Nordyne E3EB-017H, E3EB-010H, E3EB-020H, E3EB-023H, E3EX-010 Owner's Manual & Installation Instructions

...
Downfl ow, Upfl ow Electric Furnaces
Owners Manual & Installation Instructions
E3 Series (Air Conditioner / Heat Pump Air Handler)
User, please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
TABLE OF CONTENTS
USER INFORMATION
IMPORTANT SAFETY INFORMATION .......................3
OPERATING INSTRUCTIONS .....................................3
Cooling Operation ................................................... 3
Heating Operation ...................................................3
Operating the Blower Continuously .........................3
Turning the Heater OFF ..........................................4
INSTALLER INFORMATION
IMPORTANT SAFETY INFORMATION .......................5
REQUIREMENTS & CODES .......................................5
Minimum Installation Clearance .............................. 5
Clearances to Combustible Materials .....................5
CIRCULATING AIR REQUIREMENTS ........................ 6
Plenums & Air Ducts ...............................................6
Return Air Connections ........................................6
Supply Air Connections........................................6
Acoustical Ducts ..................................................6
Unconditioned Spaces.............................................7
Closed-Off Spaces ..................................................7
Filtering Methods - Downfl ow Furnaces .................. 7
Non-Ducted Return Air ........................................7
Without AC or HP Uncased Coil ......................7
With AC or HP Uncased Coil ...........................7
With Optional Coil Housing ..............................7
Ducted Return Air ................................................7
Without Optional Coil Housing .........................7
With Optional Coil Housing ..............................7
Filtering Methods - Upfl ow Furnaces .......................7
Non-Ducted Return Air ........................................7
Without Optional Upfl ow Stand ........................7
With Optional Upfl ow Stand .............................7
Ducted Return Air ................................................7
FURNACE INSTALLATION .........................................8
General nformation .................................................8
Before You Install this Furnace ................................8
Locating the Unit .....................................................8
Optional Equipment .................................................8
Return Air Grille ...................................................8
Automatic Furnace Damper ................................. 8
Duct Connectors for Downfl ow Systems .............. 8
Locating & Cutting Floor Openings .........................9
UNIT MAINTENANCE ..................................................4
Furnace Filter ..........................................................4
Coil Filter .................................................................4
Blower Compartment ..............................................4
TROUBLESHOOTING .................................................4
Standard Duct Connector Installation ...................10
Narrow Duct Connector Installation ......................10
Round Duct Connector Installation .......................11
Alcove Installations ...............................................11
Closet Installations ................................................11
Downfl ow Furnaces ...............................................11
Upfl ow Furnaces ...................................................12
Over the Floor Return Air (Non-Ducted) ............12
Through the Floor Return Air (Ducted) ..............13
ELECTRICAL WIRING ...............................................13
Line Voltage Wiring ................................................13
Connecting Supply Service Wires .........................14
Grounding ..............................................................14
Thermostat / Low Voltage Connections .................14
Selecting Blower Speed ........................................14
Changing Blower Speed ........................................15
Blower Installation .................................................15
Installing Control Circuit Wiring .............................15
START-UP & ADJUSTMENTS ...................................16
Pre-Start Checklist ................................................16
Start-Up Procedures ..............................................16
FIGURES & TABLES .................................................17
Figure 20. Furnace Components ..........................17
Figure 21. Furnace Physical Dimensions ..............18
Figure 22. Upfl ow Stand Dimensions ....................18
Table 6. Unit Specifi cations ...................................19
Table 7. Electrical Specifi cations ...........................20
Figure 23. E3EB-010H Wiring Diagram .................21
Figure 24. E3EB-012H Wiring Diagram .................22
Figure 25. E3EB-015H & 017H W.D. .....................23
Figure 26. E3EB-020H, 023H, & 5 Ton W.D. .........24
INSTALLATION PERFORMANCE CHECKLIST .......28
2
USER INFORMATION
IMPORTANT SAFETY INFORMATION
Safety markings are used to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or proper ty damage.
WARNING:
Improper service, adjustment or maintenance of unit may cause fi re, electrical shock, or hazardous conditions which may result in personal injury, property damage, or death. Installation or servicing should only be performed by qualified trained personnel thoroughly familiar with this type equipment
WARNING:
Do not use this furnace if any part has been under water. A fl ood damaged furnace is extremely dangerous. Attempts to use the furnace can result in fi re or explosion. A qualifi ed service agency should be contacted to inspect the furnace and to replace any electrical or control system parts that have been wet or under water.
OPERATING INSTRUCTIONS
NOTE: Thermostat styles vary. Some models may not
include the AUTO mode and others will have the AUTO in place of the HEAT and COOL. Others may include all three. Please refer to the thermostat manufacturer’s User manual for detailed programming instructions.
WARNING:
Do not store or place fl ammable or vaporous materials (paint thinners, etc.) in the vicinity of this appliance. Failure to comply may cause fi re, explosion, or other hazardous conditions which may result in serious injury, death or property damage.
The following list of chemicals should not be used or stored near the furnace:
• Chlorinated cleaners
• Water softening chemicals
• De-icing salts or chemicals
• Household Cleaning Solutions
• Printing inks, paint removers, varnishes, etc.
• Cements and glues
• Antistatic fabric softeners
NOTE: Allow at least one hour for the room temperature to stabilize before you make a second adjustment to the thermostat setting. After the desired comfort level is established, make only small adjustments to the thermostat setting to meet changing temperature conditions.
Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired temperature level. The outdoor fan, compressor, and blower motor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired temperature level. The compressor, outdoor fan, and blower motor will cycle on and off to maintain the indoor temperature at the desired heating level.
Operating the Indoor Blower Continuously
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fi replace operation.
Fan
Mode
Figure 1. Digital Thermostat
System
Mode
Temperature
Selector
Set the thermostat fan mode to ON (Figure 1). The indoor blower starts immediately, and will run continually until the fan mode is reset to AUTO.
The continuous indoor blower operation can be obtained with the thermostat system mode set in any position, including OFF.
3
USER INFORMATION
Turning the Heater OFF
Change the thermostat’s system mode to OFF and the fan mode to AUTO (See Figure 1). NOTE: The system will not operate, regardless of the temperature selector setting.
CAUTION:
For optional A/C or H/P systems, always wait at least fi ve minutes after the system shuts off before restarting the system.
UNIT MAINTENANCE
WARNING:
Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.
CAUTION:
There are No user serviceable parts inside the control panel. DO NOT OPEN.
NOTE: All servicing of this heating appliance other than
the normal maintenance described in this section must be done by authorized trained service personnel. Do not attempt any servicing which requires opening of the control panels.
Proper maintenance is most important to achieve the
best performance from the appliance and should be performed frequently at the beginning of each heating season.
• Keep the area surounding the unit clean. Keep the unit clear of obstructions.
renovated homes may require more frequent changing until the construction dust has minimized. Filter sizes shown in Table 6 (page 19) are available at most local retailers.
necessary with fi lter of same dimensional size
Filters designed to remove smaller particles such as pollen, may require additional maintenance.
Coil Filters
If a cooling coil is installed on your unit, the furnace fi lter is not used. Remove coil fi lters, wash, and allow to dry. Re-install coil fi lters to their original positions.
Blower Compartment
Dirt and lint can create excessive loads on the motor resulting in higher than normal operating temperatures and shortened service life. Vacuum or wipe clean the interior of furnace cabinet. Clean all lint and dust from around the furnace. It is recommended that the blower compartment be cleaned of dirt or lint that may have accumulated in the compartment or on the blower and motor as part of regular maintenance.
Inspect fi lters frequently and replace when
TROUBLESHOOTING
If the unit fails to operate, check the following:
• Check the thermostat setting. Make sure the system mode and temperature settings are correct.
• Check the electrical panel for tripped circuit breakers.
• Check the fi lters for dust accumulation.
• Check the unit and make sure it is clean and not covered with grass or leaves.
• If the items above don’t resolve your problems, then call your nearest service technician. Please specify the complete model and serial numbers shown on the furnace data label for all warranty service and when ordering replacement parts or optional equipment. Refer to the replacement parts list provided with the furnace for part numbers.
Furnace Filter
WARNING:
Never operate the furnace without a fi lter in place. Accumulating dust in the return air can build up on internal components, resulting in loss of effi ciency, equipment damage, and possible fi re.
E3 Furnaces are supplied with a single air fi lter when
shipped from the factory. It is recommended that the fi lter be cleaned or replaced monthly. Newly built or recently
4
INSTALLER INFORMATION
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
REQUIREMENTS & CODES
WARNING:
This unit must be installed in accordance with instructions outlined in this manual during the installation, service, and operation of this unit. Unqualifi ed individuals should not attempt to interpret these instructions or install this equipment. Failure to follow safety recommendations could result in possible damage to the equipment, serious personal injury or death.
• The installer must comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (NEC) for special installation requirements.
• All electrical wiring must be completed in accordance with local, state and national codes and regulations and with the National Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code (CSA Z240.6.1, & Z240.9.1).
• Design and construction of the home duct system, must be in accordance with: HUD Manufactured Home Construction & Safety Standard (Title 24, Part 3280) and American National Standards (ANSI) A119.11, C1-NFPA 7
• Follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
• This air handler may not be used for temporary heating of buildings or structures under construction.
Minimum Installation Clearances
• Access for positioning and servicing the unit must be considered when locating unit. The need to provide clearance for access to panels or doors may require clearance distances over and above the requirements.
For alcove installations allow 18 (46cm) inches minimum clearance from the front of the unit for future servicing. Closet installations require 36 inches minimum.
• This appliance must be installed in accordance with clearances listed in Table 1. The furnace must be installed with ample clearance for easy access to the air fi lter, blower assembly, burner assembly, controls, and vent connections.
• Locate and install this unit in position as specifi ed on page 8. This unit is designed only for Indoor installations and should be located with consideration of minimizing the length of the supply and return ducts. See Table 4 (page 15) or the rating plate for circulating airfl ow data.
• Suffi cient clearance for unobstructed airfl ow through a louvered door must be maintained in order to achieve rated performance. Air return to the furnace must have the minimum required total free area:
200 in
2
(1290 cm2 ) for furnace only. May also include return air grille and frame assembly P/N 902989 or wall mount grille P/N 902999).
235 in
2
(1516 cm2 ) with 4 ton A.C. or H.P. installed.
250 in2. (1613 cm2 ) with 4 ton A.C. or H.P. installed &
1” special clearance.
390 in2 (2516 cm2 ) with up to 5 ton A.C. or H.P. installed.
Clearances to Combustible Materials
This furnace is Design Certifi ed in the U.S. and Canada by CSA International for the minimum clearances to combustible materials. NOTE: The furnace is listed for installation on combustible or non-combustible fl ooring. To obtain specifi c clearance information, refer to the furnace rating plate, located inside of the furnace cabinet.
• 0” from all surfaces of furnace cabinet, ducts, optional coil housing and plenum connector. No separate subbase required for installations on combustible fl ooring.
ALL MODELS CLOSET ALCOVE
Front ** 6" 18" Back 0" 0" Sides* 0" 0" To p 0 " 0 " Top & Sides of Duct 0" 0" Bottom of Duct 0" 0"
** Service Clearance
* For upfl ow application using upfl ow stand, 1” minimum per side.
Table 1. Minimum Clearance Requirements
5
CIRCULATING AIR REQUIREMENTS
WARNING:
All return ducts must be secured to the furnace with sheet metal screws. All return ducts must be adequately sealed. When return air is provided through the bottom of the unit, the joint between the furnace and the return air plenum must be air tight.
Return air and circulating air ducts must not be connected to any other heat producing device such as a fi replace insert, stove, etc. This may result in fi re, explosion, carbon monoxide poisoning, personal injury, or property damage.
Plenums & Air Ducts
This unit is designed only for use with a supply and return duct. Air ducts should be installed in accordance with the standards of the National Fire Protection Association Standard for Installation of Air Conditioning Systems (NFPA 90A), Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems (NFPA 90B), and all applicable local codes. NFPA publications are available by writing to: National Fire Protection Association, Batterymarch Park, Quincy, ME 02269 or visit www.NFPA.org on the web.
• Plenums and air ducts must be installed in accordance with the Standard for the Installation of Air Conditioning and Ventilating Systems (NFPA No. 90A) or the Standard for the Installation of Warm Air Heating and Air Conditioning Systems (NFPA No. 90B).
• Design the air ducts according to methods described by the Air Conditioning Contractors of America (ACCA).
• Air ducts must be aluminum, tin plate, galvanized sheet steel, or other approved materials for outlet or return air ducts.
• Snap-Lock or Pittsburgh-Lock seams are preferred. All other types of seams must be made tight to prevent leakage.
• It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant. Requirements for sealing ducts vary from region to region. Consult with local codes for requirements specifi c to your area.
• Gas piping must not run in or through any of the air duct system.
• Applicable installation codes may limit the furnace to installation in a single-story residence only. Furnace installations other than closet or alcove require ducted return air systems.
Return Air Connections
Air return to the furnace must have a minimum free area opening (see Table 1). A return air grille for closet or alcove installations is available. Acceptable closet installations with return air entering through an opening in the fl oor or ceiling of a closet, must meet all of the following requirements:
• The return air opening, regardless of its location in the closet, must not be smaller than size specifi ed on unit data label. If located in the fl oor, the opening must be provided with a means of preventing its inadvertent closure by fl at object(s) placed over the opening.
• A return air grille must be used when furnace is installed in a closet or alcove:
Alcove installations: use return air grille & frame assembly
P/N 902989 or equivalent. See Figure 2, page.
Closet installations: use wall mount return air grilled
P/N 902999 or equivalent. NOTE: For 5 ton A.C. or H.P. system, 155 in
Downfl ow alcove installations: the grille (with frame
provided) may be attached to the top of the furnace and all paneling and trim fl ushed to it. This installation provides an access door for future installation of NORDYNE air conditioning or heat pump coils on top of the furnace.
• Materials located in return air duct system must have a fl ame-spread classifi cation of 200 or less.
• Noncombustible pans having 1” upturned fl anges must be located beneath openings in a fl oor-return duct system.
• Wiring materials located in return duct system must conform to NEC Article 300-22(c).
• If return air opening is located below top of furnace, a minimum clearance must be provided between opening and furnace. See Table 1 (page 5).
Supply Air Connections
• Supply duct system must be designed for proper air distribution. Static pressure measured externally to furnace shall not exceed static pressure rating listed on furnace nameplate.
• Duct system must be designed so that no supply registers are located in duct system directly below the furnace.
Acoustical Ducts
Certain installations may require the use of acoustical lining inside the supply duct work.
• Acoustical insulation must be in accordance with the current revision of the Sheet Metal and Air Conditioning Contractors National Association (SMACNA) application standard for duct liners.
• Duct lining must be UL classifi ed batts or blankets with a fi re hazard classifi cation of FHC-25/50 or less.
• Fiber duct work may be used in place of internal duct liners if the fi ber duct work is in accordance with the current revision of the SMACNA construction standard on fi brous glass ducts. Fibrous duct work and internal acoustical lining must be NFPA Class 1 air ducts when tested per UL Standard 181 for Class 1 ducts.
2
(1,000 cm2 ) must be added.
6
Unconditioned Spaces
Frame
Top of
Furnace
Fasteners (4)
Grille
Furnace Filter
(not used with
A/C or H/P)
All duct work passing through unconditioned space must be properly insulated to minimize duct losses and prevent condensation. Use insulation with an outer vapor barrier. Refer to local codes for insulation material requirements
Closed-Off Spaces
Living space not served by, and closed off from the return air ducts to the furnace (by doors, sliding partitions, and other means) must be provided with permanent, uncloseable openings in the doors or partitions to allow air to return to the furnace from all parts of the home. Return air grilles, with a minimum open area of one square inch for every fi ve square feet of living space closed off from the furnace, must be provided in the door or room partition.
Figure 2. Grille Support Frame & Grille Assembly
Filtering Methods - Downfl ow Furnaces
Non-Ducted Return Air
For unducted return air systems, either the optional grille and frame assembly or the optional wall mount grille is recommended.
Without A/C or H/P uncased coil:
• Use the fi lter supplied with the furnace; ensure that the fi lter is installed mat side down between the fi lter retainer and furnace top. See Figure 2.
With A/C or H/P uncased coil:
• Use the optional coil fi lters; the fi lter supplied with the furnace is not used; REMOVE AND DISCARD THIS FILTER.
With optional coil housing:
• See coil cabinet instructions for specifi c fi ltering methods.
Ducted Return Air
For ducted return air systems with air conditioners or heat pumps, either providing an access panel in the duct or using the optional coil cabinet (Figure 3) is recommended. The duct system must be properly sized to account for any additional external static pressure produced from the chosen fi ltering method.
Without optional coil housing:
• Install a fi lter with a minimum unrestricted medium area of 324 in
2
in the duct above the coil that is accessible
for monthly cleaning or replacement by homeowner.
With optional coil housing:
• Install a fi lter with a minimum unrestricted medium area of 324 in
2
in the duct above the coil that is accessible
for monthly cleaning or replacement by homeowner.
Filtering Methods - Upfl ow Furnaces
Non-Ducted Return Air
Furnaces may be installed with unducted or ducted return air. For unducted systems with air conditioners or heat pumps, the following optional equipment is recommended: upfl ow stand, coil cabinet, upfl ow duct connector, and wall mount grille.
20" (508 mm)
Cabinet
Insulation
29" (737 mm)
23 3/4" (603 mm)
Figure 3. Upfl ow Coil Cabinet
Without optional upfl ow stand:
• Install a fi lter with a minimum unrestricted medium area of 324 in
2
below the coil cabinet/furnace assembly that is accessible for monthly cleaning or replacement by the homeowner
With optional upfl ow stand:
• Stand (Figure 4, page 8) must use two fi lters: one is supplied with the stand and the other MUST be removed from the furnace and placed in the stand. See instructions supplied with the upfl ow stand for additional details.
Ducted Return Air
For ducted systems with air conditioners or heat pumps, the following optional equipment is recommended: coil cabinet and upfl ow duct connector.
• Install a fi lter with a minimum unrestricted medium area of 324 in2 below the coil cabinet/furnace assembly that is accessible for monthly cleaning or replacement by the homeowner
7
24 3/4” (628 mm)
20” (508 mm)
20” (508 mm)
Upflow Stand
Figure 4. Optional Upfl ow Stand
FURNACE INSTALLATION
NOTE: Since all installations are different, the sequence of
these steps may differ from the actual installation. These installation procedures are suggested for typical furnace installations. Only qualifi ed HVAC technicians should
install this furnace.
General Information
The E3 Electric furnace is designed only for indoor installations and can be readily connected to the high static duct system of a home. Units are approved for single/ multistory residential or mobile/modular/manufactured structures in upfl ow, downfl ow, (freestanding/closet/ alcove) confi gurations.
This appliance will provide many years of safe and dependable comfort, providing it is properly installed and maintained. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards. Please read all instructions before installing the unit.
Approved installation, operation, and maintenance of this appliance must be in accordance with the listed specifi cations contained in these instructions and other documents supplied with the furnace and/or optional air conditioning equipment. Unless it is noted differently in this manual, only use factory authorized kits and accessories when modifying this appliance. Refer to local authorities having jurisdiction for further information.
local building codes. If there is any question concerning the power supply, contact the local power company.
Verify the air delivery of the furnace is adequate to
handle the static pressure drop of the coil, fi lter, and duct work.
Locating the Unit
• Survey the job site to determine the best location for installing the unit. Consideration should be given to availability of electric power, service access, and noise.
• The dimensions of the room or alcove must be able to accommodate the overall size of the unit and the installation clearances in Table 1 (page 5). Physical dimensions for this furnace are shown in Figure 21 (page 18). If an upfl ow stand will be used, see Figure 22 for component dimensions.
• The unit must be leveled at installation and attached to a properly installed duct system.
• The surface that the furnace is mounted on must provide sound physical support of the unit.
Optional Equipment
NOTE: Refer to the instructions supplied with any additional
accessories for further installation details.
Return Air Grille
A return air grille and frame assembly (Figure 2, page
7) is available for use in unducted return air installations.
In downfl ow alcove installations, the grille and frame assembly may be mounted directly to the top of the furnace. In closet installations, a wall mount grille is available for attachment to a door or wall.
Optional Automatic Furnace Damper (901083)
Furnace may be equipped with the optional automatic damper when a packaged air conditioner is installed and connected to the warm air duct system. This damper (not required) prevents cooled air from discharging through the furnace cabinet, causing excessive cooling of the immediate area. Refer to the instructions supplied with the damper for details.
Duct Connectors for Downfl ow Systems
Duct connectors are recommended for heated air distribution in under-the-fl oor duct systems. With this system, furnaces may be installed on combustible fl ooring without a separate sub-base. The furnace rear mounting plate (Figure 8, page 10) supplied with the duct connectors is recommended for use with this type of installation.
Before You Install this Furnace
This equipment is securely packaged at the time of
shipment and upon arrival should be carefully inspected for damage prior to installing the equipment at the job site. Claims for damage (apparent or concealed) should be fi led immediately with the carrier.
Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired and provided with circuit protection in accordance with
8
REAR WALL OF CLOSET OR ALCOVE
1 3/4" MIN.
REAR WALL OF CLOSET OR ALCOVE
2 3/8" MIN.
23 3/4"
OPTIONAL
REFRIGERANT LINE
3 1/8” X 5 3/4”
23 3/4"
FLOOR CUT-OUT
17 1/2” X 14”
18 5/8"
FOR UPFLOW
FURNACES WITH
STD. DUCT
CONNECTORS
C
L
3”
10"
20"
STANDARD DUCT CONNECTOR
REAR WALL OF CLOSET OR ALCOVE
1 3/4"
MIN.
FLOOR CUT-OUT
14 1/4” DIAMETER
FOR UPFLOW
18 5/8"
FURNACES WITH
ROUND DUCT
CONNECTORS
C
L
FURNACE OUTLINE
3/4"
FURNACE
DOOR
FURNACE OUTLINE
3/4"
23 3/4"
OPTIONAL
REFRIGERANT LINE
4 1/4” X 3 3/4”
23 3/4"
FLOOR CUT-OUT
14 1/2” X 14 1/2”
17"
FOR DOWNFLOW
FURNACES WITH
STD. DUCT
CONNECTORS
C
L
5”
10"
20"
3 3/8”
STANDARD DUCT CONNECTOR
REAR WALL OF CLOSET OR ALCOVE
2 3/8"
MIN.
FLOOR CUT-OUT
17"
14 1/4” DIAMETER
FOR DOWNFLOW
FURNACES WITH
ROUND DUCT
CONNECTORS
C
L
16 5/8"
FURNACE OUTLINE
OPTIONAL SUPPLY
WIRE ENTRANCE
3” X 6 1/4”
3/4"
FURNACE
DOOR
16 5/8"
FURNACE OUTLINE
OPTIONAL SUPPLY
WIRE ENTRANCE
3” X 6 1/4”
3/4"
OPTIONAL
REFRIGERANT LINE
3 1/8” X 5 3/4”
10"
3”
FURNACE
20"
DOOR
ROUND DUCT CONNECTOR
Figure 5. Cut-Out Dimensions for Upfl ow
Furnaces
Locating & Cutting Floor Openings
Floor cut-outs must be carefully located to avoid misalignment of the furnace and air duct. Standard and round cutouts for upfl ow furnaces are shown in Figure
5. Figure 6 displays the cutouts for downfl ow furnaces.
1. Measure and mark the centerline of the cutout. Provide minimum clearances at rear and right side walls of closet or alcove for installation of furnace and wiring.
2. Using the centerline as a starting point, draw the rest of the duct cut-out to the dimensions shown in Figures 5 or 6. NOTE: Additional provisions may be necessary for optional air conditioning or heat pump if refrigerant lines are installed elsewhere than at the front of the furnace. The refrigerant and entrance supply opening dimensions may be adjusted ± 1/2”.
3. Cut out the fl oor opening 1/16” larger than the actual cutout drawn. This will allow some clearance when installing the duct connector.
OPTIONAL
REFRIGERANT LINE
4 1/4” X 3 3/4”
5”
10"
20"
3 3/8”
FURNACE
DOOR
ROUND DUCT CONNECTOR
Figure 6. Cut-Out Dimensions for Downfl ow
Furnaces
4. Measure from the top of the fl oor down to the top of the supply air duct to obtain the depth of the fl oor cavity. NOTE: The depth of the fl oor cavity shown as “X” in Figure 7 will determine the correct duct connector.
5. Determine which duct connector to use from Table 2 (page 10).
FLOOR OPENING
“X”
SUPPLY AIR DUCT
FLOOR CAVITY
Figure 7. Floor Cavity
9
Loading...
+ 19 hidden pages