minimum distance for a (1-pipe instal­lation) from any door, (openable) window, or gravity air inlet is 4 ft. below, 4 ft. horizon­tally, or 1 ft. above.
3. The minimum distance for a direct vent (2­pipe) installation) from any door, (openable) window, or air gravity inlet is 1 ft. below, 1 ft. horizontally, or 1 ft. above.
4. For one-pipe installations the recommended minimum distance from an inside corner formed by two exterior walls is 6 feet, but is not required.
18
Direct vent terminal 50,000 Btuh or less
9 in.
12 in. min
Mechanical draft vent terminal
4 ft. min
4 ft. min
12 in. min
Mechanical draft vent terminal
12 in. min
12 in. min
12 in. min
Direct vent terminal ­more than 50,000 Btuh
Figure 17. Vent Termination Clearances
Mechanical draft vent terminal
Less
than 10 ft.
3 ft. min.
Grade
Forced Air Inlet
Page 19
5. The vent termination for a 1-pipe installa-
g
tion shall be a minimum of 3 ft. above any forced air inlet within 10 ft.
6. The vent termination shall be located at least 4 ft. horizontally from any electric meter, gas meter, regulator and any relief equipment. These distances apply ONLY to U.S. installations. In Canada, the Canadian Fuel Gas Code takes precedence.
7. Avoid areas where condensate drainage may cause problems by dropping on plant­ers or patios, etc. Also ensure that exhaust gases will not impinge on windows or build­ing surfaces, which may be compromised or damaged by condensation. Do not install the vent terminal such that exhaust is di­rected into window wells, stairwells, under decks or into alcoves or similar recessed areas, and do not terminate above any public walkways.
8. Select the point of wall penetration where the minimum 1/4 inch per foot of slope up can be maintained.
Vent Configuration to Provide 12" Minimum height above Snow Level.
Outside Wall
Pipe Coupling
Figure 18. Alternate Horizontal Vent
Installation
For horizontal venting, one of the following kits is recommended:
12" Min.
19" Max.
Support
1/2" Armaflex Insulation or Equivalent
2" PVC 3" PVC
12" Above Normally Expected Snow Level
!
CAUTION:
For optimum performance, vent fur­nace through wall which experiences the least exposure to winter winds.
Horizontal Venting
Vent and combustion air intake terminations must be as shown in Figure 19.
!
WARNING:
Ensure that the combustion air vent and the exhaust vent are configured as shown in Figure 19. Improper vent termination can cause recirculation of the flue gases. This may result in fur­nace vibration. In severe cases, the furnace will cycle due to the intermit­tent contact between the flame and the flame sensor. If you note oscillations occurring, check the vent configura­tion. Make sure that the exhaust vent does not have a 90 degree termination.
Through-the-Wall Exterior Vent Mountin Neutralizer Kit - All Models
For Canadian installations please refer to the Canadian Installation Code (CAN/CGA-B149.1 or 2) and/or local codes.
The kit consists of two face plates and an insulating gasket to seal the exterior surface. A hole sized closely to the pipe diameter must first be cut through the wall. A short length of pipe is then cut such that it can penetrate the wall and be held in place by closely fitting standard cou­plings. The face plates are retained on both sides of the wall by the couplings, and the gasket is retained against the wall by the outer face plate. Face plates must be fastened to the wall and the outside one must be flashed as appro­priate to prevent entry of water.
When the above kits are not used the following steps are required:
1. Check the hole size cut through the exterior
2. Extend the vent pipe through the wall ap-
Kit
wall. Insure that the hole diameter is less than the diameter of the couplings to be used.
proximately 1" and seal the area between the wall and pipe.
9023730 9023750
9023730 9023730
19
Page 20
3. Apply couplings to the vent pipe on the interior and exterior sides of the wall to insure the pipe can not be pushed or pulled through the wall.
4. Insure the combustion air inlet pipe (for a 2 pipe installation) has a 90 degree termina­tion elbow as shown in Figures 19 and 20.
b. The top of the chimney is sealed and
weatherproofed.
c. The termination clearances shown in
Figure 20 are maintained.
d. No other gas fired appliances are vented
through the chimney.
Note that a combustion air intake must be provided with an elbow opening downward. The screen provided with the furnace must be installed in the elbow to prevent entry of debris or creatures.
When the vent pipe must exit an exterior wall close to the grade or expected snow level, a riser should be provided as shown in Figure 18. Insulation is required to prevent freezing of this section of pipe.
Vertical Venting
Figure 20 shows the proper installation and clear­ances for vertical vent termination. The roof penetra­tion must be properly flashed and waterproofed with a plumbing roof boot or equivalent flashing. Termi­nation spacing requirements from the roof and from each other must be per Figure 20.
Vent and combustion air piping may be installed in an existing chimney which is not in use provided that:
a. Both the exhaust vent and air intake run
the length of the chimney.
Vent Freezing Protection
When the vent pipe is exposed to temperatures below freezing, i.e., when it passes through unheated spaces, chimneys, etc., the pipe must be insulated with 1/2 inch thick sponge rubber insulation, Armaflex-type insulation or equiva­lent. Insulating pipe is important to avoid con­densate icing.
For extremely cold climates or for conditions of short furnace cycles (i.e. set back thermostat conditions) the last three feet of vent pipe can be reduced one nominal pipe size provided that the total vent length is at least 15 feet in length and the vent is sized in accordance with the venting requirements (Table 5) before this reduction is applied. (Example: 3" to 2-1/2" or 2" to 1-1/2") Smaller vent pipes are less susceptible to freez­ing, but must not be excessively restrictive.
Concentric Vent Termination
A concentric vent termination is approved for use with these furnaces. The kit part number is
903578. For proper installation of the concentric vent termination, follow the installation instruc­tions provided with that kit.
20
Exhaust Vent
Option B
Mounting Kit
Faceplate Secured
to Wall with Screws
Combustion
Air Inlet
Exhaust Vent
Option C
7" Min.
18" Min.
36" Max.
18" Min.
36" Max.
8" Min.
18" min.
36" max.
12" Min. to
Normal Snow Level
Inlet
Figure 19. Exhaust and Combustion Air Pipe Clearances
Exhaust Vent
Option A
Grade Level or Normal Snow
Exhaust
Page 21
Elbow
Combustion
Air
Intake
A= 12" Above Roof or Snow Accumulation Level
Figure 20. Vertical Vent Termination
Exhaust
Vent
1"
18" Min. 36" Max.
A
A
Exhaust
Plumbing Vent Roof Boot (Typ. Both Pipes)
DRAINAGE OF CONDENSATE FROM FURNACE
The condensate drainage system is internal to the furnace. The drain may exit either the right or left side of the furnace cabinet. For a right side drain simply extend the tubing out of the 7/8" hole in the cabinet, see Figure 21.
For a left side drain follow the steps below:
1. Loosen the clamp on the soft exit tube (see Figure 21.)
2. Rotate the soft exit tube (counter clockwise, 180° upflow G6RC/RD models; clockwise 90° downflow G6RL models.)
A
Collector Box
3. Re-tighten the clamp. MAKE SURE CLAMP IS TIGHT TO AVOID LEAKAGE OF CON­DENSATE.
4. Route the tubing out of the 7/8" hole located 8 inches up from the bottom furnace.
The condensate should drain from the plastic collector box (location A in Figure 21) as droplets or a small stream. If you notice the furnace has operated for more than 5 minutes without drain­ing or the red status light on the control board is pulsing a 2-blink code follow the steps below.
1. Remove the collector box soft tube at loca­tion A in Figure 21 and insure the exit from
G6RLG6RC & G6RD
A
Collector Box
Left Side
Drain
8"
"HARD" J Drain Tube
Left
Rotate counter clockwise (Step 2)
Clamp (Loosen For Step 1) (Retighten for Step 3)
Route to floor drain. ...OR Route to condensate pump. Keep downward slope.
Side Drain
8"
"HARD" J Drain Tube
Rotate clockwise
(Step 2)
Clamp (Loosen For Step 1) (Retighten for Step 3)
Figure 21. Furnace with Condensate Drain Trap Assembly
Route to floor drain. ...OR Route to condensate pump. Keep downward slope.
21
Page 22
the collector box is clear of any debris or obstructions.
2. Replace this tube and insure the fit to the header spout is air tight. Air will be drawn into the header if this connection is not tight.
3. Check other tube connections along the drain system. Insure that all are air tight.
NOTE: Industry research studies indicate that when condensate is routed to an active drain, household detergents, etc., buffer its acidity. If the drain is not actively used or if codes require, obtain a neutralizer kit (usually contains lime­stone). Proper drains and connections to the condensate tubing are required as NORDYNE cannot be held responsible for water leakage which occurs due to loose hose connections or improperly sealed drain line pipes.
GAS SUPPLY AND PIPING
This furnace is equipped for either left or right side gas entry. Typical gas service hook-ups are shown in Figure 22. When making the gas connection provide clearance between the gas supply line and the entry hole in the furnace casing to avoid unwanted noise and/or damage to the furnace.
tion must comply with the latest edition of the National Fuel Gas Code (ANSI Z223.1) or (CAN/ CGA B149) installation codes.
A 1/8" NPT plugged tap must be installed in the gas line to the unit for use when measuring the gas supply pressure. The plug should be readily accessible for service use. A drip leg should be installed in the vertical pipe run to the unit. Table 5 lists gas flow capacities for standard pipe sizes as a function of length in typical applications based on nominal pressure drop in the line.
NOTE: Gas piping must not be run in or through air ducts, chimneys, gas vents, elevator shafts, etc.
Compounds used on threaded joints of gas piping must be resistant to the actions of lique­fied petroleum gases.
The main manual gas valve and main power disconnect to the furnace must be properly labeled by the installer in case emergency shut­down is required.
!
CAUTION:
All gas piping must be installed in compliance with local codes and utility regulations. Some local regulations require the installation of a manual main shut-off valve and ground joint union external to the furnace. The shut-off valve should be readily accessible for service and/or emergency use. Consult the local utility or gas supplier for additional requirements regarding placement of the manual main gas shut-off. In the absence of local codes the gas line installa-
Burner Viewport
Denotes field­provided and installed components.
Some Utilities
Require Shut-
Off Valv e to
be 4 to 5 feet
Above Floor
Shut-Off Valv e
with 1/8" NPT
Plugged T ap
Roll-Out Limit
Burner Assembly
Ground Joint Union
Automatic Gas Valve
(with manual shut-off)
Do not use matches, lighters, candles, or other sources of open flame to check for gas leaks.
Leak Check
After the gas piping to the furnace is complete, all connections must be tested for gas leaks. To check for leaks use only a soap and water solution or other approved method.
Denotes field­provided and installed components.
Burner
Assembly
Automatic Gas Valve (with manual shut-off)
Ground Joint Union
Roll-Out Limit
Some Utilities Require Shut­Off Valve to be 4 to 5 feet Above Floor
Shut-Off Valve with 1/8" NPT Plugged Tap
Burner Viewport
22
Figure 22. Typical Gas Service Connection
Page 23
CAPACITY OF BLA CK IRON G AS PIP E (CU. FT. PER HOUR)
(
)
FOR NATURAL GAS
NOMINAL LENGTH OF PIPE RUN
BLACK IRON (feet)
PIPE DIAMETER
(in.) 1020304050607080
1/2 130 90 75 65 55 50 45 40 3/4 280 190 150 130 115 105 95 90
1 5 20 350 285 245 215 195 180 170 1 1/ 4 1050 730 590 500 440 400 370 350 1 1/ 2 1600 1100 890 760 670 610 560 530
The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas flow required by the furnace. To determine the cubic feet per hour of gas flow required by the furnace, divide the input rate of the furnace by the heating value of the gas:
SPECIFI C GRAVITY - 0.6 0
Cubic Feet Per Hour Required =
Heating Value of Gas (Btu/Cu. Ft.)
Table 6. Capacity of Black Iron Gas Pipe (cu. ft. per hour)
for Natural Gas (specific gravity = .60)
NOTE: When pressure testing gas supply lines at pressures greater than 1/2 psig (14 in. water column), the furnace must be disconnected from the gas supply piping system to prevent damage to the gas control valve.
If the test pressure is less than or equal to 1/2 psig (14 in. water column), the furnace must be isolated from the gas supply line by closing the manual shut-off valve.
!
WARNING:
This furnace was equipped at the fac­tory for use with natural gas only. A special kit, supplied by the manufac­turer, is required to convert the fur­nace to operate on LP/propane gas. Failure to use the proper conversion kit can cause fire, explosion, property damage, carbon monoxide poisoning, personal injury, or death.
Conversion
Conversion of this furnace to use LP/propane gas must be made by qualified service personnel, using only approved parts.
High Altitude Application
High altitude application with this furnace can be field performed by a simple adjustment of manifold pressure, and if necessary changing the orifices. The changes required depend on
Input To Furnace (Btu/hr)
the installation altitude and the heating value of the gas. The gas heating value based on sea level can be obtained from your local gas utility. The heating value of gas at high altitude is always lower than the sea level heating value. The heating values used in Tables 7 & 8 are based on sea level values.
Natural Gas High Altitude Conversion
All factory shipped furnaces are ready to operate between zero and 4999 ft. above sea level. For higher altitudes (between 5000 and 10,000 ft. above sea level), conversion can be achieved simply by adjusting the furnace manifold pressure
as shown in Table 7.
LP/Propane Gas Sea Level and High Altitude Conversion
Conversion of this furnace to utilize LP/propane gas must be made by qualified service personnel, using factory authorized or approved parts. Conversion to LP/propane gas can be accomplished by first replacing the natural gas orifices with the appropriate LP/propane orifices shown in Table 9 or 10. Note: for installations between zero and 5000 ft. above sea level, a #54 or #55 drill size orifice should be used depending upon the rated firing rate of the unit (see Table 9 or 10). However for installations above 5000 ft. above sea level, a # 55 or #56 drill size orifice should be used. After changing the orifices, use Table 8 to determine the appropriate manifold pressure for your installation.
23
Page 24
Conversion to LP/propane, sea level, and high
(
)
(
)
(
)
altitude is detailed in the installation instructions provided with the conversion kit. Approved conversion kits are listed below.
United States LP/Propane Gas Sea Level and High Altitude Conversion Kit - P/N 903616
This kit is for LP/propane conversion in the United States at altitudes between zero and 10,000 ft. above sea level. Follow the installation instructions supplied with the kit for proper installation.
Canadian LP/Propane Gas Sea Level and High Altitude Conversion Kit - P/N 903617
This kit is for LP/propane conversions in Canada at altitudes between zero and 4500 ft. above sea level. Follow the installation instructions supplied
with the kit for proper installation.
!
CAUTION:
To avoid electric shock, personal in­jury, or death, turn off the power at the disconnect or the main service panel before making any electrical connec­tions.
ELECTRICAL WIRING
Electrical connections must be made in accor­dance with all applicable local codes and ordi­nances, and with the current revision of the National Electric Code (ANSI/NFPA 70).
For Canadian installations electrical connec­tions and grounding must be done in accor­dance with the current Canadian Electrical Code (CSA C22.1 Part 1) and/or local codes. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wire having a minimum temperature rating of 105°C. Refer to the furnace nameplate and Table 11 for electrical requirements.
Line Voltage Wiring
The line voltage (115 volt) to the furnace must be supplied from a dedicated branch circuit con­taining the correct fuse or circuit breaker for the furnace. See Table 11. An electrical switch should be readily accessible from and within sight of the furnace. (See the Wiring Diagram label in the furnace and Figure 23.)
The furnace cabinet must have an uninterrupted, unbroken ground to minimize injury should an electrical fault condition occur. The controls
For a Natural Gas Sea Level Heating Val ue o f 800 to 899 Btu/cu.ft.
Elev at ion
zero to
1999
Ma ni fold Pressure S etti n g ( in WC)
For a Natural Gas Sea Level Heating Val ue o f 900 to 999 Btu/cu.ft.
Ma ni fold Pressure S etti n g ( in WC)
For a Natural Gas Sea Level Heating Valu e of 1,000 to 1,100 Btu/cu.ft.
Ma ni fold Pressure S etti n g ( in WC)
3.5 3.5 3. 5
zero to
1999
3.5 3.5 3. 5
zero to
1999
3.5 3.5
2000 to
4999
Elev at ion
2000 to
4999
Elev at ion
2000 to
4999
fe et above sea l evel
5000 to
5999
fe et above sea l evel
5000 to
5999
fe et above sea l evel
5000 to
5999
3.0 2.8 2. 5
6000 to
7999
3.5 3.0
6000 to
7999
3.2 2.8
6000 to
7999
Table 7. Manifold Pressure (in WC) for Natural Gas at Various Altitudes
Elev at ion (fee t a b o ve sea leve l)
0 to 2,000 to 5,000 to 6,000 to 8,000 to
1,999 4,999 5,999 7, 999 10, 000
Manifold Pressure in (WC) fo r an LP Gas Heat ing Valu e of 2,500 Btu/hr.
10.0 8.5 10.0 9.0 8.5
8000 to
10000
8000 to
10000
8000 to
10000
Table 8. Manifold Pressure (in WC) for LP/Propane Gas at Various Altitudes
24
Page 25
Furn ace Rati ng
g
Plate I n pu t (Btu/ h)
Orifice Drill Size
Nat LP
Furn ace Rati n
Plate I n pu t (Btu/ h)
Orifice Drill Size
Nat LP
45000 44 54 60000 45 55 72000 43 54
96000 43 54 120000 43 54 144000 43 54
Table 9. Natural and LP Gas Orifice Sizes
for Elevations between zero and
4999 ft. Above Sea Level
used in this furnace require an earth ground to operate properly. Acceptable methods for grounding are electrical wire or conduit ap­proved for electrical ground service. Do not use gas piping as an electrical ground.
NOTE: Proper line voltage polarity must be maintained in order for the control system to operate correctly. Verify that the incoming neutral line is connected to the white wire and the incoming "hot" line is connected to the black wire in the furnace junction box. These furnaces will not operate unless po­larity and ground are properly connected. See Figure 23.
!
CAUTION:
Label all wires prior to disconnection when servicing controls. Wiring er­rors can cause improper and danger­ous operation. Verify proper opera­tion after servicing.
Low Voltage Wiring
Install the thermostat per the manufacturer's instructions. The low voltage (24 volt) connec­tions from the thermostat are made at the terminal strip on the control board in the fur-
Field Supplied Fused Service
Panel
Black (Hot)
White (Neutral)
Green or Bare
(Ground)
Ground
Field Supplied
Panel Connector
Black White
Ground
Black
White
45000 44 55 60000 45 56 72000 43 55
96000 43 55 120000 43 55 144000 43 55
Table 10. Natural and LP gas Orifice Sizes
for Elevations between 5000 and 10,000 ft.
Above Sea Level
nace. See Figure 24 for the proper connections for heating only (two-wire) and heating/cooling (four-wire) applications. The recommended minimum wire gauge for thermostat wiring is shown in Table 11.
The thermostat must not be installed on an outside wall or any other location where its opera­tion may be adversely affected. Adverse affects include radiant loading from fireplaces, sunlight, or lighting fixtures, and convective loading from warm air registers or electrical appliances.
To check the heat anticipator setting either:
1. Add the current draw of the system compo­nents; or
2. Measure the current flow on the thermostat R-W circuit after the circulating blower mo­tor has started.
Set the heat anticipator according to the thermo­stat manufacturer's instructions for heat antici­pator settings.
START-UP AND ADJUSTMENTS
Prior to start-up, verify that:
1. The line voltage power leads are securely connected, that the polarity of the connec­tions is correct, and that the furnace is properly grounded.
Field Line Voltage
Black White
Ground
Wiring Factory Line
Voltage Wiring
Field Supplied Disconnect Within Sight of Furnace
Figure 23. Line Voltage Field Wiring
25
Page 26
Furnace Cabinet Nominal Maximum Minimum Maximum Minimum Maximum
Input W i d t h El ect ri c al Op erat ing Operati ng Furnac e Wi re Fuse o r Ci r cu it
(Btuh) (in.) Supply Voltage Voltage Amperes Gauge Breaker Amps*
40,000 14.25 115-60-1 127 103 12.2 14 15 60,000 14.25 115-60-1 127 103 12.2 14 15
80,000 19.75 115-60-1 127 103 14.1 14 15 100,000 19.75 115 -60-1 127 103 14.1 14 15 120,000 22.50 115 -60-1 127 103 17.3 12 20
* Time-delay fuses or HACR-type circuit breakers are required.
Thermostat Recommended Thermostat
Wire Wire Length
Gauge 2-wire 4 or 5-wire
(heating) (cooling)
24 55 ft. 25 ft. 22 90 ft. 45 ft. 20 140 ft. 70 f t . 18 225 ft. 110 ft .
Table 11. Electrical Data
A/C Condensing Unit
Condensing Unit
Control Box
R Y G W
Connect
R & W
For
Heating
Only
Room
Thermostat
NOTE: The "Y" terminal on the UTEC control board must be connected to the thermostat.
FIELD WIRING
Low Voltage Connections
R C Y G W
COM
3 Amp
Fuse
24 V
3
6
9
2
5
8
1
4
7
EAC
HUM
Neutrals
Unused Motor Leads
HUM
63 52 41
Blower Off
Flame Signal Light
Status Light
COOL
M1M2M3
Timing
(Yellow)
(Red)
HEAT
EAC
6090120
TWIN
XFMR
L1
Figure 24. Low Voltage Field,
Four-wire Heating/Cooling Applications
2. The thermostat wires (R, W, Y, and G) are securely connected to the correct leads on the terminal strip of the circuit board.
3. The gas line service pressure does not exceed 10.0 in. water column (0.36 psig), and is not less than 4.5 in. water column (0.16 psig) for natural gas. For LP gas the line service pressure must not exceed 14 in. water column (0.51 psig), and must not be less than 11.0 in. W.C. (0.40 psig).
4. The roll-out and vent safety manual reset switches are closed. If necessary, press the red button to reset a switch. See Figure 28
26
for location. DO NOT install a jumper wire across a switch to defeat its function. If a switch reopens on start-up, DO NOT reset the switch without identifying and correct­ing the fault condition which caused the
180
switch to trip.
5. The blower door is in place, closing the door switch in the line voltage circuit.
6. The gas line has been purged and all con­nections are leak tight.
Start-Up Procedure
1. Set the thermostat to the lowest setting.
2. Close the disconnect(s) to provide line volt­age to the furnace.
3. Follow the procedures given on the operat­ing instructions label attached to the furnace.
4. Set the thermostat above room tempera­ture and verify the sequence of operation. (See the SEQUENCE OF OPERATION.)
5. After the furnace has run for approximately five minutes, set the thermostat below room temperature and verify steps (9) through (11) of the SEQUENCE OF OPERATION.
Verifying and Adjusting Firing Rate
The firing rate must be verified for each installa­tion to prevent over-firing the furnace.
NOTE: The firing rate must not exceed the rate shown on the furnace rating plate. At altitudes above 2000 ft. the firing rate must be adjusted as described in the high altitude section.
Page 27
Use the following procedure to determine the firing rate:
1. Shut off all other gas fired appliances.
2. Start the furnace and allow it to run for at least three minutes.
3. Measure the time (in seconds) required for the gas meter to complete one revolution.
4. Convert the time per revolution to cubic feet of gas per hour using Table 12.
5. Multiply the gas flow rate in cubic feet per hour by the heating value of the gas in Btu per cubic foot to obtain the firing rate in Btuh. Example:
Time for 1 revolution of a gas meter with
a 1 cubic foot dial = 40 seconds.
From Table 9 read 90 cubic feet per hour
of gas.
Heating value of the gas (obtained from
gas supplier) = 1040 Btu per cubic foot.
Firing rate = 1040 x 90 = 93,600 Btuh.
6. Adjustments to the firing rate can be made by adjusting the gas manifold pressure. See the High Altitude Application section for additional information of firing rate at elevations above 2000 ft.
The manifold pressure must be set to the appro­priate value for your installation. Refer to either Table 7 for natural gas or Table 8 for LP/propane gas to verify the manifold pressure setting re­quired for your particular installation. To adjust the manifold pressure, remove the regulator cap and turn the adjusting screw clockwise to in­crease pressure or counterclockwise to reduce pressure. Replace the regulator cap after adjust­ments are complete.
!
CAUTION:
Do not re-drill the burner orifices. If the orifice size must be changed, use only new orifices.
Verifying and Adjusting Temperature Rise
Verify that the temperature rise through the furnace is within the range specified on the furnace rating plate. Temperature rises outside the specified range could result in premature heat exchanger failure.
Place thermometers in the return and supply air stream as close to the furnace as possible. The
thermometer on the supply air side must be shielded from direct radiation from the heat exchanger to avoid false readings. Adjust all registers and duct dampers to the desired posi­tion and run the furnace for fifteen minutes before taking any temperature readings. The temperature rise is the difference between the supply and return air temperatures.
For typical duct systems, the temperature rise will fall within the range specified on the rating plate with the blower speed at the factory recom­mended setting. If the temperature rise mea­sured is outside the range specified, it may be necessary to change the blower speed. Lower blower speeds will increase the temperature rise and higher blower speeds will decrease the temperature rise.
The furnace is equipped with a multispeed mo­tor. Heating and cooling speed selection is made by moving the leads on the integrated control board located in the furnace. The wiring diagram on the furnace and Figures 25, 26 and 27 show the speed taps for adjusting motor speed.
If it is desired that the blower operate at the same speed for heating and cooling, tape off the terminal of the unused blower wire. Install the jumper wire, found in the plastic instruction bag, across the HEAT and COOL taps on the control board. Reconnect the desired blower tap to the piggyback quick connect.
The blower control is designed to start the circulating air blower 30 seconds after the gas valve is opened. The blower control is factory wired to turn the blower motor off 120 seconds after the gas valve is closed. This timing can be changed using the BLOWER OFF timing switch opposite the terminal block on the control board. (See Figure 25.)
Verifying Burner Operation
To verify operation of the burners, make sure that the blower compartment door is in place and that there is power to the furnace. Set the thermostat above room temperature and ob­serve the ignition sequence. The flame can be observed through the small clear window on the burner box. The burner flame should carry over between all burners. The flames should be blue, without yellow tips. Flames should extend from each burner without lifting, curling, or floating. After verifying ignition, set the thermostat below room temperature and verify that the burner flame extinguishes completely.
27
Page 28
28
U
TIME FOR
ONE REVOLUTION
(SECONDS) 1 5 10
80 45 225 450 82 44 220 439 84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375
98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 327 112 32 161 321 114 32 158 316 116 31 155 310 118 31 153 305 120 30 150 300
CUBIC FEET PER REVOL UTI ON OF
METER
TIME FOR
ONE REVOLUTION
(SECONDS) 1 5 10
CUBIC FEET PER REVOL UTI ON OF
METER
24 150 750 1500 26 138 692 1385 28 129 643 1286
Table 12. Gas Flow Rate
30 120 600 1200 32 113 563 1125 34 106 529 1059 36 100 500 1000 38 95 474 947 40 90 450 900 42 86 429 857 44 82 409 818 46 78 391 783 48 75 375 750 50 72 360 720 52 69 346 692 54 67 333 667 56 64 321 643 58 62 310 621 60 60 300 600 62 58 290 581 64 56 281 563
GAS F LOW RATE (C
BIC F EET PER HOUR )
Page 29
Verifying Operation of the Supply Air Limit Switch
To verify operation of the supply air limit switch, make sure that the blower door is in place and that there is power to the furnace. Completely block the return airflow to the fur­nace by installing a close-off plate in place of or upstream of the filter(s). Set the thermostat above room temperature and verify that the Sequence of Operation is as described in these instructions. The supply air limit switch should function to turn off the gas valve within approxi­mately five minutes. The circulating air and combustion blowers should continue to run when the supply air limit switch opens. Remove the close-off plate immediately after the supply air limit switch opens. If the furnace operates for more than five minutes with no return air, set the thermostat below room temperature, shut off the power to the furnace, and replace the supply air limit switch.
Flame Sensor – The flame sensor acts to prove that flame has carried over from the ignitor to the opposite end burner. If no flame is sensed, the furnace will be shut down automatically.
Gas Valve – The gas valve controls the flow of gas to the burners. When the gas valve is energized it automatically opens and regulates the gas pressure in the manifold.
Pressure Switch – The pressure switch verifies that the inducer is drawing the combustion gases through the heat exchanger. It also senses a blocked condensate drain condition.
Vent Pressure Switch (G6RD Only) – The vent pressure switch reacts to blockage in the vent or combustion air piping. It is utilized in G6RD furnaces only.
Supply Air Limit Switch – The supply air limit switch prevents the air temperature leaving the furnace from exceeding the maximum outlet air temperature.
DESCRIPTION OF COMPONENTS
Figure 28 shows the location of each of the functional components described below. If any component of the furnace must be re­placed, use only factory authorized replace­ment parts. See the Replacement Parts List for each component.
Common
Leads
Connect
Neutral
Lead of
Electronic
Air Cleaner
and/or Humidifier
Here.
R C Y G W
EAC
HUM
Humidifier Tap
(.5A@ 120 VAC)
COM
24 V
3
6
9
2
5
8
1
4
7
Neutrals
63
HUM
52 41
Vent Safety Switch – The vent safety switch shuts the furnace down if the outlet flue gas temperature increases above 160°F. This switch protects the plastic flue system and the inducer from over-temperature conditions.
Flame Roll-Out Switch – This switch provides flame roll-out protection to the furnace and combustion air inlet pipe.
90
60
120
3 Amp Fuse
Unused Motor
Leads
M1M2M3
Cooling
Speed Tap
Blower Off
Timing
Flame Signal Light (Yellow)
Status
Light (Red)
COOL
HEAT
EAC
Heating Speed Tap
180
TWIN
XFMR
L1
Electronic Air Tap
(.5A@ 120 VAC)
Figure 25. Blower Speed Tap Location
29
Page 30
For G6RC, G6RD and G6RL Residential Furnaces
BLOWER
DECK SWITCH
(SELECT MODELS
ONLY)
BLUE
LIMIT SWITCH
(ALL MODELS)
WHITE (NEUTRAL)
ROOM THERMOSTAT
AIR CONDITIONER CONDENSING UNIT
FLAME SENSOR
SUPPLY AIR
BLACK 120V
GROUND
R Y G
W
GAS
VALVE
C Y
BLUE
RED
FLAME ROLL-OUT
(ALL MODELS)
YELLOW BROWN
SWITCH
BLUE
BLUE
BLUE
ORANGE
ORANGE
VENT SAFETY SWITCH
(ALL MODELS)
WHITE
GREEN
WHITE W/ BLK STRIPES
BLK W/ WHITE STRIPES
BLACK
TRANSFORMER
24 V
90
60
PRESSURE
SWITCH
BLOWER DOOR SWITCH
WHITE
120 V
BLACK
180
120
BLACK
VENT PRESSURE SWITCH (93+ MODELS ONLY)
3 OR 4 SPEED MOTOR
C
ML
L
H
MH
IGNITOR
Legend
Field Wiring
Factory Wiring:
Low Voltage High Voltage
FAULT CONDITION Power On Limit Circuit Open Pressure Switch Stuck Open Pressure Switch Stuck Closed Ignition Failure (Check Ground)
115 VAC & Neutral Reversed or no Ground
False Flame or Gas Valve Relay Shorted
Power Off
FAULT CONDITION Low Flame Sensor Signal
Flame Present
R
INDUCER
BLACK
BLACK BLACK
C
BLACK
STATUS
RED
LIGHT
ON
1 FLASH 2 FLASHES 3 FLASHES 4 FLASHES 5 FLASHES Continuous
OFF
FLAME
YELLOW
LIGHT
Continuous
Flash
ON
WHITE
RED ORANGE BLUE BLACK
WHITE
1 2 3 4
5
6
MOTOR
PLUG
THESE WIRES ARE
NOT PRESENT
ON 3 SPEED
MODELS
If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature rating of at least 105 C.
RED
BLUE
ORANGE
BLACK
Figure 26. G6RC, G6RD and G6RL Integrated Control Board System Diagram
30
Page 31
MAINTENANCE
It is recommended that the furnace be checked yearly. At a minimum, this check should include the following items.
!
WARNING:
To avoid electric shock, personal in­jury, or death, disconnect the electric power before performing any mainte­nance.
!
WARNING:
Holes in the vent pipe or heat ex­changer can cause products of com­bustion to enter the home. Replace the vent pipe or heat exchanger if leaks are found. Failure to prevent products of combustion from being circulated into the living space can create potentially hazardous condi­tions including carbon monoxide poi­soning that could result in personal injury or death.
Combustion Air and Vent System
Check the combustion air and vent pipe to ensure that it is not damaged, corroded or blocked by debris. Any damaged section of vent pipe must be replaced, and any obstruction or blockage must be removed prior to operating the furnace.
Air Filter(s)
The installer should provide a filter rack for a high velocity type filter in the return air duct adjacent to the furnace. Filters should be changed or cleaned monthly during the heating season. New or newly renovated homes may require more frequent changing until the construction dust has been removed.
Lubrication
The bearings in the circulating air blower motors are pre-lubricated and sealed at the factory. No further oiling of the bearings is required for the life of the motor.
Condensate Drain Assembly
Be sure the condensate lines are free and open (i.e. avoid kinking hoses). Also make sure all hose clamps are tight to avoid drawing air into the system.
Blower Compartment
The blower compartment should be cleaned monthly during the heating and cooling seasons to remove any dirt and lint that may have accu­mulated in the compartment or on the blower and motor. Dirt and lint can create excessive loads on the motor resulting in higher than normal operating temperatures and shortened service life.
Heat Exchanger and Burner Maintenance
The furnace should operate for many years without excessive soot buildup in the flue pas­sageways, however, the flue passageways, the vent system, and the burners should be in­spected and cleaned (if required) by a qualified serviceman annually to ensure continued safe operation. Particular attention must be given to identify deterioration from corrosion or other sources.
!
WARNING:
Never operate the furnace without a filter in place. Dust and lint in the return air can build up on internal components, resulting in loss of effi­ciency, equipment damage, and pos­sible fire.
AIR FILTER(S) ARE NOT SUPPLIED WITH THE FURNACE AS SHIPPED FROM THE FACTORY. FILTERS FOR SIDE RETURN AND BOTTOM RETURN APPLICATIONS ARE AVAILABLE FROM NORDYNE DISTRIBUTORS.
SYSTEM OPERATION INFORMATION
Proper maintenance is most important to achieve the best performance from a furnace. Follow these instructions for years of safe, trouble free operation.
• Do not place combustible materials on or against the furnace cabinet or the vent pipe.
• Do not store gasoline or any other flam­mable vapors and liquids in the vicinity of the furnace.
31
Page 32
G6RC & G6RD Upflow Furnaces
1
2
3
4
9
10
11
12
17
19
5 7
8
13
14
15
16
18
1 Ignitor (Not Shown) 2 Flame Sensor (Not
Shown) 3 Gas Valve 4 Flame Roll-out Switch(s) 5 Pressure Switch 6 Vent Pressure Switch
(G6RD Only, Not Shown) 7 Control Board 8 Blower Door
Switch 9 Vent Safety Switch
10 Low Voltage
Transformer
11 Supply Air Limit
Switch
12 Circulating Air
Blower Assembly-
13 Induced Draft
Blower
14 Condensate Drain Tube 15 In-Line Drain
Assembly
16 Burner View Port 17 Front Header Box 18 Combustion Air
Intake
19 Exhaust Vent
G6RL Downflow Furnace
1 Ignitor (Not Shown) 2 Flame Sensor (Not
Shown) 3 Gas Valve 4 Flame Roll-out
Switch(s) 5 Pressure Switch 7 Control Board 8 Blower Door
Switch 9 Vent Safety Switch
10 Low Voltage
Transformer
11 Supply Air Limit
Switch
12 Circulating Air
Blower Assembly-
13 Induced Draft
Blower
14 Condensate Drain
Tube
15 In-Line Drain
Assembly
16 Burner View Port 17 Front Header Box 18 Combustion Air
Intake
19 Exhaust Vent
10
7 8
5
13
9
14
11
3
1 4
19 18
12
15
17
2
16
Figure 28. Location of Major Components
32
Page 33
• Change or replace the air filters monthly during any period when the circulating blower is operating regularly.
• Always replace the doors on the furnace after servicing. Do not operate the furnace without all doors and covers in place.
• Avoid operating the furnace when win­dows and doors are open.
• Be sure that the thermostat is properly installed and is not being affected by drafts or heat from lamps or other appliances.
Sequence of Operation
Operating sequences for the heating, cooling, and fan modes are described below. Refer to the wiring diagrams (Figures 26 and 27) and the low voltage field wiring diagram (Figure 24).
Heating Mode:
1. On a call for heat the thermostat closes, applying 24 VAC to the W terminal on the control board.
2. The control board checks for continuity on the 24 VAC limit control circuit (over-tem­perature limit switch, flame rollout switches and blocked vent switch in series). If an open limit is detected the control board will energize the inducer and the conditioned air blower. All other system functions will be inoperable until the limit circuit closes. While the limit is open, the red LED will pulse at a rate of 1 blink per unit time.
3. The furnace control checks for continuity across the pressure switch (24 VAC). If the pressure switch is closed the heat mode sequence will not continue. If it remains closed for 10 seconds the red LED will blink 3 times repetitively until the fault condition clears.
4. The inducer is energized.
5. The pressure switch will close. If the pres­sure switch does not close after 10 seconds the fault LED will blink 2 times repetitively and the inducer will continue to run until the switch is closed.
6. The inducer will pre-purge for 30 seconds and then the ignitor will start its warm-up. After 30 seconds of ignitor warm-up the gas valve (24 VAC) will open. The ignitor circuit stays energized for 6 seconds after the gas valve opens.
7. The furnace control must prove flame via the flame sensor six seconds after the gas valve opens. If flame is sensed, all burners are on and the ignitor cools off. If no flame is sensed, the gas valve closes immediately and the inducer continues to run. A second trial for ignition (step 6) begins if no flame is sensed. On the fifth try for ignition, the furnace control is locked out and the red LED will blink 4 times repetitively. The ther­mostat must be opened for at least ten seconds to reset the furnace control after a lock out. Otherwise, the furnace will attempt another ignition sequence in 1 hour.
8. The furnace control energizes the circulat­ing air blower on the heating speed 30 seconds after the gas valve circuit is ener­gized .
9. When the thermostat has been satisfied, gas valve is de-energized.
10. The inducer is de-energized after a 30 second postpurge.
11. The furnace control keeps the circulating air blower energized for 120 seconds (factory set) or 60, 90, or 180 seconds (field adjust­able). (See Figure 25.)
12. Abnormal conditions: If a limit opens during operation, the inducer and circulating air blower continue to operate. The gas valve is de-energized immediately. The blowers continue to operate until the limit closes. When the limit closes the inducer blower is de-energized immediately. The circulating air blower continues to operate for the speci­fied delay (factory set at 120 seconds).
Cooling Mode:
1. On a call for cooling the thermostat closes, applying 24 VAC to the G and Y terminals on the furnace control. This closes the compressor contactor.
2. The furnace control energizes the circulat­ing blower (115 VAC) on the cooling speed.
3. When the thermostat is satisfied, the G and Y terminals on the control board are de-energized opening the compressor con­tactor.
4. The circulating air blower is de-energized after a 90 second delay.
33
Page 34
Fan Mode:
1. On a call for fan operation, the thermostat applies 24 VAC to the G terminal on the furnace control board.
2. The circulating air blower is energized im­mediately on the heating speed.
3. If the furnace is operated in the continuous ON position at the thermostat and is then switched to AUTO, the circulating blower will operate for a specified delay (factory set at 120 seconds).
Furnace Fails to Operate
If the furnace does not operate check the follow­ing:
1. Is the thermostat operating properly?
2. Are the blower compartment door(s) in place?
3. Is the furnace disconnect closed?
4. Has the circuit breaker tripped or the control board fuse burned open?
5. Is the gas turned on?
6. Are any manual reset switches open?
7. Is the filter dirty or plugged?
8. Is the flame sensor coated? (Remove and clean with emery cloth.)
If the furnace locks out after 5 attempts for ignition, it will try again every hour if a call for heat remains. If the inducer and circulating air blowers are operating, and items 1 through 8 have been checked, press the red reset button on the vent safety switch. (See Figure 28.) If the furnace operates after depressing the reset button, contact a qualified serviceman to identify and repair the problem.
If the furnace continues to not operate, depress the red reset buttons on the flame rollout switches. (See Figure 28.) If the furnace operates after depressing the reset buttons, contact a qualified servicemen to identify and repair the problem.
Twinning of Two Furnaces
The control board on these furnaces is capable of being twinned to another G6 furnace, pro­vided the circuit boards are both UTEC type. If using UTEC control boards, leave the fuses installed on each board. The thermostat wires and the 1/4 inch quick-connect terminals marked "TWIN" on the furnace controls must be con­nected together for twinning. (See Figure 29.)
Thermostat W G Y R
A/C Unit
R C Y G W
Twin Terminal
R C Y G W
Twin Terminal
Figure 29. Twinning
34
Page 35
INSTALLATION/PERFORMANCE CHECK LIST
LOCATION __________________________ CITY ____________________ STATE _____ INSTALLER _________________________ CITY ____________________ STATE _____ UNIT MODEL #_______________________ UNIT SERIAL # ________________________
Minimum Clearances per Table 3? ________
Electrical Connections tight?_____________ Line Voltage Polarity correct? ____________ Supply Voltage:___________________ Volts Blower Motor HP: _____________________ FUEL TYPE: Natural Gas _______ LP/Propane________ Gas Piping Connections leak-tested?______ Gas Line Pressure: ____________________
(in. water column, with furnace operating) Manifold Pressure: ____________________
(in. water column, with furnace operating) Is there adequate fresh air supply for
combustion and ventilation? _____________ Furnace Input: __________________ (Btuh)
Supply Air Temperature: ____________ (° F) Return Air Temperature: ____________ (° F) Temperature Rise: ________________ (° F) Are Flue Connections tight? _____________ Is there Proper Draft? __________________ Is Vent free from restrictions?____________ Is the Filter(s) secured in place?__________ Is the Filter(s) clean? __________________ Has the Thermostat been calibrated?______ Is the Thermostat level? ________________ Is the Heat Anticipator Setting correct? ____ Has the Owner's Information been reviewed
with the home-owner?__________________ Has the Literature Package been left near the
furnace? ____________________________
35
Page 36
St. Louis, MO
¢707931*¤
707931
7079310 (Replaces 7078950)
Specifications and illustrations subject to change without notice and without incurring obligations.
Printed in U.S.A. (9/99)
Loading...