G6RC Series 90+ Upflow Condensing Furnace
G6RD Series 93+ Upflow Condensing Furnace
G6RL Series 90+ Downflow Condensing Furnace
G6RC 90+, G6RD 93+ UpflowG6RL 90+ Downflow
!
WARNING:
Improper installation, adjustment, alteration, service, or maintenance can
cause injury or property damage. Refer to this manual for assistance. For
additional information consult a qualified installer, service agency, or the
gas supplier.
!
FOR YOUR SAFETY:
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
!
FOR YOUR SAFETY:
WHAT TO DO IF YOU SMELL GAS:
These instructions are primarily intended to
assist qualified individuals experienced in
the proper installation of this appliance.
Some local codes require licensed installation/service personnel for this type of equipment. Read all instructions carefully before
starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR
FUTURE REFERENCE.
• Do not try to light any appliance.
• Do not touch any electrical switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor's phone. Follow the
gas supplier's instructions.
• If you cannot reach your gas supplier,
call the fire department.
NOTES: 1. Airflow rates of 1800 CFM or more require two return air connections. Data is for operation with filter(s).
2. Temperature rises in the table are approximate. Actual temperature rises may vary.
3. Temperature rises and airflows for external static pressures greater than 0.5 are for reference only.
These conditions are not recommended.
** Factory Set Cooling Speed
** Factory Set Heating Speed
- Not Recommended
Page 8
INSTALLATION REQUIREMENTS
(
)
Requirements and Codes
This furnace must be installed in accordance
with these instructions, all applicable local building codes, and the current revision of the National Fuel Gas Code (ANSI-Z223.1, NFPA-54).
The current revision of the National Fuel Gas
Code is available from:
American National Standards Institute, Inc.
1430 Broadway
New York, New York 10018
Canada installations shall comply with CAN/
CGA-B149 installation codes, local plumbing or
waste water codes and other applicable codes.
Additional helpful publications are:
• NFPA-90A - Installation of Air Conditioning
and Ventilating Systems.
• NFPA-90B - Warm Air Heating and Air
Conditioning Systems.
These publications are available from:
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, Massachusetts 02269
!
WARNING:
This furnace is not approved for installation in mobile homes. Installation in a mobile home could cause
fire, property damage, and/or personal
injury.
This furnace is Designed Certified by AGA/CGA Laboratories for the minimum clearances to
combustible material listed in Table 4. See the furnace name plate, located inside the furnace
cabinet, for specific model number and clearance information.
MINIM UM CL EARANCES TO COMBUS TI BLE MATERI AL
Furn aceCabi n etMi n imu m Cl earan ces (In ch es)
* 24 inches is the minimum clearance for servicing.
36 inches is the recommended clearance for service.
Table 4. Minimum Clearances to Combustible Materials
8
Page 9
Location
The furnace must be installed on a level surface,
and as close to the center of the air distribution
system as possible. See Table 3 for overall
dimensions to determine the required clearances in hallways, doorways, stairs, etc. to allow
the furnace to be moved to the installation point.
The furnace must be installed so that all electrical components are protected from water.
Minimum clearances to combustible materials
are listed in Table 4. Access for positioning and
servicing must be considered when locating the
unit. 24 inches is the minimum required clearance for servicing the unit. 30 inches is the
minimum required clearance for positioning the
unit. 36 inches is the recommended clearance
from the front of the unit. Please note that a
panel or door can be located such that the
minimum clearance on the rating plate is satisfied, but that panel or door must be removable
and allow the appropriate clearance for your
installation.
This furnace is certified for use on wood flooring.
The furnace must be installed on a solid surface
and must be level front to back and side to side.
This furnace must not be installed directly on
carpeting, tile, or any combustible material other
than wood flooring.
DOWNFLOW WARNING
(G6RL Models):
The design of the downflow furnace is certified
for natural or propane gas and for installation on
non-combustible flooring. A special combustible floor sub-base is required when installing
on a combustible floor. Failure to install the subbase may result in fire, property damage and
personal injury. The special downflow sub-bases
are factory supplied accessories, part numbers
902677 and 902974. When the furnace is installed on a factory or site-built cased air conditioning coil, the sub-base is not necessary.
However, the plenum attached to the coil casing
must be installed such that its surfaces are at
least 1" from combustible construction.
A gas-fired furnace installed in a residential
garage must be installed so that the bottom of
the furnace is located a minimum of 15" from the
floor. The furnace must be located or protected
to avoid physical damage by vehicles.
HORIZONTAL INSTALLATIONS
The G6RC model furnaces are approved for
horizontal installation. Installation Kit #903568
is required for horizontal applications. Follow
the installation instructions in the kit for proper
conversion. NOTE: The G6RD and G6RL models are NOT approved for horizontal installation.
SUPPLY AIR PLENUM INSTALLATION
A. Installation on a concrete slab - G6RL
1. Construct a hole in the floor per the
dimensions in Figure 3.
2. Place the plenum and the furnace as
shown in Figure 4.
B.Installation on a combustible floor - G6RL
1. Cut and frame the hole in the floor per
the dimensions in Figure 5.
2. Place the sub-base for combustible floors
over the hole with its duct collar extended
downward. Attach the supply air plenum to
the base in a manner which will ensure 1"
clearance to the flooring or other combustible
material. Place furnace on the combustible
base as shown in Figure 6.
3. When the furnace is installed on a factory
or site-built cased air conditioning coil,
the sub-base is not necessary. However,
the plenum attached to the coil casing
must be installed such that its surfaces
are at least 1" from combustible material.
18.75"
19.25"
Hole in
Floor
G6RL 080/100G6RL 040/060
Figure 3. Opening for Concrete Slab
13.25"
19.25"
Hole in
Floor
9
Page 10
Concrete
Furnace
Floor
Sheet
Metal
Plenum
Figure 4. Furnace on a Concrete Slab
18.75"
or 13.25"*
16.75"
or 11.25"*
* Smaller
dimensions for
G6RL 040/060
9.25"
2.0"
28.38"
18.75"
19.63"
Hole in
Floor
G6RL 080/100G6RL 040/060
Figure 5. Opening in Wood Floor
Downflow
Sub-base
Furnace
13.25"
19.63"
Hole in
Floor
Wood
Floor
Sheet
Metal
Plenum
Figure 6. Furnace on a Wood Floor
CIRCULATING AIR SUPPLY
Plenums and air ducts must be installed in
accordance with the Standard for the Installation of Air Conditioning and Ventilating Systems
(NFPA No. 90A) or the Standard for the Installation of Warm Air Heating and Air Conditioning
Systems (NFPA No. 90B).
1.50"
1.58"
1 inch thick fiberglass 3 lb density
19.75"
or 14.25"*
Figure 7. Downflow Sub-Base Dimensions
If outside air is utilized as return air to the furnace
for ventilation or to improve indoor air quality, the
system must be designed so that the return air to
the furnace is not less than 50°F (10°C) during
heating operation. If a combination of indoor and
outdoor air is used, the ducts and damper system
must be designed so that the return air supply to
the furnace is equal to the return air supply under
normal, indoor return air applications.
When a cooling system is installed which uses
the furnace blower to provide airflow over the
indoor coil, the coil must be installed downstream (on the outlet side) or in parallel with the
furnace.
If a cooling system is installed in parallel with the
furnace, a damper must be installed to prevent
chilled air from entering the furnace and condensing on the heat exchanger. If a manually
operated damper is installed, it must be designed so that operation of the furnace is prevented when the damper is in the cooling position and operation of the cooling system is
prevented when the damper is in the heating
position.
19.63"
3"
10
Page 11
!
WARNING:
Products of combustion must not be
allowed to enter the return air ductwork
or the circulating air supply. Failure to
prevent products of combustion from
being circulated into the living space
can create potentially hazardous conditions including carbon monoxide
poisoning that could result in personal injury or death.
All return ductwork must be adequately sealed, all joints must be
taped, and the ductwork must be
secured to the furnace with sheet metal
screws. When return air is provided
through the bottom of the furnace, the
joint between the furnace and the return air plenum must be sealed.
The floor or platform on which the
furnace is mounted must provide
sound physical support of the furnace
with no gaps, cracks, or sagging between the furnace and the floor or
platform.
Return air and circulating air ductwork
must not be connected to any other
heat producing device such as a fireplace insert, stove, etc.
An important consideration in selecting one or
two pipe installation is the quality of the combustion air. Indoor air is sometimes contaminated
with various household chemicals which can
cause severe corrosion in the furnace combustion system. Some common sources of these
chemicals are detergents, bleaches, aerosol
sprays, and cleaning solvents. Unless indoor air
is known to be free of these materials, two pipe
installation is recommended.
Provisions must be made for adequate supply of
air for combustion and ventilation. For United
States installations, the adequacy of air provisions can be determined by consulting the current version of the National Fuel Gas Code
(ANSI Z223.1/NPFA-54). For Canadian installations, requirements are specified in the National
Standard of Canada (CAN/CGA B149.1 & .2).
Consult local codes for special requirements.
NOTE: If the furnace is operated without adequate air for combustion and ventilation, it may
not perform properly. Furnace components may
be strained by high temperature and could fail
prematurely.
!
WARNING:
Furnace installation using methods
other than those described in the following sections must comply with the
National Fuel Gas Code and all applicable local codes to provide sufficient
combustion air for the furnace.
Return Air
The return air ductwork may be connected to
any or all of the following: left side return, right
side return, or bottom return. Tables 1 and 2
show the airflow data for each furnace model.
Where maximum airflow is 1800 CFM or
more two openings must be used.
VENTING AND COMBUSTION AIR
REQUIREMENTS
NORDYNE condensing furnaces may be installed with outdoor combustion air piped directly to the furnace, or without such special
piping. Codes refer to the former as "direct vent"
or "two pipe" installation. Installation with air
taken from around the furnace is sometimes
referred to as "one pipe" installation - i.e. only
the vent (exhaust) pipe is provided.
G6RC/G6RD
Protective Screen
G6RL
Figure 8. Protective Screen for One Pipe
Installations
11
Page 12
80,000
Vent or
Chimney
Each opening must
be at least 100 sq. in.
or 1 sq. in. per 1000
Btuh of total input
rating, whichever is
greater. See minimum
area per table.
12" Max.
Each opening
to outside must
be at least
1 sq. in. per
4000 Btuh of
total input
rating.
10 sq. in.
15 sq. in.
20 sq. in.
25 sq. in.
30 sq. in.
35 sq. in.
40 sq. in.
Round Duct
Diameter
4"
5"
5"
6"
6"
7"
8"
Figure 10. Equipment in a Confined Space
with all Combustion Air drawn from
Outdoors through Exterior Wall
Vent or
Chimney
Ventilation Louvers
(each end of attic)
---------
Furnace
Alternate
Air Inlet
Outlet
Air
Water
Heater
Inlet Air
---------
---------
Ventilation Louvers For
Unheated Crawl Space
NOTE: Air openings shall each
have a free area
of not less than
one square inch
per 4,000 Btuh of
the total input rating of all equipment
in the enclosure.
---------
Figure 11. Equipment in a Confined Space
with all Combustion Air drawn from
Outdoors through Vertical Ducts – from
Ventilated Attic
12
Figure 12. Equipment in a Confined Space
with all Combustion Air drawn from
Outdoors through Ventilated Crawl Space
and Ventilated Attic
Page 13
Vent or
Chimney
Air Duct
must be
at least
1 sq. in.
per 2000
Btuh of
total input
rating.
20 sq. in.
30 sq. in.
40 sq. in.
50 sq. in.
60 sq. in.
70 sq. in.
80 sq. in.
Figure 13. Equipment in a Confined Space
with all Combustion Air Drawn from the
Outside through Horizontal Ducts
Air Requirements For One-Pipe
Installation
When air for combustion is to be taken from
around the furnace, a protective screen must be
installed over the combustion air intake opening. This screen is provided with the furnace
installation instructions and functions to prevent
debris from entering the combustion system. It
should be installed on the combustion air intake
collar or inlet PVC. If furnace location is such
that this opening might be unintentionally obstructed, a 3" PVC elbow should be installed on
the collar, and the screen placed inside the inlet
of the elbow. See Figure 8.
Installation In An Unconfined Space
!
CAUTION:
"Tight" buildings (with weather stripping and caulk to reduce infiltration),
may require special provisions for introduction of outside air to ensure
satisfactory combustion and venting,
even though the furnace is located in
an unconfined space.
An unconfined space is an area including all
rooms not separated by doors with a volume
greater than 50 cubic feet per 1,000 Btuh of the
combined input rates of all appliances which draw
combustion air from that space. For example, a
space including a water heater rated at 45,000
Btuh and a furnace rated at 75,000 Btuh requires
a volume of 6,000 cubic feet [50 x (45 + 75) =
6,000] to be considered unconfined. If the space
has an 8 foot ceiling, the floor area of the space
must be 750 square feet (6,000 / 8 = 750). In
general, a furnace installed in an unconfined
space will not require outside air for combustion.
!
WARNING:
Furnaces installed with combustion
air drawn from a heated space which
includes exhaust fans, fireplaces, or
other devices that may produce a
negative pressure should be considered confined space installations.
Installation In A Confined Space
A confined space is one which does not meet the
unconfined space volume requirements, and
typically involves installation in a small room. All
such installations must have specific provisions
for introduction of combustion and ventilation
air.
Codes require that two openings be provided for this - one with bottom edge within 12"
of the floor and one with top edge within 12" of
the ceiling.
openings must be per the following sections.
Combustion air openings must not be restricted
in any manner.
Furnaces installed in a confined space which
supply circulating air to areas outside of the
space must draw return air from outside the
space and must have return air ducts tightly
sealed to the furnace.
Air From Inside
Air for combustion and ventilation may be taken
from inside the building through an interior wall
if the building is not "tight" and if the total volume
of the furnace space and the space from which
air is drawn meets the volume requirements for
an unconfined space.
openings in the wall must each have free area of
at least one square inch per 1000 Btuh of
appliance input, but not less than 100 square
The size and other criteria for these
In such cases, the two
total
13
Page 14
inches of free area. See Figure 9. For example,
if the combined input rate of all appliances is less
than or equal to 100,000 Btuh,
must have a free area of at least 100 square
inches. If the combined input rate of all appliances is 120,000 Btuh,
a free area of at least 120 square inches.
Air Directly Through An Exterior Wall
If combustion air is provided directly through an
exterior wall, the two openings must
free area of at least one square inch per 4000
total
Btuh of
appliance input. (See Figure 10.)
each
each
opening
opening must have
each
have
NORDYNE condensing furnaces are classified
as "Category IV" appliances, which require special venting materials and installation procedures. Category IV appliances operate with
positive vent pressure and therefore require
vent systems which are thoroughly sealed. They
also produce combustion condensate, which is
slightly acidic and can cause severe corrosion of
ordinary venting materials. Furnace operation
can be adversely affected by restrictive vent and
combustion air piping. Therefore,
bustion air piping lengths must conform completely to the requirements of Table 5.
vent and com-
Outdoor Air Through Vertical Openings or Ducts
If combustion air is provided through vertical
ducts or openings to attics or crawl spaces, the
two openings must each have free area of at
least one square inch per 4000 Btuh of total
appliance input. Ducts must have cross-sectional areas at least as large as the free area of
their respective openings to the furnace space.
Attics or crawl spaces must communicate freely
with the outdoors if they are the source of air for
combustion and ventilation. (See Figures 11
and 12.)
Outdoor Air Through Horizontal
Openings or Ducts
If combustion air is taken from outdoors through
horizontal ducts, the openings must
free area of at least one square inch per 2000
Btuh of total appliance input. Ducts must have
cross-sectional area at least as large as the free
area of their respective openings to the furnace
space. (See Figure 13.)
!
CAUTION:
each
have
Do not supply combustion air from an
attic space that is equipped with power
ventilation or any other device that
may produce a negative pressure.
VENTING REQUIREMENTS
This section specifies installation requirements
for vent and "2-pipe" combustion air piping. For
"one pipe" installations, install vent piping per
this section and provide air for combustion and
ventilation per the previous section. The capacity table provided in this section applies to the
total of vent and combustion air piping for either
type of installation.
The furnace must be vented to the outdoors. It
must not be vented in common with any other
appliance, even if that appliance is of the condensing type. Common venting can result in
severe corrosion of other appliances or their
venting and can allow combustion gases to
escape through such appliances or vents. Do
not vent the furnace to a fireplace chimney or
building chase.
!
WARNING:
FURNACE MUST NOT BE COMMON
VENTED WITH OTHER APPLIANCES.
Vent Pipe Material
Vent and combustion air pipe and fittings must
be one of the following materials and must
conform to the indicated ANSI/ASTM standards:
Cement and primer must conform to ATSM
Standard D2564 for PVC and Standard D2235
for ABS. When joining PVC piping to ABS, use
PVC solvent cement. (See procedure specified
in ASTM Standard D3138.)
Vent Pipe Length and Diameter
In order for the furnace to operate properly, the
combustion air and vent piping must not be excessively restrictive. To ensure this use Table 5, which
indicates the maximum allowable piping length for
a furnace of specified input rate, when installed
14
Page 15
with piping of selected diameter and number of
elbows. This table applies to the length and number of elbows for each pipe. To use the table, the
furnace input rate, the centerline length and the
number of elbows on each pipe must be known.
Choose the diameter for which the tabulated length
is equal to or greater than required.
Proper use of the table is illustrated by the
following example:
Example:
An 80,000 Btuh furnace is to be installed in a
"one-pipe" system with 40 feet of vent piping.
There are four elbows, including those exterior
to the building.
Solution:
Consulting Table 5, in the single pipe length
column for an 80,000 Btuh furnace, the maximum allowable length of 2" is 60 feet with one
elbow. Select 2-1/2 or 3" pipe. For three additional elbows, deduct 2.5 ft. for each elbow, or
7.5 ft. for a maximum installed vent length of
52.5 ft.
NOTE: Always use the same or larger size
piping for combustion air as is used for the
exhaust vent.
Vent Pipe Installation
Pipe Routing and Support
Route piping as directly as possible between the
furnace and the outdoors and remember that
routing affects pipe size requirements per the
preceding section. If a two pipe system is used,
locate the combustion air intake and the vent
exhaust in the same atmospheric pressure zone
- i.e. both must exit the building though the same
portion of exterior wall or roof. Vent piping must
be sloped upwards not less than 1/4" per foot in
the direction from the furnace to the terminal.
This is to ensure that any condensate flows back
to the furnace (where it can be disposed of
through the condensate disposal system).
The quality of outdoor air must also be considered. Be sure that the combustion air intake is
not located near a source of solvent fumes or
other chemicals which can cause corrosion of
the furnace combustion system.
Condensing furnace combustion products have
very little buoyancy, so Table 5 is to be used
without consideration of any vertical rise in the
piping.
with 1 long radius el bows* .with 1 long radi us el bow s on each pi pe.*
PVC,CPVC or ABSOutletOutletInlet/OutletInlet/OutletInlet/Outlet
SCH. 40 Pipe Size2"3"2"2"3"2"3"3"
Models
G6RC,D,L80150404050509090
040
Models
G6RC,D,L60150303035359090
060 & 080
Models
G6RC,D,L30150151525259090
100 & 120
*NOTES
1.Subtract 2.5 ft. for each additional 2" elbow and 3.5 ft. for each additional 3" elbow.
2.Two 45 degree elbows are equivalent to one 90 degree elbow.
3.One short radius elbow is equivalent to two long radius elbows
4.Do not include termination elbows in calculation of vent length
5.This table is applicable for elevations from sea level to 2000 ft. For higher elevations decrease
vent pipe lengths by 8% per 1000 ft. of altitude.
6.Only the above pipe materials are approved for use with G6 Condensing Furnaces.
Table 5. Vent Table
15
Page 16
G6RC & G6RD Upflow Furnaces
Exhaust
Inlet
5/8"
Supports at Minimum of 5 ft. Intervals
Combustion
Offset with
Exhaust Pipe
for Adequate
Dimensional
Clearance
PVC or
ABS Pipe
Straight Neoprene Coupling
with 2 Hose Clamps*
(Optional - Not Shown)
G6RL Downflow Furnaces
See Vent T able 4
Straps or Other Suitable
Coupling
Upward Pitch - 1/4" per Foot
Outlet Exhaust Vent
First Support Placed
as Close to Furnace
Connection as Possible
Exhaust Vent
Seal/Caulk
around Pipe
at Building
90˚ Elbow
12" Min.
7"
Wall
Normal Snow Level
Seal/Caulk
around Pipe
at Building
90˚ Elbow
12" Min.
Normal Snow Level
See Vent T able 4
Straps or Other Suitable
Supports at Minimum of 5 ft. Intervals
Coupling
Upward Pitch - 1/4" per Foot
Outlet Exhaust Vent
First Support Placed
Wall
as Close to Furnace
Connection as Possible
Exhaust Vent
Exhaust
Inlet
5/8"
Combustion Air
Inlet
Offset with Exhaust
Pipe for Adequate
Dimensional
Clearance
PVC or
ABS Pipe
Straight Neoprene
Coupling with
2 Hose Clamps
Figure 14. Horizontal Venting
* These couplings are field-supplied and can be used if the installation requires breakable
connections in the piping. Note that a maximum of two couplings per pipe are allowed.
16
Page 17
G6RC & G6RD Upflow
Furnaces
Support System on
Vertical Rise Below Joints
Support System with
first support as close
to furnace as Possible
5'
Combustion
Air Pipe
Furnace Front
Exhaust
Vent
Straight Neoprene
Couplings with
2 Hose Clamps*
(Optional - Not
Shown)
G6RL Downflow Furnaces
Exhaust
Vent
Combustion
Air Pipe
Cabinet
Support System on
Vertical Rise Below Joints
Support System with
first support as close
to furnace as Possible
Upward Pitch
1/4" per Foot
5'
Straight Neoprene
Rubber Couplings
with 2 Hose Clamps
Cabinet
Furnace Front
Upward Pitch
1/4" per Foot
Figure 15. Vertical Venting
* These couplings are field-supplied and can be used if the installation requires breakable
connections in the piping. Note that a maximum of two couplings per pipe are allowed.
G6RC & G6RD Upflow
Furnaces
Combustion Air Inlet Pipe Collar
Diameter 3" for coupling or reducer
Furnace Top
2" PVC
Exhaust Vent
All Models
G6RL Downflow Furnaces
Combustion Air Inlet
2" PVC on G6RL 040/060 models,
3" PVC on G6RL 080/100 models
Furnace Top
2" PVC
Exhaust Vent
All Models
Figure 16. Furnace Pipe Adaptions
17
Page 18
Piping must be mechanically supported so that
its weight does not bear on the furnace. Supports must be at intervals no greater than five
feet, and at smaller intervals if necessary to
ensure that there are no sagging sections to trap
water. (See Figures 14 and 15.)
Figure 16 illustrates vent and combustion air
pipe sizes exiting the furnace. Transition to the
correct pipe size must be done close to the
furnace so that the full length of pipe is of proper
size.
Straight neoprene couplings are supplied with
the downflow furnaces only. These couplings
are to be installed in the combustion air inlet (if
present) and exhaust vent piping at the furnace
as shown in Figures 13 and 14. For an upflow
furnace installation, if breakable connections
are required in the combustion air inlet (if present)
and exhaust vent piping, then straight neoprene
couplings for 2” or 3” piping with hose clamps
can be used. These couplings can be ordered
through your local furnace distributor.
To install a coupling, slide the rubber coupling
over the end of the pipe that is attached to the
furnace and secure it with one of the hose
clamps. Then slide the other end of the rubber
coupling onto the other pipe from the vent and
secure the coupling with the second hose clamp.
Ensure that the connection is tight and leak free.
NORDYNE condensing furnaces have been
certified for installation with zero clearance be-
tween vent piping and combustible surfaces.
However, it is good practice to allow space for
convenience in installation and service.
Location of Outdoor Terminations
Vent and combustion air intake terminations
must be located to ensure proper furnace operation and to conform to applicable codes. Figure
16 illustrates necessary distances from the vent
termination to windows and building air intakes.
In Canada, the Canadian Fuel Gas Code
takes precedence over these instructions.
Specifically, all minimum distance requirements with respect to termination of the vent
piping listed below (items 1 through 8).
The following list is a summary of vent terminal
location requirements:
1.The termination must be 12 inches above
snow level or grade level whichever is higher.
See Figure 18 for alternate method to
achieve 12" above snow level.
2.The minimum distance for a (1-pipe installation) from any door, (openable) window,
or gravity air inlet is 4 ft. below, 4 ft. horizontally, or 1 ft. above.
3.The minimum distance for a direct vent (2pipe) installation) from any door, (openable)
window, or air gravity inlet is 1 ft. below, 1 ft.
horizontally, or 1 ft. above.
4.For one-pipe installations the recommended
minimum distance from an inside corner
formed by two exterior walls is 6 feet, but is
not required.
18
Direct vent
terminal
50,000 Btuh
or less
9 in.
12 in. min
Mechanical
draft vent
terminal
4 ft. min
4 ft. min
12 in. min
Mechanical
draft vent
terminal
12 in. min
12 in. min
12 in. min
Direct vent
terminal more than
50,000 Btuh
Figure 17. Vent Termination Clearances
Mechanical
draft vent
terminal
Less
than 10 ft.
3 ft. min.
Grade
Forced
Air Inlet
Page 19
5.The vent termination for a 1-pipe installa-
g
tion shall be a minimum of 3 ft. above any
forced air inlet within 10 ft.
6.The vent termination shall be located at
least 4 ft. horizontally from any electric
meter, gas meter, regulator and any relief
equipment. These distances apply ONLY to
U.S. installations. In Canada, the Canadian
Fuel Gas Code takes precedence.
7.Avoid areas where condensate drainage
may cause problems by dropping on planters or patios, etc. Also ensure that exhaust
gases will not impinge on windows or building surfaces, which may be compromised
or damaged by condensation. Do not install
the vent terminal such that exhaust is directed into window wells, stairwells, under
decks or into alcoves or similar recessed
areas, and do not terminate above any
public walkways.
8.Select the point of wall penetration where
the minimum 1/4 inch per foot of slope up
can be maintained.
Vent Configuration to
Provide 12" Minimum
height above
Snow Level.
Outside
Wall
Pipe
Coupling
Figure 18. Alternate Horizontal Vent
Installation
For horizontal venting, one of the following kits
is recommended:
12" Min.
19" Max.
Support
1/2"
Armaflex
Insulation or
Equivalent
2" PVC3" PVC
12" Above
Normally
Expected
Snow
Level
!
CAUTION:
For optimum performance, vent furnace through wall which experiences
the least exposure to winter winds.
Horizontal Venting
Vent and combustion air intake terminations
must be as shown in Figure 19.
!
WARNING:
Ensure that the combustion air vent
and the exhaust vent are configured as
shown in Figure 19. Improper vent
termination can cause recirculation of
the flue gases. This may result in furnace vibration. In severe cases, the
furnace will cycle due to the intermittent contact between the flame and the
flame sensor. If you note oscillations
occurring, check the vent configuration. Make sure that the exhaust vent
does not have a 90 degree termination.
Through-the-Wall
Exterior Vent
Mountin
Neutralizer Kit - All
Models
For Canadian installations please refer to the
Canadian Installation Code (CAN/CGA-B149.1
or 2) and/or local codes.
The kit consists of two face plates and an
insulating gasket to seal the exterior surface. A
hole sized closely to the pipe diameter must first
be cut through the wall. A short length of pipe is
then cut such that it can penetrate the wall and
be held in place by closely fitting standard couplings. The face plates are retained on both
sides of the wall by the couplings, and the gasket
is retained against the wall by the outer face
plate. Face plates must be fastened to the wall
and the outside one must be flashed as appropriate to prevent entry of water.
When the above kits are not used the following
steps are required:
1.Check the hole size cut through the exterior
2.Extend the vent pipe through the wall ap-
Kit
wall. Insure that the hole diameter is less than
the diameter of the couplings to be used.
proximately 1" and seal the area between
the wall and pipe.
90237309023750
90237309023730
19
Page 20
3.Apply couplings to the vent pipe on the
interior and exterior sides of the wall to
insure the pipe can not be pushed or pulled
through the wall.
4.Insure the combustion air inlet pipe (for a 2
pipe installation) has a 90 degree termination elbow as shown in Figures 19 and 20.
b. The top of the chimney is sealed and
weatherproofed.
c. The termination clearances shown in
Figure 20 are maintained.
d. No other gas fired appliances are vented
through the chimney.
Note that a combustion air intake must be
provided with an elbow opening downward.
The screen provided with the furnace must be
installed in the elbow to prevent entry of debris
or creatures.
When the vent pipe must exit an exterior wall
close to the grade or expected snow level, a riser
should be provided as shown in Figure 18.
Insulation is required to prevent freezing of this
section of pipe.
Vertical Venting
Figure 20 shows the proper installation and clearances for vertical vent termination. The roof penetration must be properly flashed and waterproofed with
a plumbing roof boot or equivalent flashing. Termination spacing requirements from the roof and from
each other must be per Figure 20.
Vent and combustion air piping may be installed
in an existing chimney which is not in use
provided that:
a. Both the exhaust vent and air intake run
the length of the chimney.
Vent Freezing Protection
When the vent pipe is exposed to temperatures
below freezing, i.e., when it passes through
unheated spaces, chimneys, etc., the pipe must
be insulated with 1/2 inch thick sponge rubber
insulation, Armaflex-type insulation or equivalent. Insulating pipe is important to avoid condensate icing.
For extremely cold climates or for conditions of
short furnace cycles (i.e. set back thermostat
conditions) the last three feet of vent pipe can be
reduced one nominal pipe size provided that the
total vent length is at least 15 feet in length and
the vent is sized in accordance with the venting
requirements (Table 5) before this reduction is
applied. (Example: 3" to 2-1/2" or 2" to 1-1/2")
Smaller vent pipes are less susceptible to freezing, but must not be excessively restrictive.
Concentric Vent Termination
A concentric vent termination is approved for
use with these furnaces. The kit part number is
903578. For proper installation of the concentric
vent termination, follow the installation instructions provided with that kit.
20
Exhaust Vent
Option B
Mounting Kit
Faceplate Secured
to Wall with Screws
Combustion
Air Inlet
Exhaust Vent
Option C
7" Min.
18" Min.
36" Max.
18" Min.
36" Max.
8" Min.
18" min.
36" max.
12" Min. to
Normal Snow Level
Inlet
Figure 19. Exhaust and Combustion Air Pipe Clearances
Exhaust Vent
Option A
Grade
Level
or Normal
Snow
Exhaust
Page 21
Elbow
Combustion
Air
Intake
A= 12" Above Roof or Snow Accumulation Level
Figure 20. Vertical Vent Termination
Exhaust
Vent
1"
18" Min.
36" Max.
A
A
Exhaust
Plumbing Vent Roof Boot
(Typ. Both Pipes)
DRAINAGE OF CONDENSATE
FROM FURNACE
The condensate drainage system is internal to
the furnace. The drain may exit either the right or
left side of the furnace cabinet. For a right side
drain simply extend the tubing out of the 7/8"
hole in the cabinet, see Figure 21.
For a left side drain follow the steps below:
1.Loosen the clamp on the soft exit tube (see
Figure 21.)
3.Re-tighten the clamp. MAKE SURE CLAMP
IS TIGHT TO AVOID LEAKAGE OF CONDENSATE.
4.Route the tubing out of the 7/8" hole located
8 inches up from the bottom furnace.
The condensate should drain from the plastic
collector box (location A in Figure 21) as droplets
or a small stream. If you notice the furnace has
operated for more than 5 minutes without draining or the red status light on the control board is
pulsing a 2-blink code follow the steps below.
1.Remove the collector box soft tube at location A in Figure 21 and insure the exit from
G6RLG6RC & G6RD
A
Collector Box
Left Side
Drain
8"
"HARD" J
Drain Tube
Rotate counter
clockwise (Step 2)
Clamp
(Loosen For Step 1)
(Retighten for Step 3)
Figure 21. Furnace with Condensate Drain Trap Assembly
Route to
floor drain.
...OR
Route to
condensate
pump. Keep
downward
slope.
Left
Side
Drain
8"
"HARD" J
Drain Tube
Rotate clockwise
(Step 2)
Clamp
(Loosen For Step 1)
(Retighten for Step 3)
Route to
floor drain.
...OR
Route to
condensate
pump. Keep
downward
slope.
21
Page 22
the collector box is clear of any debris or
obstructions.
2.Replace this tube and insure the fit to the
header spout is air tight. Air will be drawn
into the header if this connection is not tight.
3.Check other tube connections along the
drain system. Insure that all are air tight.
NOTE: Industry research studies indicate that
when condensate is routed to an active drain,
household detergents, etc., buffer its acidity. If
the drain is not actively used or if codes require,
obtain a neutralizer kit (usually contains limestone). Proper drains and connections to the
condensate tubing are required as NORDYNE
cannot be held responsible for water leakage
which occurs due to loose hose connections or
improperly sealed drain line pipes.
GAS SUPPLY AND PIPING
This furnace is equipped for either left or right
side gas entry. Typical gas service hook-ups are
shown in Figure 22. When making the gas
connection provide clearance between the gas
supply line and the entry hole in the furnace
casing to avoid unwanted noise and/or damage
to the furnace.
tion must comply with the latest edition of the
National Fuel Gas Code (ANSI Z223.1) or (CAN/
CGA B149) installation codes.
A 1/8" NPT plugged tap must be installed in the
gas line to the unit for use when measuring the
gas supply pressure. The plug should be readily
accessible for service use. A drip leg should be
installed in the vertical pipe run to the unit. Table
5 lists gas flow capacities for standard pipe sizes
as a function of length in typical applications
based on nominal pressure drop in the line.
NOTE:Gas piping must not be run in or
through air ducts, chimneys, gas vents, elevator
shafts, etc.
Compounds used on threaded joints of gas
piping must be resistant to the actions of liquefied petroleum gases.
The main manual gas valve and main power
disconnect to the furnace must be properly
labeled by the installer in case emergency shutdown is required.
!
CAUTION:
All gas piping must be installed in compliance
with local codes and utility regulations. Some
local regulations require the installation of a
manual main shut-off valve and ground joint
union external to the furnace. The shut-off valve
should be readily accessible for service and/or
emergency use. Consult the local utility or gas
supplier for additional requirements regarding
placement of the manual main gas shut-off. In
the absence of local codes the gas line installa-
Burner Viewport
Denotes fieldprovided and
installed
components.
Some Utilities
Require Shut-
Off Valv e to
be 4 to 5 feet
Above Floor
Shut-Off Valv e
with 1/8" NPT
Plugged T ap
Roll-Out Limit
Burner
Assembly
Ground
Joint
Union
Automatic Gas Valve
(with manual shut-off)
Do not use matches, lighters, candles,
or other sources of open flame to
check for gas leaks.
Leak Check
After the gas piping to the furnace is complete,
all connections must be tested for gas leaks. To
check for leaks use only a soap and water
solution or other approved method.
Denotes fieldprovided and
installed
components.
Burner
Assembly
Automatic
Gas Valve
(with manual
shut-off)
Ground Joint
Union
Roll-Out Limit
Some Utilities
Require ShutOff Valve to
be 4 to 5 feet
Above Floor
Shut-Off Valve
with 1/8" NPT
Plugged Tap
Burner Viewport
Figure 22. Typical Gas Service Connection
22
Page 23
CAPACITY OF BLA CK IRON G AS PIP E (CU. FT. PER HOUR)
The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas
flow required by the furnace. To determine the cubic feet per hour of gas flow required by the
furnace, divide the input rate of the furnace by the heating value of the gas:
SPECIFI C GRAVITY - 0.6 0
Cubic Feet Per Hour Required =
Heating Value of Gas (Btu/Cu. Ft.)
Table 6. Capacity of Black Iron Gas Pipe (cu. ft. per hour)
for Natural Gas (specific gravity = .60)
NOTE: When pressure testing gas supply lines
at pressures greater than 1/2 psig (14 in. water
column), the furnace must be disconnected from
the gas supply piping system to prevent damage
to the gas control valve.
If the test pressure is less than or equal to 1/2
psig (14 in. water column), the furnace must be
isolated from the gas supply line by closing the
manual shut-off valve.
!
WARNING:
This furnace was equipped at the factory for use with natural gas only. A
special kit, supplied by the manufacturer, is required to convert the furnace to operate on LP/propane gas.
Failure to use the proper conversion
kit can cause fire, explosion, property
damage, carbon monoxide poisoning,
personal injury, or death.
Conversion
Conversion of this furnace to use LP/propane
gas must be made by qualified service
personnel, using only approved parts.
High Altitude Application
High altitude application with this furnace can be
field performed by a simple adjustment of
manifold pressure, and if necessary changing
the orifices. The changes required depend on
Input To Furnace (Btu/hr)
the installation altitude and the heating value of
the gas. The gas heating value based on sea
level can be obtained from your local gas utility.
The heating value of gas at high altitude is
always lower than the sea level heating value.
The heating values used in Tables 7 & 8 are
based on sea level values.
Natural Gas High Altitude
Conversion
All factory shipped furnaces are ready to operate
between zero and 4999 ft. above sea level. For
higher altitudes (between 5000 and 10,000 ft.
above sea level), conversion can be achieved
simply by adjusting the furnace manifold pressure
as shown in Table 7.
LP/Propane Gas Sea Level and
High Altitude Conversion
Conversion of this furnace to utilize LP/propane
gas must be made by qualified service personnel,
using factory authorized or approved parts.
Conversion to LP/propane gas can be
accomplished by first replacing the natural gas
orifices with the appropriate LP/propane orifices
shown in Table 9 or 10. Note: for installations
between zero and 5000 ft. above sea level, a
#54 or #55 drill size orifice should be used
depending upon the rated firing rate of the unit
(see Table 9 or 10). However for installations
above 5000 ft. above sea level, a # 55 or #56 drill
size orifice should be used. After changing the
orifices, use Table 8 to determine the appropriate
manifold pressure for your installation.
23
Page 24
Conversion to LP/propane, sea level, and high
(
)
(
)
(
)
altitude is detailed in the installation instructions
provided with the conversion kit. Approved
conversion kits are listed below.
United States LP/Propane Gas Sea Level and
High Altitude Conversion Kit - P/N 903616
This kit is for LP/propane conversion in the
United States at altitudes between zero and
10,000 ft. above sea level. Follow the installation
instructions supplied with the kit for proper
installation.
Canadian LP/Propane Gas Sea Level and High
Altitude Conversion Kit - P/N 903617
This kit is for LP/propane conversions in Canada
at altitudes between zero and 4500 ft. above sea
level. Follow the installation instructions supplied
with the kit for proper installation.
!
CAUTION:
To avoid electric shock, personal injury, or death, turn off the power at the
disconnect or the main service panel
before making any electrical connections.
ELECTRICAL WIRING
Electrical connections must be made in accordance with all applicable local codes and ordinances, and with the current revision of the
National Electric Code (ANSI/NFPA 70).
For Canadian installations electrical connections and grounding must be done in accordance with the current Canadian Electrical Code
(CSA C22.1 Part 1) and/or local codes. If any of
the original wire as supplied with the furnace
must be replaced, it must be replaced with wire
having a minimum temperature rating of 105°C.
Refer to the furnace nameplate and Table 11 for
electrical requirements.
Line Voltage Wiring
The line voltage (115 volt) to the furnace must be
supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the
furnace. See Table 11. An electrical switch
should be readily accessible from and within
sight of the furnace. (See the Wiring Diagram
label in the furnace and Figure 23.)
The furnace cabinet must have an uninterrupted,
unbroken ground to minimize injury should an
electrical fault condition occur. The controls
For a Natural Gas Sea Level Heating Val ue o f 800 to 899 Btu/cu.ft.
Elev at ion
zero to
1999
Ma ni fold Pressure S etti n g ( in WC)
For a Natural Gas Sea Level Heating Val ue o f 900 to 999 Btu/cu.ft.
Ma ni fold Pressure S etti n g ( in WC)
For a Natural Gas Sea Level Heating Valu e of 1,000 to 1,100 Btu/cu.ft.
Ma ni fold Pressure S etti n g ( in WC)
3.53.53. 5
zero to
1999
3.53.53. 5
zero to
1999
3.53.5
2000 to
4999
Elev at ion
2000 to
4999
Elev at ion
2000 to
4999
fe et above sea l evel
5000 to
5999
fe et above sea l evel
5000 to
5999
fe et above sea l evel
5000 to
5999
3.02.82.5
6000 to
7999
3.53.0
6000 to
7999
3.22.8
6000 to
7999
Table 7. Manifold Pressure (in WC) for Natural Gas at Various Altitudes
Elev at ion (fee t a b o ve sea leve l)
0 to2,000 to5, 000 to6,000 to8,000 to
1,9994, 9995,9997,99910,000
Manifold Pressure in (WC)
fo r an LP Gas Heat ing
Valu e of 2,500 Btu/hr.
10.08.510.09.08. 5
8000 to
10000
8000 to
10000
8000 to
10000
Table 8. Manifold Pressure (in WC) for LP/Propane Gas at Various Altitudes
24
Page 25
Furn ace Rati ng
g
Plate I n pu t (Btu/ h)
Orifice Drill Size
NatLP
Furn ace Rati n
Plate I n pu t (Btu/ h)
Orifice Drill Size
NatLP
450004454
600004555
720004354
960004354
1200004354
1440004354
Table 9. Natural and LP Gas Orifice Sizes
for Elevations between zero and
4999 ft. Above Sea Level
used in this furnace require an earth ground to
operate properly. Acceptable methods for
grounding are electrical wire or conduit approved for electrical ground service. Do not use
gas piping as an electrical ground.
NOTE: Proper line voltage polarity must be
maintained in order for the control system to
operate correctly. Verify that the incoming
neutral line is connected to the white wire
and the incoming "hot" line is connected to
the black wire in the furnace junction box.
These furnaces will not operate unless polarity and ground are properly connected.
See Figure 23.
!
CAUTION:
Label all wires prior to disconnection
when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Low Voltage Wiring
Install the thermostat per the manufacturer's
instructions. The low voltage (24 volt) connections from the thermostat are made at the
terminal strip on the control board in the fur-
Field Supplied
Fused Service
Panel
Black (Hot)
White (Neutral)
Green or Bare
(Ground)
Ground
Field Supplied
Panel Connector
Black
White
Ground
Black
White
450004455
600004556
720004355
960004355
1200004355
1440004355
Table 10. Natural and LP gas Orifice Sizes
for Elevations between 5000 and 10,000 ft.
Above Sea Level
nace. See Figure 24 for the proper connections
for heating only (two-wire) and heating/cooling
(four-wire) applications. The recommended
minimum wire gauge for thermostat wiring is
shown in Table 11.
The thermostat must not be installed on an
outside wall or any other location where its operation may be adversely affected. Adverse affects
include radiant loading from fireplaces, sunlight,
or lighting fixtures, and convective loading from
warm air registers or electrical appliances.
To check the heat anticipator setting either:
1.Add the current draw of the system components; or
2.Measure the current flow on the thermostat
R-W circuit after the circulating blower motor has started.
Set the heat anticipator according to the thermostat manufacturer's instructions for heat anticipator settings.
START-UP AND ADJUSTMENTS
Prior to start-up, verify that:
1.The line voltage power leads are securely
connected, that the polarity of the connections is correct, and that the furnace is
properly grounded.
* Time-delay fuses or HACR-type circuit breakers are required.
Thermostat Recommended Thermostat
Wire Wire Length
Gauge2-wire 4 or 5-wire
(heating)(cooling)
2455 ft.25 ft.
2290 ft.45 ft.
20140 ft.70 f t .
18225 ft.110 ft.
Table 11. Electrical Data
A/C Condensing Unit
Condensing Unit
Control Box
R Y G W
Connect
R & W
For
Heating
Only
Room
Thermostat
NOTE: The "Y"
terminal on the
UTEC control board
must be connected
to the thermostat.
FIELD WIRING
Low Voltage
Connections
R C Y G W
COM
3 Amp
24 V
3
6
9
2
5
8
1
4
7
EAC
HUM
Neutrals
Unused Motor Leads
HUM
63
52
41
Blower Off
Fuse
Flame Signal Light
Status Light
COOL
M1M2M3
Timing
(Yellow)
(Red)
HEAT
EAC
6090120
TWIN
XFMR
L1
Figure 24. Low Voltage Field,
Four-wire Heating/Cooling Applications
2.The thermostat wires (R, W, Y, and G) are
securely connected to the correct leads on
the terminal strip of the circuit board.
3.The gas line service pressure does not
exceed 10.0 in. water column (0.36 psig),
and is not less than 4.5 in. water column
(0.16 psig) for natural gas. For LP gas the
line service pressure must not exceed 14 in.
water column (0.51 psig), and must not be
less than 11.0 in. W.C. (0.40 psig).
4.The roll-out and vent safety manual reset
switches are closed. If necessary, press the
red button to reset a switch. See Figure 28
26
for location. DO NOT install a jumper wire
across a switch to defeat its function. If a
switch reopens on start-up, DO NOT reset
the switch without identifying and correcting the fault condition which caused the
180
switch to trip.
5.The blower door is in place, closing the door
switch in the line voltage circuit.
6.The gas line has been purged and all connections are leak tight.
Start-Up Procedure
1.Set the thermostat to the lowest setting.
2.Close the disconnect(s) to provide line voltage to the furnace.
3.Follow the procedures given on the operating instructions label attached to the furnace.
4.Set the thermostat above room temperature and verify the sequence of operation.
(See the SEQUENCE OF OPERATION.)
5.After the furnace has run for approximately
five minutes, set the thermostat below room
temperature and verify steps (9) through
(11) of the SEQUENCE OF OPERATION.
Verifying and Adjusting
Firing Rate
The firing rate must be verified for each installation to prevent over-firing the furnace.
NOTE: The firing rate must not exceed the rate
shown on the furnace rating plate. At altitudes
above 2000 ft. the firing rate must be adjusted as
described in the high altitude section.
Page 27
Use the following procedure to determine the
firing rate:
1.Shut off all other gas fired appliances.
2.Start the furnace and allow it to run for at
least three minutes.
3.Measure the time (in seconds) required for
the gas meter to complete one revolution.
4.Convert the time per revolution to cubic feet
of gas per hour using Table 12.
5.Multiply the gas flow rate in cubic feet per
hour by the heating value of the gas in Btu
per cubic foot to obtain the firing rate in
Btuh. Example:
•Time for 1 revolution of a gas meter with
a 1 cubic foot dial = 40 seconds.
•From Table 9 read 90 cubic feet per hour
of gas.
•Heating value of the gas (obtained from
gas supplier) = 1040 Btu per cubic foot.
•Firing rate = 1040 x 90 = 93,600 Btuh.
6.Adjustments to the firing rate can be
made by adjusting the gas manifold
pressure. See the High Altitude
Application section for additional
information of firing rate at elevations
above 2000 ft.
The manifold pressure must be set to the appropriate value for your installation. Refer to either
Table 7 for natural gas or Table 8 for LP/propane
gas to verify the manifold pressure setting required for your particular installation. To adjust
the manifold pressure, remove the regulator cap
and turn the adjusting screw clockwise to increase pressure or counterclockwise to reduce
pressure. Replace the regulator cap after adjustments are complete.
!
CAUTION:
Do not re-drill the burner orifices. If
the orifice size must be changed, use
only new orifices.
Verifying and Adjusting
Temperature Rise
Verify that the temperature rise through the
furnace is within the range specified on the
furnace rating plate. Temperature rises outside
the specified range could result in premature
heat exchanger failure.
Place thermometers in the return and supply air
stream as close to the furnace as possible. The
thermometer on the supply air side must be
shielded from direct radiation from the heat
exchanger to avoid false readings. Adjust all
registers and duct dampers to the desired position and run the furnace for fifteen minutes
before taking any temperature readings. The
temperature rise is the difference between the
supply and return air temperatures.
For typical duct systems, the temperature rise
will fall within the range specified on the rating
plate with the blower speed at the factory recommended setting. If the temperature rise measured is outside the range specified, it may be
necessary to change the blower speed. Lower
blower speeds will increase the temperature rise
and higher blower speeds will decrease the
temperature rise.
The furnace is equipped with a multispeed motor. Heating and cooling speed selection is made
by moving the leads on the integrated control
board located in the furnace. The wiring diagram
on the furnace and Figures 25, 26 and 27 show
the speed taps for adjusting motor speed.
If it is desired that the blower operate at the
same speed for heating and cooling, tape off the
terminal of the unused blower wire. Install the
jumper wire, found in the plastic instruction bag,
across the HEAT and COOL taps on the control
board. Reconnect the desired blower tap to the
piggyback quick connect.
The blower control is designed to start the
circulating air blower 30 seconds after the gas
valve is opened. The blower control is factory
wired to turn the blower motor off 120 seconds
after the gas valve is closed. This timing can be
changed using the BLOWER OFF timing switch
opposite the terminal block on the control board.
(See Figure 25.)
Verifying Burner Operation
To verify operation of the burners, make sure
that the blower compartment door is in place and
that there is power to the furnace. Set the
thermostat above room temperature and observe the ignition sequence. The flame can be
observed through the small clear window on the
burner box. The burner flame should carry over
between all burners. The flames should be blue,
without yellow tips. Flames should extend from
each burner without lifting, curling, or floating.
After verifying ignition, set the thermostat below
room temperature and verify that the burner
flame extinguishes completely.
Verifying Operation of the Supply
Air Limit Switch
To verify operation of the supply air limit
switch, make sure that the blower door is in
place and that there is power to the furnace.
Completely block the return airflow to the furnace by installing a close-off plate in place of or
upstream of the filter(s). Set the thermostat
above room temperature and verify that the
Sequence of Operation is as described in these
instructions. The supply air limit switch should
function to turn off the gas valve within approximately five minutes. The circulating air and
combustion blowers should continue to run
when the supply air limit switch opens. Remove
the close-off plate immediately after the supply
air limit switch opens. If the furnace operates
for more than five minutes with no return air, set
the thermostat below room temperature, shut
off the power to the furnace, and replace the
supply air limit switch.
Flame Sensor – The flame sensor acts to prove
that flame has carried over from the ignitor to the
opposite end burner. If no flame is sensed, the
furnace will be shut down automatically.
Gas Valve – The gas valve controls the flow of
gas to the burners. When the gas valve is
energized it automatically opens and regulates
the gas pressure in the manifold.
Pressure Switch – The pressure switch verifies
that the inducer is drawing the combustion gases
through the heat exchanger. It also senses a
blocked condensate drain condition.
Vent Pressure Switch (G6RD Only) – The vent
pressure switch reacts to blockage in the vent or
combustion air piping. It is utilized in G6RD
furnaces only.
Supply Air Limit Switch – The supply air limit
switch prevents the air temperature leaving the
furnace from exceeding the maximum outlet air
temperature.
DESCRIPTION OF COMPONENTS
Figure 28 shows the location of each of the
functional components described below. If
any component of the furnace must be replaced, use only factory authorized replacement parts. See the Replacement Parts List
for each component.
Common
Leads
Connect
Neutral
Lead of
Electronic
Air Cleaner
and/or Humidifier
Here.
R C Y G W
EAC
HUM
Humidifier Tap
(.5A@ 120 VAC)
COM
24 V
3
6
9
2
5
8
1
4
7
Neutrals
63
HUM
52
41
Vent Safety Switch – The vent safety switch
shuts the furnace down if the outlet flue gas
temperature increases above 160°F. This switch
protects the plastic flue system and the inducer
from over-temperature conditions.
Flame Roll-Out Switch – This switch provides
flame roll-out protection to the furnace and
combustion air inlet pipe.
90
60
120
3 Amp Fuse
Unused Motor
Leads
M1M2M3
Cooling
Speed Tap
Blower Off
Timing
Flame Signal
Light (Yellow)
Status
Light (Red)
COOL
HEAT
EAC
Heating Speed Tap
180
TWIN
XFMR
L1
Electronic Air Tap
(.5A@ 120 VAC)
Figure 25. Blower Speed Tap Location
29
Page 30
For G6RC, G6RD and G6RL Residential Furnaces
BLOWER
DECK SWITCH
(SELECT MODELS
ONLY)
BLUE
WHITE (NEUTRAL)
ROOM THERMOSTAT
AIR CONDITIONER
CONDENSING UNIT
FLAME SENSOR
SUPPLY AIR
LIMIT SWITCH
(ALL MODELS)
BLACK 120V
GROUND
R
Y
G
W
C
Y
GAS
VALVE
BLUE
RED
FLAME ROLL-OUT
(ALL MODELS)
YELLOW
BROWN
SWITCH
BLUE
BLUE
BLUE
ORANGE
ORANGE
VENT
SAFETY
SWITCH
(ALL MODELS)
WHITE
GREEN
WHITE W/ BLK STRIPES
BLK W/ WHITE STRIPES
BLACK
TRANSFORMER
24 V
90
60
PRESSURE
SWITCH
BLOWER DOOR
SWITCH
WHITE
120 V
BLACK
180
120
BLACK
VENT
PRESSURE SWITCH
(93+ MODELS ONLY)
3 OR 4 SPEED MOTOR
C
ML
L
H
MH
IGNITOR
Legend
Field Wiring
Factory Wiring:
Low Voltage
High Voltage
FAULT CONDITION
Power On
Limit Circuit Open
Pressure Switch Stuck Open
Pressure Switch Stuck Closed
Ignition Failure (Check Ground)
If any of the original wire as supplied with
the furnace must be replaced, it must be
replaced with wiring material having a
temperature rating of at least 105 C.
RED
ORANGE
BLUE
BLACK
Figure 26. G6RC, G6RD and G6RL Integrated Control Board System Diagram
30
Page 31
MAINTENANCE
It is recommended that the furnace be checked
yearly. At a minimum, this check should include
the following items.
!
WARNING:
To avoid electric shock, personal injury, or death, disconnect the electric
power before performing any maintenance.
!
WARNING:
Holes in the vent pipe or heat exchanger can cause products of combustion to enter the home. Replace
the vent pipe or heat exchanger if
leaks are found. Failure to prevent
products of combustion from being
circulated into the living space can
create potentially hazardous conditions including carbon monoxide poisoning that could result in personal
injury or death.
Combustion Air and Vent System
Check the combustion air and vent pipe to
ensure that it is not damaged, corroded or
blocked by debris. Any damaged section of vent
pipe must be replaced, and any obstruction or
blockage must be removed prior to operating the
furnace.
Air Filter(s)
The installer should provide a filter rack for a
high velocity type filter in the return air duct
adjacent to the furnace. Filters should be changed
or cleaned monthly during the heating season.
New or newly renovated homes may require
more frequent changing until the construction
dust has been removed.
Lubrication
The bearings in the circulating air blower motors
are pre-lubricated and sealed at the factory. No
further oiling of the bearings is required for the
life of the motor.
Condensate Drain Assembly
Be sure the condensate lines are free and open
(i.e. avoid kinking hoses). Also make sure all
hose clamps are tight to avoid drawing air into
the system.
Blower Compartment
The blower compartment should be cleaned
monthly during the heating and cooling seasons
to remove any dirt and lint that may have accumulated in the compartment or on the blower
and motor. Dirt and lint can create excessive
loads on the motor resulting in higher than
normal operating temperatures and shortened
service life.
Heat Exchanger and Burner Maintenance
The furnace should operate for many years
without excessive soot buildup in the flue passageways, however, the flue passageways, the
vent system, and the burners should be inspected and cleaned (if required) by a qualified
serviceman annually to ensure continued safe
operation. Particular attention must be given to
identify deterioration from corrosion or other
sources.
!
WARNING:
Never operate the furnace without a
filter in place. Dust and lint in the
return air can build up on internal
components, resulting in loss of efficiency, equipment damage, and possible fire.
AIR FILTER(S) ARE NOT SUPPLIED WITH THE
FURNACE AS SHIPPED FROM THE FACTORY.
FILTERS FOR SIDE RETURN AND BOTTOM
RETURN APPLICATIONS ARE AVAILABLE
FROM NORDYNE DISTRIBUTORS.
SYSTEM OPERATION
INFORMATION
Proper maintenance is most important to achieve
the best performance from a furnace. Follow
these instructions for years of safe, trouble free
operation.
• Do not place combustible materials on or
against the furnace cabinet or the vent
pipe.
• Do not store gasoline or any other flammable vapors and liquids in the vicinity of
the furnace.
(G6RD Only, Not Shown)
7 Control Board
8 Blower Door
Switch
9 Vent Safety Switch
10 Low Voltage
Transformer
11 Supply Air Limit
Switch
12 Circulating Air
Blower Assembly-
13 Induced Draft
Blower
14 Condensate Drain Tube
15 In-Line Drain
Assembly
16 Burner View Port
17 Front Header Box
18 Combustion Air
Intake
19 Exhaust Vent
G6RL Downflow Furnace
1 Ignitor (Not Shown)
2 Flame Sensor (Not
Shown)
3 Gas Valve
4 Flame Roll-out
Switch(s)
5 Pressure Switch
7 Control Board
8 Blower Door
Switch
9 Vent Safety Switch
10 Low Voltage
Transformer
11 Supply Air Limit
Switch
12 Circulating Air
Blower Assembly-
13 Induced Draft
Blower
14 Condensate Drain
Tube
15 In-Line Drain
Assembly
16 Burner View Port
17 Front Header Box
18 Combustion Air
Intake
19 Exhaust Vent
10
7
8
5
13
9
14
11
3
1
4
19
18
12
15
17
2
16
Figure 28. Location of Major Components
32
Page 33
• Change or replace the air filters monthly
during any period when the circulating
blower is operating regularly.
• Always replace the doors on the furnace
after servicing. Do not operate the furnace
without all doors and covers in place.
• Avoid operating the furnace when windows and doors are open.
• Be sure that the thermostat is properly
installed and is not being affected by drafts
or heat from lamps or other appliances.
Sequence of Operation
Operating sequences for the heating, cooling,
and fan modes are described below. Refer to the
wiring diagrams (Figures 26 and 27) and the low
voltage field wiring diagram (Figure 24).
Heating Mode:
1.On a call for heat the thermostat closes,
applying 24 VAC to the W terminal on the
control board.
2.The control board checks for continuity on
the 24 VAC limit control circuit (over-temperature limit switch, flame rollout switches
and blocked vent switch in series). If an
open limit is detected the control board will
energize the inducer and the conditioned
air blower. All other system functions will be
inoperable until the limit circuit closes. While
the limit is open, the red LED will pulse at
a rate of 1 blink per unit time.
3.The furnace control checks for continuity
across the pressure switch (24 VAC). If the
pressure switch is closed the heat mode
sequence will not continue. If it remains
closed for 10 seconds the red LED will blink
3 times repetitively until the fault condition
clears.
4.The inducer is energized.
5.The pressure switch will close. If the pressure switch does not close after 10 seconds
the fault LED will blink 2 times repetitively
and the inducer will continue to run until the
switch is closed.
6.The inducer will pre-purge for 30 seconds
and then the ignitor will start its warm-up.
After 30 seconds of ignitor warm-up the gas
valve (24 VAC) will open. The ignitor circuit
stays energized for 6 seconds after the gas
valve opens.
7.The furnace control must prove flame via
the flame sensor six seconds after the gas
valve opens. If flame is sensed, all burners
are on and the ignitor cools off. If no flame
is sensed, the gas valve closes immediately
and the inducer continues to run. A second
trial for ignition (step 6) begins if no flame is
sensed. On the fifth try for ignition, the
furnace control is locked out and the red
LED will blink 4 times repetitively. The thermostat must be opened for at least ten
seconds to reset the furnace control after a
lock out. Otherwise, the furnace will attempt
another ignition sequence in 1 hour.
8.The furnace control energizes the circulating air blower on the heating speed 30
seconds after the gas valve circuit is energized .
9.When the thermostat has been satisfied,
gas valve is de-energized.
10. The inducer is de-energized after a 30
second postpurge.
11. The furnace control keeps the circulating air
blower energized for 120 seconds (factory
set) or 60, 90, or 180 seconds (field adjustable). (See Figure 25.)
12. Abnormal conditions: If a limit opens during
operation, the inducer and circulating air
blower continue to operate. The gas valve is
de-energized immediately. The blowers
continue to operate until the limit closes.
When the limit closes the inducer blower is
de-energized immediately. The circulating
air blower continues to operate for the specified delay (factory set at 120 seconds).
Cooling Mode:
1.On a call for cooling the thermostat closes,
applying 24 VAC to the G and Y terminals
on the furnace control. This closes the
compressor contactor.
2.The furnace control energizes the circulating blower (115 VAC) on the cooling speed.
3.When the thermostat is satisfied, the G
and Y terminals on the control board are
de-energized opening the compressor contactor.
4.The circulating air blower is de-energized
after a 90 second delay.
33
Page 34
Fan Mode:
1.On a call for fan operation, the thermostat
applies 24 VAC to the G terminal on the
furnace control board.
2.The circulating air blower is energized immediately on the heating speed.
3.If the furnace is operated in the continuous
ON position at the thermostat and is then
switched to AUTO, the circulating blower
will operate for a specified delay (factory set
at 120 seconds).
Furnace Fails to Operate
If the furnace does not operate check the following:
1.Is the thermostat operating properly?
2.Are the blower compartment door(s) in
place?
3.Is the furnace disconnect closed?
4.Has the circuit breaker tripped or the control
board fuse burned open?
5.Is the gas turned on?
6.Are any manual reset switches open?
7.Is the filter dirty or plugged?
8.Is the flame sensor coated? (Remove and
clean with emery cloth.)
If the furnace locks out after 5 attempts for
ignition, it will try again every hour if a call for
heat remains. If the inducer and circulating air
blowers are operating, and items 1 through 8
have been checked, press the red reset button
on the vent safety switch. (See Figure 28.) If the
furnace operates after depressing the reset
button, contact a qualified serviceman to identify
and repair the problem.
If the furnace continues to not operate, depress
the red reset buttons on the flame rollout switches.
(See Figure 28.) If the furnace operates after
depressing the reset buttons, contact a qualified
servicemen to identify and repair the problem.
Twinning of Two Furnaces
The control board on these furnaces is capable
of being twinned to another G6 furnace, provided the circuit boards are both UTEC type. If
using UTEC control boards, leave the fuses
installed on each board. The thermostat wires
and the 1/4 inch quick-connect terminals marked
"TWIN" on the furnace controls must be connected together for twinning. (See Figure 29.)
Thermostat
W G Y R
A/C
Unit
R
C
Y
G
W
Twin
Terminal
R
C
Y
G
W
Twin
Terminal
Figure 29. Twinning
34
Page 35
INSTALLATION/PERFORMANCE CHECK LIST
LOCATION __________________________ CITY ____________________ STATE _____
INSTALLER _________________________ CITY ____________________ STATE _____
UNIT MODEL #_______________________ UNIT SERIAL # ________________________
Minimum Clearances per Table 3? ________
Electrical Connections tight?_____________
Line Voltage Polarity correct? ____________
Supply Voltage:___________________ Volts
Blower Motor HP: _____________________
FUEL TYPE:
Natural Gas _______ LP/Propane________
Gas Piping Connections leak-tested?______
Gas Line Pressure: ____________________
(in. water column, with furnace operating)
Manifold Pressure: ____________________
(in. water column, with furnace operating)
Is there adequate fresh air supply for
combustion and ventilation? _____________
Furnace Input: __________________ (Btuh)
Supply Air Temperature: ____________ (° F)
Return Air Temperature: ____________ (° F)
Temperature Rise: ________________ (° F)
Are Flue Connections tight? _____________
Is there Proper Draft? __________________
Is Vent free from restrictions?____________
Is the Filter(s) secured in place?__________
Is the Filter(s) clean? __________________
Has the Thermostat been calibrated?______
Is the Thermostat level? ________________
Is the Heat Anticipator Setting correct? ____
Has the Owner's Information been reviewed
with the home-owner?__________________
Has the Literature Package been left near the
furnace? ____________________________
35
Page 36
St. Louis, MO
¢707931*¤
707931
7079310 (Replaces 7078950)
Specifications and illustrations subject to change
without notice and without incurring obligations.
Printed in U.S.A. (9/99)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.