Nordyne E3EH017H, E3EH010H, E3EH012H, E3EH015H, E3EH020H Owner's Manual & Installation Instructions

...
Page 1
Downflow, Upflow Electric Furnaces
Owners Manual/Installation Instructions
E3 Series
(Air Conditioner/Heat Pump Air Handler)
IMPORTANT: Read this owner information to become familiar with the capabilities and use of your heating appliance. Keep this literature where you will have easy access to it in the future. If a problem occurs, check the instructions and follow recommenda­tions given. If these suggestions don’t eliminate your problem, call the appropriate NORDYNE distributor. A distributor service list is included with this appliance.
!
WARNING:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Improper installation, adjustment, alteration, service or maintenance can cause injury, property damage, or death. Refer to this manual. For assistance or additional information consult a qualified dealer or service agency. To avoid personal injury or property damage, ask a service technician to inspect the furnace and to replace any part of the control system which has been under water.
SECTION 1. OWNER INFORMATION
OPERATING INSTRUCTIONS Before Operating System
Before operating your heating/cooling system (see Figure 1), make sure that:
• Control panel covers are closed.
• Blower and/or relay control plugs are plugged in.
• Fan switch is set to “AUTO” (E3EH units only).
!
CAUTION:
No user serviceable parts inside control panel. DO NOT OPEN.
• Circuit breakers are in “ON” position.
• All power supply switches for furnace and outside unit (if installed) are turned on.
• Furnace door is closed and properly latched.
Refer to the owner’s manual supplied with the optional heat pump or air conditioner for further information.
Page 2
2
Page 3
Temperature Selector
10 20 30
50 60 70 80 90
SYSTEM
HEAT OFF COOL
VENTILATE
ON AUTO
Temperature Scales
Fan Switch (optional sub-base)
System Switch (optional sub-base)
Coil Air Filters
(used with indoor coil)
Furnace Air Filter
(NOT used with
coil air filters)
Blower Selector Switch (EH only)
Blower
Indoor Coil (optional)
Figure 1. Furnace Parts Identification
Product Type
E - Electric Furnace
Generation
3 - Third Series
Product Identifier
EH - Heat Only
EB - A/C Blower Equipped Relay
EX - Multi-Speed, X13 Motor
Used with Platinum Series
A/C or H/P Relay Box
(optional)
Circuit Breakers
Data Label
Control Panel
Cover (left)
Control Panel Cover (right)
E 3 EB - 010 H
Electrical Code
H - 240-1-60
Primary Capacity
010 - 10 kw 012 - 12 kw 015 - 15 kw 017 - 17 kw 020 - 20 kw 023 - 23 kw
Model Identification
3
Page 4
!
CAUTION:
For optional A/C or H/P systems, always wait at least five minutes after the system shuts off before restarting the system. Observe this procedure when operating the system per the following instructions.
To Operate System in Cooling Mode
NOTE: The “FAN ON/FAN AUTO” (fan switch)
and “HEAT/OFF/COOL” (system switch) are located either on your thermostat (if it’s supplied with a sub-base) or on the relay box added to your furnace.
1. Make sure blower selector switch is on “Auto.”
2. Set fan switch to “AUTO.”
3. Set system switch to “COOL.”
4. Set thermostat temperature selector to desired comfort level.
To Operate System in Heating Mode
1. Make sure blower selector switch is on “Auto.”
2. Set fan switch to “AUTO.”
3. Set system switch to “HEAT.”
4. Set thermostat temperature selector switch to desired comfort level.
NOTE: Allow at least one hour for the room temperature to stabilize before you make a second adjustment to the thermostat setting. Once the desired comfort level is established, make only small adjustments to the thermostat setting to meet changing temperature condi­tions.
for several hours with all air registers open.
2. With system on, check temperature in all rooms.
3. Partially close registers in rooms that are too warm (in heating mode) or too cool (in cooling mode) and in rooms that are infre­quently occupied.
4. Re-check room temperature and adjust registers as needed.
To Shut Off System
1. Make sure blower selector switch is on “Auto”.
2. Set thermostat temperature selector to low­est temperature setting, OR...
3. For thermostats with optional sub-base (see Figure 1), or for systems with relay box, set system switch to “OFF.”
!
WARNING:
To prevent hazard of electrical shock and injury from moving parts, be certain the thermostat is off and the furnace circuit breaker(s) are in the “OFF” position before servicing. Close and properly latch the outer door after doing the following recommended maintenance.
MAINTENANCE INSTRUCTIONS
Regularly NOTE: If a cooling coil is installed, furnace filter
is not used.
1. Replace furnace air filter (see Figure 1), OR...
2. Remove coil filters, wash, and allow to dry. Re-install coil filters to original positions.
3. Vacuum or wipe clean interior of furnace cabinet.
4. Clean all lint and dust from around furnace.
To Operate Blower Continuously
1. Set blower selector switch to “ON” for sum­mer air circulation only (see Figure 1), OR...
2. If thermostat is equipped with optional heat­ing/cooling sub-base or relay box (see Figure 1), set fan switch to “ON.”
To Balance Air Distribution
1. On a typical day, set thermostat selector to desired comfort level and operate system
4
Every Six Months
1. Vacuum or wipe away any dust or lint on blower motor.
Before Each Heating Season NOTE: If a cooling coil is installed, furnace filter
is not used.
1. Replace furnace air filter (see Figure 1), OR...
2. Remove coil filters, wash, and allow to dry. Re-install coil filters to original positions.
Page 5
3. Have a qualified serviceman inspect all furnace components and field wiring and clean and service heating system as needed. If this furnace was installed with aluminum power supply wiring, have ser­viceman periodically check all connections to prevent possible equipment failure and/ or fire hazard. Do not attempt any service function yourself which requires opening furnace control panel covers.
Environmental Testing Laboratories (ETL) and certified by ARI and the Canadian Standards Association (CSA), or Warnock Hersey or ETLC. These cooling systems include energy­saving components to provide maximum cool­ing performance at electrical energy usage levels established by federal standards. Refer to the operation instruction label on your fur­nace for the optional air conditioning equipment approved for your heating appliance.
BEFORE YOU CALL A SERVICEMAN
1. Make sure thermostat temperature selec­tor is set above room temperature for heat­ing or below room temperature for cooling. If thermostat is equipped with heating/cool­ing sub-base, make sure system switch (see Figure 1) is set to “HEAT” for furnace operation or set to “COOL” for optional air­conditioning operation.
2. Check main household service panel to see if appropriate circuit disconnect(s) for appliance power supply is on.
3. Refer to instructions under Before Operat­ing System for pre-operation checks.
4. Refer to instructions under Before Each Heating Season for maintenance proce­dures and recommended service checks.
5. Refer to owner’s manual provided with optional air conditioner or heat pump (if installed) for service and maintenance.
NOTE: All servicing of this heating appliance other than the normal maintenance described in this section must be done by authorized trained service personnel. Do not open the control panels (see Figure 1) at any time.
Please specify the complete model and serial numbers shown on the furnace data label (see Figure 1) for all warranty service and when ordering replacement parts or optional equip­ment. Refer to the replacement parts list pro­vided with the furnace for part numbers.
OPTIONAL AIR CONDITIONER AND HEAT PUMP
Your E3 Series electric furnace is approved for use with an optional central air conditioner or a heat pump. To adapt this heating appliance to a “total comfort system,” contact your nearest NORDYNE distributor.
Optional air conditioners and heat pumps are listed by Underwriters’ Laboratories (UL) or
SECTION 2. INSTALLER INFORMATION
GENERAL
These instructions and specifications are pri­marily intended to assist qualified individuals experienced in the proper installation of home heating and air conditioning appliances. Some local codes require licensed personnel for the installation and service of this type of equip­ment. Approved installation, operation, and maintenance of this central heating system appliance must be in accordance with the listed specifications contained in these instructions and other documents supplied with the furnace and/or optional air conditioning equipment. Refer to local authorities having jurisdiction for further information.
Before beginning installation, read these in­structions thoroughly. Follow all warnings and cautions in the instructions and on the unit.
Improper installation, service adjustment, or maintenance can cause explosion, fire, electri­cal shock or other conditions which may result in personal injury or property damage. Unless otherwise noted in these instructions, use only factory-authorized kits and accessories when modifying this product.
Overview of E3 Furnace
E3E(-) Series electric furnaces are available in two models. E3EH models are equipped with the standard two-speed blower. E3EH models can be easily converted for use with NORDYNE split-system air conditioners and heat pumps. E3EB models are air-conditioning ready; that is, they are equipped with a multi-speed (four­speed) blower, blower relay, and cabinet insu­lation kit. See Table 3 for cooling and heat pump availability with factory installed blower.
5
Page 6
For typical non-ducted return air downflow applications, an air-conditioner or heat-pump coil can be installed by mounting the coil directly on top of the furnace without adding sheet metal cavities or cutting and trimming wood panels.
number (see furnace data label) for future reference.
3. Carefully read all instructions supplied with optional equipment to be installed with furnace.
A return air grille for closet or alcove installations is available. For downflow alcove installations, the grille (with frame provided) may be attached to the top of the furnace and all paneling and trim flushed to it. This installation provides an ac­cess door for future installation of NORDYNE air conditioning or heat pump coils on top of the furnace.
Power entrance for all models may be through the right side or through the bottom of the unit (when viewing the unit in a downflow position).
UNIT CHECKOUT
Before installing this furnace:
1. Inspect unit for possible shipping damage. If shipping damage is found, file claim with transportation company.
2. Record furnace model number and serial
May vary by model, check the unit data label for
Listing agency(s)
Approved Installation Configurations
applicable agency listing mark. Approved for: single/multistory residential or mobile/modular/manufactured structures. Upflow, downflow, (freestanding/closet/alcove)
CODES, SPECIFICATIONS, AND REQUIREMENTS
Furnace Codes
Installation and wiring of this furnace, as well as the design and construction of the home duct system, must be in accordance with one or more of the following codes:
• HUD MANUFACTURED HOME CON­STRUCTION AND SAFETY STANDARD (Title 24, Part 3280)
• American National Standards (ANSI) A119.11, C1-NFPA 7 (National Electrical Code)
• CANADIAN STANDARDS (C.S.A.) Z240.6.1, and Z240.9.1.
All local codes having jurisdiction shall also apply.
Accessibility for Servicing Minimum of 18" (46 cm) required in front of unit. Minimum Clearance to Combustibles
0" from all surfaces of furnace cabinet, ducts, optional coil housing and plenum connector. No separate subbase required for installations on
combustible flooring. Minimum return air 200 in. opening required (total free area) 235 in
250 in
2
(1290 cm2) heating only*
2
(1516 cm2) A/C or H/P up to 4-ton installed.*
2
(1613) cm2 A/C or H/P up to 4 ton w/1"
clearance installed.
2
390 in.
(2516 cm2) A/C or H/P up to 5 ton installed. *or return air grille and frame assembly p/n 902989 or wall mount grille p/n 902999. Use return air grille and frame assembly P/N 902989-
Return air grille
or equivalent for alcove installation. Use wall mount return air grilled P/N 902999- or
(closet or alcove installation)
equivalent for closet installation. 155 in.
2
(1000 cm2) must be added for 5-ton A/C or H/P system.
Table 1. Miscellaneous Listings & Installation Requirements
6
Page 7
Air Duct Codes and Specifications
Air ducts must be installed in accordance with National Fire Protection Association standards NFPA 90A and NFPA 90B, these instructions, and all applicable local codes.
• Materials: Air ducts must be aluminum, tin plate, galvanized sheet steel, or other ap­proved materials for outlet or return air ducts.
• Construction: Snap-Lock or Pittsburgh-Lock seams are preferred. All other types of seams must be made tight to prevent leak­age.
Sizing: Supply duct system must be designed for proper air distribution. Static pressure measured externally to furnace shall not ex­ceed static pressure rating listed on furnace nameplate.
• Location of Openings: Duct system must be designed so that no supply registers are located in duct system directly below furnace.
• Wiring materials located in return duct sys­tem must conform to NEC Article 300-22(c).
• Gas piping must not run in or through return air duct system.
• If return air opening is located below top of furnace, a minimum clearance must be pro­vided between opening and furnace (see “Accessibility for servicing” in Table 1).
Closed-Off Space Requirements
Living space not served by, and closed off from, the return air ducts to the furnace by doors, sliding partitions, and other means must be provided with permanent, uncloseable open­ings in the doors or partitions to allow air to return to the furnace from all parts of the home. Return air grilles, with a minimum open area of one square inch for every five square feet of living space closed off from the furnace, must be provided in the door or room partition.
Return Air Codes and Requirements
Non-ducted return air systems may be used for closet or alcove installations.
NOTE: Applicable installation codes may limit the furnace to installation in a single-story resi­dence only. Furnace installations other than closet or alcove installations require ducted return air systems.
Air return to the furnace must have a minimum free area opening (see Table 1).
Acceptable floor or ceiling return air systems for closet installations with return air entering through an opening in the closet floor or ceiling must meet all of the following requirements:
• Return air opening into closet, regardless of its location, must not be smaller than size specified on unit data label.
• If located in floor of closet, return air opening must be provided with means of preventing its inadvertent closure by a flat object placed over opening.
• Materials located in return air duct system must have a flame-spread classification of 200 or less.
• Noncombustible pans having 1" upturned flanges must be located beneath openings in a floor-return duct system.
OPTIONAL EQUIPMENT
Contact your nearest NORDYNE distributor for a complete list of electric furnace accessories.
Return Air Grille
A return air grille and frame assembly (see Figure 2) is available for use in non-ducted return air installations. In downflow alcove in­stallations, the grille and frame assembly may be mounted directly to the top of the furnace. In closet installations, a wall mount grille is avail­able for attachment to a door or wall.
Optional Automatic Furnace Damper #901083 -
Furnace may (not required) be equipped with the optional automatic damper when a pack­aged air conditioner is installed and connected to the warm air duct system. This damper pre­vents cooled air from discharging through the furnace cabinet, causing excessive cooling of the immediate area. Refer to instructions sup­plied with the damper for details.
Multi-Speed Blower Conversion Package (4 or 5 ton):
Upgrade blower packages are available for adding air conditioning or heat pump systems. See furnace “Options and Compatibility” label for systems available.
7
Page 8
)
4
23 3/4"
(603 mm)
Cabinet
Insulation
8
Item
Number
7
(See Fig. Description
14-Speed Blower
27" (686 mm)
4 Ton - See Notes: 1 & 5 5 Ton - See Note: 1
2 A.C./H.P. Relay Control
See Note: 1
3 Cabinet Insulation Kit
1
2
29" (737 mm)
3
4 "A"-Coil Conversion Kit
5 Coil Cabinet
See Notes: 1 & 5
See Note: 2
See Note: 3
6Upflow Stand
See Note: 4
20"
(508 mm)
20" (508 mm)
29" (737 mm)
Notes:
1) For A/C and H/P use.
2) Includes coil filters.
3) For upflow or downflow installations.
4) For upflow A/C or H/P installations (includes
5) Standard in EB models.
7 A/C and H/P Indoor Coils 8 Return Air Grille and
Frame Assembly
one filter; use filter from furnace to complete filtering system in this accessory).
23 3/4" (603 mm)
Upflow Coil Cabinet
20" (508 mm)
14" (357 mm
23 3/4" (603 mm)
Filters (one obtained from furnace)
Upflow Stand
NOTE: See Table 2 for descriptions
and notes
Figure 2. Optional Accessories
Table 2. Optional Air Conditioning and
Heat Pump Equipment
11/16"
20-1/8"
(511 mm)
3"
(76 mm)
(17 mm)
Figure 3. Optional Rear Mounting Plate
(P/N 389080)
8
Page 9
Electric Furnace Models
Rated Heating Output, Btuh
Watts (T otal kw, Heating
Test ESP, in. w.c. Max
Optional Cooling Av ailable with
factory installed blower
Optional Heat Pump Available
with factory installed blower
(see note 1)
Elements and Blower)
Supply Voltage
Heating Elements,
No.(Total kw)
Blower Wheel Size 10.5" Dia., 8" Wide
Motor Speed,
H.P. Rating, Amps
Air Filter ( Standard) 16" x 20" x 1" (nominal)
Furnace Dimensions Width-20" (508mm), Height-29" ( 737mm) (see note 2), Depth-24 1/2" (623mm)
010H 012H 015H 017H 020H 023H
35,000 41,000 53,000 57,000 70,000 75,000
10.4 12.0 15.4 16.6 20.4 22.0
2 (10.0) 2 (11.6) 3 (15.0) 3 (16.2) 4 (20.0) 4 (21.6)
2.0 - 3.0 Ton ( see note 3) n/a (see note 3)
E3EH
240 Volts/60Hz/1-Phase
2 Speed, 1/5 HP, 2.0
0.3
2.0 - 3.0 Ton ( see note 3)
E3EB
240 Volts/60Hz/1-Phase
4 Spd, 3/4HP
3.8 Amps
0.3
2.0 - 5.0 Ton
2.0 - 4.0 Ton
16" x 20" x 1" (nominal)
Electric Furnace Models
Rated Heating Output, Btuh
Watts (T otal kw, Heating
Test ESP, in. w.c. Max
Optional Cooling Av ailable with
factory installed blower
Optional Heat Pump Available
with factory installed blower
Electric Furnace Models
Rated Heating Output, Btuh
Watts (T otal kw, Heating
Test ESP, in. w.c. Max
Optional Cooling Av ailable with
factory installed blower
Optional Heat Pump Available
with factory installed blower
(see note 1)
Elements and Blower)
Supply Voltage
Heating Elements,
No.(Total kw)
Blower Wheel Siz e 11" Dia., 8" W
Motor Speed,
H.P. Rating, Amps
Air Filter ( Standard)
Furnace Dimensions
(see note 1)
Elements and Blower)
Supply Voltage
Heating Elements,
No.(Total kw)
Blower Wheel Size 10.5" Dia., 8" Wide
Motor Speed,
H.P. Rating, Amps
Air Filter ( Standard) 16" x 20" x 1" (nominal)
Furnace Dimensions
010H 012H 015H 017H 020H 023H 023H 5-Ton
35,000 41,000 53,000 57,000 70,000 75,000 75,000
10.4 12.0 15.4 16.6 20.4 22.0 22.0
2 (10.0) 2 (11.6) 3 (15.0) 3 (16.2) 4 (20.0) 4 (21.6) 4 (21.6)
4 Speed, 1/3 HP, 2.9
2.0 - 4.0 Ton ( see note 4)
Width-20" (508mm), Height-29" (737mm) (s ee note 2), Depth-24 1/2" (623mm)
E3EX
010H 012H 015H 017H 020H
35,000 41,000 53,000 57,000 70,000
11.4 13.0 16.4 17.6 21.4 240 Volts/60Hz/1-Phase
2 (10.0) 2 (11.6) 3 (15.0) 3 (16.2) 4 (20.0)
2 Speed, 1/5 HP, 2.0
0.3
2.0 - 4. 0 Ton
2.0 - 4. 0 Ton
Width-20 " (508m m), Height -29" ( 737mm) ( see no te 2), Dept h-24 1/ 2" (623m m)
1. Heating output rated at listed voltage. For outputs at voltages other than 240V, multiply Btuh rating by the following factors: x 0.92 (230V), x 0.84 (220V), x 0.75 (208V)
2. Height is 56" with return air grille installed, 58" with coil cabinet and 72" with coil cabinet and upflow stand.
3. The factory installed blower for the EH models can be replaced with a multi-speed blower allowing the units to accept up to 5 tons of air conditioning or 4 tons heat pump.
4. The factory installed blower for the EB models can be replaced with a multi-speed blower allowing the units to accept up to 5 tons of air conditioning.
Table 3. Unit Specifications
9
Page 10
TYPICAL INSTALLATION OF
)
DOWNFLOW SYSTEMS OR PLATINUM SYSTEM
The following steps describe installation in­structions for an under-the-floor supply duct system with a return air system that can be either non-ducted or ducted. Duct connectors (Table 4) are recommended for this application. NOTE: Before installing this furnace, consider all clearances for the installation and future servicing of the furnace. Refer to Table 1.
Return Air and Filtering Systems
Furnaces may be installed with non-ducted or ducted return air. For non-ducted return air systems, either the optional grille and frame assembly or the optional wall mount grille is recommended. For ducted return air systems with air conditioners or heat pumps, either providing an access panel in the duct or using the optional coil cabinet is recommended. The duct system must be properly sized so as to account for any additional external static pres­sure produced from the chosen filtering method.
3. With optional coil housing:
- see coil cabinet instructions for specific filtering methods.
Filtering Methods - Ducted Return Air
1. Without optional coil housing:
- install a filter with a minimum unrestricted medium area of 324 square inches in the duct above the coil that is accessible for monthly cleaning or replacement by home­owner.
2. With optional coil housing:
-install a filter with a minimum unrestricted medium area of 324 square inches in the duct above the coil that is accessible for monthly cleaning or replacement by home­owner.
Optional Duct Connectors for Downflow Systems
Duct connectors are recommended for heated air distribution in under-the-floor duct systems. With this system, furnaces may be installed on combustible flooring without a separate sub­base. Also, the furnace rear mounting plate
NOTE: Refer to the instructions supplied with any additional accessories for further installa­tion details.
Filtering Methods - Non-Ducted Return Air
1. Without A/C or H/P uncased coil:
- use the filter supplied with the furnace; ensure that the filter is installed mat side down between the filter retainer and fur­nace top (see Figure 4).
2. With A/C or H/P uncased coil:
- use the optional coil filters; the filter sup­plied with the furnace is not used; REMOVE AND DISCARD THIS FILTER.
FLOOR CAVITY
x
SUPPLY AIR DUCT
*Felt Seal
Corner
Spacers
Reducer
C
*Indicates only applicable for Finger Tab Duct Connector
*OPENING TO DUCT A= 13-1/4" (337 mm)
B= 10-3/4" (274 mm) WITH PLATE (C) REMOVED OPENING BECOMES 13-1/4” x 13-1/4”
Frame
Fasteners (4)
Grille
Furnace Filter
(not used with
A/C or H/P
Figure 4. Grille Support Frame and Grille
Assembly
TOP VIEW
19”
(483 mm)
A
B
19"
X
(483 mm)
Top of
Furnace
Figure 5. Duct Connector Selection (Non-Platinum)
10
Page 11
(see Figure 3) supplied with the duct connec­tors is recommended for use with this type of installation.
Selecting Duct Connector
Non Platinum Duct Connector
1. Determine depth of floor cavity from sur­face of floor to top of supply air duct (see Figure 5).
2. Select appropriate model from Table 4 which matches X-dimension of floor cavity. To maximize air delivery, remove reducer (C in Figure 5) to obtain largest open area that will fit duct/floor construction. NOTE: Duct connectors may be installed in any one of four positions.
Platinum Duct Connector
1. The 14” round duct connector (903896) is designed to connect directly to a 14” flex­duct.
If “X” Use Duct Connector
floor cavity is: Model Part N umber
English Metric (mm) Finger Tab Screw Down
7/8" 22 901987 904008
2" 51 901988 904009 4 1/4" 108 901989 904010 6 1/4" 159 901990 904011 8 1/4" 210 901991 904012
10 1/4" 260 901992 904013 12 1/4" 311 901993 904014
Table 4. Floor Cavity Sizes
Preparing Floor Opening(s)
1. Mark floor opening(s) as shown in Figure
6. Provide minimum clearances at rear and
right side walls of closet or alcove for
installation of furnace and wiring.
2. Cut floor opening on outside edge of marked line so that opening is slightly larger than area marked.
2-3/8" MIN (60 mm)
(432 mm)
23-3/4"
(603 mm)
17"
3-3/4"
(95 mm)
REAR WALL OF ENCLOSURE
Center Line
14-1/2"
(368 mm)
14-1/2"
(368 mm)
Optional Supply Wire
Entrance
A/C Or HP
(Not required
for Platinum)
Optional
Refrigerant
Line
Furnace Outline
16-5/8"
(422 mm)
3" (76 mm)
3/4"
(19 mm)
Furnace Outer Door
Figure 6. Downflow Floor Cutout Locations (nominal dimensions)
"4-1/4 "5
(108 mm)
(127 mm) "10
(254 mm)
(86 mm)
20
"
(508 mm)
"3-3/8
6-1/4
"
(159 mm)
11
Page 12
Floor Opening
Refrigerant Line Opening
Mounting Plate
Cut Duct Opening 1/16th. Larger Than Plenum Connector
Rear Wall
Optional Supply Entrance
Cut-out Area
Supply Air Duct
Figure 7. Rear Mounting Plate
Secure Duct Connector & Mtg Plate With 2 Flat Head Screws or Nails At Dimpled Locations
Mounting Plate
Plenum
Refrigerant Line Opening
Supply Air Duct
Figure 8. Duct Connector (Non Platinum)
3. Additional provisions may be necessary for optional air conditioning or heat pump if refrigerant lines are installed elsewhere than at the front of the furnace.
4. The refrigerant and entrance supply open­ing dimensions may be adjusted ± 1/2”.
Installing Duct Connector
NOTE: The duct connector is designed for use
on ducts down to 12" wide. On typical ducts, the finger tab duct connector may be installed using Method B. On narrow ducts, there may be
Rear Wall
Bend Connector Tabs Under Duct Opening
insufficient clearance to bend the tabs on two sides of the finger tab duct connector. In such cases, use Method C or D. For screw down duct connector use method E. For Platinum models always use method A.
Method A - Platinum Series
NOTE: Flex duct used must have a minimum
temperature rating of 200
° F and meet all
other applicable codes and standards.
1. Place duct connector through opening in floor. See Figure 9.
2. Connect 14” supply duct.
12
Page 13
Mounting Plate
Duct
Connector
Secure Duct Connector and Mounting Plate with 2 Flat-Head Screws or Nails
Figure 9. Platinum Duct Connector
Method B
1. Place duct connector through floor opening with bottom tabs resting on top of supply air duct. Mark cutout area around inside of tabs.
2. Remove duct connector and cut out duct opening slightly larger than area marked.
3. If using optional rear mounting plate (sup­plied with duct connector), install it to back edge of floor opening (see Figure 7). Re­install duct connector in floor opening. A shim may be used, if necessary, to ensure the furnace is level.
4. Secure duct connector to floor with two flat-
TABS
14" Supply Connection
head fasteners at dimpled locations (see Figure 8).
5. Secure connector to duct by bending bot­tom tabs under and up against duct sur­faces (see Figure 10).
Method C
1. Attach tabs to sides of duct (one on each side) using sheet metal fasteners or other method, ensuring that the duct connector is secure and sealed to the duct (see Figure 11).
2. Seal the duct flap edges with an approved tape or compound for a leak-free joint.
TABS
DUCT
1. INSERT DUCT CONNECTOR INTO DUCT CUT-OUT
Figure 10. Duct Connector Installation B
DUCT
2. BEND BOTTOM TABS OVER AND ONTO THE UNDER­NEATH DUCT SURFACE
13
Page 14
Method D
1. Score and cut top of metal duct as indicated in Figure 12, Step 1 or Step 2. If using Step 1, also cut out metal from the shaded area “A”.
2. Fold the duct flap “B” up (see Figure 12, Step 3).
3. At the front-to-back of duct run (see Figure 12, area “A”), bend the duct connector tabs and secure them directly to the duct.
4. At area “B”, bend the duct connector tabs up and back over, around the duct connec­tor (see Figure 12, step 3).
5. Fold/form the duct flap against the side of the duct connector and attach as shown (see Figure 12, Step 4). Use at least three staples on each duct flap OR... if a 2X block/
Duct Connector
Narrow Duct
Duct
Figure 11. Alternate Duct
Connector Installation C
joist is not provided, use at least two sheet metal fasteners on each duct flap.
6. Seal the duct flap edges with an approved tape or compound for a leak-free joint.
Method E
1. Apply a bead of caulking, mastic, or other approved sealant around bottom side of 1/2” flange and restrictor plate, when applicable.
2. Locate the duct connector over duct and carefully lower screw down duct connec­tor into place.
3. Once duct connector is located on duct, temporarily hold in place while fastening duct connector to the floor using flat head screws or nails. Be sure flanges of duct connector stay in contact with the duct.
4. Screw duct connector to duct making sure a seal is made between the duct and the duct connector. Additional screws may be added if required.
5. Cut away duct along edge of duct connec­tor flange allowing the center to drop into the duct. Remove section of duct with caution, as edges will be sharp.
Alcove Installation
1. Cut alcove rough openings to minimum dimensions shown in Figure 13.
2. Attach frame assembly with four fasteners
STEP 1.
Fold Back Flap "B"
Cut- Out Area "A"
STEP 3.
Bend Duct Connector Tabs Up
and Over- (along length of duct)
"B"
"A" "A"
"B"
Fold Back Flap "B"
Duct
Cut- Out Area"A"
Top of Duct
Duct Flap "B"
STEP 2.
Fold Back Flap"B"
Cut
Lines
STEP 4.
Staple Folded Duct
Flap (typ) to side of
Duct Connector
"B"
"B"
Fold Back Flap"B"
Duct
Duct
Figure 12. Alternate Duct Connector Installation D
14
Page 15
Coil Air
Filters
Wall
Panel
A/C or H/P
Coil
24 3/4"
(629 mm)
Floor
Furnace
Front
(508 mm)
20"
Return
Air
Grille
27"
(686 mm)
(1423 mm)
29"
( 737 mm)
18" Nearest Wall or Partition
Holes (4)
56"
Wall-Mount
Return Air Grille
Closet
Door
Figure 13. Typical Alcove Installation
(provided or equivalent) into pre-punched holes on top of furnace (see Figure 5).
3. At manufacturers discretion, if additional securement is required attach each side of frame assembly to alcove opening using holes provided.
4. Attach return air grille to frame assembly by hooking grille over flange on top of frame and into channel on bottom.
Closet Installation
NOTE: For closet installations, the return air
grille mounting frame is not used since the furnace is located inside the closet (see Figure 14 and 15).
1. Cut return air opening in desired position in door or wall, preferably above top of fur­nace. Refer to Table 1 for return air opening requirements.
2. Insert four fasteners, securing grille to door or wall.
Figure 14. Typical Closet Installation
Provide min. 235 sq. in. (1516 cm ) open free area in front or side wall or in top of closet door
0" Side Clearance to Furnace Cabinet
6"
(152 mm)
CLOSET DOOR
Standard Closet Installation
Provide min. 250 sq. in. (1613 cm2 ) open free area in front or side wall or in top of closet door
Furnace Installation
1. Install 240V supply circuit(s) and 24V wir­ing to closet or alcove (see Figure 16 for appropriate locations).
2. Remove refrigerant line knockouts in fur­nace only when installing indoor coil of an air conditioner or heat pump system, or for hook-up of a VentilAire accessory when the furnace is used in the upflow position.
0" Side Clearance to Furnace Cabinet
1"
(25 mm)
Special 1" Clearance
Figure 15. Closet Installation
CLOSET DOOR
15
Page 16
Low Voltage Wire Entrances
Power
Supply
Wire
Entrances
Power Supply Wire
Refrigerant
Line Knockouts
Blower Selector
Switch (EH Only)
Tie-Down Tab
(See Inset)
Entrances
Tie Down Tab
Low Voltage Wire Entrances
DOWNFLOW INSTALLATION UPFLOW INSTALLATION
Figure 16. Downflow and Upflow Installations
Refrigerant Line Knockouts
Blower Selector
Switch (EH Only)
Refer to instructions supplied with acces­sory equipment.
3. Remove unit front door and slide back until bottom slots in rear of unit engage with both tabs of optional rear mounting plate, OR... If mounting plate is not used, an equivalent method of securing the rear of the unit may be used as long as it prevents displace­ment during transport if used in a manufac­tured home.
Upflow Duct Connector
Furnace
Upflow Stand
Filters
NOTE: The furnace does not need to be hard
up against the rear mounting plate. The tabs will engage into the slots and allow approximately 1/2” of furnace adjustment front to back and right to left.
4. Secure front of unit with one or more fas­teners at mounting hole(s) provided or at tie-down tab (see Figure 16).
5. See Electrical System Installation to com­plete furnace installation.
TYPICAL INSTALLATION OF UPFLOW SYSTEMS
The following steps describe installation in­structions for an overhead supply duct system with a return air system that can be either over the floor (non-ducted) or through the floor (ducted).
NOTES:
• Before installing this furnace, consider all
clearances for the installation and future servicing of the furnace. Refer to Table 1.
• The 2 Wire Relay Control is NOT recom-
mended for upflow applications, instead, the AC/HP Relay Control (4-7 wire) should be used when converting some models to ac­cept an air conditioner. See Relay Control installation instructions for further details.
Figure 17. Over-the-Floor Return Air
System with Upflow Stand
16
Return Air and Filtering Systems
Furnaces may be installed with non-ducted or ducted return air. For non-ducted systems with air conditioners or heat pumps, the following
Page 17
optional equipment is recommended: upflow stand, coil cabinet, upflow duct connector, and wall mount grille. For ducted systems with air conditioners or heat pumps, the following op­tional equipment is recommended: coil cabinet and upflow duct connector.
NOTE: Refer to the instructions supplied with any additional accessories for further installa­tion details.
Filtering Methods - Non-Ducted Return Air
1. Without optional upflow stand: (see Figure 18)
-install a filter with a minimum unrestricted medium area of 324 square inches below the coil cabinet/furnace assembly that is accessible for monthly cleaning or re­placement by the homeowner
2. With optional upflow stand: (see Figure 17)
-stand must use two filters; one is supplied with the stand and the other MUST be removed from the furnace and placed in the stand - see upflow stand instructions for additional details.
Filtering Methods - Ducted Return Air
1. Install a filter with a minimum unrestricted medium area of 324 square inches below the coil cabinet/furnace assembly that is accessible for monthly cleaning or replace­ment by the homeowner
Applications and Furnace Installation
NOTE: Remove refrigerant line knockouts in
furnace only when installing indoor coil of an air conditioning or heat pump system.
Refer to instructions supplied with accessory equipment.
4. Position optional coil cabinet onto upflow stand or mounting platform and secure with three or more fasteners.
5. Position furnace in upflow mode onto coil cabinet and secure with two or more fasten­ers.
6. Use optional upflow duct connector or field supplied connector to attach furnace to overhead supply duct. (see Figure 17)
7. Install return air grille in closet preferably at same level as upflow stand or below mount­ing platform (see Figure 18).
NOTE: Be certain to provide an adequate free return air area as described under Return Air Codes and Requirements and Closed-Off Space Requirements.
Through-the-Floor Return Air System (Ducted)
1. Prepare Floor Opening(s): a. Mark floor opening(s) as shown in Fig-
ure 19. Provide minimum clearances at rear and left side walls of closet for installation of furnace and wiring.
b. Cut floor opening on outside edge of
marked line so that opening is slightly larger than area marked.
c. Additional provisions may be necessary
for optional air conditioning if refrigerant lines are installed other than at the front of the furnace.
2. If return air duct is made of combustible material, locate a pan fabricated of non­combustible material with 1" upturned flanges under furnace return air opening.
Coil Cabinet
Over-the-Floor Return Air System (Non-Ducted)
1. If floor underneath furnace is made of com­bustible material, locate a pan fabricated of non-combustible material with 1" upturned flanges under furnace return air opening (see Figure 18).
2. Use optional upflow stand with filters or construct a suitably braced mounting plat­form in closet (see Figure 17 or 18).
3. Install 240V supply circuit(s) and 24V wir­ing to closet (see Figure 16 for appropriate locations).
Air Filter
Braced Mounting Platform
Front Grille
Non-combustible Pan or Enclosure
WAL L
FLOOR
Figure 18. Over-the-Floor Return Air
System
17
Page 18
1 3/4" MIN
(45 mm)
REAR WALL OF ENCLOSURE
CENTER LINE
18 5/8" (474 mm)
23 3/4"
(604 mm)
3 1/8"
(80 mm)
3/4"
(20 mm)
Furnace
Outer Door
Figure 19. Upflow Floor Cutout Locations (nominal dimensions)
3. Install 240V supply circuit(s) and 24V wir­ing to closet (see Figure 16 for appropriate locations).
4. Position optional coil cabinet over floor cutout and secure with three or more fas­teners.
5. Position furnace onto coil cabinet and se­cure with two or more fasteners.
6. Use optional upflow duct connector or field supplied connector to attach furnace to overhead supply duct (see Figure 17).
(147 mm)
17 1/2"
(445 mm)
5 3/4"
ELECTRICAL SYSTEM INSTALLATION
!
WARNING:
To avoid the risk of electrical shock, personal injury or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical power supply.
Furnace Outline
14" (356 mm)
For Optional A/C Or H/P
3"
(73 mm)
20"
(508 mm)
Codes, Specifications, and Requirements
The wiring, installation, and electrical hookup of this furnace must comply with the National Electrical Code (or the Canadian Electrical Code) and all regulations of local authorities having jurisdiction. See Table 9a & 9b for mini­mum circuit ampacity, maximum over-current protection, and recommended wire size. See the unit wiring diagram for other wiring details. Supply-circuit requirements are as follows:
• -010 model is factory-wired for single-branch supply circuit only.
• -012 models are factory-wired for single­branch supply circuit (single-circuit kit in­stalled). Dual-branch circuit can be used by removing factory-installed single-circuit kit (see Figures 20 and 21).
• -015, -017, -020 and -023 models are factory-wired for dual-branch supply circuit. Single-branch circuit can be used by installing optional single-circuit kit .
18
Page 19
!
IMPORTANT:
Note: Circuit breakers installed within this unit are for short-circuit protection of the internal wiring and to serve as a disconnect. Circuit breakers installed within this unit DO NOT provide over-current protection of the supply wiring and therefore may be sized larger than the branch circuit protection.
Connecting Supply Service Wires
1. Remove right-hand control panel (when viewing in downflow position).
2. Locate power supply hole plugs in side of unit and in bottom of unit. Remove appropriate plug(s) or knockout opening applicable to recommended wire size(s).
3. Install listed cable connector(s) in opening(s). If metal-sheathed conduit is
used for incoming power line(s), provide an approved metal clamp on conduit and secure it in entrance knockout.
4. Insert supply service wire(s) through cable connector(s) and connect wires to circuit breakers (Figures 20 and 21). NOTE: To install single-circuit kit, perform step 5. If single-circuit kit installation is not necessary, go to step 6.
5. To install single-circuit kit: a. Loosen lugs at supply side of circuit
breakers.
b. Remove cover from single-circuit kit (if
supplied).
c. Insert metal buss bars of kit into lugs of
circuit breaker.
d. Tighten lugs securely (45 in.-lbs.
recommended).
6. Connect service ground wire(s) to ground­ing lug(s) provided. One ground is required for each supply circuit used.
Circuit Breaker
Circuit
Breaker
Wire
Assemblies
(Factory
Installed)
Bracket
OFF
OFF
60A
60A
ON
ON
Optional Single Circuit Adaptor Kit
Supply Service Wire Connection With Single Circuit
Adaptor Kit
Figure 20. Installation of Optional Single Circuit Adaptor Kit
Circuit Breaker
Bracket
Circuit
Breaker
Wire
Assemblies
(Factory
Installed)
OFF
OFF
60A
60A
ON
Supply Service
ON
Wire Connection Without Single Circuit Adaptor Kit
Figure 21. Installation of Supply Service Wires
19
Page 20
!
WARNING:
To avoid personal injury or property damage, make certain that the motor leads cannot come into contact with non-insulated metal components of the unit.
Blower Installation:
1. Turn off all electrical supply circuits to the furnace at the main service panel.
2. Remove furnace front door and switch furnace circuit breaker(s) to “OFF”.
3. Disconnect the motor plug from the control panel receptacle.
4. Remove one screw from left side of blower and three screws from right side of blower; slide blower forward and remove.
5. Install new blower ensuring the side flanges engage under side mounting tabs (three on one side, one on the other) and the long tab in the rear.
6. Replace screws previously removed from blower.
7. Connect the motor plug to the control panel receptacle.
8. Switch circuit breaker(s) to “ON”, reinstall furnace front door, and turn on electrical supply circuits to the furnace.
Selecting Blower Speed
See Table 5 for the lowest speed approved for the heating output of the unit. Since the blower leads connect to the control box, blower speed selection is accomplished through use of the proper color-coded blower lead located inside the control box. The speed(s) set by the factory may be different from that shown on the wiring diagrams. See the unit control box for blower speed(s) set at factory.
!
IMPORTANT:
If a relay box is installed, blower speeds for heating and cooling are set inside the relay box (see instructions included with relay box). The blower speed inside the furnace control box
must
be set to low or medium-low. Never change to a heating speed lower than that shown in Table 5.
Changing Blower Speed
E3EH: The selected heating blower lead is
attached to the wire lead attached to terminal 2 of the blower selector switch. a. Remove blower lead from the wire lead off
of terminal 2. b. Choose desired speed. c. Attach new blower lead to wire lead off
terminal 2 of blower selector switch.
E2EB: The selected heating blower lead is attached to terminal 6 on blower relay. The selected cooling blower lead is attached to terminal 4 on blower relay. a. Remove heating blower lead from terminal
6 on blower relay. b. Choose desired speed and install new
blower lead onto terminal 6 of blower relay
for new heating speed. c. Remove cooling blower lead from terminal
4 on blower relay. d. Install new blower lead onto terminal 4 of
blower relay for new cooling speed.
E3EX: The selected heating blower lead is attached to terminal 6 on blower relay and is the red wire attached to the motor pin terminals 1-
3. The selected cooling blower lead is attached
Plug/Receptacle Position Pin1 Pin2 Pin3 Pin4 Pin5
2 Speed Blower Low High - - -
4 Speed Blower Low Med-Lo Med-Hi High -
Control Box Blower Lead Red Yellow Blue Black -
Minimum approved Speed for 010 and 012 models
Multi-Speed, E3EX Low Med-Lo Med Med-Hi High
20
Minimum approved speed for 015, 017, 020, 023 model s.
Table 5. Furnace Blower Speed Data
Page 21
to terminal 4 on blower relay and is the blue wire
ALL MODELS
Service Clearance
† For upflow application using upflow stand,
1" minimum per side.
attached to the motor pin terminals 1-3. a. Remove heating and cooling leads from
motor terminals 1-5.
b. Choose desired speeds and seat terminal
back into motor terminals 1-5.
Same Speed, Heating and A/C: Use loose white jumper wire supplied with unit and jumper between terminals 5 & 2 on blower relay. On E3EX, remove one wire from motor terminals 1-
5.
See Table 6 for blower performance data.
Installing Control Circuit Wiring
NOTE: Installation of a five-wire thermostat
circuit is recommended to provide for future addition of a heat/cool thermostat.
1. Install the 24V control-circuit cable through
plastic bushing at either side of furnace. a. For models without a relay box, connect
wires to furnace at blower plug pigtails (see
wiring diagrams). Secure all connections
with wire nuts. b. For units with a relay box installed, make
wiring connections at relay box low-volt-
age terminal board. (See relay box instal-
lation instructions.)
2. Route control circuit wiring to wall
thermostat and outdoor section, if installed.
(See relay box installation instructions if
applicable.)
3. Set anticipator per Table 7 or per the
marking on the unit.
4. See Figure 31 (non-Platinum) and Figure
32 (Platinum) for E3EB thermostat con-
nections.
Standard E3EH Blower with Filter, @ 0.3" ESP
Pin No. Speed CFM
#1 Low 840
#2 High 1160
4-Ton Blower with Coil and Coil and Filters, @ 0.3" ESP
Pin No. Speed CFM
#1 Low 880
#2 Med.-Low 1170
#3 Med.-High 1310
#4 High 1460
5-Ton Blower, with Coil and Coil Filters, @ 0.3" ESP
Pin No. Speed CFM
#1 Low 990
#2 Med.-Low 1320
#3 Med.-High 1620
#4 High 1790
Multi-Speed, X13, Blower, with Coil and Filters, @ 0.3" ESP
Pin No. Speed CFM
#1 Low 880 #2 Med.-Low 1000 #3 Med 1170 #4 Med.-High 1260 #5 High 1460
SYSTEM CHECKOUT Checking Installation
1. Refer to appropriate wiring diagram and
recheck all wiring connections. Ensure
that all connections are tight.
2. Check blower motor and relay box
connectors for proper connection.
3. Reinstall control box cover(s).
4. Switch circuit breaker(s) to “ON” position.
5. Set furnace blower selector switch (see
Figure 16) to “AUTO” (EH Units only).
6. Replace outer furnace door.
7. Check all duct connections and tape for air
leakage.
Furnace Thermostat
Model Anticipator Setting
010, 012 0.20
015, 017, 020, 023 0.40
Table 7. Anticipator Settings
CLOSET ALCOVE
Front ‡ 6" 18"
Back 0" 0"
Sides 0"† 0"†
Top 0" 0"
Top and Sides of Duct 0" 0"
Bottom of Duct 0" 0"
Table 6. Blower Performance
Table 8. Clearances
21
Page 22
Model
Number
E3E(*)
-010-H
Supply Circuit
Single 45.5 60 57 4 6 10
Total
Amperes
Single 52.1 70 65 4 6 8
-012H
Dual "A" 28.0 40 35 8 8 10 Dual "B" 24.2 30 30 10 10 10
Single 66.3 90 83 2 4 8
-015H
Dual "A" 45.5 60 56 4 6 10 Dual "B" 20.8 30 26 10 10 10
Single 71.3 90 89 2 4 8
-017H
Dual "A" 48.8 60 60 4 6 10 Dual "B" 22.5 30 28 10 10 10
Single 87.1 125 109 0 2 6
-020H
Dual "A" 45.5 60 57 4 6 10 Dual "B" 41.7 60 52 4 6 10
Single 93.8 125 117 0 2 6
-023H
Dual "A" 52.1 60 60 4 6 10 Dual "B" 41.7 60 56 4 6 10
Model
Number
(E3EX)
-010
Supply Circuit
Single 47.7 60 57 4 6 10
Total
Amperes
Single 54.3 70 67 4 6 8
-012
Dual "A" 30.2 40 35 8 8 10 Dual "B" 24.2 30 30 10 10 10
Single 66.0 90 83 2 4 8
-015
Dual "A" 46.0 60 57 4 6 10 Dual "B" 20.0 30 25 10 10 10
Single 71.5 90 89 2 4 8
-017
Dual "A" 51.0 60 60 4 6 10 Dual "B" 22.5 30 28 10 10 10
Single 86.0 125 109 0 2 6
-020
Dual "A" 46.0 60 57 4 6 10 Dual "B" 40.0 60 50 4 6 10
Replacement f urnac e for E2E(*) -015H B
E2E(*)-
015HBR
Single 67.1 90 83 2 4 8 Dual "A" 35.5 50 44 6 8 10 Dual "B" 31.7 40 39 8 8 10
* Can be H or B
Maximum
Over-current
Rating
Maximum
Over-current
Rating
Minimum
Circuit
Ampacity
Minimum
Circuit
Ampacity
Cop per Wi re Size - See
Caution Below
60°C 90°C
(e.g., Romex) (e.g., SEU)
Cop per Wi re Size - See
Caution Below
60°C 90°C
(e.g., Romex) (e.g., SEU)
Ground
Wire Size
Ground
Wire Size
Low
Voltage
Thermostat
Wire Size
2-Wire
system
maximum
wire lengths :
24 Ga.= 55'
22 Ga.= 90' 20 Ga.= 140' 18 Ga.= 225'
4 or more
Wire
systems
maximum
wire lengths :
24 Ga.= 25' 22 Ga.= 45' 20 Ga.= 70'
18 Ga= 110'
Low
Voltage
Thermostat
Wire Size
2-Wire system maximum wire
lengths: 24 Ga.= 55' 22 Ga.= 90'
20 G a.= 140' 18 Ga.= 2 25'
4 or m ore
Wire systems
maximum wire
lengths: 24 Ga.= 25' 22 Ga.= 45' 20 Ga.= 70'
18 G a = 110 '
Replacem ent
furnace fo r
E2E(*)-015H B
CAUTION: When sizing the wire, you must follow the guidelines of the latest revision of the NEC. NM-B wire is equivalent to “Romex” cable. SEU is equivalent to service entry cable. For NEC type NM-B wire, you must size the wire using 60C ratings per NEC article 326.
* Minimum overcurrent protection per NEC 424-3b not to be less than
125% of total amps for fixed resistance heat.
Table 9a. Electrical Specifications
Circuit "A" Circuit "B"
Model Number
E3E( *)
-012H
-015H
-017H
-020H
-023H
Wire G a uge
and Type
#8 NM-B
#6 SEU #6 SEU #6 SEU #6 SEU
Replacement furnace for E2E(*)- 015HB
E2E(*)-015HBR
#8 SEU
Breaker
Size
40 amp 60 amp 60 amp 60 amp 60 amp
50 amp
Wire Gauge and
Type
Breaker Size
#10 NM-B 30 amp #10 NM-B 30 amp #10 NM-B 30 amp
#6 SEU #6 SEU
60 amp 60 amp
#8 NM-B 40 amp
Table 9b. Recommended Electrical Application Guide
for Dual Circuit Installations**
** Alternate wiring combinations can be used. Refer to the latest revision of the NEC for these
appropriate alternate combinations.
22
Page 23
Cont – Contactor
240V
Transformer
Cont
1
24V
Red Pig-Tail
White Pig-Tail
Cont 1
C
L
IFM
CB-A
CB-A
IFS
LS
Btm - 10.0
6
H
12345
Red
Blue
Black
E
Cont 1
IFS
Yellow
Grey
Org.
(See Note 7)
Grey Pig-Tail
Fuse
Legend:
CB – Circuit Breaker
E – Heater Element
Line
Voltage
Supply
Circuit A
ON
60A
OFF
IFS – Fan Switch
LS – Limit Switch
– Fan Plug
IFM – Fan Motor
WARNING:
!
replaced with 105°C thermoplastic copper wire of the
same gauge.
ground.
sory Installation Instructions for further details.
5) If any wire in this unit is to be replaced it must be
NOTES:
1) See unit data label for recommended supply wire
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See acces-
C
L
H
sizes.
2) Thermostat anticipator setting: 0.20 Amps.
installed refer to installation instructions.
thermostat connections.
3) To change blower speeds on units without a relay box
4) Refer to furnace and/or relay box installation for
SWITCH
BLOWER
1
BLACK
Switch circuit breakers to
the OFF position before
servicing the furnace.
RED
GREY
ORANGE
6
3
2
5
1
4
RED
YELLOW
BLACK
FUSE
BLACK
RED
BLACK
3
2
1
ORANGE
6
5
4
2
3
YELLOW
BLACK
TRANSFORMER
BROWN
240V
COM
GRD Ground
RED
VIOLET
RED
WHITE
GREY
24V
CIRCUIT
BREAKER
BLACK
BLACK
2
4
RED
RED
BOTTOM ELEMENTS, 10.0 KW
BLACK
BLACK
1
3
ELEMENTS
GREY
LIMITS
BLACK
CONTACTOR
RED
Figure 22. E3EH 010H Wiring Diagrams
23
Page 24
y
CB-B
Org.
6
CB-A
C
IFM
L
H
Blue
Grey
Black
Yellow
E
12345
Red
LS
Transformer
240V
E
Btm - 11.6
IFS
IFS
24V
1
Cont
(See Note 7)
Grey Pig-Tail
Cont – Contactor
Legend:
CB – Circuit Breaker
E – Heater Element
Single
Supply
IFS – Fan Switch
(standard)
LS – Limit Switch
– Fan Plug
IFM – Fan Motor
Dual
(optional)
Suppl
Cont 1
CB-B
CB-A
WARNING:
!
Switch circuit breakers to
the OFF position before
servicing the furnace.
ORANGE
with 105°C thermoplastic copper wire of the same
gauge.
ground.
accessory Installation Instructions for further details.
5) If any wire in this unit is to be replaced it must be replaced
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
C
L
H
RED
BLACK
3
6
2
5
1
4
Fuse
White Pig-Tail
Red Pig-Tail
3
6
2
5
1
4
RED
YELLOW
BLACK
ORANGE
BLACK
GREY
RED
FUSE
RED
ON
60A
OFF
BLACK
VIOLET
RED
GREY
Ground
OR
ON
60A
OFF
GRD
CIRCUIT
BREAKERS
BLACK
WHITE
BOTTOM ELEMENTS, 10.0 KW
BLACK
2
RED
Line
Voltage
Circuit B
ON
60A
OFF
4
RED
Ground
GRD
1
3
ELEMENTS
Line
Voltage
Ground
Circuit A
ON
60A
OFF
GRD
LIMITS
BLACK
RED
CONTACTOR
BLACK
refer to installation instructions.
thermostat connections.
2) Thermostat anticipator setting: 0.20 Amps.
3) To change blower speed on units without a relay box
NOTES:
1) See unit data label for recommended supply wire sizes.
4) Refer to furnace and/or relay box installation for
24
1
SWITCH
BLOWER
BLACK
2
3
YELLOW
BLACK
BROWN
240V
COM
TRANSFORMER
Figure 23. E3EH 012H, Wiring Diagrams
24V
GREY
Page 25
!
Legend:
240V
Cont 1
C
L
IFM
CB-A
CB-A
CB-B
CB-B
IFS
Transformer
LS
Bottom -
5.0/5.4
Top -
10.0/10.8
H
12345
Red
Yellow
Blue
E
Cont 1
IFS
Cont 2
LS
Cont
2
Cont
1
24V
Red Pig-Tail
White Pig-Tail
6
Black
Grey
Org.
(See Note 7)
Grey Pig-Tail
E
Fuse
Line
Voltage
Circuit B
ON
60A
OFF
CB – Circuit
Breaker
E – Heater Element
Dual
Supply
Line
Voltage
Ground
Ground
Circuit A
ON
60A
GRD
OFF
Cont – Contactor
LS – Limit Switch
IFS – Fan Switch
Single
OR
ON
60A
OFF
GRD
CIRCUIT
BREAKERS
– Fan Plug
IFM – Fan Motor
(optional)
Supply
Ground
ON
60A
OFF
GRD
with 105°C thermoplastic copper wire of the same
gauge.
ground.
accessory Installation Instructions for further details.
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
NOTES:
1) See unit data label for recommended supply wire sizes.
refer to installation instructions.
2) Thermostat anticipator setting: 0.40 Amps.
3) To change blower speed on units without a relay box
thermostat connections.
4) Refer to furnace and/or relay box installation for
C
SWITCH
BLOWER
5) If any wire in this unit is to be replaced it must be replaced
Figure 24. E3EH 015H, E3EH 017H Wiring Diagrams
WARNING:
Switch circuit breakers to
the OFF position before
servicing the furnace.
ORANGE
3
BLACK
L
RED
456
2
3
YELLOW
12
BROWN
H
1
BLACK
3
2
1
RED
ORANGE
56
4
YELLOW
BLACK
BLACK
BLACK
RED
GREY
FUSE
TRANSFORMER
RED
WHITE
240V
COM
BLACK
VIOLET
RED
BLACK
BLACK
RED
1
423
RED
RED
TOP ELEMENTS, 10.0/10.8 KW
BLACK
GREY
24V
BLACK
CONTACTOR
GREY
LIMITS
RED
BOTTOM ELEMENT, 5.0/5.4 KW
ELEMENTS
BLACK
WHITE
CONTACTOR
GREY
RED
25
Page 26
WARNING:
60A
ON
OFF
GRD
Single
Supply
(optional)
OR
Circuit A
Circuit B
GRD
GRD
Ground
Dual
Supply
60A
60A
ON
ON
OFF
OFF
Ground
Line
Voltage
Ground
Line
Voltage
60A
ON
OFF
CIRCUIT
BREAKERS
240V
Cont 1
C
L
IFM
CB-A
CB-A
CB-B
CB-B
IFS
Transformer
LS
Top -
10.0/11.6/7.6
Btm - 10.0/7.6
H
12345
Red
Yellow
Blue
E
E
Cont 1
IFS
Cont 2
Cont 2
LS
Cont
2
Cont
1
24V
Red Pig-Tail
White Pig-Tail
6
Black
Grey
Org.
(See Note 7)
Grey Pig-Tail
Fuse
!
Switch circuit breakers to
the OFF position before
servicing the furnace.
Fan Plug
Cont – Contactor
LS – Limit Switch
Legend:
D E R
D E R
K C A L
K
B
C A
D
L
E
B
R
D E R
K
IFS – Fan Switch
CB – Circuit Breaker
E – Heater Element
K
C
A
L
B
C
A
L
B
IFM – Fan Motor
C
with 105°C thermoplastic copper wire of the same
gauge.
ground.
accessory Installation Instructions for further details.
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
R
H
E W
ITC W
LO
S
B
NOTES:
1) See unit data label for recommended supply wire sizes.
26
refer to installation instructions.
thermostat connections.
2) Thermostat anticipator setting: 0.40 Amps.
3) To change blower speed on units without a relay box
4) Refer to furnace and/or relay box installation for
5) If any wire in this unit is to be replaced it must be replaced
Figure 25. E3EH 020H, 023H, E2EH-015HBR Wiring Diagrams
E
K
L
H
2
1
3
K C A
W
L
O
B
L L E Y
W K
E G N A R
G
N
A
R
O
6
3
5
C
A
L
B
D
E
12
R
4
O
3
2
1
456
D
E
R
W
O
L
L
E
Y
K
C
A
L
B
K C A L B
N
W
O
R
B
E IT H W
D E
R Y E
R G
E
IT
H
W
K C
E
LA
S
B
U F
T
E
L
IO
V
R
E
V
M
R
O
F
S
N
A
R
T
V
240
24
M O C
K
C
A
.6/7.6 1
/1
0.0 D
E
, 1 S
R
T N E M E L
E P O T
K C A L B
Y E R G
L
B
W K
1
2
4
D E R
2 /7.6.0 ,10
3
T
D
N
E
E
R
M E L
E M O
T T O B
R TO
C A T N O C
Y
Y E R G
S
1
IT IM
L
3
4
D E R
TS
S T
N
N
E
E
M
M
E L
E L
E
E
E
K C A L B
R O T C A T N O C
R
G
D E R
Page 27
Legend:
240V
Cont 1
C
L
IFM
CB-A CB-A
Transformer
LS
Btm - 10.0
ML
12345
IFR
Red
Blue
E
Cont 1
IFR
Cont
1
24V
Red Pig-Tail
White Pig-Tail
IFR
Green Pig-Tail
Grey Pig-Tail
Yellow
MH
H
6
Black
Grey
Org.
White Jumper Wire
(See note 7)
Fuse
CB – Circuit Breaker
E – Heater Element
IFR – Fan Relay
Cont – Contactor
LS – Limit Switch
Line
Voltage
Supply
Circuit A
ON
60A
OFF
GRD Ground
RED
RED
BLACK
BLACK
CIRCUIT
BREAKER
– Fan Plug
IFM – Fan Motor
C
H
5) If any wire in this unit is to be replaced it must be replaced
with 105°C thermoplastic copper wire of the same
gauge.
ground.
accessory Installation Instructions for further details.
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
refer to installation instructions.
thermostat connections.
2) Thermostat anticipator setting: 0.20 Amps.
3) To change blower speed on units without a relay box
NOTES:
1) See unit data label for recommended supply wire sizes.
4) Refer to furnace and/or relay box installation for
WARNING:
RED
E
6
45
BLACK
GREEN
BLACK
GREY
FUSE
ER
TRANSFORM
GREEN
ORANG
240V
COM
!
Switch circuit breakers to
the OFF position before
servicing the furnace.
ORANG
E
ER W
BLO
2
5
1
BLACK
RELAY
4
6
3
3
2
1
RED
YELLOW
ITE H
W
3
6
5
2
RED
L
ML
MH
YELLO
W
BLUE
1
BLACK
4
BLACK
Figure 26. E3EB 010H Wiring Diagrams
VIOLET
GREY
24V
HITE W
TOP ELEMENTS, 10.0 KW
BLACK
R
TACTO
ON C
REY
1
2
ITS
LIM
3
4
RED
RED
ENTS
ELEM
BLACK
G
RED
27
Page 28
CB-B
CB-A
IFM
Org.
6
C
L
H
ML
MH
LS
1
Cont
IFR
CB-B
E
Blue
Grey
Black
(See note 7)
White Jumper Wire
IFR
CB-A
12345
Red
Yellow
IFR
240V
E
Btm - 11.6
Cont 1
– Fan Plug
LS – Limit Switch
IFM – Fan Motor
Transformer
24V
Fuse
Green Pig-Tail
Grey Pig-Tail
White Pig-Tail
Red Pig-Tail
RED
Line
Voltage
Circuit B
ON
60A
OFF
BLACK
Dual
Supply
Ground
GRD
BLACK
RED
Line
Voltage
Circuit A
ON
60A
OFF
WARNING:
!
Switch circuit breakers to
the OFF position before
Single
Supply
Ground
OR
ON
60A
60A
GRD
CIRCUIT
OFF
BREAKERS
servicing the furnace.
(optional)
Ground
ON
OFF
GRD
Legend:
CB – Circuit Breaker
E – Heater Element
IFR – Fan Relay
Cont – Contactor
with 105°C thermoplastic copper wire of the same
gauge.
ground.
accessory Installation Instructions for further details.
5) If any wire in this unit is to be replaced it must be replaced
NOTES:
1) See unit data label for recommended supply wire sizes.
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
C
L
ML
MH
H
refer to installation instructions.
thermostat connections.
2) Thermostat anticipator setting: 0.20 Amps.
3) To change blower speed on units without a relay box
4) Refer to furnace and/or relay box installation for
BLUE
YELLOW
RED
BLACK
ORANGE
123
456
BLACK
ORANGE
123
456
RED
YELLOW
BLACK
RELAY
BLOWER
2
4
5
6
3
1
WHITE
BLACK
BLACK
GREY
GREEN
FUSE
TRANSFORMER
RED
GREY
VIOLET
240V
COM
GREY
24V
WHITE
TOP ELEMENTS, 11.6 KW
BLACK
2
RED
4
1
3
RED
ELEMENTS
GREY
LIMITS
BLACK
RED
BLACK
CONTACTOR
28
Figure 27. E3EB 012H Wiring Diagrams
Page 29
WARNING:
240V
Cont 1
C
H
L
IFM
CB-A
CB-A
CB-B
CB-B
Transformer
LS
Btm -
5.0/5.4
Top -
10.0/10.8
ML
MH
12345
IFR
Red
Yellow
Blue
E
Cont 1
IFR
Cont 2
LS
Cont
2
Cont
1
24V
Red Pig-Tail
White Pig-Tail
IFR
Green Pig-Tail
Grey Pig-Tail
6
Black
Grey
Org.
White Jumper Wire
(See note 7)
E
Fuse
!
Switch circuit breakers to
the OFF position before
servicing the furnace.
– Fan Plug
LS – Limit Switch
IFM – Fan Motor
Legend:
CB – Circuit Breaker
E – Heater Element
IFR – Fan Relay
Cont – Contactor
with 105°C thermoplastic copper wire of the same
gauge.
ground.
accessory Installation Instructions for further details.
5) If any wire in this unit is to be replaced it must be replaced
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
C
L
ML
MH
H
3
2
1
3
6
5
12
4
BLACK
ORANGE
6
5
4
RED
BLACK
YELLOW
GREEN
GREY
GREY
RED
RED
WHITE
Line
60A
BLACK
Voltage
Circuit B
ON
OFF
Dual
Supply
Line
Voltage
Ground
GRD
RED
Ground
Circuit A
ON
60A
OFF
RED
BLACK
BLACK
TOP ELEMENTS, 10.0/10.8 KW
BLACK
OR
GRD
CIRCUIT
BREAKERS
2
RED
Single
Supply
ON
60A
OFF
1
3
4
RED
RED
BOTTOM ELEMENT, 5.0/5.4 KW
(optional)
ON
60A
OFF
LIMITS
ELEMENTS
Ground
GRD
WHITE
BLACK
refer to installation instructions.
2) Thermostat anticipator setting: 0.40 Amps.
NOTES:
3) To change blower speed on units without a relay box
1) See unit data label for recommended supply wire sizes.
thermostat connections.
4) Refer to furnace and/or relay box installation for
Figure 28. E3EH 015H, E3EB 017H Wiring Diagrams
BLACK
RELAY
BLOWER
4
2
5
6
1
3
WHITE
BLACK
FUSE
GREY
VIOLET
240V
COM
TRANSFORMER
24V
BLACK
GREY
CONTACTOR
GREY
CONTACTOR
RED
29
Page 30
CB-B
CB-B
LS
E
Cont 2
Top -
10.0/11.6/7.6
White Jumper Wire
Cont 2
CB-A
CB-A
IFM
H
Grey
Black
(See note 7)
MH
Blue
IFR
Org. 6
C
ML
Yellow
2
1
L
LS
12345
Red
E
IFR
Btm - 10.0/7.6
Cont 2
Cont 2
240V
Cont
Transformer
24V
Fuse
IFR
Cont
Green Pig-Tail
Grey Pig-Tail
White Pig-Tail
Red Pig-Tail
Line
Voltage
Cont – Contactor
IFR – Fan Relay
E – Heater Element
Legend:
CB – Circuit Breaker
Dual
Supply
Line
Voltage
Ground
Ground
– Fan Plug
IFM – Fan Motor
LS – Limit Switch
Single
Supply
(optional)
Ground
WARNING:
!
Switch circuit breakers to
the OFF position before
servicing the furnace.
ORANGE
C
with 105°C thermoplastic copper wire of the same
gauge.
ground.
accessory Installation Instructions for further details.
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
L
ML
MH
H
RED
YELLOW
BLUE
3
2
1
BLACK
56
4
56
4
123
RED
YELLOW
BLACK
WHITE
BLACK
GREY
GREEN
RED
FUSE
RED
RED
ORANGE
Circuit B
ON
60A
OFF
BLACK
BLACK
GREY
VIOLET
Circuit A
ON
GRD
60A
GRD
OFF
CIRCUIT
RED
RED
2
4
WHITE
RED
TOP ELEMENTS, 10.0/11.6/7.6 KW
BLACK
CONTACTOR
OR
ON
60A
OFF
BREAKERS
BLACK
BLACK
2
1
4
3
RED
RED
ELEMENTS
BOTTOM ELEMENT, 10.0/7.6 KW
1
3
RED
ELEMENTS
ON
60A
OFF
LIMITS
CONTACTOR
GRD
BLACK
WHITE
refer to installation instructions.
thermostat connections.
2) Thermostat anticipator setting: 0.40 Amps.
3) To change blower speed on units without a relay box
4) Refer to furnace and/or relay box installation for
NOTES:
1) See unit data label for recommended supply wire sizes.
5) If any wire in this unit is to be replaced it must be replaced
Figure 29. E3EB 020H, 023H, and 023H - 5 Ton, E2EB-015HBR Wiring Diagrams
30
BLACK
RELAY
BLOWER
2
4
5
6
1
3
BLACK
240V
TRANSFORMER
COM
GREY
24V
GREY
GREY
BLACK
RED
Page 31
Notes :
1) See unit data label for recommended supply wire sizes.
2) Thermostat anticipator setting : 0.40 Amps
3) To change blower speed on units without a relay box installed refer to installation instructions
4) Refer to furnace and/or relay box installation instructions for thermostat connections.
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.
6) Not suitable for use on systems exceeding 120V to ground.
7) Refer to Installation Instructions for complete wiring diagram.
8) Heating and cooling may be wired on the same speed using the provided jumper wire.
RED
152
BLOWER RELAY
6
GRAY
RED
GREEN
WHITE
GRAY WHITE
4
RED
FUSE
3
BLUE
CONTACTOR
123
456
WHITE
BLACK
BLUE
VIOLET
ORANGE
BLACK
BLACK BLACK
123
456
240V COM
GRAY
BLACK
BLACK
RED
BLUE
WHITE
BLACK
ORANGE
24V
ELEMENTS LIMIT
RED
RED
RED
RED
RED
T1
T2
T3
X13
T4
T5
G
N
L
C
GREEN/ YELLOW STRIP
Figure 30. E3EX 010H
Notes :
1) See unit data label for recommended supply wire sizes.
2) Thermostat anticipator setting : 0.40 Amps
3) To change blower speed on units without a relay box installed refer to installation instructions
4) Refer to furnace and/or relay box installation instructions for thermostat connections.
5) If any wire in this unit is to b
6) Not suitable for use on systems exceeding 120V to ground.
7) Refer to Installation Instructions for complete wiring diagram.
8) Heating and cooling may be wired on the same speed using the provided jumper wire.
152
BLOWER RELAY
GREY
RED GREEN
WHITE
GREY
WHITE
e replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.
RED
463
RED
FUSE
BLUE
WHITE
CONTACTOR
123
45
BLACK
BLUE
VIOLET
BLACK
BLACK
(25)
6
ORANGE
BLACK
123
45
BLACK
BLACK
(26)
6
240V COM
24V
GREY
ELEMENTS LIMIT
RED
BLUE
WHITE BLACK
ORANGE
RED
RED
RED
RED
RED
T1
T2
T3
X13
T4
T5
G
GREEN/ YELLOW STRIP
N
L
C
Figure 31. E3EX 012H
31
Page 32
Models: E3EX - 015/017H
Notes :
1) See unit data label for recommended supply wire sizes.
2) Ther mostat anticipator setting : 0.40 Amps
3) To change blower speed on units without a relay box installed refer to installation instructions
4) Refer to furnace and/or relay box installation instructions for thermostat connections.
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.
6) Not suitable for use on systems exceeding 120V to ground.
7) Refer to Installation Instructions for complete wiring diagram.
8) Heating and cooling may be wired on the same speed using the provided jumper wire.
1
3 64
WHITE
GREY
GREY
WHITE
GREEN
52
BLOWER RELAY
RED
RED
BLUE
(25)
FUSE
RED
GREY
1 2 3
456
WHITE
VIOLET
CONTACTOR
BLACK
BLUE
BLACK BLACK
BLACK
ORANGE
BLACK
1 2 3
456
BLACK
BLACK
BLACK
GREY
(26)
240V COM
24V
GREY
RED
BLUE
ORANGE
BLACK
WHITE
RED
RED
RED
ELEMENTS LIMIT
RED
ELEMENTS LIMIT
RED RED
T1
G
GREEN/ YELLOW STRIP
T2
N
T3
X13
L
T4
C
T5
RED
Figure 32. E3EX 015/017H
Models: E3EX - 020H
Notes :
1) See unit data label for recommended supply wire sizes.
2) Thermostat anticipator setting : 0.40 Amps
3) To change blower speed on units without a relay box installed refer to installation instructions
4) Refer to furnace and/or relay box installation instructions for thermostat connections.
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.
6) Not suitable for use on systems exceeding 120V to ground.
7) Refer to Installation Instructions for complete wiring diagram.
8) Heating and cooling may be wired on the same speed using the provided jumper wire.
1
GRAY
GRAY
WHITE
RED GREEN
WHITE
63
RED
BLUE
52
BLOWER RELAY
4
RED
FUSE
RED
(25) (26)
123
456
WHITE
BLACK
CONTACTOR
GRAY
BLACK
BLUE
VIOLET
ORANGE
123
456
GRAY
240V COM
GRAY
BLACK
BLACK
BLACK
BLACK
BLUE
ORANGE
BLACK WHITE
24V
ELEMENTS LIMIT
ELEMENTS LIMIT
RED
RED
RED
RED
RED
RED
RED
T1
G
X13
T5
GREEN/ YELLOW STIPE
N
L
C
T2
T3
T4
RED
RED
32
BLACK
BLACK
BLACK BLACK
Figure 33. E3EX 020H
Page 33
5-Wire Thermostat
W Y RC RH G
4-Wire Thermostat
W Y R G
Wire nuts
White
Grey
Red
E3EB FURNACE Control Wiring
2-Wire Thermostat
W R
Wire nuts
White
Red
Grey
E3EB FURNACE Control Wiring
Figure 34. E3EB Thermostat Connection
Wire from furnace to Platinum unit
PLATINUM
Red and white t-stat wire connected by OEM
Yellow
Green
Unstripped
Wires
Green
Black
To A /C
Wire nuts
Wire nuts
White
Grey
Red
E3EB FURNACE Control Wiring
Heat Pump Thermostat
G R W2 C E O Y
Green
White
Red
Grey
E3EB FURNACE Control Wiring
Typical AC
Green White Red Yellow or Blue
FURNACE
Grey White Red Green
Green
To A /C
To H/P
Yellow or Blue
RGW
Y
THERMOSTAT
White Green Red
Wire from thermostat to furnace
Platinum installer disconnects white and red t-stat wires
PLATINUM Grey or Green White Orange or Red Ye l l o w
Wire from furnace to Platinum unit
Green White Red Yellow or Blue
Typical HP
FURNACE
Grey White Red Green
Yellow or Blue
R
GW
Y
THERMOSTAT
White Green Red
Wire from thermostat to furnace
Figure 35. E3 Furnace Low Voltage Wiring if Installed with Platinum Series Models
33
Page 34
Furnace Inspection Report
Please Write In Appropriate
Response Electrical Wiring (If single circuit , write “N/A” in circuit B) Breaker Size? Furnac e Wire Size? Thermostat Wire Size?
Electrical Is the furnace grounded properly ? Yes No N/A Is wiring routed s afely with approved connectors? Yes No N/A
Closet Ins tallation Is front clearance a minimum of 6 inches? Yes No N/A Is return air opening a minimum of 235 s q. inches? Yes No N/A Is front clearance less than 6 inches (minimum of 1 inch)? Yes No N/A Is return air opening a minimum of 250 s q. inches? Yes No N/A Does the furnace have the 5-ton AC coil installed? Yes No N/A Is the return air opening a minimum of 390 sq inches? Yes No N/A
Plenum (Base) Connec tor Is mounting plate secured properly? Yes No N/A Is furnace locked and secured in front? Yes No N/A Is plenum f ree of debris? Yes No N/A Has plenum opening been reduc ed in size to accommodate offset? Yes No N/A Has plenum spacer been removed if duct size is large enough? Yes No N/A
Circuit A
Please Circle A ppropriate
Response
Circuit B
Testing Is someone in the plant trained to perform duct tests? Yes No N/A
VentilAire III __ IV __ Is VentilAire duct connected properly to furnace? Yes No N/A Is depressuriz ation vent (if required) installed properly? Yes No N/A Is roof assembly installed properly? Yes No N/A Is roof assembly a minimum of 3 inches from any other vents? Yes No N/A
General Is filter in place? Yes No N/A Is owner’s packet included? Yes No N/A Checked storage area for damage to product and proper storage? Yes No N/A Is installation in accordance wit h installat ion instructions? Yes No N/A
Comments
34
Page 35
35
Page 36
INSTALLER: Do Not Discard These Instructions
After completing the installation, return these instructions
to the Homeowner’s Package for owner-user’s future reference.
Complies with H.U.D. Manufactured Home Construction & Safety Standards.
O’Fallon, MO
¢708322}¤
708322D
708322D (Replaces 708322C)
Specifications and illustrations subject to change
without notice and without incurring obligations.
Printed in U.S.A. (10/06)
Loading...